HomeMy WebLinkAboutProject Information- wrightsoft Manual S Compliance Report Job: Lot 182 Phase 3 Watersto... ® Date: Entire House By: DCS DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAY,SANFORD,FL32771 Pbore:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Project• • r For: ADAMS HOMES 5326 Vespera Street, Fort Pierce, FL 34951 Cooling Equipment Design Conditions design DB: 90.4 OF Sensible gain: 24176 Btuh Outdoor design W B: 77.4 OF Latent gain: 4767 Btuh Indoor design DB: 75.0 OF Total gain: 28942 Btuh Indoor FIR 50% Estimated airflow: 1167 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Sensible capacity: 26995 Btuh 112%of load Latent capacity: 5613 Btuh 118% of load Total capacity: 32608 Btuh 113% of load SHR: 83% Heating Equipment Design Conditions design DB: 41.0 OF Heat loss: 28592 Btuh Indoor design DB: 70.0 OF Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Output capacity: 31707 Btuh 111 % of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1167 cfm Output capacity: 7.6 kW 91 % of load Temp. rise: 20 OF Meets all requirements ofACCA Manual S. Entering coil DB: 76.4°F Entering coil WB: 63.2°F Entering coil DB: 69.5°F Capacity balance: 36 OF Economic balance: -99 °F .� Wrightsoft® 2021-Jur0809:51:43 ^� •� w ,gym• Rigid-Sute®Uriversal 2021 21.0.02 RSU23828 Page 1 terstorel820CGR\Lotl82Pis3Watersb elB2OCGR.rLp Calc=MJB FrordDoorfaces: W Com onent Constructions Job: Lot 182 Phase 3 Watersto... wrightsoft° p Date: Entire House By. DCS DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phim:407-333-2665 Fax:407-333-3853 Web: WWW.DELAIR.COM iLroject intormation For: ADAMS HOMES 5326 Uespera Street, Fort Pierce, FL 34951 Design Conditions Location: Indoor: Heating Cooling St Lude Cc Inti, FL, US Indoor temperature (OF) 70 75 Elevation: 26 ft Design TD (OF) 29 15 Latitude: 28 °N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (grit) 2.4 56.9 Dry bulb (°F) 41 90 Infiltration: Daily range (°F) - 15 (L ) Method Simplified Wet bulb (T) - Wind speed (mph) 15.0 77 7.5 Construction quality Fireplaces Average 0 Construction descriptions or Area u-value lnsul R Htg HTM Loss Clg HTM Gain ft2 Btuh/ftz°F ftz`F/Btuh BtutVft' Btuh BtuhfiP Stuh Walls 16B-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum board int fish Blk wall,stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh Partitions 12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"A" wood frm, 16" o.c. stud Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang (5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht 10C-v: 2 glazing, clr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.70); 12 ft overhang (6.7 ft window ht, 0.5 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 12 ft overhang (5.3 ft window ht, 0.5 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vni frm mat, dr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang (3.2 ft window ht, 0.8 ft sep.); 6.67 ft head ht n 20 0.049 19.0 1.42 28 2.59 52 e 20 0.049 19.0 1.42 28 2.59 52 s 20 0.049 19.0 1.42 28 2.59 52 W 20 0.049 19.0 1.42 28 2.59 52 all 80 0.049 19.0 1.42 114 2.59 207 n 611 0.201 4.1 5.83 3561 4.06 2481 e 317 0.201 4.1 5.83 1846 4.06 1286 s 534 0.201 4.1 5.83 3113 4.06 2168 W 121 0.201 4.1 5.83 703 4.06 490 all 1582 0.201 4.1 5.83 9224 4.06 6425 270 0.091 13.0 2.64 713 1.31 354 n 49 0.330 0 9.57 469 8.52 418 e 33 0.330 0 9.57 313 22.4 731 s 49 0.330 0 9.57 469 8.52 418 all 131 0.330 0 9.57 1251 12.0 1567 e 18 0.550 0 16.0 285 16.2 289 e 33 0.330 0 9.57 313 8.52 279 s 7 0.330 0 9.57 66 8.52 59 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" w 39 0.330 0 9.57 369 21.0 808 thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.33 ft overhang (6.25 ft window ht, 0.8 ft sep.); 6.67 ft head ht " wrightsoft" 2021-Ami-0809:51:43 +w •t• � mow- �. Right-Sute@Uriversa12021 2l.O.O2 RSU23828 Page 1 ..terstore1820CGR1Lot182PhMaterstore1820CGR.np Calc=MJ8 FrordDoor faces: W 2B-2fv: 2 glazing, dr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" w 7 0.330 0 9.57 67 11.6 81 thk; NFRC rated (SHGC=0.31); 9 ft overhang (1.4 ft window ht, 0.5 ft sep.); 6.67 ft head ht 2B-2fv: 2 glazing, dr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" w 13 0.330 0 9.57 128 13.4 179 thk; NFRC rated (SHGC=0.31); 50%drapes, medium; 9 ft overhang (6.7 ft window ht, 2 ft sep.); 6.67 ft head ht Doors 11 JO: Door, mtl fbrgl type w 20 0.600 6.3 17.4 355 17.6 359 Ceilings 16B-3Oad:Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" 1835 0.032 30.0 0.93 1703 1.69 3100 gypsum board int fish Floors 22A-tpl: Bg floor, light dry soil, on grade depth 212 0.989 0 28.7 6080 0 0 t � Wtrlghtsc ft" 2021 -Jun-08 09:51.43 •r •N ,�mo Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 2 terstorel820CGR\Lotl82PFs3Watersbrel82OCGR.nip Calc=MJB FrortDoorfaces: W - wrightsofto Project Summary Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phom:407-333-2665 Fax:407-333-3853 Web: WWW.DELAIR.COM Project• • Job: Lot 182 Phase 3 Watersto... Date: By: DCS For: ADAMS HOMES 5326 Vespera Street, Fort Pierce, FL 34951 Notes: JA8-18-15 Change to 3.0 ton 2/16/16 S. Finch L. S. 6-8-21 VWK DesicIn Information Weather: St Lude Co Inti, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 °F Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 grflb Heating Summary Sensible Cooling Equipment Load Sizing Structure 24372 Btuh Structure 18399 Btuh Ducts 4220 Btuh Ducts 5777 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh none (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 28592 Btuh Use manufacturer's data Infiltration Rate/swin multiplier Equipmenisensible load 1.00 24176 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3364 Btuh Ducts 1403 Btuh Central vent (0 cfm) 0 Btuh Area Heating Cooling (none) (ftz) 1820 1820 Equipment latent load 4767 Btuh Volume (ft3) 18350 18350 Air changes/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 28942 Btuh Equiv. AVF (cfm) 116 61 Req. total capacity at 0.75 SHR 2.7 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER Trade CARRIER Model 25HBC537AP03 Cond 25HBC537AP03 AHRI ref 204837926 Coil FX4DNF037L00 Efficiency 8.5 HSPF AHRI ref 204837926 Efficiency 12.5 EER,16 SEER Heating input Heating output 34600 Btuh @ 470F Sensible cooling Latentcooling 26250 8750 Btuh Btuh Temperature rise 27 OF Total cooling 35000 Btuh Actual air flow 1167 cfm Actual air flow 1167 cfm Air flow factor 0.041 cfm/Btuh Air flow factor 0.048 cfm/Btuh Static pressure 0.40 in H2O Static pressure 0.40 in H2O Space thermostat Load sensible heat ratio 0.84 Capacity balance point = 36 OF Backup: Input = 8 kW, Output = 25913 Btuh,100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed .�, -rk wri9htsoft2021-Jur0809:51:43 14C'CA Rigid-Sute®Uriversal 2021 21.0.02 RSU23828 Page 1 terstorel820GGR1Lotl82Pts3Watersbrel82000R.rLp Calc=MJ8 FrordDoorfaces: W - wrightsoftRight-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: WW W.DELAIR.COM Job: Lot 182 Phase 3 Waterston 1... Date: By: DCS 1 Room name Entire House BDRM2 2 3 Exposed wall Room height 212.0 It 36.0 It 4 Room dimensions 10.0 ft d 10.0 ft heaUcool 5 Room area 1835.0 It! 13.0 x 13.0 ft 169.0 ftz Ty Construction U-value Or HTM Area (ft') Load Area (ftz) Load number (Btuh/ -fl (BtuhRt2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Gross N/P/S Heat Cool Gross N/P/S Heat Cool Heat Cool 6 1N'____ VV 16Br19ad_--- Blk wall, stuao extt 004E 40.201 .,..n_ n 142 - - 5 83 259 4.06 _. . _20 660 _ _ < 20 611 28 ' "M52 2481 .:�0 130 .__ _ _0 130 __0 _ _._0. 3561 _( 2A-2ov 0.330 n 957 852 49 0 469 418 0 758 528 11 _._ 19ad---.___.� _ _ Blk wall, stucco eM 10C-v _._ _: 0049 0201 0.550 __ 1,42 5.83 15.95 259 4.06 1620 _ _ __20 400 18 _ _.?0 317 18 _ _ - - 28 '1846 285 _ _. _ 52 1286 289 0 130 0 0 .. w9 114 0 0 663 0 _o 461 e_: a a 2A-2ov 0230 a 957 22.36 33 2 313 731 16 1 0 156 0 365 2A 2ov 0230 a ,. 957 852 33 33 313 279 0 0 0 0 W 16B19ad.:� : Blk yell, stu000 ext 2A-2ov _ _0049 0.201 _s- s _ 1:42 5.83 _.._259 4.06 `_.y'20,-_ 590 .._20 534 - -v _=.__ 28 3113 ---.52 2168 _ _0 100 v- 0 100 - ----, - -Lo 583 .,._. .,_0. 406 0.330 s 957 852 7 7 66 59 0 0 0 0 2A2ov _ 0330 0049 s_ -957 1,42 ...,_8.52 49 20 49 , ___.469 28 _. 418 Blk wall, stu000 ext 2A-2ov 0.201 0.330 -_w _ w w _ - 5B3 957 _259 4.06 2097 206 39 __--�_-.?0 121 2 _ _._.� 703 369 __.._ _52 460 808 0 0 0 0 0 0 _ 0 0 2B-2fv 0.330 w 957 11.58 7 7 67 2B-2fv 0.330 w 957 1325 13 11 128 81 179 0 0 0 0 0 0 0 0 11Jo 0600 0 091 w _wr 17.40 _ ..264 17.58 1.31_ 20 _ 270 20 ,270 __. 355 359 0 0 ,_ 0 0 ' 0. C -_ 16E00ad., _ ......0032 _0.98.9 _-_rv_ _ _-- _ 0.93 -.-_28.68 ,._,- 169 _ 0.06 _ 1835 -_-_1835 ., ,. 1835 __ _.212 _ __,1703 _ -._,._ 3100. _� _169 __„_ , 169 _. 38 _ ..._ . 157 _-- -- _1033 _ 280 ---- ___0 6 c) AED excursion 107 2 Envelope loss/gain 20668 13813 3349 2048 12 a) Infiltration b) Room ventilation 3704 1035 691 193 0 0 0 0 13 Internal gains: Occupants@ 230 5 1150 0 0 Appliances/other P400 0 Subtotal (lines 6 to 13) 24372 18399 4040 2241 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 15 Subtotal Duct loads 24372 18399 4040 2241 17% 31 % 4220 5777 17% 31% 700 704 Total room load Air required (cfm) 28592 24176 4739 2945 1167 1167 193 145 Calculations approved byACCAto meet all requirements of Manual J 8th Ed �- wrightsoft^ Right-Srite®Uriversa12021 21.0.02 RSU23828 2021-Jun-0809:57:43Page 7 terstore1820CGR\Lot182Phs3Waterstore1820CGR.rLip Calc=MJ8 FrortDoorfaces: W - i- wrightsoft® Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531CODISCOWAY, SANFORD,FL32771Phore:407-333-2665Fax:407-333-3853 Web:WWW.DELAIR.COM Job: Lot 182 Phase 3 Waterston 1... Date: By: DCS 1 Room name BATH BDRM3 2 Exposedwall 6.0 It 13D It 3 Room height 10.0 It heaVcool 10.0 ft heaV000l 4 Room dimensions 13D x 6.0 ft 13D x 13D It 5 Room area 78D ft2 169.0 ft2 Ty Construction U-value Or HTM Area (ftz) Load Area (111) Load number (BtuhRt2-9 (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/Pr5 Heat Cool 6_16819ad,_,_,_— ...._.. 0049 _n .. ..42 -;-259. 0 —" 0 0 _.___..__0 V)/ Blk Blk vdl, stucoo eM 0.201 n 5.83 4.06 60 60 350 244 130 114 663 461 2A-2ov _ 0.330 v n _ 9,57 852 0 0 0 0 16 0 156 139 w- ;168�19$d_.- :. a 142 _ _.259 _,.._._.0 r_'0 M _ . _.. _ _ _0049 l l �Blk well, stucoo e)d 10C-v 0.201 0550 a a 5.83 15.95 4.06 1620 0 0 0 0 0 0 0 0 ___0 0 0 __--0-_. 0 0 0 0 0 0 2A-2ov 0.330 a 957 2236 0 0 0 0 0 0 0 0 2A-2ov _ _._�'_:. 0.330 a 957 852 0 0 0 0 0 0 0 0 16619ad ___0049 _s• — _1„42_._259 .. Blk yell, stucco eid 2A 2ov 0.201 0230 s s 5.83 957 4.06 852 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 _ 2A-2ov_ __0.330 0049 _s _ _ w_ 957 _ .. 1,42, _, 852 _ ,_ 259 0 ._ .. _,._ 0 --_... _ 0 _. 0 _. __. _ .-0 -_ . _ ..__,0 _... .._ 0 -- .—,_ 0 .__ 0 ._. 8 ...0 .._ _0 0 _ 0 Blk wall, stucco e)d 2A-2ov 0.201 0.330 w w 5B3 957 4.06 2027 0 0 0 0 0 0 0 0 _._ 0 0 0 0 0 0 0 0 213-21v 0230 w 9.57 11.58 0 0 0 0 0 0 2B-2fv 0330 w 957 1325 0 0 0 0 0 0 0 0 0 0 __-. 11J0 .. 0.600 w 17AO 1758 0 0 0 0 0 0 0 0 P 12C 0sw .- _0W 264 131 __ 0 0 C _._. 16B-30ad_ _ ._ .__0032 u89 _� _ 023_ 1.69 _- 78 _ 78 72 132 -_ �0 169 _f __ 169 _0 _ 157 --__ _ --_28.68, 0.00. 77, :_7.8 _— _ _6 172 __ ._ _. 0 _. 1.69 _ _... _--13 6 c) AED excursion -19 -46 Envelopeloss/gain 594 356 1349 841 12 a) Infiltration 115 32 249 70 b) Room ventilation 0 0 0 0 13 Internal gains: OocupantsQa 230 0 0 0 0 Appliancesslother 0 0 Subtotal (lines6 to 13) 709 388 1598 910 Less e)dernal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 709 388 1598 910 151 Duct loads 17% 31%1 123 122 17% 31 % 277 286 Total room load 832 510 1875 1196 Air required (ctm) 34125 77 58 Calculations approved byACCAto meet all requirements of Manual J 8th Ed 4ja- wr7ghtsoTt• A Right-SuPage 2te®Uriversal 2021 21.0.02 RSU23828 2021-Jur08 09:age 2 ...terstore1820CGR\Lot182PIs3Waterston ne1820CGR.p CaIc=MJB FrordDoorfaces: W - wrightsoft° Right-J® Worksheet Job: Lot 182 Phase 3 Waterston 1... Entire House Date: DEL AIR KrG, A/C & REFRIG. INC By: DCS 531 CODISCO WAY SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: WW W.DELAIR.COM 1 Room name DINING/FOYER DENBDRM4 2 3 4 5 Exposed wall Room height Room dimensions Room area 25.0 It 10.0 it heaVwcl 1.0 x 276.0 It 276.0 ft2 31.0 It 10.0 ft heat/cool 13.0 x 13.0 It 169.0 ft2 Ty Construction number U-value (BtuhHtz-'q Or HTM (Btuht2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PS Heat Cool 6 11 V/ ,_u, V?/ Imo_ _ W _ VhBIk _ _. _J6619ad-,_ P C.__- E ,- 16619ac1,__._.-__0049 BIk wall, stucco ext 2A 2ov _ 16B-19atl �_ _ _ �.__ vidl, stucco ext 10C-v 2A-2ov 2A-2ov BIk v�all, stucco e)d 2A 2ov 2A2ov .___._. BIk Ml, stu000 ext 2A-20v 2B-2fv 2B-2fv 11J0 16B-30ad _ 22A_>pl : -n ..__ :. _: 0.201 0230 0201 0.550 0.330 0.330 _-_0049 0201 0.330 0.330 .. 0049_w-. 0201 0.330 0.330 0.330 0.600 0 091 ___-_ 0032 _._ �0989 n n _ a a a a --s-. s s s._ w w w w w _ _ _ ;._ _ 5,83 957 Y_ 5B3 15.95 957 957 .-:1.42 5,83 957 957• __142 5B3 957 957 957 17.40 2,64 -__ 0.93 .28.6$ 259 4.06 8.52 . _ _. _ 0 110 33 �0 0 0 0 0 -- -- 0 0 -0 __,_0__: 70 0 7 13 20 70 _ - 276 _ '..__ 276�31 .. __. ;Q 77 0 0 0 0 0 ----- -;0 0 0 0 _ ._ 0-- 29 0 7 11 20 -- 70 __ ,_ 276 __,.�. 0 451 313 V 0 0 0 0 ._. 0 0 0 0 ____ 0�_._0_Q 170 0 67 128 355 : _ 185 _ _ 256 ____.___U 314 _ 279 0 0 0 0 - -.:.0 0 0 __ 0 119 0 81 179 359 .. _ _ _ 92 466 _ -_ _. 0 130 __. 0 0 0 0 0 . __ 0 50 0 __ 0_ 130 39 0 0 0 0 169 ._ --•--4 130 _,. 0 0 0 0 0 r _� _0 50 0 _0 ____ �---- 91 2 0 0 0 _ 0 .-_ _- 169 ,r_. 0. 758 .. .__.. 0 0 0 0 0 _�..-._ 291 0 0 __-Q 533 369 0 0 0 . - _. _0 . 157 _ -889 _ A 528 _ _ 0 0 0 0 0 203 0 _0 -0 371 808 0 0 0 - - 286 . _„,...-_ 0. 4.08 1620 22.36 852 -'_2 4.06 852 8.52 _,__259 4.06 20.97 11.58 13.35 1758 131_ 1.69 -_-- 0.00 6 c) AED exarsion P88 348 Envelope loss/gain 2642 2176 2997 2544 12 a) Infiltration b) Room ventilation 345 0 97 0 595 0 166 0 13 internal gains: Occupants@ 230 Appliances/other 1 230 0 0 0 0 Subtotal (lines6 to 13) 2987 2502 3592 2710 14 15 Less extemalload Less transfer Redistribution Subtotal Dud loads 179/. 31 % 0 0 0 2987 517 0 0 0 2502 786 17 % 31 % 0 0 0 3592 622 0 0 0 2710 851 Total room load Air required (dm) 3504 143 3288 159 4214 172 3561 172 Calculations approved bvACCAto meet all requirements of Manual J 8th Ed. -43 wrigf•�ts4�ta- AeuA Right-SuteOUriversal 2021 21.0.02 RSU23828 2021-Jun0 Pa1 e 3 terstore1820CGR\Lot182Pts3Waterstore1820CGR.np Calc=MJ8 FrortDoorfaces: W g - wrightsoft Right-JO Worksheet Job: Lot 182 Phase 3 Waterston 1... Entire House Date: DEL AIR HTG, A/C & REFRIG. INC By: DCS 531 CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM 1 Room name FAMILY RM MSTR BDRM 2 Exposed vvall 13.0 It 41.0 It 3 Room height 10.0 It heat/cool 10.0 ft heaUmol 4 Room dimensions 13.0 x 22.0 It 14.0 x 17.0 ft 5 Room area 286.0 ft2 238.0 ft2 Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuh4t2-Cq (Btuh4t2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross NAS Heat Cool Gross N/PIS Heat Cool 6 W ..__ 16619ad. n _ _ 1.42 - 259 _ _ _ 20 - -20 _� _ 28 Vi/ Blk Hall stucco ext 0.201 n 5B3 4.06 0 0 0 0 100 100 583 406 -G 2A 2ov J 0.330 n 957 8.52 0 0 0 0 0 0 0 0 .16B 19ad _ : _-_ _ ,0049 _e _ _1.42_ ._._ - , . ;_ ..:_2Q :.._ 20 _-_ . 28 _52 V 0 11 Blk vial), stucco e)d 10C-v 2A-2ov 0.201 0550 a a 5.83 15.95 4.06 1620 130 18 79 18 463 285 ___-. 323 289 ., _ ._ A. 140 0 . __._.0 124 0 _.Q 721 0 ._ 502 0 0230 a 9.57 22.36 0 0 0 0 16 1 156 365 2A-2ov 0230 a 957 852 33 33 313 279 0 0 0 0 16&19ad-_ _ - -- -0049 s_ _ -. , 142 259 _ _ ___.20 ^ _._ _20 _._ . 28 --- _-- 92 .,.. _� 0 0 V6Blk Hell, stu000 eM 2A-2ov 0.201 0.330 s s 5.83 957 4.06 852 0 0 0 0 0 0 0 0 170 0 _._ _ 154 0 896 0 624 0 2A 2ov _ - Blk Hall, stucco ext 0 330 0201 s_.. w 957 1,42. 5.83 8.52 259 4.06 - -0 __ _.20 0 -_.0 .__ _.._20-- 0 - - 28 0 0 _. 52 0 1 6 0 - 16 0 - 156 0 _ . _ 139 0 0 2A-2ov 0.330 w 957 20.97 0 0 0 0 0 0 0 0 2B-2N 0.330 w 957 11.58 0 0 0 0 0 0 0 0 2B-2fv 0.330 w 957 13.35 0 0 0 0 0 0 0 0 11J0 0.600 w 17AO 1758 0 0 0 0 0 0 0 0 P 12C Osw :` _ . 009f ._ 264, -121 __0 _ 0 C . -_ ._ -1 6B-30.ad-,,- - _ __ , _„ 0032 _ �_ _ 093 1;69 286 286 265 483 238 - 238 221 - 402 7. _-.---_0989 ._-28,68 ----..,9.00 - ,- _ __0 _ _ .. �_ 238 _ __ _ 6 c) AED excursion -114 -149 Envelope losstgain 1813 1467 3909 2289 12 a) Infiltration 403 113 787 220 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 3 690 1 230 Appliances/other 0 600 Subtotal (lines6 to 13) 2216 2270 4696 3339 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2216 2270 4696 3339 15 Duct loads 179/. 31% 384 713 17 % 31%1 813 1049 Total room load 2600 2982 5509 4388 Airrequired((ftn) 106 144 225 212 Calculations approved bVACCA to meet all requirements of Manual J 8th Ed. Art- A Right -Sate® Universal 2021 21.0.02 RSU23828 2021-Jtpr08 0 Page e 4 terstone1820CGR\Lot182Pts3Waterstore1820CGR.nq� Calc=MJ8 FroNDoorfaces: W g - wrightsoft® Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: WWW.DELAIR.COM Job: Lot 182 Phase 3 Waterston 1... Date: By: DCS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area M BATH 12.0 ft 10.0 It heal/cool 1.0 x 119.0 ft 119.0 ft2 M WIC 0 ft 10.0 ft heaV000l 7.0 x 7.0 ft 49.0 ftz Ty Construction number U-value (Btuh4tZ-F) Or HTM (Btuht2) Area (ftz) or perimeter (ft) Load (Btuh) Area (ft) or perimeter (ft) Load (Btuh) Heat Cool Gross N/PS Heat Cool Gross N/P/S Heat Cool 6 11 W.. __..16B-19ad_ Vj% L—GG W :_. VhBlk C ,;. __.._.. Bik %%all, stucoo ext 2A 2ov :16619ad'� --- -: mall, stucco ext 10C-v 2A-2ov 2A 2ov 16&19ad_ _r. ___ Blk mall, stu000 e)d 2A-2ov 2A 2ov Blk v�all, stu000 ext 2A-2ov 213-2ty 2B-2fv 11J0 2162A&W30�a_d _. 0049 0.201 0.330 _._.�. 0049 0.201 0,550 0230 0230 :_. ?_ _0049 0.201 0230 - _ -230 0.201 0.330 0.330 0.330 0.600 0 091 00093692 n.. n n _e a a a a __s_. s s s . W w w w w w _ -.._ 142 5b3 99557 _-1.42- 5.83 15.95 957 957 _ 1.42 5.83 957 9B7 - 1.42 5.83 957 957 9.57 17AO 2.64 v93 _259 4.06 8.52 ._ _259.,`_ 4.06 1620 2226 852 259 4.06 8.52 8.52.4 ., -.- 259 4.06 2027 11.58 13.35 1758 1.31- 0 - 0 __ . -o 0 0 0 0 __ _ _:0 120 7 .-- - _0 0 0 0 0 0 . 0 0 0 .__ _..__d 0 0 0 0_ ._ 0 113 7 _ .._.:_ .0 0 0 0 0 0 __ 0 12 0 0 0 0 0 01 _- —___Q 659 66 9 A .__._ . _ Q 0 0 0 0 0 0 �+ - 0 0 0'-' 0 0 0 ..__.__ --� 459 59 _ .-_..._ 0 0 0 0 0 0 _ _ 0 201 0 0 0 0 0 0 _ —0 0 0 ..._-_ Y P 0 0 0 0 0 ... _0 49 _..._49 0 0 0 0 0 _ 0 ._ __-6 0 0 __. _0 0 0 0 0 0 _ _. _ .._ _ _0 49 _._-_----r0 0 _.. _0 0 0 0 0 • -- -- --9 0 0 _ ... 0 0 0 0 0 0 45 _- 0 ... W _ u 0 0 0 0 0 _.::_- --0- 0 0 ,-----_ -� 0 0 0 0 0 83F_7 . 6 c)AED..ion _37 -4 Envelope losstgain 1180 682 45 79 12 a) Infiltration b) Room ventilation 230 0 64 0 0 0 0 0 13 Internal gains: Ooipants@ 230 Applianoes/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 1410 746 45 79 14 15 Less extemalload Less transfer Redistribution Subtotal Duct loads 17% 31%1 0 0 0 1410 244 0 0 0 746 234 179/6 31% 0 0 0 45 8 0 0 0 79 25 Total room load Air required (cfm) 1655 681 980 471 53 21 104 5 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -*- wrigF�tso�ft� A Rigld-Suite® Uriversal 2021 21.0.02 RSU23828 Page 5 2021-J rr08 09:age 5 ...terstone1820CGR1Lot182Pls3Watersbre1820CGR.rup CaIc=MJB FronlDoorfaces: W - wrightsofV Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 182 Phase 3 Waterston 1... Date: By: DCS 1 Room name KrrCHENMOOK LAUNDRY 2 Exposed wall 29.0 ft 6.0 ft 3 Room height 10.0 ft heaUmol 10.0 ft heat/000l 4 Room dimensions 1.0 x 246.0 ft 6.0 x 6.0 ft 5 Room area 246.0 ftz 36D ftz Ty Construction U-value Or HTM Area (ft') Load Area (ft') Load number (Btuh/ftz-cq (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W .. _ -166 19ad� _ _-.___0649 . _n _ _ 1.42 __:259 _. __. _ 0 0 0 0 . 0 0 0.. Blk val, stucco ext 0201 n 5.83 4.06 0 0 0 - _ . 0 0 _. 0 _ 0 _ _ . _.._0 0 2A-2ov _ 0330 n 9.57 8.52 0 0 0 0 0 0 0 0 W . 1613-19ad_-_____ _ _ 11 Blk Half, stuoo7 ext 10C-v 0201 0550 e a 5 83 15.95 4.06 1620 0 0 0 0 0 0 0 0 - 0 0 0 0 0- 0 0 0 2A-2ov 0.330 a 9.57 2226 0 0 0 0 0 0 0 0 2A-2ov _ _ _ 0.330 e _ 9.57 852 0 0 0 0 0 0 0 0 W_ 16619ad..4__.� -- .. _ a0049 _ _ _ __. T . �0 _ 0 V6Blk wall, stucco e)d 2A-2ov 0201 0330 s s 5.83 9.57 4.06 852 150 0 117 0 684 0 476 0 ' 0 0 ' 0 0 - 0 n 0 0 2A 2ov__ _ J66.19ad_v. 0330 _ _..__0049 _ s, .. w- 9.57 _-1.42 ,. 8.52 33 33 . -__ 31'3 _ _._ 279 0 _ _- _ _ _ 0 _- _ _0 0 0 Blk veil, stucco ext 2A-2ov 0.201 0330 w w 5.83 9.57 4.06 2027 6 0 0 0 - 0 0 0 0 0 0 0 0 0 0 0 0 2B-2fv 0330 w 9.57 11.58 0 0 0 0 0 0 2B-2fv 0230 w 957 1325 0 0 0 0 0 0 0 0 0 0 11J0 __ 0600 w 17.40 - --- 17.58 0 0 0 0 0 0 0 0 _ 1613-30ad -._ _2.64 131 - 140 - _ 140 369 - --- - 183 - _. -.__ --60 _ a..., _. 60 .. �_ _158 --- --. 79 C.__. _ 0032 0.93 _ _...169 _ 46_ .._.__246 228 416 36. _ 6 c) AED excursion -126 -35 Envelope loss/gain 2426 1228 364 104 12 a) Infiltration 288 80 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Applianoes/other 1200 600 Subtotal (lines 6 to 13) 2714 2509 364 704 Less extemal load 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2714 2509 364 704 15 Dud loads 17 % 31 % 470 788 17°/ 31 % 63 221 Total room load 3184 3296 427 925 Air required (cfm) 130 159 17 45 Calculations approved byACCAto meet all requirements of Manual J 8th Ed -&- wrigl�tso4ft^ A R gt6-Sute®Uriversal 2021 21.0.02 RSU23828 Page 6 2021-Jur08 09:age 6 ...terstone1820CGR1Lot182Pts3Waterstore18200GR.rLp CaIc=MJB FrortDoortaces: W wrightsoft® stem Duct S Summary Job: Lot 182 Phase 3 Watersto... Y rY Date: Entire House By. DCs DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Project• • For: ADAMS HOMES 5326 Vespera Street, Fort Pierce, FL 34951 External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length.(TEL) Heating 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170/0.170 in H2O 0.300 in/100ft 1167 cfm 113 ft Supply Branch Detail Table Cooling 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.300 in/100ft 1167 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Mati Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 832 34 25 0.394 4.0 Ox 0 VI Fx 16.3 70.0 BDRM2 h 4739 193 142 0.366 8.0 Ox 0 VIFx 22.9 70.0 BDRM3 h 1875 77 58 0.433 5.0 Ox0 VIFx 8.6 70.0 DENODRM4 c 4214 172 172 0.409 7.0 Ox0 VIFx 13.2 70.0 DINING/FOYER c 3288 143 159 0.444 7.0 Ox0 VIFx 6.5 70.0 FAMILYRM c 2982 106 144 0.330 8.0 Ox 0 VIFx 17.9 85.0 st1 KrrCHEN/NOOK c 3296 130 159 0.323 8.0 Ox0 VIFx 20.1 85.0 st1 LAUNDRY c 925 17 45 0.316 4.0 Ox 0 VIFx 22.7 85.0 sti M. BATH h 1655 68 47 0.317 5.0 Ox 0 VI Fx 22.2 85.0 st1 KWIC c 104 2 5 0.318 4.0 Ox0 VIFx 21.9 85.0 sti MSTRBDRM h 5509 225 212 0.300 8.0 Ox0 VIFx 28.2 85.0 st1 Supply Trunk Detail Table Name Trunk Type Htg (cfm) Clg (cfm) Design FIR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk st1 PeakAVF 548 612 0.300 572 14.0 0 x 0 VinlFlx - -rk wrightsoft" Righ-Sute®Uriversal202121.0.02RSU23828 XM terstore1820CGR1Lot182PFs3Waterstore1820CGR.rup CaIc=W8 FrontDooriaces: W 2021-Aui-08 09:51:44 Page 1 Return Branch Detail Table Name Grille Size (in) Htg (Cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat Trunk rbi Ox 0 1167 1167 0 0 0 0 Ox 0 VIFx .� Ak wrightsofta Right-Sute®Uriversal202121.0.02RSU23828 terstore1820CGR1Lot182PFs3Waterstore1820CGR.rup Calc=MJ8 FroMDoorfaces: W 2021-Jzr08 09:51.44 Page 2 2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 182 Phase 3 Waterstone 1820 CGR Builder Name: ADAMS HOMES Street: 5326 Vespera Street Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 w Design Location: FL, ST_LUCIE_CO_INTL U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/door jambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace wall . Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac 9s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. I Caulking or other adhesive sealants shall not be used to fill voids ddi a. n ation, inspection of log walls shall be in accordance with the provisions of ICC-400. 6/8/2021 10:23 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 6/8/2021 10:23:22 AM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: Job Information Builder: ADAMS HOMES Community: Lot: 182-3 Address: 5326 Vespera Street City: Fort Pierce State: FL Zip: 34951 Air Leaka a Test: Results Passin results must meet either the Performa g g. rice. Prescriptive, or.ERf'Method , ` PRESCRIPTIVE METHOD .The building or dwelling unit_shall be tested and verified as having an airleakage rate of nWexceeding 7,air , O ;changes per, hour at -`a pressur"'of 0;2`inch`w:g.'(50 P,aseals) in'Climate Zones'"f`and 2. ,Q PERFORMANCE or,.ERI METHOD=The building or dwelliog.,bnit shall'be tested.and')ierified as having`an air leakage,rate of.not,exceedirig the selected ACH(50) value as "'shown on Form R405 2020:(Performance) or R406-2020 (ERI), section labeled as infiltration,. sub -sect on.ACH50. ACH(50) specified,on Form R405 2020-Energy Calc (Performance)„or R4062020 (ERI)Z000 x 60 _ 18200 = Method for calculating buildinq volume: CFM(50) Building Volume ACH(50) Q Retrieved from architectural plans F-1 PASS Code • software calculated When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. .'Testing Company Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 6/8/2021 10:24:02 AM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods FADDRESS: 5326 Vespera Street Permit Number: Fort Pierce , FL , 34951 MANDATORY REQUIREMENTS - See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. C1R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm L per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 6/8/2021 10:23 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. ❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS ❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (1), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. ❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. ❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. ❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. ❑ R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C) or below 55°F (13°C) shall be insulated to a minimum of R-3. ❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall ❑ be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 6/8/2021 10:23 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) El R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60°C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of combustion types of service water -heating systems to be turned off. ❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida .Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TMA, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. ❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. ❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 6/8/2021 10:23 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 6/8/2021 10:23 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5 QR403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. ❑ R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. FJ R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 6/8/2021 10:23 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5