HomeMy WebLinkAboutAPPROVED Banks - Wind Loads eSEALProject:
Location:
Project ID:
Date:
Design Information
Risk Category II
Windspeed 170 mph
Exposure D
Int. Press. Coef., GCpi(+/‐)0.18
a 6.50 feet
ID
Area
(sqft) Zone
Florida
Product
Approval #
or NOA Manufacturer Model
1.0 126.7 4 20‐0429.09 PGT SGD770 54.9 ‐58.4 90.0 ‐90.0
2.0 94.8 4 20‐0429.09 PGT SGD770 56.5 ‐59.4 90.0 ‐90.0
3.0 102.8 4 20‐0429.09 PGT SGD770 56.1 ‐59.1 90.0 ‐90.0
4.0 72.8 4 20‐0429.09 PGT SGD770 58.0 ‐60.4 90.0 ‐90.0
WALL:Edward K Roske, PE
Select the appropriate fastener size and spacing using the pre‐engineered attachment schedule for the Florida Approved Product(s) or NOA used on this job. The
contractor is responsible to ensure the use of the proper material, reinforcement, components, etc. to meet the indicated pressure per the product approval
engineering document. The contractor is responsible to verify the component is in the appropriate zone using the "a" dimension shown above and diagrams
shown below. The building pressures are calculated using the Allowable Stress Design. Contact Seaside Engineers immediately if the substrate at the attachment
locations appears to have deterioration, abnormalities, damage, or other conditions resulting in questionable integrity.
June 14, 2021
Banks Residence
(722) 202‐8008 info@seasideengineers.com
Prepared for White Aluminum
6/14/2021 www.seasideengineers.com
Jensen Beach, FL 34957 Vero Beach, Florida 32967
Product Design
Pressure (PSF)
SGD
Opening Description
Building Design
Pressure (PSF)
Certificate of Authorization No. 32048
4265 60th Court
Component & Cladding Wind Loads
Calculations by Seaside Engineers
8750 S Ocean Drive, Unit #PH45
SGD
SGD
SGD
4 4
5
5
5
5 a
aa
a
h