Loading...
HomeMy WebLinkAboutResponses to Commentsi K Y t KELLY ARCHF!OECTS ELL RESIDENTIAL AND COMMERCIAL ARCHITECTURE. SINCE IS60 REG.# 8341 August 25, Mll St.. Lucie County Building. Department 2300 Virginia Avenue Ft Pierce, Florida 34982 RE; Lauletta Residence 804 Winters Creek Road . Palm .City; Florida 34990 Permit Number: 2106-0353 Dear'Sir or. Madam, Please-note'the following regarding the above referenced project: Plans Examiner Review. Comment #1:.Due to the location of the residence a geotechnical report in..-. compliance with and Section 10,7.1 of the FBC 7th Edition 2020 is required. • See attached geotechnical report.' . Comment #2: The structural plans submitted need to be wet signed and sealed or wet signed and embossed 107.1 of the FBC 7th Edition 2020. • Please see attached structural plans wet signed and embossed. Comment #3: The structural plans page S-4.1 is missing legends and details section are incomplete 107.1 of the FBC 7th Edition '2020. • Revised beams on Second Floor Epicore Metal Deck.Plan and added Sections 3, 4 & 5. Lthe ment #4: ' Furnish 2 sets of engineering truss plan and truss drawings (cut ts)'reviewed and approved by the design professional of record. 107.2.1 of BC 20207th Edition. Agreed. Contractor will submit prior to tie beam inspection. Comment #5: Provide the attic access location for the second floor pursuant to R807 of the FBC - Residential. • See Sheet #3 - Second Floor Plan for.location of attic access in Storage Room. Cb� Comment. #6.. The energy calculation is missing the builder information and references the wrong county 107.1 FBC2020 7th Edition. • See attached energy calculation with builder's information. • Please see attached energy calculation with correct county (St. Lucie). • Please Note: Did not include the heat loads with the energy calculations because they remained unchanged with St. Lucie County temperatures. 115 S.W. SIXTH STREET STUART, FLORIDA 34994 (112) 283-3492 UJWUJ. KELLYANDKELLYARCHITECTS. COM I Lauletta Residence Permit Number: 2106-0353 August 25, 2021 Comment #7: The architect plans indicate one gas tankless water heater but the electrical load indicates two electric water heaters. The energy calcs indicate one electric water. Review, correct and resubmit. 107 FBC 2020 7th Edition. • See Sheet #2 — First Floor Plan for location of two tankless gas water heaters. • Two electric water heaters were eliminated from the electrical loads on Sheet #12. • See attached revised energy calculation indicating gas water heater. Comment #8: The energy calcs are missing the exterior frame wall insulation. Review, correct and. resubmit. 107 FBC 2020 7th Edition. • See attached revised energy calculation with exterior frame wall insulation. Comment #9: Provide product approval for the roll down shutters. 107 FBC 2020 7th Edition. • See attached revised Product Approval Affidavit with an approval for a roll down shutters. • See attached two complete copies of product approval for roll down shutter by American Shutter Systems Association, Inc. Comment #10: Provide product approval for the roof covering. 107 FBC 2020 7th Edition. • See attached revised Product Approval Affidavit with an approval for Boral concrete roof tile. • See attached two complete copies of product approval for Boral concrete roof tile. Comment #11: Submit product approval for the roof underlayment. 107 FBC 2020 7th Edition. • See attached revised Product Approval Affidavit with an approval for Boral roof underlayment. • See attached two complete copies of product approval for Boral roof underlayment. • See revised Sheets #4 & 8 indicating Boral roof underlayment in lieu of 90# hot mopped granular felt on sections. Comment #12: Note that the comments are for clarification, correction and or missing documents. Additional review may be required after responding to the comments • Agreed. Page 2 of 3 Lauletta Residence Permit Number: 2106-0353 August 25, 2021 Zoning Comments Comment #1: The survey is incomplete: • Indicate as proposed SFR — See attached revised survey • Indicate setback on the right side to garage — See attached revised survey • Indicate rear setback to house — See attached revised survey • Indicate all covered areas/porches — See attached revised survey • Indicate all dimensions, we are not able to check the proposed structure with the Foundation Plans — See attached revised survey for dimensions along with Sheet #2 — Floor Plan for reference. • Pool required separate permit — See note on Sheet #1. • Remove all indication to existing structure that will not stay on the property — See attached revised survey Comment #2: Please indicate on Page 2 of the building set the sf of living area, porches/ balcony, verandah and garage per floor. • See Sheet #2 for square footage areas as requested. Additional Revisions to Structural Plans: Sheet #S-3: • See highlighted notes. Sheet #S-4: • Revised beams on Second Floor Epicore Slab & Beam Plan • Added Beam Schedule & Beam Details Sheet #S-4.2: • . Revised beams & shoring on Second Floor Epicore Shoring Plan. Certified by, Kelly & Kelly Gary R. Kelly Architect Reg GRK/dm Page 3 of 3