HomeMy WebLinkAboutPRODUCT REVIEWSYSTEM
SENSORO
Indoor Selectablem
Output Horns,
Strobes, and
Horn Strobes for
Wall Applications
SpectrAlert° Advance audible visible notification products
are rich with features guaranteed to cut installation times
and maximize profits.
Features
• Plug-in design with minimal intrusion into the back box
• Tamper -resistant construction
• Automatic selection of 12- or 24-volt operation at
15 and 15/75 candela
• Field -selectable candela settings on wall units: 15, 15/75,
30, 75, 95, 110, 115, 135, 150, 177, and 185
• Horn rated at 88+.dBA at 16 volts
• Rotary switch for horn tone and three volume selections
• Universal mounting plate for wall units
• Mounting plate shorting spring checks wiring continuity before
device installation
• Electrically Compatible with legacy SpectrAlert devices
• Compatible with MDL3 sync module
• Listed for ceiling or wall mounting
Agency Listings
SIGNALING
UL
F M>
ME
LISTED
APPROVED
approved
7125-1653:186 (Indoor strobes)
71 25-1 653:188 (horn strobes,
54011 (chimes, horn strobes, horns)
55512 (strobes)
3023572
MEA452-05-E
chime strobes)
7135-1653:189 (horns, chimes)
f r 9 V s t S r e o r
The SpectrAlert Advance series offers the most versatile and
easy -to -use line of horns, strobes, and horn strobes in the industry.
With white and red plastic housings, wall and ceiling mounting
options, and plain and FIRE -printed devices, SpectrAlert Advance
can meet virtually any application requirement.
Like the entire SpectrAlert Advance product line, wall -mount horns,
strobes, and horn strobes include a variety of features that increase
their application versatility while simplifying installation. All devices
feature plug-in designs with minimal intrusion into the back box,
making installations fast and foolproof while virtually eliminating
costly and time-consuming ground faults.
To further simplify installation and protect devices from construction
damage, SpectrAlert Advance utilizes a universal mounting plate
with an onboard shorting spring, so installers can test wiring
continuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range of
application requirements using field -selectable candela settings,
automatic selection of 12- or 24-volt operation, and a rotary switch
for horn tones with three volume selections:
SpectrAlert Advance Specifications
General
SpectrAlert Advance horns, strobes, and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or
double -gang back box. Two -wire products shall also mount to a single -gang 2 x 4 x 17/8-inch back box. A universal mounting plate shall
be used for mounting ceiling and wall products. The notification appliance' circuit wiring shall terminate at the universal mounting plate.
Also, SpectrAlert Advance products, when used with the Sync•Circuit' Module accessory,_ shall be powered from a non -coded notification
appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification,
appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between
16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full -
wave rectified unfiltered power supply. Strobes and horn strobes shall have field -selectable_. candela settings including 15, 15/75, 30, 75, 95,
110, 115, 135, 150, 177, and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service.
The strobe shall be wired as a primary -signaling notification appliance and comply with the Americans, with Disabilities Act requirements for
visible signaling appliances, flashing at 1 'Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash
tube and associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for
fire protective service. The horn strobe shall be Wired as a primary -signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances, flashing at 1 Hi over the strobe's entire operating voltage range. The strobe light
shall, consist of a xenon flash tube and associated lens/reflector system. The horn shall have three. audibility options and an option to switch
between a temporal three pattern and a non -temporal (continuous) pattern. These options are set by a multiple position switch. On four -wire
products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non -coded
power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module
shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 411/16 x 411/16 x 21/8-inch back box. The module shall also
control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synch ronize'multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32°F to 1209F (0°C to 49°C)
Humidity. Range 10 to 93% non -condensing
Strobe Flash Rate 1 flash per.second
Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR?
Operating Voltage Range2 8 to 17.5 V (12 V nominal) or'16 to 33. V (24 V nominal)
Operating Voltage Range MDL3 Sync Module 8.5 to 1.7.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
Input Terminal Wire Gauge 12'to 18 AWG.
Wall -Mount Dimensions (including lens) 5.6% x 4.7"W.x 2.5"D (142 mm L x 119 mm W. x 64 mm D)
Horn Dimensions 5.6"L x 4.7"W x 1.31D (142 mm L x 119 mm W x 33 mm D)
Wall -Mount Trim Ring Dimensions (sold as a 5 pack) (TR-HS) 5.7"L x 4.8"W x 0.35"D (145 mm L x 122 mm W x 9 mm D)
Notes:
1. Full Wave Rectified (FWR) voltage is a non -regulated, time -varying power source that is used on some power supply,and panel outputs.
2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
UL Current Draw Data
8-17.5 Volts 16-33 Volts
Candela DC FWR DC FWR
Standard 18 123 128 66 71
Candela 15/75 . 142 148 77 81.
Range
30' NA NA ' 94 96
75
NA
NA
158 .
153
95
NA
NA
181
176
110.
NA
NA
202
195
115
NA
NA
210,
205
High 185
NA
NA
228
207
Candela 150
NA
NA'
246
220
Range 117
NA
NA
281
251
185
NA
NA
286
258
UL-Max. Horn Current
..
Sound Patter
dB
8-17.5 Volts
DC FWR
16-33 Volts
DC FWR
Temporal
High
57
65
69
75
Temporal
Medium.
4:4
49 '
58
69
Temporal
Low
38
44
44
48,
Non -temporal
High
57
56 •
69
75 .
Non -temporal
Medium
42
50
60
69
Non -temporal
Low
41
44-
50
.50
Coded
High.
57
55
69
75•
Coded
Medium
.44
51
56
69
Coded
Low
40
46
52
50
Max. Current Draw (mA
DC Input
RMS), 2-Wire
8-1 Z5 Volts
15
Horn
15/75
Strobe,UL ..rd
16-33 Volts
15
Candela Range (15-115
15/75 30
cd)
75
95
110
115
Temporal High
137 . '
147
79
90
107
176
194
212
218.
Temporal.Medium
132'
144
69
80
97
157
182
201
210
Temporal Low
132
143
66
77
'93
1'54
179
198
207
Non-Temporal.High
141
152
91
100
116
176
201
221' '
-229
Non -Temporal Medium
133
145
75
85
102
163 -
187
207
'216
Non -Temporal Low
131
14.4
68
79
96
156
182
201
210
FWR Input'
Temporal High
136
155
'88
97
112
168
190
210
218
Temporal Medium
120
152
78
88
103
160
184
202
206
Temporal Low
129
151 .
76
86
101 .
160
184
194 .
201
Non -Temporal High
142
161
103.
112
126
181
203
221
229.
Non -Temporal Medium. ,
134
155
85
95
110
166
189
208
216 .
Non -Temporal Low
132
154
'80
90
105
161
184
202'
- 211
UL Max. Current •Strobe,
DC Input
16-33 Volts
135 150
117
185
FWR Input
16=33 Volts
135 150
177
185
Temporal High.
245 259
290
297
Temporal High
215 23.1
258
265
Temporal Medium
235 253
288
297
Temporal -Medium
209 224
250
'258
Temporal Low
232. 251
282
292
Temporal Low .
207 221 .
248
.256
Non -Temporal High 255 270 303 309 Non -Temporal High.- 233 248 275 281
Non -Temporal Medium ' 242 259 293_ 299 Non -Temporal Medium 219. 232 •262 .267
Non -Temporal Low 238 254 291 295 Non -Temporal Low 214 229 256 262.
Horn Tones and Sound Output Data
Morn . Morn StrobeOutput
8-17.5 16-33 24-Volt Nominal
Switch Volts Volts Reverberant Anechoic
Position Sound Pattern dB DC, FWR- DC FWR DC FWR - DC FWR
1 Temporal 'High' 78 78 84 ' 84 '88'. 88 ,. 99. 98.
2
Temporal
Medium
75
75•
80
80
86
86
96
96
3
Temporal
Low
71
71
76
76
83
80
94 '
89
4
Non -Temporal
High
82
82
88
88
93
92
100
100
6
Non -Temporal
Medium
'78
78
85
85
90
90
98
98
6
Non -Temporal
Low
73
74
81
81
88
84
96
92
7t
Coded
High
82
82
88
88
93
'92
101
101
8t
Coded
Medium
78
78
85
85
90
90
97.
98
9t
Coded
Low ..
74
75
81
81
88
85
96.
92
tSettings 7, 8, and 9 are not available on 2-wire horn strobes
SpectrAlert Advance Dimensions
Wall -mount horn strobes
SpectrAlert Advance Ordering Information
r..- .- . .
Wall Horn Strobes
P2R
2-Wire Horn Strobe, Standard cd, Red
P2R-P
2-Wire'Horn.Strobe, Standard cd, Red, Plain
P2R-SP
277re Horn Strobe, Standard cd, Red, "FUEGO"
72RH
2-Wire Horn Strobe, High cd, Red'
P2RH-P
2-Wire Horn Strobe, High cd, Red, Plain
P2W
2-Wire. Horn Strobe, Standard cd, White
P2W-P
2-Wire Horn Strobe, Standard cd, White, Plain
P2WH
2-Wire Horn Strobe, High cd, White.
P2WH-P
2-Wire Horn Strobe, High cd, White, Plain
P4R
4-Wire Horn Strobe, Standard cd, Red
P4R-P
4-Wire Horn Strobe, Standard. cd, .Red, Plain
P4RH
4-Wire Horn Strobe, High cd, Red
P4W
4-Wire Horn Strobe, Standard cd, White
Wall Strobes
SR
Strobe, Standard cd, Red
SR-P,
Strobe, Standard cd, Red; Plain
SR-SP.
Strobe,_Staridard cd, Red,"'FUEGO" .. '
ModelDescription
Wall Strobes (cont.).
SRH
_Strobe, High cd, Red
SRH-P
Strobe; High cd, Red, Plain
SRH-SP
Strobe, High cd, 'Red, "FUEGO" .
SW
Strobe,' Standard cd, White
SW-P
Strobe, Standard cd, White, Plain
SWH
Strobe, High cd, White
SWH-P
Strobe, High cd, White; Plain
Horns
HR
Horn, Red
HW
Horn, White
Accessories
TR-HS
Trim Ring, Wall, Red
SBBR
Indoor Surface Mount Back Box, Red
SBBW
Indoor Surface. Mount Back Box; White
Notes:
All -P models have a plain housing (no "FIRE" marking on cover)
All -SP models have "FUEGO" marking on cover
"Standard cd" refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings.
"High cd" refers to strobes that include 135, 150, 177, and 185 candela settings.
o�J 1
STEM 3825 Ohio Avenue • St. Charles, IL 60174 @2014 System Sensor.
�. SENSOR® Phone: 800-SENSOR2 •Fax: 630-377-6495 subjecA to
I., current product information, including the latest version of this data sheet