HomeMy WebLinkAboutPROJECT INFORMATIONRECEIVED Project wri htsoft° ect Summary Date: Apr16,2021 9 AHU 1 JUN 2 5 2021 By: QUICK CALCS, INC. St. Lucie County Permitting 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772.466-6796 Email: QUICKCALCS(,AOL.COM For: CRADY RESIDENCE, ASSOCIATED BUILDERS 9507 S INDIAN RIVER DRIVE, FORT PIERCE, FL Notes: Weather. Fort Pierce, FL, US Winter Design Conditions Outside db 42 OF Inside db 70 OF Design TD 28 OF Heating Summary Structure 14090 Btuh Ducts 2618 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 16708 Btuh Infiltration Method Construction quality Fireplaces Simplified Average 0 Heating Cooling Area (ft2) 1263 1263 Volume (ft3) 11241 11241 Air changes/hour 0.29 0.15 Equiv. AVF (cfm) 54 29 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat 100 EFF 4.6 kW 15700 Btuh 24 OF 600 cfm 0.036 cfm/Btuh 1.00 in H2O Summer Design Conditions Outside db 90 OF Inside db 75 OF Design TD 15 OF Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Sensible Cooling Equipment Load Sizing Structure 9594 Btuh Ducts 3912 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data Rate/swing multiplier n 0.95 Equipmenf sensible load 12830 Btuh Latent Cooling Equipment Load Sizing Structure 2197 Btuh Ducts 1045 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 3242 Btuh Equipment Total Load (Sen+Lat) 16073 Btuh Req. total capacity at 0.70 SHR 1.5 ton Cooling Equipment Summary Make Lennox Trade LENNOX Cond ML14XC1S018-230A** Coil CBA27UHE-018-230"++TDR AHRI ref 10259433 Efficiency 13.0 EER, 16 SEER Sensible cooling 12600 Btuh Latent cooling 5400 Btuh Total cooling 18000 Btuh Actual air flow 600 cfm Air flow factor 0.044 cfm/Btuh Static pressure 1.00 in H2O Load sensible heat ratio 0.81 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -r k =Ightsof - 2021-Apr-16 11:38:19 s- .�,.,•, Right -Suite® Universal 2021 21.0.02 RSU08101 Page 1 �� E:\Documnets\Wrightsoft WAC\CRADY RESIDENCE.rup Cato = MJ8 Front Door faces: E 14 -�- wrightsoft, Project Summary AHU 2 QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM For. CRADY RESIDENCE, ASSOCIATED BUILDERS 9507 S INDIAN RIVER DRIVE, FORT PIERCE, FL Notes: Weather. Fort Pierce, FL, US Winter Design Conditions Outside db 42 OF Inside db 70 OF Design TD 28 OF Heating Summary Structure 23189 Btuh Ducts 8242 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 31431 Btuh Infiltration Method Construction quality Fireplaces Simplified Average 0 Heating Cooling Area (ft2) 2223 2223 Volume (ft3) 26434 26434 Air changes/hour 0.28 0.15 Equiv. AVF (cfm) 122 66 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 100 EFF 8.4 kW 28509 Btuh 17 OF 1567 cfm 0.050 cfm/Btuh 1.00 in H2O Job: Date: Apr 16, 2021 By: Summer Design Conditions Outside db 90 OF Inside db 75 OF Design TD 15 OF Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Sensible Cooling Equipment Load Sizing Structure 23198 Btuh Ducts 11771 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 33221 Btuh Latent Cooling Equipment Load Sizing Structure 4737 Btuh Ducts 3248 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 7985 Btuh Equipment Total Load (Sen+Lat) 41205 Btuh Req. total capacity at 0.70 S H R 4.0 ton Cooling Equipment Summary Make Lennox Trade LENNOX Cond ML14XC1SO48-230A** Coil CBA27UHE-048-230-FAN AHRI ref 10259429 Efficiency 12.5 EER, 15 SEER Sensible cooling 32900 Btuh Latent cooling 14100 Btuh Total cooling 47000 Btuh Actual air flow 1567 cfm Air flow factor 0.045 cfm/Btuh Static pressure 1.00 in H2O Load sensible heat ratio 0.81 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. 1 -rk- wrightsoft- 2021-Apr-1611:38:19 • ^^ate TM� Right -Suite® Universal 2021 21.0.02 RSU08101 Page 2 dam` E:\Documnets\Wrightsoft WAC\CRADY RESIDENCE.rup Calc = MJ8 Front Door faces: E -- wrightsoft Right-J® Worksheet Job: AHU 1 Date: Apr 16, 2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM 1 Room name AHU 1 BATH 2 2 Exposed wall 142.0 ft 20.0 ft 3 Room height 8.9 ft 8.9 ft heat/cool 4 5 Room dimensions Room area 1263.0 ftz 1.0 x 80.0 ft 80.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuh/ftx-°F) (Btuh/ft) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cod 6 13A0cs .- 2 glazing, clr low-e 2 glazing, clr low-e 0:143 0.450 0.450 n n n 4.00' 0.00 0:00 219 0.00 0.00 312 0 0 -312 0 0 _1247 0 0 - -- 662 0 0 ----62 0 0 - 62 0 0 - 249 0 0 136 0 0 11 2 glazing, clr low a 2 glazing, clr low-e 0.450 0.450 n n 0.00 0.00 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 D 0 2 glazing, clr low-e clrlow .__....__ 0.450 - . 0.450 0.143 n n._ a 0.00 0.00 4.00 0.00 _ - _0.00 2.19 0 .. .._._0 98 0 _- _..0 74 0 - _ ...- 296 0 162 0 0 0 -0 0 0 0 0 0 - 0 0 -._" -.._ ..2.glazing, T�13A-4ocs 2 glazing, clr low-e 2 glazing, clr low-e 0.450 0.450 a a 0.00 0.00 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 D 11 DO - .. - - 13A-4ocs 2 glazing, clr low-e -" - 0.390 6.143 0.450 -e - s s• 10.92 4.00 0.00' _. 10.34 2.19 0.00 . - 24 507 0 -- - --24 357 0 - - - 262 1431 0 - -2` 8 782 0 - - --0 0 0 0 0 0 0 , 0 0 2 glazing, clr low-e ;, 2 glazing, clr low-e 0.450 0.450 s s 12.60 12.60 11.99 11.99 30 96 30 96 378 1210 360 1151 0 0 0 0 0 0 0 0 .2 glazing, clrlow-e ___ . -. .._ 0.450 . s __12.60 _ . 7:98 - 24 _ .. 24 _ _ . 302 _ _ 192 0 _ _ 0 _ _ _ . 0 0 V+! �L--GGG 13A-4ocs 2 glazing, clr low-e 0.143 0.450 w w 4.00 12.60 2.19 30.77 347 15 296 0 1186 189 648 462 116 15 101 0 403 189 220 462 2 glazing, clr low-e 291azinq,cIrlow-e -- 16X19-0md_. .: -_ 0.450 ---_0.450--w---12.60--- : 0.408 w .- 0.00 .1.59 0.00 18.27 . 1.37 0 -- - 36----- -- 57 0 --- __0------454- 57 0 -- 90 0 --658---- :_ 78 0 --0 _ _.- _ 15 0 ----,--Q----- _ - 15 0 0-- _ -- 24. 0 -- -0 21 C F _22A-tph - _-1 358 - 38.02 _ _ _ _ 0.00 - - - _ 1263 _ __142 _ - _ .. 5399 - - -, . _ _ 0___ __ - - 80 _. _ 20 ... _ 760- - - -0 6 c) AED excursion 251 175 Envelope loss/gain 12444 5671 1626 1013 12 a) Infiltration 1646 473 232 67 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 3450 0 Subtotal (lines 6 to 13) 14090 9594 1858 1080 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 609 164 14 Subtotal 14090 9594 2467 1244 15 Duct loads 19% 41% 2618 3912 19% 41% 458 507 Total room load 16708 13506 2926 1751 Air required (cfm) 600 600 105 78 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. 1 wr➢ghtsoft� �� Right-SuiteiN Universal 2021 21.0.02 RSU2021-Apr-16 11:38:19 08101 Page 1 E:\Documnets\WrightsoftWAC\CRADYRESIDENCE.rup Calc = MJ8 Front Doorfaces: E -�- wrightsoft Right-J® Worksheet Job: AHU 1 Date: Apr 16, 2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM 1 Room name H\/AC CLST CLST 2 2 Fposed wall 4.0 ft 2.0 ft 3 Room height 8.9 ft heat/cool 8.9 ft heat/cool 4 5 Room dimensions Room area 7.0 x 4.0 ft 28.0 ft2 7.0 x 2.0 ft 14.0 ft2 Ty Construction U-value Or HTM Area (ftj Load Area (ftj Load number (Btuh/ft'L°F) (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cod Gross N/P/S Heat Cool Grass N/P/S Heat Cod 6 % . 13A�ocs ._ ... ; 2 glazing, cir low-e 2 glazirig, cir'low-e 0.143-_� 0.450 0.450 n n -. --4'00 0.00 0.00 __ -219 0.00 0.00 - ---- _0-_ . 0 0 - 0 -0 .0 --- ---0---------0..0 0 0 0 0 0 0 _- ----. 0 0 0 -.--- -0 0 0 -----0 0 0 11 2 glazing, clr low-e 2 glazing, clr lowm - 0.450 0.450 " n n " 0.00 . 0.00, 6.00 0.00 6 '. 0 0 0 0 0 0 0 0 0 0 0 0 . 0 0 0 2 glazing, cir low-e 2:glazing, cldow-je...- 0.450 0.450 n _ n:..: 0.00 _ 0.00; 0.00 ._ . - :0.00 0 0 0 - _...0 0 ' 0_ 0 . __ ..0 0 - -_-_0 0 .._'- . ' 0 0 - 0 0 0 0.450 a 4.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 2 glazing, 2 glazing, cir low-e 0.450 0.450 a a 0.00 0.00 0.00 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 19D0-----_. ._._, 13A-4ocs 2 glazing, cir low-e .___ 0.390_e_ 0.143 0.450 s s _...10.92._ 4.00 0.00 10.34 -19'. 0.00' -. 0 0 0 0 0 0-- 0 0 _ 0 0 0 0......_..--0---- 0 0 0 -0 0 --0 0 0 2'glazing, clrlow-e 0.450 s 12.60' 11.99' 0 0 0 0 0 0 0 0 2 glazing, cir low-e 2glazing,_clr low.e. _ _ : 0.450 . _. -_ _ 0.450.-, s, s : 12.60' _ - 12.60. 11.99 _. _ ". 7.98' 0 . 0 0 '---.-- _ 0 0 .. - . _ -0- 0 .._ _0__ 0 -0 0 . ----- _- 0 0 _ -.- - - 0 0 _ 0 13A4ocs 0.143 w 4.00 2.19 36 36 143 78 18 18 71 39 2 glazing, cir low-e 0.450 w 12.60 30.77 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.450 w 0.00 0.00 0 0 0 0 0 0 0 0 C. .. _z glazhq, cir low-e.._ _ .16X19710md -- -__-- _ 0.450 _0.408 _w_ -- 12.60 1.% . _._ _18.27 - _ 1.37 _ . . _0 _8 _...__ - 0 - 8 0 .13 _ . 0 ..__... .11 F...._ .22Atph- - _1.358 -=-- -_38.02 _. _0.00 28 _4---- 152---- �- - 14 -_ . --2 76 - 0 6 c) AED excursion -4 -2 Envelope loss/gain 307 85 154 42 12 a) Infiltration 46 13 23 7 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Applianceslother 0 0 Subtotal (lines 6 to 13) 354 98 177 49 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -354 -98 -177 -49 14 Subtotal 0 0 0 0 15 Duct loads 19% 41% 0 0 19% 41% 0 0 Total mom load 0 0 0 0 Air required (cfm) 0 0 0 0 Calculations EIDDroved bvACCA to meet all reauirements of Manual J 8th Ed. -rw wrlightsoftm 2021-Apr-16 11:38:19 Right -Suite® Universal 2021 21.0.02 RSW8101 Page 2 E:\Documnets\WrightsoftWAC\CRADYRESIDENCE.rup Calc = MJ8 Front Doorfaces: E -P- wrightsoft Right-J® Worksheet Job: AHU 1 Date: Apr 16, 2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM 1 Room name BEDROOM 2 LINEN 2 E)posed wall 27.0 ft 6.0 ft 3 Room height 8.9 ft heattcool 8.9 ft heat/cool 4 5 Room dimensions Room area 1.0 x 173.0 ft 173.0 ft2 6.0 x 20 ft 12.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2--°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cod Gross N/P/S Heat Cod Gross N/P/S . Heat Cod 6 13AAocs - 2 glazing, clrlow-e 2 glazing, cir low-e - 0.143 0.450 0.450 n n n 4.00 0.00 0.00 2-19 0.00 0.00 0 0 0 0 0 0 - - - 0 0 0 - - 0 0 0 -63 0 0 - - 53 0 0 214 0 0 117 0 0 2 glazing, cir low- 0.450 n 0.06 0.00 0 0 0 0 0 0 0. 0 11 2 glazing, cir low-e 0.450 n 0.00 0.00 0 0 0, 0 0 0 0 0 2 glazing, cir lower 0.450 n 0.00 0.00 0 0 0 0 0 0 0 0 .2.glazing, cir. lowre. --- _ --_0:450 n_ , _ . 0.00 0.00 0 .-- 0 _- .. -._ 0 - .._. - _0 -_ -. _ 0 . _. - -.0 0 _ 0 13AAocs 0.143 a 4.00 2.19 0 _ 0 0 0 0 0 _ 0 D 2 glazing, cir low-e 2 glazing, cir low-e 0.450 0.450 a a 0.00 0.00 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 D 11 DO. - -- I - - --- - 13A-4ocs 2 glazing, cir lower. - -- 0.390 0.143 0.450 e-- s s - 10.92 4.00 0:00 _ 10.34 2.19 0.00 --0 116 0 -0 92 0 - 0 367 0 -- --0 201 0 -- - 0 0 0 --- - ---- 0- 0 0 0 0 0 0 0 2 glazing, cir low-e 0.450 s 12:60 11.99 0 0 0 0 0 0 0' 0 2 glazing, cir low-e 0.450 s 12.60 11.99 0 0 0 0 0 0 0 0 -. - .2 glazing; cir, low-e .. _ 0.450 - - s 12.60 - 7.98 -- _ - 24 24 -. _302 .192.. - . 0 0 0 - 0. 0.450 w 219 120 89 350 194 0 0 0 0 2 glazing, cir lower 2 glazing, 0.450 w 2.60 12.60 30.77 0 0 0 0 0 0 0 0 2 glazing, cir low-e 0.450 w 0.00 0.00 0 0 0 0 0 0 0 0 2 plazin4, cir low-e _ - 16X19-0md _- . 0.450 0:406 w_ 12.60 1.59 -- 18.27 1.37 .._ 36 19 -- 0 19 454 30 _ -.--. -658 26 -- _ -_ -- .0 0 --- _ _ 0 _ 0 _---- _ --0 0 0 0 -Vh C F -- _ 22A-tph -- - _ ..-- , - 1.3 - -_.. 58 . r--- 38.02 - _. 0.00 173 - - - - - 27 . --, 1027 _-- 0 _ 12 - .6 228 _ . 0 6 c)AED excursion 289 -5 Envelope loss/gain 2535 1559 442 111 12 a) Infiltration 313 90 70 20 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1 2848 1649 1 512 131 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 177 49 -512 -131 14 Subtotal 3025 1698 0 0 15 Duct loads 19% 41% 562 692 19% 41% 0 0 Total room load 3587 2390 0 0 Air required (cfm) 1291 1061 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrigtitsoft- 2021-Apr-16 11:38:19 Right -Suite@) Universal 2021 21.0.02 RSU08101 Page 3 E:\Documnets\Wrightsoft HVAC\CRADY RESIDENCE.rup Calc = MJ8 Front Door faces: E -�- wrightsoft, Right-J® Worksheet Job: AHU 1 Date: Apr 16, 2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM 1 Room name KITCHENETTE PANTRY 2 Exposed wall 18.0 ft 0 ft 3 Room height 8.9 ft heat/cool 8.9 ft heattcod 4 5 Room dimensions Room area 18.0 x 20.0 ft 360.0 ft2 3.0 x 3.0 ft 9.0 ft2 Ty Construction number U-value (Btuh/ft2L-°F) Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cod 6 - -13A4ocs - - 2 glazing, clrlow-e 2'glazing, clrlow-e - 0.143 0.450 0.450 -,n"'-" n n -4.00 0.00 0.00 .. ..219 0.00 ` 0.00 ° . 0 0 __, .... -._0 0 0 -0 0 0 - - -0 0 0 0 0 0 0: 0 0 0 0 0 11 _ .. L�2 D 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clrlow-e 2 glazing, clr. low- 13A-4ocs 2 glazing, clr low-e 2 glazing, clr low-e 11DO ..- - - -- -- 13A-4ocs 2 glazing, cirlow-e 2 glazing, drlow-e 2 glazing, clr low-e 2' glazing, .cir.-lower 2 glazing, clr low-e 2 glazing, 0.450 0.450 0.450 0.450 0.143 0.450 0.450 ----_0.3.90--e 0.143 0.450 0.450 0.450, 0.450 0.450 0.450 n n n n-. a a a s s s s _ _s- w w 0.00 0.00 0.00 _ _ _0.00 4.00 0.00 0.00 --.-10.92 4.00 0.00 12:60 12:60 12.60 2.60 12.60 0.00 0.00 0.00 0.00,- 219 0.00 0.00 _ .-10.34 2-19 0:00 11.99 11.99 . -- _ 7.98 219 30.77 0 0 0 0 0 0 0 - -0 160 0 0 96 - _ 0 0 0 0 0 0 - - _ ' 0 0 0 0 - ---0------�-- 64 0 0 96 -0 0 0 0 0 0 _ _ _ _.0., 0 0 0 257 0 0 1210 -. - --- 0-- 0 0 0 0 0 0 0 0 0 0 140 0 0 1151 .. . -0 0 0 0 0 0 0 _ - -0 0 0 0 --- -0 0 0 0 0 _ _ . --. -0 0 0 0 0 0 _ .. _.. 0. 0 0 0 - --0 0 0 0 0 _ 0 0 0 0 0 0 0 0 0 0 0. 0 0 0 0 A 0 0 0 0 0 0 0 0 0 _ .. 0 0 0 0 0 - 0 0 0 C- 2 glazing, cir low-e 2glazinq,clrlow-e =19-0md 0.450 0.450_w12.60 ;, . 0,408 w . - -.. 0.00 1.59, 0.00 -- 18.27 1.37 0 ----- - 00-_---- 0 0 0 -0___-----.0-_-_.-.- - 0.. 0 .. 0 0 0 0 0 --- -_ 0 - .0. 0 _ ---0 0 0 0 0 _ E. - 22A-tph - -- _1.358 _ ,. - -- 38.02 - 0.00 360 . - -16 - 684 - - 0 9 0 - - 0 - 0 6 c) AED excursion -6 0 Envelope loss/gain 2151 1286 0 0 12 a) Infiltration 209 60 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 500 0 0 0 Subtotal (lines 6 to 13) 2360 1845 0 0 Less wdemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2360 1845 0 0 15 Duct loads 19% 41% 438 752 19% 41% 0 0 Total room load 2798 2598 0 0 Air required (cfm) 100 1151 1 01 0 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -44- 2021-Apr-16 11:38:19 Right -Suite@) Universal 2021 21.0.02 RSU08101 Page 4 ACCE:\DocurnnelskWrightsoftHVACNCRADYRESIDENCE.rup Calc = MJ8 Front Door faces: E -�- wrightsoft' Right-J® Worksheet Job: AHU 1 Date: Apr 16, 2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS ,AOL.COM 1 Room name LAUNDRY HALLWAY 2 3 Exposed wall Room height 7.0 It 8.9 ft heat/cool 0 ft 8.9 ft heat/cool 4 5 Room dimensions Room area 7.0 x 10.0 ft 70.0 ft2 6.0 x 17.0 ft 102.0 ft2 Ty Construction number U-value (Btuh/ft;°F) Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cod Gross N/P/S Heat Cod Gross WP/S Heat Cod 6 11 - 13A-4ocs - 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, cir low-e, 2glazing, cirlow-4 2 glazing, dr low-e 2 glazing,, clr low-e - .. 2 glazing, cir low-e 2 glazing, cir low-e 11D0 - 13A-4ocs 2 glazing; clrlowme 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing, clr lower .. 13A-4ocs 2 glazing, cir low-e 2 glazing, cir low-e 2 glazinq, cir lower. 16X19-0md, - -0.143 0.450 0.450 0.450 0.450 0.450 - -- _ 0.450 0.143 0.450 0.450 - 0.390 0.143 0.450 0.450 0.450 .. -. 0.450 0.143 0.450 0.450 - - 0.450 0.408 n- n n n n n n a a a e_- s s s s _. s-. w w w - w _-. 4.00 0.00 0.00 0.00 0.00 0.00 0.00 4.00 0.00 0.00 _ .._10.92 4.00 0.00 12.60 12.60 _; 12.60 4.00 12.60 0.00 --12.60_ . 1,59 , 219. 0.00 0.00 0.00 0.00 0.00 , 0.00 219 0.00 0.00 _ ..10.34 ' 2.19 0.00 11.99 11.99 ..... 7.98 219 30.77 0.00 ._ 18.27 1.37 -------62 0 0 0 0 0 - : 0 0 0 0 --0 0 0 0 0 .0 0 0 0 _ .0 0 - 62 0 0 0 0 0 .._ . ... _ _ 0, 0 0 0 - - -0 0 0 0 0 . _ - _ 0 0 0 0 - - 0 - 0 - 249 0 0 0 0 0 _. 0'. 0 0 0 ---- - --- 0 0 0 0 0 __ . - A, 0 0 0 - - _.0 0. --- -13_B 0 0 0 0 0 .0 0 0 0 _. - --0 0 0 0 0 - .. _,. _0 0 0 0 _ .. - 0 0 - - 0 0 0 0 0 0 0 0 0 0 - - 0 0 0 0 0 0 0 0 0 - -- . 0 0 -- -- -0 0 0 0 0 0 -0-- 0 0 0 -- --0 0 0 0 0 _ :0 0 0 0 ... _ . 0 . - 0 -0 0 0 0 0 0 0, 0 0 0 - --0. 0 0 0 0 _ -0 0 0 0 - 0 - 0 - 0 0 0 0 0 0 0, 0 0 0 - 0. 0 0 0 0. 0 0 0 0 0 6 , '[�13A-4ocs D C - E. -. -- 22A-tph - 1.358 - _ . -. _ _ _... 38.02 0.00 70 - - 7 - - 266 -- -- ---0 - 102 - _0 - -0 -0 6 c)AED excursion -34 0 Envelope loss/gain 516 102 0 0 12 a) Infiltration 81 23 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 700 0 Subtotal (lines 6 to 13) 597 826 0 0 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 597 826 0 0 15 Duct loads 19% 41% 111 337 19% 41% 0 0 Total room load 708 1162 0 0 Air required (cfm) 25 52 01 0 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. Q. -r- =iofttsoftm 2021-Apr-16 11:38:19 Right -Suite@ Universal 2021 21.0.02 RSU08101 Page 5 E:1Documnets\Wrightsoft HVAC\CRADY RESIDENCE.rup Calc = MJ8 Front Door faces: E �+ wrightsoft' Right-J® Worksheet Job: AHU 1 Date: Apr 16, 2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466.6796 Email: QUICKCALCS@aj40L.COM 1 Room name FOYER LIVING RM 2 Exposed wall 43.0 ft 15.0 ft 3 Room height 8.9 ft heat/cool 8.9 ft heat1cod 4 5 Room dimensions Room area 1.0 x 220.0 ft 220.0 ft2 15.0 x 13.0 ft 195.0 ft2 Ty Construction number U-value (Btuh/ft2L"F) Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cod 6 13A-40cs Y - - - . 2 glazing, .clr low- 2 glazing, clr low-e - - 0.143 0.450 0.450 n n n 4X 0.00 0.00 ' 219 0.00 , 0.00 . 0 ' 0 0 , 0 0 0 0 0 0 0 0 0 134 0 0 134 0 0 . 535 0 0 .. 292 0 0 11 2 glazing, cir 'low-e 2 glazing, clrlow.-e 2 glazing, cir low-e 2 glazing,.cir low-e_ _ 2 glazing, cir low-e 2 glazing, cir low-e 0.450 0.450 0.450 _0.450 0.450 0.143 0.450 0.450 n n n _ .n a a a 0.00 0.00 0.00 0'.00 4.00 0.00 0.00 0.00 0.00 0.00 , - ,.0.00 2.19 0.00 0.00 0 0 0 ... -0 98 0 0 0 0 0 .:-....... -.0 74 0 0 0 0. 0 __ ._ 0 296 0 0 0 0 0 .... - 0'- 162 0 0 0 0 0 ..0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 - 0 0 0 0 b13A-4ocs 11t]0--- -- 13A flocs 2 glazing, cir low- 2,glazing, cir low-e 2: glazing, clrlow-e 2 glazing, clr low-e .. 2 lazi cir low-e 2 glazing, 9 n9� -- - 0.390--e 0.143 0.450 0.450 0.450 ..._ _0.450 0.450 0.450 s s s s -, s. w w --_ 10.92- 4.00 0.00 12.60 12.60 __12.60 _12.60 12.60 2.60 -10.34--- 2.19 0.00 11.99 11.99 :, 7.98 219 30.77 -24 231 0 30 0• _..0 53 0 -24-----262- 201 0 30 0 _ -.. 0 53 0 806 0 378 0 _ _- .0 214 0 - 248--____0_- 441 0 360 0 :. -- -. - -A 110 0 0 0 0 0 . _ _ .- -0 0 0 "--0 0 0• 0 0 - ____,__0 0 0 -----0 0 0 0 0 _ .--. - 0 0 0 0 0 0 . 0 0 0 0 0 2 glazing, cir low-e 2 glaz!Rq, cir lower _ 16X19_0md__. 0.450 _.0.450 0.408 w _w-_ - 0.00 12.60 _-. 1.59,, 0.00 18.27 1.37 0 _ -.0 .. ..11 0 - . . 0 .- -11 0 _______0 - -- 0 --. _ 0 -. 15 0 _ ... 0 -- - - 0 0 .. - 0 - -- -0 0 . - --0.... - 0 0 0 .. 0 _ _ _ C F ._._ 22A-tph _--- . _ -- . -1.358 _. --.- _ --- 38.02 _ 0.00. - _ -- .220 -----_..43 . ---- 16317. 5 .- -- __0 _-- -- 195 15 --- . -- 570 _ 0 6 c)AED excursion -88 -73 Envelope loss/gain 3609 1254 1105 219 12 a) Infiltration 499 143 174 50 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 750 0 0 1500 Subtotal (lines 6 to 13) 4107 2147 1279 1769 Less extemal Iced 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 256 66 14 Subtotal 4107 2147 1535 1835 15 Duct loads 19% 41% 763 875 19% 41% 285 748 Total room load 4870 3022 1820 2683 Air required (cfm) 175 134 65 115 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -r i - ='Sol t mwrt- 2021-Apr-16 11:38:19 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 6 ZCp' EADocumnets\Wrightsoft HVAC\CRADY RESIDENCE.rup Calc = MJ8 Front Door faces: E -�- wrightsoft° Right-J® Worksheet Job: AHU 2 Date: Apr 16, 2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS ,AOL.COM 1 Room name AHU 2 STAIRS UP 2 Exposed wall 266.0 ft 0 ft 3 Room height 11.9 ft 22.5 ft heat/cool 4 5 Room dimensions Room area 2223.0 ft2 4.0 x 20.0 ft 80.0 ft2 Ty Construction number U-value (Btuh/ft'L-°F) Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cod Gross N/P/S Heat Cool Gross N/P/S Heat Cod 6 13A-466; ' - - 2 glazing, clr low- 2 glazing,. clFlow-e 0.143 0.450 0.450 " in n n 400 12.60 12.60 219 11.99 11:99 752 20 15 - -521 0 0 -2086 252 189 - - 1136 240 180 -- -----0 0 0 0 0 . 0 -0 0 0 - 0 0 0 11 2.glazing; clr low-e 2 glazing, clrlow-e 0.450 0.450 n n 12.60 12.60 11.99 11.99 20 72 0 0 252 907 240 863 0 0 0 0 0 0 0 0 2 glazing, clr low- 2_glazing; clr lower -_ _ 13A-4ocs 0.450 . ,_. 0.450 0.143 n n- a 12.60 ; - 12.60 4.00 11.99 _. _ 11:99 219 80 .24 615 0 _ _ 0 541 1013 _ -_ _-302 2166 964 _ ,_.. 288 1184 0 - __-- 0 0 •• 0 ,. 0 0 0 - 0 0 0 0 0 2 glazing, clr low-e 2 glazing, cir low-e 0.450 0.450 a a 12.60 12.60 30.77 30.77 20 54 0 0 252 680 615 1662 0 0 0 0 0 0 0 0 .D 11D0 _ 13A-4ocs 2 glazing, clr low-e _--0.390--e...._ 0.143 .0.450 s s _0.00 4.00 12.60 -.._ 0,00 2.19 11.99 - _.-0 912 45 .-- - -0 741 45 --0----p- 2966 567 1621 540 - --0 0 0 - 0 0 0 _ . _. - 0 0 0 - 0 0 2,glazing, cir low-e 2. glazing, clrlow-e .2.glazing, clr low-e- 13A�ocs 2 glazing, cir low-e 0.450 0.450 -- .0.450 0.143 0.450 s s _-s_ w w 12.60 12.60 -0.00: 4.00 12.60 11.99 11.99 _. _0:00 2.19 30.77 30 96 0. 610 45 30 96 -- 0_ 541 0 378 1210 -. -- -0 2166 567 360 1151 _._0.- 1184 1385 0 0 _-- 0 0 0 0 0 _ _. .0.- 0 0 0 0 _ 0 0 0 0 0 0 0 0 .- VI/ llL---G-GG 2 glazing, clr low-e 2 glazinq, clr low-e 16X19-0md _ 0.450 - - 0.450 0.408 w --w_ '- .-- 12.60 - 0.00 -1.59::_ 30.77 0.00 1.3-7 24 . --0 .. 1911 0 .. 0 . 1911 302 - --- 0 --- _3030 739 - .-.__0 _ _ .. 2615:- 0 .. -- 0 -.. _ 0 0 -0 . -_.0 0 - - - 0 _ 0 0 0 0 C .._. F _ 22A-tph - 1 358 __ . _ 38.02 0.00 - 70 -- - 4 - -140 - --0---- 40 - _0 - 0 0 6 c) AED excursion 0 -37 Envelope loss/gain 19426 16968 0 -37 12 a) Infiltration 3764 1080 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 5150 1400 Subtotal (lines 6 to 13) 23189 23198 0 1363 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 207 109 14 Subtotal 23189 23198 207 1472 15 Duct loads 36% 51% 8242 11771 36% 51% 73 747 Total room load 1 31431 34969 280 2219 Air required (cfm) 1 1567 1567 14 99 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -*- 2021-Apr-16 11:38:19 Right -Suite@ Universal 2021 21.0.02 RSU08101 Page 7 E:\Documnets\Wrightsoft HVAC\CRADY RES[DENCE.rup Calc = M,18 Front Doorfaces: E - wrightsoft® Right-J® Worksheet Job: AHU 2 Date: Apr 16, 2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM 1 Room name M HALL M WIC 2 Exposed wall 9.0 ft 0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 9.0 x 7.0 ft 63.0 ft2 5.0 x 17.0 ft 85.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2L-°F) (Btuh/ft2) or perimeter (ft) ' (Btuh) or perimeter (ft) (Btuh) Heat Cod Gross N/P/S Heat Cool Gross N/P/S Heat Cod 6 ,- 13A flocs - . - 2 glazing, clr low-e 2,glazing, cfr low-e 0.193 0.450 0.450 J n n n 4:00 12.60 12.60 _ ...-219 11.99 11.99 . ' 0 0 0 - - 0 .0 0 - _ - 0 0 0 -- -0 0 0 .-..._ _. 0 0 0 - -- - 0 0 0 - 0 0 0 -- 0 0 0 11 2 glazing, clr low-e 2 glazing, cir low-e 0.450 0.450 n n 12.60 12.60 11.09 11.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, cir low-e 2 glazing,.-clnlow7e_ 13A-4ocs 2 glazing, cir low-e 2 glazing, dr low-e 0.450 0.450 0.143 0.450 0.450 n _n - a a a 12.60, - - -12.60 4.00 12.60 12.60 11,99 - 11 99 219 30.77 30.77 0 _ 0 0 0 0 0 - - _ 0 0 0 0 0 -- -- _ 0 0 0 0 0 _ _ _ ..0 0 0 0 0 0 0 0 0 0 - - - __. _ 0, 0 0 0 0 .. 0 0 0 0 0 0 0 0 0 VVVV����IIll _11D0 __-_---._ . - 13A-4ocs 2 glazing, cir low-e - 0.390 0.143 0.450 e s s --0,00- .4.00 12.60 .-0.00 Z19 11.99 -- 0_- 90 0 __ -- -- 0 90 0 - --�-- 360 0 --0-- 197 0 -0 ' 0 0 - - _0- 0 0 _....0 0 0 _ 0 0 0 2 glazing, cir low-e 2 glazing, clraow-e 2.glezing, cir low-e 2 glazing, cir low-e 0.450 0.450 _0.450 0.143 0.450 s s .. s- w w 12.60 12.60 _0.00 4.00 12.60 11.99 11.99 . 0.00 2.19 30.77 0 0 0 0 0 0 0 -- _. _ 0 0 0 0 0 _ _ . " . 0_ 0 0 0 0 _ . __ 0 0 0 0 0 ...... ____0 0 0 0 0 _ _ 0 0 0 0 0 0 0 0 0 0 0 Vh13A-4ocs 2 glazing, cir low-e 2 glazinq,-clr low-e-- 16X19,Omd. 0.450 - 0.450 0.408 w w - 12.60 0.00- _ 9.5q 30.77 _0.00 ,_ - - 1.37 0 _ .._ 9 . 63 0 _... 0 _. 63 0 - 0 - 100 0 - _.___0 .. --- . _86 0 - - 0 _ 55 0 - -- . -0 _. _ ._ 55 0 _.. __0 _ 87 0 -- 0 75 C F .__._ 22A-tph - 1.358 - - -38.02 _ - 0.00 0 - - 0 -- - 0 - 0 6 c) AED excursion -8 -22 Envelope loss/gain 460 275 87 54 12 a) Infiltration 117 34 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 750 Subtotal (lines 6 to 13) 577 308 87 804 Less odemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 577 -308 130 71 14 Subtotal 0 0 218 875 15 Duct loads 36% 51%1 0 0 36% 51% 77 444 Total room load 0 0 295 1318 Air required (cfm) 0 01 115 59 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ -rW =igti §tso t:- 2021-Apr-16 11:38:19 Right -Suite@ Universal 2021 21.0.02 RSU08101 Page 8 EADocumnetslWrightsoft FIVAMCRADY RESIDENCE.rup Calc = MJ8 Front Door faces: E 1- wrightsoft' Right-J® Worksheet Job: AHU 2 Date: Apr 16, 2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS ,AOL.COM 1 Room name AHU 2 CLST POWDER RM 2 Exposed wall 0 ft 5.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 3.0 x 3.0 ft 9.0 ft2 5.0 x 9.0 ft 45.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft'L°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cod Grass N/P/S Heat Cool Gross N/P/S Heat Cod 6 13A ocs 2 glazing, .cir low-e 2 glazing, cir low-e 0.143 0.450 0.450 n n --- 4.00 12.60 12.60 - 21 I 11.99 11.99 - - -6--- 0 0 - - -0 0 0 - - - 0 0 0 - - -- -0 0 0 - 50 10 0 --- - 40 0 0 - 160 126 0 88 120 0 - 2 glazing, clr low-e '0.450 n 12.60 11.99 0 0 0 0. 0 0 0 0 11 2 glazing, cir low- 0.450 n 12.60 11.99 0 0 0 0 0 0 0 0 2 glazing, cir low-e 2 glazing, clr_low,e .. s 0.450 ` ____0.450 0.143 n . n:_ a 12.60 . 12.60, 11.99 ' 11.99 2.19 0 _' _. ..0 0 0 ,- - 0 0 0 -.. - 0 0 0 _ - _ 0 0 0 .. -- - 0- 0 0 0 0 0 0 0 0 0 0 2 glazing, cir low-e 2 glazing, 2 glazing, cir low-e 0.450 0.450 a a 12.60 2.60 12.60 30.77 30.77 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11D0. - - 13AAocs 2 glazing, cir low-e - 0.390 0.143 0.450 _ _e _ s s . .. _-0.00- 4.00 12.60 - _0..00 Z19 . 11.99 0- 0 0 -0, 0 0 . -0 0 0 - -- 0--- 0 0 0 0 0 - -- 0 0 0 .- 0 0 0 - 0 0 0 2 glazing; cir low-e 2 glazing, cir low-e 0.450 0.450 s s 12.60 12.60 11.99 11.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Vh13A-4ocs 2 glazing, clr.low-e. 2 glazing, cir low-e A.450 0.143 0.450 s _ w w 0.00 4.00 12.60 . A00 2.19 30.77 _ 0 0 0 ._ .._ _ 0 0 0 _ 0 0 0 . _ . _- _ .0 0 0 . __ _._ 0 0 0 ..,- -0 0 0 0 _ . .- 0 0 0 _ 0 0 0 2 glazing, cir low-e 0.450 w 12.60 30.77 0 0 0 0 0 0 0 0 2glazinq, cir low-e 16X19-0md .. __- . 0.450 ; - _ 0.408 _ w - _- -_. 0.00 1.69 0.00 , - 0 - - --0 - ----0 - - -.0 -----0, --- 0 0 -_ .. _ 0 62 C F 22A-tph-. - - 1,358 _ - _ 38.02 . - -0.00 . -- -0 - - - - 0 - -0 - - 0 - 0- 0 - - - 0 0 6 c)AED excursion 0 -18 Envelope loss/gain 14 12 358 251 12 a) Infiltration 0 0 65 19 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 400 Subtotal (lines 6 to 13) 114 12 4231 670 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -14 -12 157 80 14 Subtotal 0 0 580 750 15 Duct loads 36% 51% 0 0 36% 51% 206 381 Total room load 0 0 786 1131 Air required (cfm) 0 0 391 51 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - wrightsoftr 2021-Apr-1611:38:19 Right -Suite@ Universal 2021 21.0.02 RSU08101 Page 9 E:\Documnets\WrightsoftHVACICRADYRESIDENCE.rup Calc = MJ8 Front Door faces: E �+ wrightsoft9 Right-J® Worksheet Job: AHU 2 Date: Apr 16, 2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@4OL.COM 1 Room name M BATH MASTER BEDROOM 2 Exposed wall 18.0 ft 53.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 1.0 x 188.0 It 188.0 ftz 1.0 x 414.0 ft 414.0 ftz Ty Construction number U-value (Btuh/ftl-°F) Or HTM (Btuh/ft) Area (ftz) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cod Gross N/P/S Heat Cod 6 ---13A-4ocs - 2 glazing, cir low-e 2 glazing, clr low-e ".0.143 0.450 0.450 n- n n 4.00 12.60 12.60 - 219 11.99 ' 11.99 _ 80 0 0 - 60 0 0 - --246 0 0 - - 131 0 0 - - Q 0 0 - - :0 0 0 -- -0 0 0 6 0 0 11 2 glazing, clr lows 2glazing, cir low-e 2 glazing, cir low-e 2 glazing, cir lower -.., 13A4ocs 2 glazing, cir low-e 2 glazing, cir low-e 11DO _..- . 13A-flocs 2 glazing, cir lower 2 glazing, clr low-e 2 glazing, clr low-e 2.glazing,.clriow-e __. 13A4ocs 2 glazing, cir low-e 2 glazing, cir low-e 2 glaziRq,.clr.low-e . 16X19-Omd ; . 0.450 0.450 0.450 - :-..0.450 0.143 0.450 0.450 - --- 0.390 0.143 0.450 0.450 0.450 ." 0.450 0.143 0.450 0.450 _- -- 0.450 0.408 n n n n- a a a . -a- s s s s _s w w w _- w-- - 12.60 12.60 12.60 12.60 4.00 12.60 12.60 _0.00. 4.00 12.60 12.60 12.60 .._-0.00. 4.00 12.60 12.60 ---_0.00 1.59 ' 11.99 11.99 11.99 11.99 2.19 30.77 30.77 - --- 0.00 ` 2.19 11.99 11.99 11.99 .. _0.00. 2.19 30.77 30.77 .. _0.00 _ -1:37 20 0 0 _ _ .: '0., 100 10 0 - 0 0 0 0 0 - -0_- 0 0 0 .. _.. _- 0 . 188 0 0 0 _ --,--,0 90 0 0 - - - q 0 0 0 0 -.- ...0 0 0 0 ._-_.__ _ _ 0 _ _ _ 188, 252 .0 0 _ _ _ 0 360 126 0 - ---0 0 0 0 0 .._,. 0 0 0 0 __---.. - __0 -- __.298 240 0 0 _. -.._ -. _ A, 197 308 0 - -- - 0 0 0 0 0 . -.-.. 0 0 0 0 _. ---.-.0 . ... 257 0 0 0 . _.. - 0 270 0 54 a 180 0 30 0 0 80 0 24 ._ __ _ _ .. - _ 40$ 0 0 0 0 216 0 0 - - ---0 150 0 30 0 .. ..... 0.. 56 0 0 -- 408 0 0 0 _... ___0 865 0 680 - -- 0 601 0 378 0 ._- -_0. 224 0 302 . _ 647 0 0 0 0 473 0 1662 -0 328 0 360 0 0 123 0 739 _ - 558 _ - D C - F_ ._ _. _ .22A-tph -- -- _ _ 1.358 _ - - - - 38.02 -- . 0.00 . _18 -0 - - 25 . .. - - 3 --.. 12.2 _ _. 0 1 6 c)AED excursion -31 -116 Envelope loss/gain 1295 1101 3819 4125 12 a) Infiltration 235 67 690 198 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1529 1169 4510 4323 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 176 94 14 Subtotal 1529 1169 4685 4417 15 Duct loads 36% 51% 544 593 36% -T 51% 1665 2241 Ff Total room load 1 2073 1762 6351 6658 Air required (cfm) 103 79 317 298 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -F- wrigtits4Vrt- 2021-Apr-16 11:38:19 " Right -Suite® Universal 2021 21.0.02 RSU08101 Page 10 .�CCA EADocumnets\Wrightsoft WAC\CRADY RESIDENCE.rup Calc = M,18 Front Door faces: E -+ wrightsoft Right-J® Worksheet Job: AHU 2 Date: Apr 16, 2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name HALL DINING RM 2 Exposed wall 7.0 ft 17.0 ft 3 Room height 10.0 ft heat/cool 8.9 ft heat1cod 4 5 Room dimensions Room area 7.0 x 6.0 ft 42.0 ft2 17.0 x 16.0 ft 272.0 ft' Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/fV "F) (Btuh/ft) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cod 6 -_ ._ - - 13A flocs - 2 glazing, clr low-e 2 glazing, cir low-e 0.143 0.450 0.450 n n n 74.00 12.60 12.60 - 2`9 11.99 11.99 70 0, 0 -- -- 70 0 0 - -280 0 0 - - -153 0, 0 -- - ----151 0 0 55 0 0 -- 221 0 0 121 0 0 11 2 glazing, cir low-e 2 glazing, cir low-e 0.450 0.450 n n 12.60 12.60 11.99 11.99 01 0 0 0 0 0 0 0 0 72 0 0 01. 907 0 863 9 90 i �,.clrlow-e--._ . 0.450 .. e . ---- 14.00 -11. 9 _0 .._... 0 ._.. .0 _- __. 0 _ _ , ...244 -_ _ .0 ..__.. 302 . 288 0 ILD 2 glazing, cir Iow-e 2 glazing, cir low-e 0.450 0.450 a a 12.60 12.60 30.77 30.77 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -11D0. _.. .. - 13A- ocs 2 glazing, drlow-e - 0.390 0.143 0.450 ---e-- s s - 0.00- 4.00 12.60 -- 0.00 2.19 11.99 --0 0 0 - -- -0 0 0 _ - --0 0 0 - -- _0 0 0 - ---0 0 0 ---- 0 0 0 --0 0 0 - - - -0 0 0 2 glazing, clr low-e 2 glazing, cir low-e 2glazing, clrlbw-e_. .__ 0.450' 0.450 ..._0.450 s s _.s_'..-_ 12.60 12,60 0.00 11.99 11.99 0.00--- 0 0 -.. 0 0 0 --_.-- -0 0 0 __ ._-_ 0 0 0 - 0- 0 0 0. 0. 0 __ 0 0 0 ___ Q 0 0 -0 VVVVtt������!!!!!! l--G 13A-4ocs 2 glazing, cir low-e 0.143 0.450 w w 4.00 12.60 219 30.77 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 lL��� C,. _ 2 glazing, clr low-e 2 glazing, _cir low- _ _16X19.0md -. 0.450 0.450 0 408 w w " -- 12.60 0.00- 1.5.9 30.77 0.00 ' - 137 0 0 22 0 _.---.--- -0 - .22 0 - - - - - 0 "-35 0 ._ --- 0 - 3-0 0 - . --- - - 0 ._ _.. 32, 0 _0 - _ - 32 0 -- - -- - 0 --51 0 0 44 _ 38.02 . . 0.00 .- ... - 9 - 0 . _ . 6 - ---0 --0 - - 0 -- -- 0. - 0 6 c) AED excursion -5 -67 Envelope loss/gain 315 178 1482 1248 12 a) Infiltration 91 26 197 57 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 1200 Subtotal (lines 6 to 13) 406 204 1679 2505 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -406 -204 152 76 14 Subtotal 0 0 1831 2582 15 Duct loads 36% 51% 0 0 36% 51% 651 1310 Total room load 0 0 1 2482 3891 Air required (cfm) 0 0 11241 174 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -* wrigFxtsoftm 2021-Apr-1611:38:19 '"° Right -Suite® Universal 2021 21.0.02 RSU08101 Page 11 �� E:1DocumnetslWrightsoft HVAC\CRADY RESIDENCE.rup Calc = M,18 Front Door faces: E -�+ wrightsoft' Right-J® Worksheet Job: AHU 2 Date: Apr 16, 2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name LIVING RM 2ND FLR LAUNDRY2ND FUR 2 Exposed wall 17.0 ft 24.0 ft 3 Room height 24.2 ft heaticool 10.0 ft heat/cool 4 5 Room dimensions Room area 17.0 x 17.0 ft 289.0 ft2 12.0 x 12.0 ft 144.0 ft2 Ty Construction number U-value (Btuh/ft2L°F) Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat cool Gross N/P/S Heat Cod Gross N/P/S Heat Cod 6 13A-0ocs -- '2 glazing, cir low-e 2 glazing, cir low-e _0.143 0.450 0.450 - n n n 4.00 12.60 12.60 2.19 11.99 11.99 - 0 " 0 . 0 - - 0 ._ 0 0 -- _ _- _0 0 0 - - 0 0 0 - . 120 0 15 - 105 0 0 - - 420 0 189 230 0 180 11 W �C VVV���lll 2 glazing, cir low-e 2 glazing; ch low-e 2 glazing, cU low-e 2 glazing, cir low-e- . - 13A-4ocs 2 glazing, cir low-e 2 glazing, clr low-e 1113.0. 13A-4ocs 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing,-clr-low-e _. 13AVh-flocs 2 glazing, cir low-e 2 glazing, clr low-e 2 glazinq,_clr lower -- - - 16X19-0md_ -.. 0.450 0.450 0.450 _ 0.450 0.143 0.450 0.450 0.143 0.450 0.450 0.450 --.. --0.450, 0.143 0.450 0.450 _ -. 0.450 0.408 n n n -__n a a a a s s s s _s w w w - --w-- 12.60 12.60 12.60 -_12.60 4.00 12.60 12.60 _0.00 4.00 12.60 12.60 12.60 ..._-.0.00 4.00 12.60 12.60 _--- 0.00 _...1_,59 : 11.99 11.99 11.99 . 11.99 2-19 30.77 30.77 - _U,00... 2.19 11.99 11.99 11.99 :. - -0.00 219 30.77 30.77 _ 0.00 .- 1.37 0 0, 0 0 0 0 0 - 434 45 0 96 .0 112 0 0 _ -- -" -- 0 _ .353 0 0 0 .. 0 0 0 - 293 45 0 96 .. _ 0 112 0 0 -- _ _____0 - _ __.353 0 0 0 _0 0 0 0 - -0 1173 567 0 1210 _ ... - -0 448 0 0 --__-.-� • - ... 560 0 0 0 --- -- -- -_ 0 0 0 0 ---------- U- 641 540 0 1151 -- -_ .. .0 245 0 0 _._ . -__ ____0__ .. _ - 48.3 0 0 0 -_.. _._ :0 0 0 0 - - --0-- 0 0 0 0 __. _____0 120 15 0 - _..-.. 0 _. .-_ 144 0 0 0 0 0 0 0 - ---0-------__0___ 0 0 0 0 _ .-- - '__0 105 0 0 _ . --. _ ---0 _ ._ -144 0 0 0 , ....... 0 0 0 0 0 0 0 0 _ -_ . _ .0 420 189 0 _-- 0 ___ _228 0 0 0 .. 0 0 0 0 0 0 0 0 0 0 230 462 0 _ _0. - 197. .F---- - _- -_ -22A-tph_ . _ - 1.358 - .--- _. __ _ 38.02 0.00 .. ---0 -- 0 '____0_ -0 -- - - 0.- .. 0- 6 c) AED excursion -117 145 Envelope loss/gain 3958 2943 1447 1443 12 a) Infiltration 711 204 313 90 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 1200 0 Subtotal (lines 6 to 13) 4669 4347 1760 1533 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 176 94 0 0 14 Subtotal 4845 4441 1760 1533 15 Duct loads 36% 51% 1722 2253 360/6 51% 625 778 Total mom load 6567 6694 E2385 2311 Air required (cfm) 327 300 119 104 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. ••rw 2021-Apr-1611:38:19 Right -Suite@ Universal 2021 21.0.02 RSU08101 Page 12 AWN E:1DocumnetslWrightsoft HVAC\CRADY RESIDENCE.rup Calc = MJ8 Front Door faces: E -�+ wrightsoft° Right-J® Worksheet Job: AHU 2 Date: Apr 16, 2021 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name KITCHEN 2ND FLR LOFT 2 Exposed wall 33.0 ft 54.0 ft 3 Room height 10.0 ft heat1cool 8.0 ft heat/cool 4 5 Room dimensions Room area 12.0 x 21.0 ft 252.0 ft2 1.0 x 276.0 ft 276.0- ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft-) Load number (Btuh/ft7-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross NI/P/S Heat cod 6 13A-docs - 2 glazing, cir low-e 2 glazing, clrlow-e - _OA43 0.450 0.450 n n n _ A,00 12.60 12.60 _ --.. 21g 11.99 11.99 .- -. ___0 0 0 - --0 0 0 - - - -0._0 0 0 0 0 .. - 180 0 0 _ - ---86 0 0 - 319 0 0 ------- 174 0 0 11 2 glazing, cir low-e 2 glazing, cir low-e 0.450 0.450 n n 12.60 12:60 11.99 11.99 0 , 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, cir low-e 2 glazing,: cir low-e 13A-4ocs 0.450 _.0.450 0A43 n - _n: a 12.60 12.60, 4.00 11.99 11.99 2.19 0 _0 0 0 0 0 0 -- 0,- 0 0 0 0 80 - _0 1M 0 ..-- ._ -.. __0 152 1013 0 609 964 _ . 0 333 VN 2 glazing, clr low-e 2 glazing, cir low-e 0.450 0.450 a a 12.60 12.60 30.77 30.77 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -11DO. - -- .-_. _.. - 13A-4ocs - - 0.390 0.143 _e_ 's .. -,.. _ 0..00 4.00 _ _-0.00 219 _ ._. _0 120 - 0 120 9 480 ------ ---0 263 --- - - 0 32 - - 0._ 32 _ ..- 0 128 0 70 2 glazing, cir low-e 2 glazing, cir low-e 0.450 0.450 s s 12.60 12.60, 11.99 11.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.450 s 12.60 11.99 . 0 0 0 0 0 0 0 0 Uj! 2.'glazing,.-clr low_4_.. 13A-4ocs 0.450 0.143 ---s _ w _ __ 0.00 4.00 _ .. '0.00'_ 219 __0 210 " _ __ .. 0 180 _ . _ _0 721 - _ _ _ 0 394 ._ 0 88 - . _0 88 ,. - 0 352 . - 0 193 2 glazing, dr low-e 0.450 w 12.60 30.77 30 0 378 923 0 0 0 0 IIL--EGG 2 glazing, clr low-e 0.450 w 12.60 30.77 0 0 0 0 0 0 0 . 0 2 glazinq, olr low-e... 16X19.0md ...._ _ 0.450 0.408 -w- - _-- - 0.00- . 1,59 0.00 - 1.37 - -0 _ , 252 --- -0 - _ .. 252 - 0 _- ,- . _400 - --- -0 -_ 345 ____0 -- _ 276 0-- , .. - 276 ______0 4313 0 378 .C, - F_ 22A-tph .. ; - - _1.358.. - 38.02 0•00 - -.0 0 0 --0 ... 0.. -. 0 .__.-. 0 0 6 c) AED excursion 373 -60 Envelope loss/gain 1979 2297 2858 2051 12 a) Infiltration 430 123 563 162 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 2409 2421 3421 2213 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2409 2421 3421 2213 15 Duct loads 36% 51% 856 1228 36% 51% 1216 1123 FTTotal room load 3265 3649 4637 3336 Ajr required (cfm) 163 164 231 149 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -rw wrightsoft 2021-Apr-16 11:38:19 Right -Suite@) Universal 2021 21.0.02 RSU08101 Page 13 EADocumnets\Wrightsoft WAMCRADY RESIDENCE.rup Calc = MJ8 Front Door faces: E -�- wrightsoftm Right-M Worksheet Job: AHU 2 Date: Apr 16, 2021 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M TOILET POWDER RM LOFT 2 Exposed wall 11.0 ft 18.0 ft 3 Room height 9.3 ft heat/cool 9.3 ft heat1cool 4 5 Room dimensions Room area 7.0 x 4.0 ft 28.0 ft2 6.0 x 6.0 ft 36.0 ftz Ty Construction U-value Or HTM Area (ft� Load Area (ft� Load number (Btuh/ft2L-°F) (Btuh/ft�) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Grass N/P/S Heat Cod 6 -: - 13A-4ocs - -- 2 glazing, clr low-e. 2 glazing, clr low-e ---0.1A3 0.450 0.450 - n n 4 00 12.60 12.60 -.. 2.19 11.99 11.99 . -6 10 0 55 0 0 __ .... 221 126 0 121 120 0 - 56 0 0 --66 0 0 - -223 0 0 122 0 0 2 glazing, clr lower 0.450 n 12.60 11.99 0 0 0 0 0 0 0 0 11 2, glazing; cir low-e 0.450 n 12.60 11.99 0 0 0 0. 0 0 0 0 2 glazing, cir low-e 2glazing, clrlow-e-._ ... 0.450 _ .....0.450 n -n,. 12.60 -_.. 12.60,_ 11.99 11.99 0 0 0 -: _. _ .:0 0 ._ .._. 0-0' 0 0 ......_0.. 0 ._....---0 0' _ ..__ . 0 0 __... . 0 13A4ocs 0.143 a 4.00 2.19 37 27 109 60 56 56 223 122 2 glazing, cir low-e 2 glazing, cir low-e 0.450 0.450 a a 12.60 12.60 30.77 30.77 10 0 0 0 126 0 308 0 0 0 0 0 0 0 0 0 D 11D0.-- - .._ .. - 13A-4ocs 2 glazing, cir low-e ---- - 0.390 0.143 0.450 _ e_ s s _ __-- 0.00. 4.00 12.60 _. _0.00 2.19 '11.99 - - 0 0 0 -- ____0 0 0 ____0 0 0 ------0 0 0 - - 0 56 0 - - - --0 56 0 .__0 223 0 - __0 122 0 2 glazing, clr low-e 2 glazing, clr low-e 0.450 0.450 s s 12.60 12:60 11.99 11.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.giazing, cir lower __-. ... .._0.450 0.143,50 s- w _ 0:00: _ 0.00. 2.77 .- .. 0 0 ..... , 0, 0 . 0 0 0 0 ....... 0 0 0 0 0 2 glazing, cir lower 2 glazing, 0.450 w 2.60 12.60 30.77 0 0 0 0 0 0 0 0 2 glazing, cir low-e 0.450 w 12.60 30.77 0 0 0 0 0 0 0 0 2 plazinq, cir lower.- 16X19-0md _.._ - 0 450 - -0.408 - w _- . - --0•0-0 . _ _ 1.59; -0.00 _ 1_.37 __0 - - 28 --- 0 - - - -28 0 _ _44 ---- - -0 _--- -- :38 - -_. - - -- 36 --- - - 0 _ _ ..._36 -- ----0 _ .. 57 . _. _ 0 49 C F - -22A-tph- - - 1'358 - - -- - 3802 - _. 0.00 _ ..-..._-0 - 0 - - 0 - .. -0 - ._.0 - 0 ._ . _. _0. _ -. 0 6 c)AED excursion -23 -13 Envelope loss/gain 626 623 727 403 12 a) Infiltration 133 38 218 63 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 200 0 Subtotal (lines 6 to 13) 759 861 945 466 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 759 861 945 466 15 Duct loads 36°/u 51% 270 437 36% 51% 336 236 Total room load 1029 1298 1281 702 Air required (cfm) 51 58 64 31 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. -lid- 2021-Apr-16 11:38:19 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 14 E:\Documnets\WrightsoftHVAC\CRADYRESIDENCE.rup Calc = M,18 Front Door faces: E Duct System Summary .lob: -�- wrightsoft° y Date: Apr 16, 2021 AHU 1 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM For. CRADY RESIDENCE, ASSOCIATED BUILDERS 9507 S INDIAN RIVER DRIVE, FORT PIERCE, FL Heating Cooling External static pressure 1.00 in H2O 1.00 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 1.00 in H2O 1.00 in H2O Supply / return available pressure 0.500 / 0.500 in H2O 0.500 / 0.500 in H2O Lowest friction rate 1.000 in/100ft 1.000 in/100ft Actual air flow 600 cfm 600 cfm Total effective length (TEL) 184 ft Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 2926 105 78 1.000 6.0 Ox 0 VIFx 10.7 115.0 st1 BEDROOM 2 h 3587 129 106 1.000 7.0 Ox0 VIFx 14.2 115.0 st2 FOYER h 2435 87 67 1.000 6.0 Ox0 VIFx 48.8 135.0 st7 FOYER -A h 2435 87 67 1.000 6.0 Ox 0 VIFx 48.8 135.0 st7 KITCHENETTE c 2598 100 115 1.000 7.0 Ox 0 VIFx 14.2 115.0 st2 LAUNDRY c 1162 25 52 1.000 6.0 Ox 0 VIFx 27.5 115.0 st1 LIVING RM c 2583 65 115 1.000 7.0 Ox 0 VIFx 13.1 115.0 st1 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st7 Peak AVF 175 134 1.000 501 8.0 0 x 0 VinlFlx st2 SO Peak AVF 196 244 1.000 553 9.0 0 x 0 VinlFlx st2 Peak AVF 404 356 1.000 741 10.0 0 x 0 VinlFlx Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb2 Ox 0 600 600 0 0 0 0 Ox 0 VIFx 1 wri htsoft- 2021-ApM611:38:30 s �� ���_�•� 9�wti-r�ma Right -Suite® Universal 2021 21.0.02 RSU08101 Page 1 /�� E:\DocumnetskWhghtsoftHVAC\CRADYRESIDENCE.rup Calc = MJ8 Front Door faces: E ® Duct System Summary Job: wrightsoft y Date: Apr 16, 2021 AHU 2 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS a,10L.COM Project• • For. CRADY RESIDENCE, ASSOCIATED BUILDERS 9507 S INDIAN RIVER DRIVE, FORT PIERCE, FL Extemal static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 1567 cfm Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 1567 cfm 175 ft Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk DINING RM c 3891 124 174 1.000 8.0 Ox 0 VIFx 26.3 115.0 st6 KITCHEN 2ND FLR c 3649 163 164 1.000 8.0 Ox 0 VIFx 31.4 115.0 st6 LAUNDRY 2ND FLR h 2385 119 104 1.000 7.0 Ox 0 VIFx 32.2 115.0 st6 LIVING RM 2ND FLR h 3283 164 150 1.000 8.0 Ox0 VIFx 24.4 150.0 st8 LIVING RM 2ND FLR-A h 3283 164 150 1.000 8.0 Ox0 VIFx 25.4 150.0 st8 LOFT h 4637 231 149 1.000 8.0 Ox0 VIFx 9.4 130.0 st5 M BATH h 2073 103 79 1.000 6.0 Ox0 VIFx 16.1 115.0 st4 M TOILET c 1298 51 58 1.000 6.0 Ox0 VIFx 17.4 115.0 st4 M Wlc c 1318 15 59 1.000 6.0 Ox 0 VIFx 30.1 115.0 st3 MASTER BEDROOM h 3175 158 149 1.000 8.0 Ox 0 VIFx 23.5 115.0 st3 MASTER BEDROOM -A h 3175 158 149 1.000 8.0 Ox 0 VIFx 24.5 115.0 st3 POWDER RM c 1131 39 51 1.000 6.0 Ox0 VIFx 3.6 95.0 POWDER RM LOFT h 1281 64 31 1.000 5.0 Ox 0 VIFx 11.1 130.0 st5 STAIRS UP c 2219 14 99 1.000 7.0 Ox0 VIFx 31.2 115.0 st3 Name Trunk Type Htg (cfm) Clg (cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk st5 Peak AVF 622 481 1.000 793 12.0 0 x 0 VinlFlx st6 Peak AVF 405 441 1.000 562 12.0 0 x 0 VinIFIX st8 Peak AVF 327 300 1.000 741 9.0 0 x 0 VinlFlx st5 st3 Peak AVF 345 457 1.000 582 12.0 0 x 0 VinlFlx st4 Peak AVF 155 137 1.000 443 8.0 0 x 0 VinlFlx * wrightsoft- 2021-Apr-16 11:38:30 �t •�*��w-ray Right -Suite® Universal 2021 21.0.02 RSU08101 Page 2 J CA EADocumnets\Wrightsoft HVAC\CRADY RESIDENCE.rup Cale = MJ8 Front Door faces: E Name Grille Size (in) Htg (cfm) Cig (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mati Trunk rb1 ox0 1567 1567 0 0 0 0 Ox 0 VIFx wrightsoft" 2021-Apr-16 11:38:30 .—•io m••w �� Right -Suite® Universal 2021 21.0.02 RSU08101 Page 3 �� E:\Documnets\Wrightsoft HVAC\CRADY RESIDENCE.rup Calc = MJ8 Front Doorfaces: E