Bryant whole house Manual J_10-5-21
Residential System Sizing Calculation Summary Patricia M F Bryant ST LUCIE BLVD FORT PIERCE, FL 34946 Project Title: BRYANT_WHOLE HOUSE BLOCK 10/5/2021 Location for weather data: St. Lucie, FL - Defaults: L a t i t u d e ( 2 7 . 4 8 ) Altitude(7 ft.) Temp Range(M) Humidity data: Interior RH (50%) Outdoor wet bulb (78F) Humidity difference(58gr.) Winter design temperature(TMY3 99%) 40 F Summer design temperature(TMY3 99%) 91 F Winter setpoint 70 F Summer setpoint 75 F Winter temperature difference 30 F Summer temperature difference 16 F Total heating load calculation 21619 Btuh Total cooling load calculation 21984 Btuh Submitted heating capacity % of calc Btuh Submitted cooling capacity % of calc Btuh Total (Electric Heat Pump)115.6 25000 Sensible (SHR = 0.75)80.4 16500 Heat Pump + Auxiliary(0.0kW) 115.6 25000 L a t e n t 374.8 5500 T o t a l (Electric Heat Pump) 100.1 22000 WINTER CALCULATIONS Winter Heating Load (for 984 sqft) Load component Load Window total 296 sqft 10049 Btuh Wall total 1059 sqft 4603 Btuh Door total 40 sqft 552 Btuh Ceiling total 984 sqft 2430 Btuh Floor total See detail report 2571 Btuh Infiltration 43 cfm 1414 Btuh Duct loss 0 Btuh Subtotal 21619 Btuh Ventilation 0 cfm 0 Btuh TOTAL HEAT LOSS 21619 Btuh Summer Cooling Load (for 984 sqft) Load component Load Window total 296 sqft 10805 Btuh Wall total 1059 sqft 4219 Btuh Door total 40 sqft 497 Btuh Ceiling total 984 sqft 2057 Btuh Floor total 943 Btuh Infiltration 32 cfm 566 Btuh Internal gain 1430 Btuh Duct gain 0 Btuh Sens. Ventilation 0 cfm 0 Btuh Blower Load 0 Btuh Total sensible gain 20516 Btuh Latent gain(ducts)0 Btuh Latent gain(infiltration)1268 Btuh Latent gain(ventilation)0 Btuh Latent gain(internal/occupants/other)200 Btuh Total latent gain 1468 Btuh TOTAL HEAT GAIN 21984 Btuh EnergyGauge® / USRCZB v7.0.00 SUMMER CALCULATIONS 8th Edition EnergyGauge® System Sizing PREPARED BY: _________________________________ DATE: ________________________________________October 5, 2021 Certificate of Product Ratings † DISCLAIMER AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for, the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the directory at www.ahridirectory.org. TERMS AND CONDITIONS This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated; entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual, personal and confidential reference. CERTIFICATE VERIFICATION The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link and enter the AHRI Certified Reference Number and the date on which the certificate was issued, which is listed above, and the Certificate No., which is listed at bottom right. © Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: Date : 10-05-2021 Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published rating is shown along with the previous (i.e. WAS) rating. †"Active" Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale; OR new models that are being marketed but are not yet being produced.“Production Stopped” Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still selling or offering for sale. 2021 AHRI Certified Reference Number : 201754902 Model Status : Active AHRI Type : HMSV-A-CB-O (Multi-Split Heat Pump, Free Delivery) Series Name : M-Series Outdoor Unit Brand Name : Mitsubishi Electric Outdoor Unit Model Number : MXZ-3C24NA2 Indoor Type : Non-Ducted Indoor Units Rated as follows in accordance with the latest edition of AHRI 210/240 with Addendum 1, Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump Equipment and subject to rating accuracy by AHRI-sponsored, independent, third party testing: Cooling Capacity (95F) : 22000 EER (95F) : 13.60 SEER : 20.00 High Heat (47F) : 25000 Low Heat (17F) : 14000 HSPF : 9.80 Sold in? : USA Eligible for Federal Tax Credit. Eligible For Federal Tax Credit (installed between 2/17/09 and 12/1/16) 132779137655113198 System Sizing Calculations - Winter Residential Load - Whole House Component Details Patricia M F Bryant ST LUCIE BLVD FORT PIERCE, FL 34946 Project Title: BRYANT_WHOLE HOUSE BLOCK Building Type: User 10/5/2021 Reference City: St. Lucie, FL ( D e f a u l t s ) Winter Temperature Difference: 30.0 F (TMY3 99%) Component Loads for Whole House Window Frame UP a n e s / T y p e Orientation Area(sqft) X HTM=L o a d 1 1, Tint Metal 1.13 S 13.7 33.9 465 Btuh 2 1, Tint Metal 1.13 E 12.0 33.9 407 Btuh 3 1, Tint Metal 1.13 E 12.0 33.9 407 Btuh 4 1, Tint Metal 1.13 S 10.8 33.9 367 Btuh 5 1, Tint Metal 1.13 S 10.8 33.9 367 Btuh 6 1, Tint Metal 1.13 S 10.8 33.9 367 Btuh 7 1, Tint Metal 1.13 W 10.8 33.9 367 Btuh 8 1, Tint Metal 1.13 W 10.8 33.9 367 Btuh 9 1, Tint Metal 1.13 W 10.8 33.9 367 Btuh 10 1, Tint Metal 1.13 W 8.3 33.9 282 Btuh 11 1, Tint Metal 1.13 W 8.3 33.9 282 Btuh 12 1, Tint Metal 1.13 W 8.3 33.9 282 Btuh 13 1, Tint Metal 1.13 W 9.4 33.9 320 Btuh 14 1, Tint Metal 1.13 N 9.4 33.9 320 Btuh 15 1, Tint Metal 1.13 N 9.4 33.9 320 Btuh 16 1, Tint Metal 1.13 E 9.4 33.9 320 Btuh 17 1, Tint Metal 1.13 E 9.4 33.9 320 Btuh 18 1, Tint Metal 1.13 E 9.4 33.9 320 Btuh 19 1, Tint Metal 1.13 N 13.7 33.9 465 Btuh 20 1, Tint Metal 1.13 N 13.7 33.9 465 Btuh 21 1, Tint Metal 1.13 E 13.7 33.9 465 Btuh 22 1, Tint Metal 1.13 E 13.7 33.9 465 Btuh 23 1, Tint Metal 1.13 E 13.7 33.9 465 Btuh 24 1, Tint Metal 1.13 E 13.7 33.9 465 Btuh 25 1, Tint Metal 1.13 S 13.7 33.9 465 Btuh 26 1, Clear Metal 1.13 S 16.0 33.9 542 Btuh Window Total 296.4(sqft)10049 Btuh Walls Ornt.Ueff.R-ValueT y p e Area X HTM=L o a d ( C a v / S h ) 1 Frame - Wood - Ext (0.145)4.1/0.0 63 4.35 272 Btuh 2 Frame - Wood - Ext (0.145)4.1/0.0 38 4.35 164 Btuh 3 Frame - Wood - Ext (0.145)4.1/0.0 50 4.35 215 Btuh 4 Frame - Wood - Ext (0.145)4.1/0.0 428 4.35 1859 Btuh 5 Frame - Wood - Ext (0.145)4.1/0.0 71 4.35 309 Btuh 6 Frame - Wood - Ext (0.145)4.1/0.0 157 4.35 683 Btuh 7 Frame - Wood - Ext (0.145)4.1/0.0 79 4.35 341 Btuh 8 Frame - Wood - Ext (0.145)4.1/0.0 175 4.35 759 Btuh Wall Total 1059(sqft)4603 Btuh Doors Storm Ueff.Type Area X HTM=L o a d 1 Wood - Exterior,n (0.460) 24 13.8 331 Btuh 2 Wood - Exterior,n (0.460) 16 13.8 221 Btuh Door Total 40(sqft)552Btuh EnergyGauge® / USRCZB v7.0.00 Page 1 Manual J Winter Calculations Residential Load - Component Details (continued) Patricia M F Bryant ST LUCIE BLVD FORT PIERCE, FL 34946 Project Title: BRYANT_WHOLE HOUSE BLOCK Building Type: User 10/5/2021 Ceilings Ueff.T y p e / C o l o r / S u r f a c e R - V a l u e Area X HTM=L o a d 1 Cathedral/W /M e t a l (0.082)9.0/0.0 672 2.5 1659 Btuh 2 Cathedral/W /M e t a l (0.082)9.0/0.0 312 2.5 770 Btuh Ceiling Total 984(sqft)2430Btuh Floors Ueff.T y p e R - V a l u e Size X HTM=L o a d 1 Raised - Open ( 0 . 0 8 7 )9.0 672.0 s q f t 2.6 1756 Btuh 2 Raised - Open ( 0 . 0 8 7 )9.0 312.0 s q f t 2.6 815 Btuh Floor Total 984 s q f t 2571 Btuh Envelope Subtotal: 20205 Btuh Infiltration Type Wholehouse ACH Volume(cuft)Wall Ratio CFM= Natural 0.33 7872 1.00 42.9 1414 Btuh Duct load NA, R0.0, Supply(), Return()(DLM of 0.000)0 Btuh All Zones Sensible Subtotal All Zones 21619 Btuh WHOLE HOUSE TOTALS Subtotal Sensible Heat Loss 21619 Btuh Totals for Heating Ventilation Sensible Heat Loss 0 Btuh Total Heat Loss 21619 Btuh EQUIPMENT 1. Electric Heat Pump # M X Z 3 C 2 4 N A 2 25000 Btuh Key: Window types - NFRC (Requires U-Factor and Shading coefficient(SHGC) of glass as numerical values) or - Glass as 'Clear' or 'Tint' (Uses U-Factor and SHGC defaults) U - (Window U-Factor) HTM - (ManualJ Heat Transfer Multiplier) Version 8 EnergyGauge® / USRCZB v7.0.00 Page 2 System Sizing Calculations - Summer Residential Load - Whole House Component Details Patricia M F Bryant ST LUCIE BLVD FORT PIERCE, FL 34946 Project Title: BRYANT_WHOLE HOUSE BLOCK 10/5/2021 Reference City: St. Lucie, FL Temperature Difference: 16.0F(TMY3 99%)Humidity difference: 58gr. Component Loads for Whole House Type*Overhang Window Area(sqft)HTM L o a d Window Panes SHGC U InSh IS O r n t Len Hgt Gross Shaded Unshaded Shaded Unshaded 1 1 Tint 0 . 5 2 , 1.13 N o No S 7.0ft 2.0ft 13.7 13.7 0.0 29 32 401 Btuh 2 1 Tint 0 . 5 2 , 1.13 N o No E 12.0f 2.0ft 12.0 12.0 0.0 29 69 351 Btuh 3 1 Tint 0 . 5 2 , 1.13 N o No E 12.0f 2.0ft 12.0 12.0 0.0 29 69 351 Btuh 4 1 Tint 0 . 5 2 , 1.13 N o No S 4.5ft 0.2ft 10.8 10.8 0.0 29 32 316 Btuh 5 1 Tint 0 . 5 2 , 1.13 N o No S 4.5ft 0.2ft 10.8 10.8 0.0 29 32 316 Btuh 6 1 Tint 0 . 5 2 , 1.13 B-L No S 4.5ft 0.2ft 10.8 10.8 0.0 24 26 255 Btuh 7 1 Tint 0 . 5 2 , 1.13 N o No W 9.0ft 3.0ft 10.8 10.8 0.0 29 69 316 Btuh 8 1 Tint 0 . 5 2 , 1.13 B-L No W 9.0ft 3.0ft 10.8 10.8 0.0 24 53 255 Btuh 9 1 Tint 0 . 5 2 , 1.13 N o No W 9.0ft 3.0ft 10.8 10.8 0.0 29 69 316 Btuh 10 1 Tint 0 . 5 2 , 1.13 N o No W 9.0ft 3.0ft 8.3 8.3 0.0 29 69 243 Btuh 11 1 Tint 0 . 5 2 , 1.13 N o No W 9.0ft 3.0ft 8.3 8.3 0.0 29 69 243 Btuh 12 1 Tint 0 . 5 2 , 1.13 N o No W 9.0ft 3.0ft 8.3 8.3 0.0 29 69 243 Btuh 13 1 Tint 0 . 5 2 , 1.13 N o No W 9.0ft 3.0ft 9.4 9.4 0.0 29 69 276 Btuh 14 1 Tint 0 . 5 2 , 1.13 B-L No N 3.0ft 0.2ft 9.4 0.0 9.4 24 24 222 Btuh 15 1 Tint 0 . 5 2 , 1.13 B-L No N 3.0ft 0.2ft 9.4 0.0 9.4 24 24 222 Btuh 16 1 Tint 0 . 5 2 , 1.13 N o No E 3.0ft 0.2ft 9.4 6.6 2.9 29 69 388 Btuh 17 1 Tint 0 . 5 2 , 1.13 N o No E 3.0ft 0.2ft 9.4 6.6 2.9 29 69 388 Btuh 18 1 Tint 0 . 5 2 , 1.13 B-L No E 3.0ft 0.2ft 9.4 6.6 2.9 24 54 311 Btuh 19 1 Tint 0 . 5 2 , 1.13 B-L No N 4.0ft 0.2ft 13.7 0.0 13.7 24 24 323 Btuh 20 1 Tint 0 . 5 2 , 1.13 B-L No N 4.0ft 0.2ft 13.7 0.0 13.7 24 24 323 Btuh 21 1 Tint 0 . 5 2 , 1.13 N o No E 4.0ft 0.2ft 13.7 10.0 3.7 29 69 548 Btuh 22 1 Tint 0 . 5 2 , 1.13 N o No E 4.0ft 0.2ft 13.7 10.0 3.7 29 69 548 Btuh 23 1 Tint 0 . 5 2 , 1.13 N o No E 4.0ft 0.2ft 13.7 10.0 3.7 29 69 548 Btuh 24 1 Tint 0 . 5 2 , 1.13 N o No E 4.0ft 0.2ft 13.7 10.0 3.7 29 69 548 Btuh 25 1 Tint 0 . 5 2 , 1.13 N o No S 4.0ft 0.2ft 13.7 13.7 0.0 29 32 401 Btuh 26 1 Clear 0 . 7 4 , 1.13 N o No S 0.0ft 0.0ft 16.0 0.0 16.0 34 38 603 Btuh E x c u r s i o n 1548 Btuh Window Total 296 ( s q f t ) 10805 Btuh Walls Type U-Value R-Value Area(sqft)HTM Load Cav/Sheath 1 Frame - Wood - Ext 0.14 4.1/0.0 62.6 4.0 249 Btuh 2 Frame - Wood - Ext 0.14 4.1/0.0 37.8 4.0 151 Btuh 3 Frame - Wood - Ext 0.14 4.1/0.0 49.5 4.0 197 Btuh 4 Frame - Wood - Ext 0.14 4.1/0.0 427.7 4.0 1704 Btuh 5 Frame - Wood - Ext 0.14 4.1/0.0 71.1 4.0 283 Btuh 6 Frame - Wood - Ext 0.14 4.1/0.0 157.2 4.0 626 Btuh 7 Frame - Wood - Ext 0.14 4.1/0.0 78.6 4.0 313 Btuh 8 Frame - Wood - Ext 0.14 4.1/0.0 174.8 4.0 696 Btuh Wall Total 1059 ( s q f t )4219 Btuh Doors Type Area (sqft)HTM Load 1 Wood - Exterior 24.0 12.4 298 Btuh 2 Wood - Exterior 16.0 12.4 199 Btuh Door Total 40 ( s q f t )497 Btuh Ceilings U-Value R-ValueType/Color/Surface Area(sqft)HTM Load 1 Cath/Sngl Assem/White/Metal 0.082 9.0/0.0 672.0 2.09 1405 Btuh 2 Cath/Sngl Assem/White/Metal 0.082 9.0/0.0 312.0 2.09 652 Btuh Ceiling Total 984 ( s q f t )2057 Btuh EnergyGauge® / USRCZB v7.0.00 Page 1 Manual J Summer Calculations Residential Load - Component Details (continued) Patricia M F Bryant ST LUCIE BLVD FORT PIERCE, FL 34946 Project Title: BRYANT_WHOLE HOUSE BLOCK Climate:FL_VERO_BEACH_MUNICIPAL_A 10/5/2021 Floors R-ValueType Size HTM Load 1 Raised - Open 9.0 672 ( s q f t )1.0 644 Btuh 2 Raised - Open 9.0 312 ( s q f t )1.0 299 Btuh Floor Total 984.0 ( s q f t )943 Btuh Envelope Subtotal: 18521 Btuh Infiltration AverageType A C H Volume(cuft) Wall Ratio CFM=Load Natural 0.25 7872 1 32.1 566 Btuh Internal Occupants Btuh/occupant Appliance Load gain 1 X 230 +1200 1430 Btuh Sensible Envelope Load: 20516 Btuh Duct load N A , Supply(R0.0-None), Return(R0.0-None)(DGM of 0.000) 0 Btuh Sensible Load All Zones 20516 Btuh EnergyGauge® / USRCZB v7.0.00 Page 2 Manual J Summer Calculations Residential Load - Component Details (continued) Patricia M F Bryant ST LUCIE BLVD FORT PIERCE, FL 34946 Project Title: BRYANT_WHOLE HOUSE BLOCK Climate:FL_VERO_BEACH_MUNICIPAL_A 10/5/2021 WHOLE HOUSE TOTALS Sensible Envelope Load All Zones 20516 Btuh Sensible Duct Load 0 Btuh Total Sensible Zone Loads 20516 Btuh Sensible ventilation 0 Btuh B l o w e r 0 Btuh Whole House Total sensible gain 20516 Btuh Totals for Cooling Latent infiltration gain (for 58 gr. humidity difference)1268 Btuh Latent ventilation gain 0 Btuh Latent duct gain 0 Btuh Latent occupant gain (1.0 people @ 200 Btuh per person)200 Btuh Latent other gain 0 Btuh Latent total gain 1468 Btuh TOTAL GAIN 21984 Btuh EQUIPMENT 1. Central Unit # M X Z 3 C 2 4 N A 2 22000 Btuh *Key: Window types (Panes - Number and type of panes of glass) (SHGC - Shading coefficient of glass as SHGC numerical value) (U - Window U-Factor) (InSh - Interior shading device: none(No), Blinds(B), Draperies(D) or Roller Shades(R)) - For Blinds: Assume medium color, half closed For Draperies: Assume medium weave, half closed For Roller shades: Assume translucent, half closed (IS - Insect screen: none(N), Full(F) or Half(½)) (Ornt - compass orientation) Version 8 EnergyGauge® / USRCZB v7.0.00 Page 3 System Sizing Calculations - Winter Residential Load - Room by Room Component Details Patricia M F Bryant ST LUCIE BLVD FORT PIERCE, FL 34946 Project Title: BRYANT_WHOLE HOUSE BLOCK Building Type: User 10/5/2021 Reference City: St. Lucie, FL ( D e f a u l t s ) Winter Temperature Difference: 30.0 F (TMY3 99%) Component Loads for Room #1: Main Window Frame UP a n e s / T y p e Orientation Area(sqft) X HTM=L o a d 2 1, Tint Metal 1.13 E 12.0 33.9 407 Btuh 3 1, Tint Metal 1.13 E 12.0 33.9 407 Btuh 4 1, Tint Metal 1.13 S 10.8 33.9 367 Btuh 5 1, Tint Metal 1.13 S 10.8 33.9 367 Btuh 6 1, Tint Metal 1.13 S 10.8 33.9 367 Btuh 7 1, Tint Metal 1.13 W 10.8 33.9 367 Btuh 8 1, Tint Metal 1.13 W 10.8 33.9 367 Btuh 9 1, Tint Metal 1.13 W 10.8 33.9 367 Btuh 10 1, Tint Metal 1.13 W 8.3 33.9 282 Btuh 11 1, Tint Metal 1.13 W 8.3 33.9 282 Btuh 12 1, Tint Metal 1.13 W 8.3 33.9 282 Btuh 13 1, Tint Metal 1.13 W 9.4 33.9 320 Btuh 14 1, Tint Metal 1.13 N 9.4 33.9 320 Btuh 15 1, Tint Metal 1.13 N 9.4 33.9 320 Btuh 16 1, Tint Metal 1.13 E 9.4 33.9 320 Btuh 17 1, Tint Metal 1.13 E 9.4 33.9 320 Btuh 18 1, Tint Metal 1.13 E 9.4 33.9 320 Btuh Window Total 170.7(sqft)5786 Btuh Walls Ornt.Ueff.R-ValueT y p e Area X HTM=L o a d ( C a v / S h ) 2 Frame - Wood - Ext (0.145)4.1/0.0 38 4.35 164 Btuh 3 Frame - Wood - Ext (0.145)4.1/0.0 50 4.35 215 Btuh 4 Frame - Wood - Ext (0.145)4.1/0.0 428 4.35 1859 Btuh 5 Frame - Wood - Ext (0.145)4.1/0.0 71 4.35 309 Btuh 6 Frame - Wood - Ext (0.145)4.1/0.0 157 4.35 683 Btuh Wall Total 743(sqft)3230 Btuh Doors Storm Ueff.Type Area X HTM=L o a d 1 Wood - Exterior,n (0.460) 24 13.8 331 Btuh 2 Wood - Exterior,n (0.460) 16 13.8 221 Btuh Door Total 40(sqft)552Btuh Ceilings Ueff.T y p e / C o l o r / S u r f a c e R - V a l u e Area X HTM=L o a d 1 Cathedral/W /M e t a l (0.082)9.0/0.0 672 2.5 1659 Btuh Ceiling Total 672(sqft)1659Btuh Floors Ueff.T y p e R - V a l u e Size X HTM=L o a d 1 Raised - Open ( 0 . 0 8 7 )9.0 672.0 s q f t 2.6 1756 Btuh Floor Total 672 s q f t 1756 Btuh Room Envelope Subtotal: 12983 Btuh Infiltration Type Wholehouse ACH Room Volume Wall Ratio CFM= Natural 0.33 5376 0.70 30.1 992 Btuh EnergyGauge® / USRCZB v7.0.00 Page 1 Manual J Winter Calculations Residential Load - Component Details (continued) Patricia M F Bryant ST LUCIE BLVD FORT PIERCE, FL 34946 Project Title: BRYANT_WHOLE HOUSE BLOCK Building Type: User 10/5/2021 Duct load No ducts assigned to this zone.(DLM of 0.000)0 Btuh Room #1 Sensible Room Subtotal 13975 Btuh Component Loads for Room #2: Living Room Window Frame UP a n e s / T y p e Orientation Area(sqft) X HTM=L o a d 1 1, Tint Metal 1.13 S 13.7 33.9 465 Btuh 19 1, Tint Metal 1.13 N 13.7 33.9 465 Btuh 20 1, Tint Metal 1.13 N 13.7 33.9 465 Btuh 21 1, Tint Metal 1.13 E 13.7 33.9 465 Btuh 22 1, Tint Metal 1.13 E 13.7 33.9 465 Btuh 23 1, Tint Metal 1.13 E 13.7 33.9 465 Btuh 24 1, Tint Metal 1.13 E 13.7 33.9 465 Btuh 25 1, Tint Metal 1.13 S 13.7 33.9 465 Btuh 26 1, Clear Metal 1.13 S 16.0 33.9 542 Btuh Window Total 125.8(sqft)4264 Btuh Walls Ornt.Ueff.R-ValueT y p e Area X HTM=L o a d ( C a v / S h ) 1 Frame - Wood - Ext (0.145)4.1/0.0 63 4.35 272 Btuh 7 Frame - Wood - Ext (0.145)4.1/0.0 79 4.35 341 Btuh 8 Frame - Wood - Ext (0.145)4.1/0.0 175 4.35 759 Btuh Wall Total 316(sqft)1373 Btuh Ceilings Ueff.T y p e / C o l o r / S u r f a c e R - V a l u e Area X HTM=L o a d 2 Cathedral/W /M e t a l (0.082)9.0/0.0 312 2.5 770 Btuh Ceiling Total 312(sqft)770Btuh Floors Ueff.T y p e R - V a l u e Size X HTM=L o a d 2 Raised - Open ( 0 . 0 8 7 )9.0 312.0 s q f t 2.6 815 Btuh Floor Total 312 s q f t 815 Btuh Room Envelope Subtotal: 7222 Btuh Infiltration Type Wholehouse ACH Room Volume Wall Ratio CFM= Natural 0.33 2496 0.30 12.8 422 Btuh Duct load No ducts assigned to this zone.(DLM of 0.000)0 Btuh Room #2 Sensible Room Subtotal 7644 Btuh EnergyGauge® / USRCZB v7.0.00 Page 2 Manual J Winter Calculations Residential Load - Component Details (continued) Patricia M F Bryant ST LUCIE BLVD FORT PIERCE, FL 34946 Project Title: BRYANT_WHOLE HOUSE BLOCK Building Type: User 10/5/2021 WHOLE HOUSE TOTALS Subtotal Sensible Heat Loss 21619 Btuh Totals for Heating Ventilation Sensible Heat Loss 0 Btuh Total Heat Loss 21619 Btuh EQUIPMENT 1. Electric Heat Pump # M X Z 3 C 2 4 N A 2 25000 Btuh Key: Window types - NFRC (Requires U-Factor and Shading coefficient(SHGC) of glass as numerical values) or - Glass as 'Clear' or 'Tint' (Uses U-Factor and SHGC defaults) U - (Window U-Factor) HTM - (ManualJ Heat Transfer Multiplier) Version 8 EnergyGauge® / USRCZB v7.0.00 Page 3 System Sizing Calculations - Summer Residential Load - Room by Room Component Details Patricia M F Bryant ST LUCIE BLVD FORT PIERCE, FL 34946 Project Title: BRYANT_WHOLE HOUSE BLOCK 10/5/2021 Reference City: St. Lucie, FL Temperature Difference: 16.0F(TMY3 99%)Humidity difference: 58gr. Component Loads for Room #1: Main Type*Overhang Window Area(sqft)HTM L o a d Window Panes SHGC U InSh IS O r n t Len Hgt Gross Shaded Unshaded Shaded Unshaded 2 1 Tint 0 . 5 2 , 1.13 N o No E 12.0f 2.0ft 12.0 12.0 0.0 29 69 351 Btuh 3 1 Tint 0 . 5 2 , 1.13 N o No E 12.0f 2.0ft 12.0 12.0 0.0 29 69 351 Btuh 4 1 Tint 0 . 5 2 , 1.13 N o No S 4.5ft 0.2ft 10.8 10.8 0.0 29 32 316 Btuh 5 1 Tint 0 . 5 2 , 1.13 N o No S 4.5ft 0.2ft 10.8 10.8 0.0 29 32 316 Btuh 6 1 Tint 0 . 5 2 , 1.13 B-L No S 4.5ft 0.2ft 10.8 10.8 0.0 24 26 255 Btuh 7 1 Tint 0 . 5 2 , 1.13 N o No W 9.0ft 3.0ft 10.8 10.8 0.0 29 69 316 Btuh 8 1 Tint 0 . 5 2 , 1.13 B-L No W 9.0ft 3.0ft 10.8 10.8 0.0 24 53 255 Btuh 9 1 Tint 0 . 5 2 , 1.13 N o No W 9.0ft 3.0ft 10.8 10.8 0.0 29 69 316 Btuh 10 1 Tint 0 . 5 2 , 1.13 N o No W 9.0ft 3.0ft 8.3 8.3 0.0 29 69 243 Btuh 11 1 Tint 0 . 5 2 , 1.13 N o No W 9.0ft 3.0ft 8.3 8.3 0.0 29 69 243 Btuh 12 1 Tint 0 . 5 2 , 1.13 N o No W 9.0ft 3.0ft 8.3 8.3 0.0 29 69 243 Btuh 13 1 Tint 0 . 5 2 , 1.13 N o No W 9.0ft 3.0ft 9.4 9.4 0.0 29 69 276 Btuh 14 1 Tint 0 . 5 2 , 1.13 B-L No N 3.0ft 0.2ft 9.4 0.0 9.4 24 24 222 Btuh 15 1 Tint 0 . 5 2 , 1.13 B-L No N 3.0ft 0.2ft 9.4 0.0 9.4 24 24 222 Btuh 16 1 Tint 0 . 5 2 , 1.13 N o No E 3.0ft 0.2ft 9.4 6.6 2.9 29 69 388 Btuh 17 1 Tint 0 . 5 2 , 1.13 N o No E 3.0ft 0.2ft 9.4 6.6 2.9 29 69 388 Btuh 18 1 Tint 0 . 5 2 , 1.13 B-L No E 3.0ft 0.2ft 9.4 6.6 2.9 24 54 311 Btuh Window Total 171 ( s q f t ) 5015 Btuh Walls Type U-Value R-Value Area(sqft)HTM Load Cav/Sheath 2 Frame - Wood - Ext 0.14 4.1/0.0 37.8 4.0 151 Btuh 3 Frame - Wood - Ext 0.14 4.1/0.0 49.5 4.0 197 Btuh 4 Frame - Wood - Ext 0.14 4.1/0.0 427.7 4.0 1704 Btuh 5 Frame - Wood - Ext 0.14 4.1/0.0 71.1 4.0 283 Btuh 6 Frame - Wood - Ext 0.14 4.1/0.0 157.2 4.0 626 Btuh Wall Total 743 ( s q f t )2961 Btuh Doors Type Area (sqft)HTM Load 1 Wood - Exterior 24.0 12.4 298 Btuh 2 Wood - Exterior 16.0 12.4 199 Btuh Door Total 40 ( s q f t )497 Btuh Ceilings U-Value R-ValueType/Color/Surface Area(sqft)HTM Load 1 Cath/Sngl Assem/White/Metal 0.082 9.0/0.0 672.0 2.09 1405 Btuh Ceiling Total 672 ( s q f t )1405 Btuh Floors R-ValueType Size HTM Load 1 Raised - Open 9.0 672 ( s q f t )1.0 644 Btuh Floor Total 672.0 ( s q f t )644 Btuh Zone Envelope Subtotal: 10521 Btuh EnergyGauge® / USRCZB v7.0.00 Page 1 Manual J Summer Calculations Residential Load - Component Details (continued) Patricia M F Bryant ST LUCIE BLVD FORT PIERCE, FL 34946 Project Title: BRYANT_WHOLE HOUSE BLOCK Climate:FL_VERO_BEACH_MUNICIPAL_A 10/5/2021 Infiltration WholehouseType A C H Volume(cuft) Wall Ratio CFM=Load Natural 0.25 5376 0.70 22.6 397 Btuh Internal Occupants Btuh/occupant Appliance Load gain 1 X 230 +1200 1430 Btuh Sensible Envelope Load: 12348 Btuh Duct load No duct systemNo ducts assigned to this zone.(DGM of 0.000)0 Btuh Sensible Zone Load 12348 Btuh Component Loads for Room #2: Living Room Type*Overhang Window Area(sqft)HTM L o a d Window Panes SHGC U InSh IS O r n t Len Hgt Gross Shaded Unshaded Shaded Unshaded 1 1 Tint 0 . 5 2 , 1.13 N o No S 7.0ft 2.0ft 13.7 13.7 0.0 29 32 401 Btuh 19 1 Tint 0 . 5 2 , 1.13 B-L No N 4.0ft 0.2ft 13.7 0.0 13.7 24 24 323 Btuh 20 1 Tint 0 . 5 2 , 1.13 B-L No N 4.0ft 0.2ft 13.7 0.0 13.7 24 24 323 Btuh 21 1 Tint 0 . 5 2 , 1.13 N o No E 4.0ft 0.2ft 13.7 10.0 3.7 29 69 548 Btuh 22 1 Tint 0 . 5 2 , 1.13 N o No E 4.0ft 0.2ft 13.7 10.0 3.7 29 69 548 Btuh 23 1 Tint 0 . 5 2 , 1.13 N o No E 4.0ft 0.2ft 13.7 10.0 3.7 29 69 548 Btuh 24 1 Tint 0 . 5 2 , 1.13 N o No E 4.0ft 0.2ft 13.7 10.0 3.7 29 69 548 Btuh 25 1 Tint 0 . 5 2 , 1.13 N o No S 4.0ft 0.2ft 13.7 13.7 0.0 29 32 401 Btuh 26 1 Clear 0 . 7 4 , 1.13 N o No S 0.0ft 0.0ft 16.0 0.0 16.0 34 38 603 Btuh Window Total 126 ( s q f t ) 4242 Btuh Walls Type U-Value R-Value Area(sqft)HTM Load Cav/Sheath 1 Frame - Wood - Ext 0.14 4.1/0.0 62.6 4.0 249 Btuh 7 Frame - Wood - Ext 0.14 4.1/0.0 78.6 4.0 313 Btuh 8 Frame - Wood - Ext 0.14 4.1/0.0 174.8 4.0 696 Btuh Wall Total 316 ( s q f t )1258 Btuh Ceilings U-Value R-ValueType/Color/Surface Area(sqft)HTM Load 2 Cath/Sngl Assem/White/Metal 0.082 9.0/0.0 312.0 2.09 652 Btuh Ceiling Total 312 ( s q f t )652 Btuh Floors R-ValueType Size HTM Load 2 Raised - Open 9.0 312 ( s q f t )1.0 299 Btuh Floor Total 312.0 ( s q f t )299 Btuh Zone Envelope Subtotal: 6451 Btuh EnergyGauge® / USRCZB v7.0.00 Page 2 Manual J Summer Calculations Residential Load - Component Details (continued) Patricia M F Bryant ST LUCIE BLVD FORT PIERCE, FL 34946 Project Title: BRYANT_WHOLE HOUSE BLOCK Climate:FL_VERO_BEACH_MUNICIPAL_A 10/5/2021 Infiltration WholehouseType A C H Volume(cuft) Wall Ratio CFM=Load Natural 0.25 2496 0.30 9.6 169 Btuh Internal Occupants Btuh/occupant Appliance Load gain 0 X 230 +0 0 Btuh Sensible Envelope Load: 6620 Btuh Duct load No duct systemNo ducts assigned to this zone.(DGM of 0.000)0 Btuh Sensible Zone Load 6620 Btuh The following window Excursion will be assigned to the system loads. Windows July excursion for System 1 1548 Btuh Excursion Subtotal: 1548 Btuh Duct load 0 Btuh Sensible Excursion Load 1548 Btuh EnergyGauge® / USRCZB v7.0.00 Page 3 Manual J Summer Calculations Residential Load - Component Details (continued) Patricia M F Bryant ST LUCIE BLVD FORT PIERCE, FL 34946 Project Title: BRYANT_WHOLE HOUSE BLOCK Climate:FL_VERO_BEACH_MUNICIPAL_A 10/5/2021 WHOLE HOUSE TOTALS Sensible Envelope Load All Zones 20516 Btuh Sensible Duct Load 0 Btuh Total Sensible Zone Loads 20516 Btuh Sensible ventilation 0 Btuh B l o w e r 0 Btuh Whole House Total sensible gain 20516 Btuh Totals for Cooling Latent infiltration gain (for 58 gr. humidity difference)1268 Btuh Latent ventilation gain 0 Btuh Latent duct gain 0 Btuh Latent occupant gain (1.0 people @ 200 Btuh per person)200 Btuh Latent other gain 0 Btuh Latent total gain 1468 Btuh TOTAL GAIN 21984 Btuh EQUIPMENT 1. Central Unit # M X Z 3 C 2 4 N A 2 22000 Btuh *Key: Window types (Panes - Number and type of panes of glass) (SHGC - Shading coefficient of glass as SHGC numerical value) (U - Window U-Factor) (InSh - Interior shading device: none(No), Blinds(B), Draperies(D) or Roller Shades(R)) - For Blinds: Assume medium color, half closed For Draperies: Assume medium weave, half closed For Roller shades: Assume translucent, half closed (IS - Insect screen: none(N), Full(F) or Half(½)) (Ornt - compass orientation) Version 8 EnergyGauge® / USRCZB v7.0.00 Page 4