In-Place Density Test Report
Client:K. HOVNANIAN HOMES UES Technician:Mark Rogers
3601 Quantum Blvd.
Boynton Beach, FL 33426
Date Tested:10/04/2021
Project:CMT/CSD Aspire at Waterstone
5130 Armina Place, Ft. Pierce, St. Lucie County, FL 34951
Type of Test:
Area Tested: Lot 32, 5113 Armina Place, Fort Pierce Field:ASTM D-6938 Nuclear Gauge Method
Material:Backfill Laboratory:ASTM D1557 Modified Proctor
Reference Datum:0 = Top of Fill
The tests below meet the 95% minimum compaction requirement.
Test
No.Location of Test Range
Maximum
Density
(pcf)
Optimum
Moisture
(%)
Field Dry
Density
(pcf)
Field
Moisture
(%)
Soil
Compaction
(%)
Pass
or
Fail
1 Northeast corner of lot 0-1 ft 120.1 10.9 117.9 10.5 98 Pass
2 Southwest corner of lot 0-1 ft 120.1 10.9 118.6 10.9 99 Pass
3 Center of lot 0-1 ft 120.1 10.9 116.7 10.3 97 Pass
Remarks:Permit: 2108-0402
Reviewed By
GFA International, Inc
FBPE Registry No.4930
Allan G. Abubakar, P.E.
STATE OF FLORIDA
Professional Engineer No. 69952
This item has been digitally signed and sealed by Allan G.
Abubakar, P.E. on the date adjacent to the seal. Printed copies of
this document are not considered signed and sealed and the
signature must be verified on any electronic copies.