Loading...
HomeMy WebLinkAboutWITHERS- MANUAL J L--r wrigni Projecty Summary Job: Date: Jun 10,2021 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM Project • • For: WITHERS RESIDENCE, JWN BUILDERS, LLC. LOT 1106 NETTLES ISLAND, JENSEN BEACH, FL Notes: Design Information Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 28 °F Design TD 15 °F Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 23836 Btuh Structure 15411 Btuh Ducts 4512 Btuh Ducts 6359 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 28348 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipmenf sensible load 20681 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3431 Btuh Ducts 1716 Btuh Central vent (0 cfm) 0 Btuh Heating Coolingg (none) Area (ft2) 1673 1673 Equipment latent load 5146 Btuh Volume (ft3) 13864 13864 Air changes/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 25828 Btuh Equiv.AVF (cfm) 88 46 Req. total capacity at 0.70 SHR 2.5 ton Heating Equipment Summary Cooling Equipment Summary Make Make Trane Trade Trade TRANE Model Cond 4TTR40311-1 AHRI ref Coil TEM6AOC36H31++TDR AHRI ref 7567544 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 8.0 kW Sensible cooling 20580 Btuh Heating output 27296 Btuh Latent cooling 8820 Btuh Temperature rise 25 °F Total cooling 29400 Btuh Actual air flow 980 cfm Actual air flow 980 cfm Air flow factor 0.035 cfm/Btuh Air flow factor 0.045 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.81 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -1)Oft—ord- W riig1 2021-Jun-10 08:24:41 Right-SuiteO Universal 2021 21.0.02 RSU08101 Page 1 = ...HVAC\WITHERS RESIDENCE-1106 NETTLES ISLAND.rup Calc=MJ8 Front Door faces: S IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: Jun 10,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name Entire House LIVING/DINING RM 2 Exposed wall 246.2 ft 58.2 ft 3 Room height 8.3 ft 8.0 ft heat/cool 4 Room dimensions 1.0 x 407.0 ft 5 Room area 1673.0 ft2 407.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�j13AB-0fcs 0.183 n 5.12 3.18 229 103 527 327 173 80 412 256 2 glazing,clr low-e 0.650 n 18.20 14.99 59 0 1074 884 59 0 1074 884 2 glazing,clr low-e 0.650 n 18.20 14.99 67 0 1219 1004 34 0 610 502 W 13AB-Ofcs 0.183 ne 5.12 3.18 58 58 296 184 29 29 148 92 11 W 13AB-Ofcs 0.183 e 5.12 3.18 608 591 3028 1882 136 136 697 433 I; GCI 2 glazing,clr low-e 0.650 a 18.20 33.77 8 0 146 270 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 33.77 9 0 164 304 0 0 0 0 W 13AB-Ofcs 0.183 se 5.12 3.18 169 142 726 451 0 0 0 0 I; GCI 2 glazing,clr low-e 0.650 se 18.20 25.27 12 2 218 303 0 0 0 0 2 glazing,clr low-e 0.650 se 18.20 25.63 15 2 273 384 0 0 0 0 V�/ 13AB-Ofcs 0.183 s 5.12 3.18 208 173 886 551 0 0 0 0 I�GCI 2 glazing,clr low-e 0.650 s 18.20 14.99 15 15 273 225 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 20 20 366 301 0 0 0 0 13AB-Ofcs 0.183 w 5.12 3.18 648 602 3085 1917 128 120 615 382 2 glazing,clr low-e 0.650 w 18.20 33.77 2 0 36 68 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 33.77 20 0 364 675 8 0 146 270 2 alazina,clr low-e 0.650 w 18.20 20.97 24 0 437 503 0 0 0 0 W 13AB-Ofcs 0.183 nw 5.12 3.18 115 86 443 275 0 0 0 0 G 2 glazing,clr low-e 0.650 nw 18.20 26.88 29 0 528 779 0 0 0 0 Cr 16X19-0md 0.408 1.59 1.37 975 975 1546 1334 80 80 127 109 F 22A-tph 1.358 38.02 0.00 975 145 5500 0 407 58 2212 0 6 c)AED excursion 0 -168 Envelope loss/gain 21134 12624 6039 2761 12 a) Infiltration 2702 762 618 174 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 2025 500 Subtotal(lines 6 to 13) 23836 15411 6657 3435 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 23836 15411 6657 3435 15 Duct loads 19% 41% 4512 6359 19% 41% 1260 1418 Total room load 28348 21770 7917 4853 Air required(cfm) 980 980 274 218 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Jun-10 08:24:41 Right-SuiteO Universal 2021 21.0.02 RSU08101 1' ✓ ......... Page 1 ...HVAC\WITHERS RESIDENCE-1106 NETTLES ISLAND.rup Calc=MJ8 Front Door faces: S IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: Jun 10,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name PANTRY BATH 2 Exposed wall 0 ft 6.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 5.0 x 4.0 ft 10.0 x 6.0 ft 5 Room area 20.0 ft2 60.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�/ 13AB-0fcs 0.183 n 5.12 3.18 0 0 0 0 0 0 0 0 I;�C 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 ne 5.12 3.18 0 0 0 0 0 0 0 0 11 W 13AB-Ofcs 0.183 e 5.12 3.18 0 0 0 0 0 0 0 0 l; GCI 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 se 5.12 3.18 0 0 0 0 0 0 0 0 I; GCI 2 glazing,clr low-e 0.650 se 18.20 25.27 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 se 18.20 25.63 0 0 0 0 0 0 0 0 V�/ 13AB-Ofcs 0.183 s 5.12 3.18 0 0 0 0 0 0 0 0 I�GCI 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 13AB-Ofcs 0.183 w 5.12 3.18 0 0 0 0 48 46 236 146 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 2 0 36 68 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 2 alazina,clr low-e 0.650 w 18.20 20.97 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 nw 5.12 3.18 0 0 0 0 0 0 0 0 G 2 glazing,clr low-e 0.650 nw 18.20 26.88 0 0 0 0 0 0 0 0 Cr 16X19-0md 0.408 1.59 1.37 0 0 0 0 6 6 10 8 F 22A-tph 1.358 38.02 0.00 20 0 0 0 60 6 228 0 6 c)AED excursion 0 12 Envelope loss/gain 0 0 510 235 12 a) Infiltration 0 0 64 18 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 75 Subtotal(lines 6 to 13) 0 0 574 328 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 0 0 574 328 15 Duct loads 19% 41% 0 0 19% 41% 109 135 Total room load 0 0 682 463 Air required(cfm) 0 0 24 21 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Jun-10 08:24:41 Right-SuiteO Universal 2021 21.0.02 RSU08101 1' ✓ ......... Page 2 ...HVAC\WITHERS RESIDENCE-1106 NETTLES ISLAND.rup Calc=MJ8 Front Door faces: S IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: Jun 10,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name WIC KITCHEN 2 Exposed wall 18.0 ft 45.4 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 10.0 x 7.0 ft 1.0 x 304.0 ft 5 Room area 70.0 ft2 304.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�/ 13AB-0fcs 0.183 n 5.12 3.18 0 0 0 0 0 0 0 0 I;�C 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 ne 5.12 3.18 0 0 0 0 0 0 0 0 11 W 13AB-Ofcs 0.183 e 5.12 3.18 8 8 41 25 184 175 897 557 I; GCI 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 9 0 164 304 W 13AB-Ofcs 0.183 se 5.12 3.18 0 0 0 0 75 63 325 202 I; GCI 2 glazing,clr low-e 0.650 se 18.20 25.27 0 0 0 0 12 2 218 303 2 glazing,clr low-e 0.650 se 18.20 25.63 0 0 0 0 0 0 0 0 V�/ 13AB-Ofcs 0.183 s 5.12 3.18 80 80 410 255 40 20 102 63 I�GCI 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 20 20 366 301 13AB-Ofcs 0.183 w 5.12 3.18 56 56 287 178 64 64 328 204 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 2 alazina,clr low-e 0.650 w 18.20 20.97 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 nw 5.12 3.18 0 0 0 0 0 0 0 0 G 2 glazing,clr low-e 0.650 nw 18.20 26.88 0 0 0 0 0 0 0 0 Cr 16X19-0md 0.408 1.59 1.37 13 13 21 18 56 56 89 77 F 22A-tph 1.358 38.02 0.00 70 18 684 0 304 45 1727 0 6 c)AED excursion -25 -117 Envelope loss/gain 1443 452 4216 1896 12 a) Infiltration 191 54 483 136 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 350 Subtotal(lines 6 to 13) 1634 505 4699 2382 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1634 505 4699 2382 15 Duct loads 19% 41% 309 209 19% 41% 889 983 Total room load 1943 714 5588 3364 Air required(cfm) 67 32 193 151 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Jun-10 08:24:41 Right-SuiteO Universal 2021 21.0.02 RSU08101 1' ✓ ......... Page 3 ...HVAC\WITHERS RESIDENCE-1106 NETTLES ISLAND.rup Calc=MJ8 Front Door faces: S IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: Jun 10,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name M BEDROOM M WIC 2 Exposed wall 40.0 ft 6.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 201.0 ft 6.0 x 6.0 ft 5 Room area 201.0 ft2 36.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�j13AB-OFcs 0.183 n 5.12 3.18 56 23 115 72 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 34 0 610 502 0 0 0 0 W 13AB-Ofcs 0.183 ne 5.12 3.18 29 29 148 92 0 0 0 0 11 W 13AB-Ofcs 0.183 e 5.12 3.18 80 80 410 255 0 0 0 0 I; GCI 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 se 5.12 3.18 0 0 0 0 0 0 0 0 I; GCI 2 glazing,clr low-e 0.650 se 18.20 25.27 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 se 18.20 25.63 0 0 0 0 0 0 0 0 V�/ 13AB-Ofcs 0.183 s 5.12 3.18 0 0 0 0 0 0 0 0 I�GCI 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 13AB-Ofcs 0.183 w 5.12 3.18 40 36 184 115 48 44 225 140 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 33.77 4 0 73 135 4 0 73 135 2 alazina,clr low-e 0.650 w 18.20 20.97 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 nw 5.12 3.18 115 86 443 275 0 0 0 0 G 2 glazing,clr low-e 0.650 nw 18.20 26.88 29 0 528 779 0 0 0 0 Cr 16X19-0md 0.408 1.59 1.37 201 201 319 275 36 36 57 49 F 22A-tph 1.358 38.02 0.00 0 0 0 0 0 0 0 0 6 c)AED excursion 92 38 Envelope loss/gain 2829 2592 355 363 12 a) Infiltration 425 120 64 18 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 200 0 Subtotal(lines 6 to 13) 3254 2912 419 381 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 19 16 14 12 14 Subtotal 3273 2927 433 393 15 Duct loads 19% 41% 620 1208 19% 41% 82 162 Total room load 3893 4135 515 555 Air required(cfm) 135 1186 18 25 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Jun-10 08:24:41 Right-SuiteO Universal 2021 21.0.02 RSU08101 1' ✓ ......... Page 4 ...HVAC\WITHERS RESIDENCE-1106 NETTLES ISLAND.rup Calc=MJ8 Front Door faces: S IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: Jun 10,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name STAIRS UP W/D 2 Exposed wall 8.0 ft 0 ft 3 Room height 14.7 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 9.0 x 8.0 ft 3.0 x 6.0 ft 5 Room area 72.0 ft2 18.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�/ 13AB-0fcs 0.183 n 5.12 3.18 0 0 0 0 0 0 0 0 I;�C 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 ne 5.12 3.18 0 0 0 0 0 0 0 0 11 W 13AB-Ofcs 0.183 e 5.12 3.18 0 0 0 0 0 0 0 0 I; GCI 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 se 5.12 3.18 0 0 0 0 0 0 0 0 I; GCI 2 glazing,clr low-e 0.650 se 18.20 25.27 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 se 18.20 25.63 0 0 0 0 0 0 0 0 V�/ 13AB-Ofcs 0.183 s 5.12 3.18 0 0 0 0 0 0 0 0 I�GCI 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 13AB-Ofcs 0.183 w 5.12 3.18 128 104 533 331 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 2 alazina,clr low-e 0.650 w 18.20 20.97 24 0 437 503 0 0 0 0 W 13AB-Ofcs 0.183 nw 5.12 3.18 0 0 0 0 0 0 0 0 G 2 glazing,clr low-e 0.650 nw 18.20 26.88 0 0 0 0 0 0 0 0 Cr 16X19-0md 0.408 1.59 1.37 80 80 127 109 18 18 29 25 F 22A-tph 1.358 38.02 0.00 60 8 304 0 0 0 0 0 6 c)AED excursion 234 -1 Envelope loss/gain 1401 1178 29 23 12 a) Infiltration 170 48 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 1571 1225 29 23 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 35 28 -29 -23 14 Subtotal 1605 1254 0 0 15 Duct loads 19% 41% 304 517 19% 41% 0 0 Total room load 1909 1771 0 0 Air required(cfm) 6618010 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Jun-10 08:24:41 Right-SuiteO Universal 2021 21.0.02 RSU08101 1' ✓ ......... Page 5 ...HVAC\WITHERS RESIDENCE-1106 NETTLES ISLAND.rup Calc=MJ8 Front Door faces: S IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: Jun 10,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name HALLWAY M TOILET 2 Exposed wall 0 ft 3.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 64.0 ft 8.0 x 3.0 ft 5 Room area 64.0 ft2 24.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�/ 13AB-0fcs 0.183 n 5.12 3.18 0 0 0 0 0 0 0 0 I;�C 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 ne 5.12 3.18 0 0 0 0 0 0 0 0 11 W 13AB-Ofcs 0.183 e 5.12 3.18 0 0 0 0 24 20 102 64 I; GCI 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 4 0 73 135 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 se 5.12 3.18 0 0 0 0 0 0 0 0 I; GCI 2 glazing,clr low-e 0.650 se 18.20 25.27 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 se 18.20 25.63 0 0 0 0 0 0 0 0 V�/ 13AB-Ofcs 0.183 s 5.12 3.18 0 0 0 0 0 0 0 0 I�GCI 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 13AB-Ofcs 0.183 w 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 2 alazina,clr low-e 0.650 w 18.20 20.97 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 nw 5.12 3.18 0 0 0 0 0 0 0 0 G 2 glazing,clr low-e 0.650 nw 18.20 26.88 0 0 0 0 0 0 0 0 Cr 16X19-0md 0.408 1.59 1.37 64 64 101 88 24 24 38 33 F 22A-tph 1.358 38.02 0.00 0 0 0 0 0 0 0 0 6 c)AED excursion -4 -4 Envelope loss/gain 101 83 213 228 12 a) Infiltration 0 0 32 9 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 101 83 245 237 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -101 -83 9 7 14 Subtotal 0 0 254 244 15 Duct loads 19% 41% 0 0 19% 41% 48 101 Total room load 0 0 302 345 Air required(cfm) 1 01 01 1 1 101 16 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Jun-10 08:24:41 Right-SuiteO Universal 2021 21.0.02 RSU08101 1' ✓ ......... Page 6 ...HVAC\WITHERS RESIDENCE-1106 NETTLES ISLAND.rup Calc=MJ8 Front Door faces: S IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: Jun 10,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name M BATH CLST 3 2 Exposed wall 11.0 ft 2.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 8.0 x 11.0 ft 7.0 x 2.0 ft 5 Room area 88.0 ft2 14.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�/ 13AB-0fcs 0.183 n 5.12 3.18 0 0 0 0 0 0 0 0 I;�C 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 ne 5.12 3.18 0 0 0 0 0 0 0 0 11 W 13AB-Ofcs 0.183 e 5.12 3.18 88 84 430 267 16 16 82 51 l; GCI 2 glazing,clr low-e 0.650 a 18.20 33.77 4 0 73 135 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 se 5.12 3.18 0 0 0 0 0 0 0 0 I; GCI 2 glazing,clr low-e 0.650 se 18.20 25.27 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 se 18.20 25.63 0 0 0 0 0 0 0 0 V�/ 13AB-Ofcs 0.183 s 5.12 3.18 0 0 0 0 0 0 0 0 I�GCI 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 13AB-Ofcs 0.183 w 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 2 alazina,clr low-e 0.650 w 18.20 20.97 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 nw 5.12 3.18 0 0 0 0 0 0 0 0 G 2 glazing,clr low-e 0.650 nw 18.20 26.88 0 0 0 0 0 0 0 0 Cr 16X19-0md 0.408 1.59 1.37 88 88 140 120 14 14 22 19 F 22A-tph 1.358 38.02 0.00 0 0 0 0 0 0 0 0 6 c)AED excursion -23 -4 Envelope loss/gain 643 500 104 67 12 a) Infiltration 117 33 21 6 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 100 0 Subtotal(lines 6 to 13) 760 633 125 73 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 99 66 -125 -73 14 Subtotal 858 698 0 0 15 Duct loads 19% 41% 162 288 19% 41% 0 0 Total room load 1021 986 0 0 Air required(cfm) 35 44 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Jun-10 08:24:41 Right-SuiteO Universal 2021 21.0.02 RSU08101 1' ✓ ......... Page 7 ...HVAC\WITHERS RESIDENCE-1106 NETTLES ISLAND.rup Calc=MJ8 Front Door faces: S IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: Jun 10,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name BEDROOM 3 BEDROOM 2 2 Exposed wall 20.6 ft 22.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 120.0 ft 1.0 x 133.0 ft 5 Room area 120.0 ft2 133.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�/ 13AB-OFcs 0.183 n 5.12 3.18 0 0 0 0 0 0 0 0 I;�C 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 ne 5.12 3.18 0 0 0 0 0 0 0 0 11 W 13AB-Ofcs 0.183 e 5.12 3.18 72 72 369 229 0 0 0 0 l; GCI 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 se 5.12 3.18 93 78 401 249 0 0 0 0 I; GCI 2 glazing,clr low-e 0.650 se 18.20 25.27 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 se 18.20 25.63 15 2 273 384 0 0 0 0 V�/ 13AB-Ofcs 0.183 s 5.12 3.18 0 0 0 0 88 73 374 232 I�GCI 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 15 15 273 225 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 13AB-Ofcs 0.183 w 5.12 3.18 0 0 0 0 88 84 430 267 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 4 0 73 135 2 alazina,clr low-e 0.650 w 18.20 20.97 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 nw 5.12 3.18 0 0 0 0 0 0 0 0 G 2 glazing,clr low-e 0.650 nw 18.20 26.88 0 0 0 0 0 0 0 0 Cr 16X19-0md 0.408 1.59 1.37 120 120 190 164 133 133 211 182 F 22A-tph 1.358 38.02 0.00 12 2 80 0 42 7 264 0 6 c)AED excursion 43 -64 Envelope loss/gain 1314 1070 1625 978 12 a) Infiltration 220 62 234 66 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 300 500 Subtotal(lines 6 to 13) 1533 1432 1859 1544 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 72 44 16 13 14 Subtotal 1605 1476 1875 1557 15 Duct loads 19% 41% 304 609 19% 41% 355 642 Total room load 1909 2085 2229 2199 Air required(cfm) 66 94 77 99 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Jun-10 08:24:41 Right-SuiteO Universal 2021 21.0.02 RSU08101 1' ✓ ......... Page 8 ...HVAC\WITHERS RESIDENCE-1106 NETTLES ISLAND.rup Calc=MJ8 Front Door faces: S IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: Jun 10,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name AHU CLST WIC 2 2 Exposed wall 0 ft 6.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 3.0 x 3.0 ft 1.0 x 33.0 ft 5 Room area 9.0 ft2 33.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�/ 13AB-0fcs 0.183 n 5.12 3.18 0 0 0 0 0 0 0 0 I;�C 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 ne 5.12 3.18 0 0 0 0 0 0 0 0 11 W 13AB-Ofcs 0.183 e 5.12 3.18 0 0 0 0 0 0 0 0 I; GCI 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 se 5.12 3.18 0 0 0 0 0 0 0 0 I; GCI 2 glazing,clr low-e 0.650 se 18.20 25.27 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 se 18.20 25.63 0 0 0 0 0 0 0 0 V�/ 13AB-Ofcs 0.183 s 5.12 3.18 0 0 0 0 0 0 0 0 I�GCI 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 13AB-Ofcs 0.183 w 5.12 3.18 0 0 0 0 48 48 246 153 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 2 alazina,clr low-e 0.650 w 18.20 20.97 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 nw 5.12 3.18 0 0 0 0 0 0 0 0 G 2 glazing,clr low-e 0.650 nw 18.20 26.88 0 0 0 0 0 0 0 0 Cr 16X19-0md 0.408 1.59 1.37 9 9 14 12 33 33 52 45 F 22A-tph 1.358 38.02 0.00 0 0 0 0 0 0 0 0 6 c)AED excursion -1 -10 Envelope loss/gain 14 12 298 188 12 a) Infiltration 0 0 64 18 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 14 12 362 206 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -14 -12 7 6 14 Subtotal 0 0 369 212 15 Duct loads 19% 41% 0 0 19% 41% 70 87 Total room load 0 0 439 299 Air required(cfm) 01 0 15 13 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Jun-10 08:24:41 Right-SuiteO Universal 2021 21.0.02 RSU08101 1' ✓ ......... Page 9 ...HVAC\WITHERS RESIDENCE-1106 NETTLES ISLAND.rup Calc=MJ8 Front Door faces: S L-7 wrignI Duct System Summary Job: Date: Jun 10,2021 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM Project • • For: WITHERS RESIDENCE, JWN BUILDERS, LLC. LOT 1106 NETTLES ISLAND, JENSEN BEACH, FL Heating Cooling External static pressure 1.00 in H2O 1.00 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 1.00 in H2O 1.00 in H2O Supply/ return available pressure 0.500/ 0.500 in H2O 0.500/0.500 in H2O Lowest friction rate 1.000 in/100ft 1.000 in/100ft Actual air flow 980 cfm 980 cfm Total effective length (TEL) 167 ft Supply Branch DetailTable Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FIR (in) (in) Matl Ln (ft) Ln (ft) Trunk BATH h 682 24 21 1.000 5.0 Ox0 VIFx 9.8 145.0 st6 BEDROOM 2 c 2199 77 99 1.000 7.0 Ox0 VIFx 8.9 115.0 st2 BEDROOM 3 c 2085 66 94 1.000 7.0 Ox0 VIFx 11.8 115.0 st2 KITCHEN h 5588 193 151 1.000 8.0 Ox0 VIFx 16.4 145.0 st6 LIVING/DINING RM h 3959 137 109 1.000 7.0 Ox0 VIFx 22.0 145.0 st5 LIVING/DINING RM-A h 3959 137 109 1.000 7.0 Ox0 VIFx 22.0 145.0 st5 M BATH c 986 35 44 1.000 6.0 Ox 0 VIFx 13.5 115.0 st 1 M BEDROOM c 2068 67 93 1.000 7.0 Ox0 VIFx 20.7 135.0 st4 M BEDROOM-A c 2068 67 93 1.000 7.0 Ox0 VIFx 21.7 135.0 st4 M TOILET c 345 10 16 1.000 4.0 Ox0 VIFx 23.3 135.0 st4 M WIC c 555 18 25 1.000 5.0 Ox 0 VIFx 14.9 115.0 st 1 STAIRS UP c 1771 66 80 1.000 6.0 Ox0 VIFx 13.5 115.0 st1 WIC h 1943 67 32 1.000 5.0 Ox0 VIFx 12.3 145.0 st6 WIC 2 h 439 15 13 1.000 4.0 Ox0 VIFx 11.5 115.0 st2 SupplyDetail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st5 Peak AVF 274 218 1.000 620 9.0 0 x 0 VinlFlx st3 st6 Peak AVF 284 204 1.000 643 9.0 0 x 0 VinlFlx st3 st3 Peak AVF 558 423 1.000 710 12.0 0 x 0 VinlFlx st4 Peak AVF 145 202 1.000 578 8.0 0 x 0 VinlFlx st1 st1 Peak AVF 264 351 1.000 643 10.0 0 x 0 VinlFlx st2 Peak AVF 158 206 1.000 591 8.0 0 x 0 VinlFlx - --30ft-pp- wrigl 2021-Jun-10 08:24:48 Right-SuiteO Universal 2021 21.0.02 RSU08101 Page 1 �L A-' ...HVAC\WITHERS RESIDENCE-1106 NETTLES ISLAND.rup Calc=MJ8 Front Door faces: S TableReturn Branch Detail Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb1 Ox0 980 980 0 0 0 0 Ox 0 VIFx -- — --311ft°S-'1•F wrigl 2021-Jun-10 08:24:48 Right-SuiteO Universal 2021 21.0.02 RSU08101 Page 2 �L A-' ...HVAC\WITHERS RESIDENCE-1106 NETTLES ISLAND.rup Calc=MJ8 Front Door faces: S This document was created with Win2PDF available at http://www.win2pdf.com. The unregistered version of Win2PDF is for evaluation or non-commercial use only. This page will not be added after purchasing Win2PDF.