HomeMy WebLinkAboutAPPROVED AC Manual JCalculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-17 12:40:34
Right-Suite® Universal 2021 21.0.05 RSU29066 Page 1
...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Load Short Form 3/16/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Chhay Residence, Air Conditioning UnlimitedFor:
TBD Carlton, Fort Pierce, FL 34983
Design Information
InfiltrationClgHtg
SimplifiedMethod9041Outside db (°F)
AverageConstruction quality7570Inside db (°F)
0Fireplaces1529Design TD (°F)
L-Daily range
5030Inside humidity (%)
572Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Goodman Mfg.
Trade Trade GOODMAN
Model Cond GSX16S481A
AHRI ref Coil ASPT49D14A
AHRI ref 201785242
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW9.2 Sensible cooling Btuh31500
Heating output Btuh31370 Latent cooling Btuh13500
Temperature rise °F19 Total cooling Btuh45000
Actual air flow cfm1500 Actual air flow cfm1500
Air flow factor cfm/Btuh0.048 Air flow factor cfm/Btuh0.053
Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.74
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
Tackle Room 36 566 247 27 13
Master Bed 236 3843 3269 185 172
M Hall 26 0 0 0 0
M Bath 75 1734 1049 84 55
WIC 2 49 1526 617 74 33
Master Bed 2 203 3890 3304 188 174
Bath 2 56 857 408 41 22
Family Room 285 2872 2401 139 127
Pantry 15 0 0 0 0
Lin 15 0 0 0 0
Bath 47 1103 565 53 30
Bed 3 149 3059 2482 148 131
Bed 2 142 2441 2286 118 120
M Hall 2 32 0 0 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-17 12:40:34
Right-Suite® Universal 2021 21.0.05 RSU29066 Page 2
...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
Kitchen 145 727 3697 35 195
Hall 106 0 0 0 0
Foyer 225 3532 1912 170 101
Living Room 266 3464 5697 167 300
WIC 47 1483 524 72 28
House 2153 31097 28458 1500 1500
Other equip loads 3493 1855
Equip. @ 0.95 RSM 28918
Latent cooling 10424
TOTALS 2153 34590 39343 1500 1500
2021-Mar-17 12:40:34
Right-Suite® Universal 2021 21.0.05 RSU29066 Page 1
...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Building Analysis 3/16/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Chhay Residence, Air Conditioning UnlimitedFor:
TBD Carlton, Fort Pierce, FL 34983
Design Conditions
Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
Other
Ceilings
Floors
Infiltration
Ducts
Ventilation
% of loadBtuhBtuh/ft²Component
20.169593.1Walls
8.7300717.9Glazing
0.72563.7Doors
6.221341.0Ceilings
20.570843.33.3Floors
10.636601.7Infiltration
23.17997Ducts
00Piping
00Humidification
10.13493Ventilation0Adjustments
100.034590Total
Cooling
Walls
Glazing
Other
Ceilings
Infiltration
Ducts
Internal Gains
Ventilation
% of loadBtuhBtuh/ft²Component
14.243021.9Walls
15.1457227.2Glazing
0.92583.7Doors
12.838861.8Ceilings
000Floors
3.29720.5Infiltration
29.68988Ducts
6.11855Ventilation
18.15480Internal gains
00Blower
0Adjustments
100.030313Total
Latent Cooling Load = 10424 Btuh
Overall U-value = 0.099 Btuh/ft²-°F
Data entries checked.
2021-Mar-17 12:40:34
Right-Suite® Universal 2021 21.0.05 RSU29066 Page 1
...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Component Constructions 3/16/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Chhay Residence, Air Conditioning UnlimitedFor:
TBD Carlton, Fort Pierce, FL 34983
Design Conditions
Location: CoolingHeatingIndoor:
7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr
BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft²
Walls
Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 19143.155.10.109608n 12242.02
6292.029843.155.10.109312e
712.021103.155.10.10935s
8442.0213193.155.10.109419s
10162.0215893.155.10.109504w
37842.0259163.155.10.1091878all
Partitions
Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16"
OC Stud
5181.4610432.9411.00.101355
Windows
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (3.17 ft window ht, 1 ft sep.); 8 ft head ht
7911.511516.800.5807n
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21);
foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.);
8 ft head ht
15710.129418.800.65016n
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 8.4 ft overhang (5.17 ft window ht, 1 ft sep.); 8 ft head ht
30813.740318.000.62022e
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.17 ft window ht, 1 ft sep.); 8 ft head ht
60927.240318.000.62022e
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (2 ft window ht, 1 ft sep.); 8 ft head ht
16928.110116.800.5806w
2021-Mar-17 12:40:34
Right-Suite® Universal 2021 21.0.05 RSU29066 Page 2
...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 8 ft head ht
131728.178716.800.58047w
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21);
foreground = green grass (0.23); 8 ft overhang (8 ft window ht, 1 ft sep.); 8
ft head ht
101121.190518.800.65048w
Doors
Fbrgls Door 1793.731773.697.00.12748e
793.73793.697.00.12721s
2583.732563.697.00.12769all
Ceilings
Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.0342153 38861.8021340.9930.0
Floors
On Grade Depth, Tile Flr Fnsh 00708428.700.989247
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-17 12:40:34
Right-Suite® Universal 2021 21.0.05 RSU29066 Page 1
...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Project Summary 3/16/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Chhay Residence, Air Conditioning UnlimitedFor:TBD Carlton, Fort Pierce, FL 34983
Notes:
Design Information
St Lucie Co Intl, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75
Design TD °F29 Design TD °F15Daily range L
Relative humidity %50Moisture difference gr/lb57
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh23101 Structure Btuh19470
Ducts Btuh7997 Ducts Btuh8988Central vent (110 cfm) 3493 Btuh Central vent (110 cfm) Btuh1855
Outside air Outside airHumidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh34590 Use manufacturer's data n
Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh28918
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh3419
Ducts Btuh2770Central vent (110 cfm) Btuh4235
CoolingHeating Outside air21532153Area (ft²) Equipment latent load Btuh10424
2153321533Volume (ft³)Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh39343
Equiv. AVF (cfm) 57115 Req. total capacity at 0.70 SHR ton3.4
Heating Equipment Summary Cooling Equipment Summary
Make Make Goodman Mfg.Trade Trade GOODMAN
Model Cond GSX16S481AAHRI ref Coil ASPT49D14A
AHRI ref 201785242Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW9.2 Sensible cooling Btuh31500Heating output Btuh31370 Latent cooling Btuh13500
Temperature rise °F19 Total cooling Btuh45000Actual air flow cfm1500 Actual air flow cfm1500
Air flow factor cfm/Btuh0.048 Air flow factor cfm/Btuh0.053Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.74
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-17 12:40:34Right-Suite® Universal 2021 21.0.05 RSU29066 Page 1...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Right-J® Worksheet 3/16/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name House Tackle Room
2 Exposed wall 247.0 ft 6.5 ft
3 Room height 10.0 ft 10.0 heat/coolft
4 Room dimensions ft5.5x6.5
5 Room area 2153.3 ft²35.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 630 608 1914 1224 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 7 0 115 79 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 10.0910.09 16 0 294 157 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 405 312 984 629 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 13.7413.74 22 22 403 308 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 22 0 403 609 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 48 48 177 179 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 35 35 110 71 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 440 419 1319 844 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 21 21 79 79 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 605 504 1589 1016 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 6 0 101 169 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 47 0 787 1317 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 21.0721.07 48 34 905 1011 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 355 355 1043 518 65 65 191 95
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 2153 2153 2134 3886 36 36 35 65
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 2153 247 7084 0 36 7 186 0
6 c) AED excursion 923 -4
Envelope loss/gain 19441 13018 413 155
12 a) Infiltration 3660 972 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 6 1380 0 0
Appliances/other 4100 0
Subtotal (lines 6 to 13)23101 19470 413 155
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 8 14
14 Subtotal 23101 19470 421 169
15 Duct loads 35%46%7997 8988 35%46%146 78
Total room load 31097 28458 566 247
Air required (cfm)Air required (cfm)1500 1500 27 13
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-17 12:40:34Right-Suite® Universal 2021 21.0.05 RSU29066 Page 2...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Right-J® Worksheet 3/16/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Master Bed M Hall
2 Exposed wall 31.0 ft 0 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft17.5x13.5 ft4.0x6.5
5 Room area 236.3 ft²26.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 10.0910.09 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 13.7413.74 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 175 175 551 353 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 135 119 376 241 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 16 0 262 439 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 21.0721.07 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 236 236 234 426 26 26 26 47
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 236 31 889 0 26 0 0 0
6 c) AED excursion 127 -1
Envelope loss/gain 2313 1585 26 46
12 a) Infiltration 536 142 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 500 0
Subtotal (lines 6 to 13)2850 2228 26 46
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 5 9 -26 -46
14 Subtotal 2855 2236 0 0
15 Duct loads 35%46%988 1032 35%46%0 0
Total room load 3843 3269 0 0
Air required (cfm)Air required (cfm)185 172 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-17 12:40:34Right-Suite® Universal 2021 21.0.05 RSU29066 Page 3...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Right-J® Worksheet 3/16/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name M Bath WIC 2
2 Exposed wall 14.5 ft 14.0 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft11.5x6.5 ft6.5x7.5
5 Room area 74.8 ft²48.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 80 80 252 161 65 65 205 131
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 10.0910.09 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 75 75 236 151
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 13.7413.74 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 65 59 186 119 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 6 0 101 169 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 21.0721.07 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 75 75 74 135 49 49 48 88
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 75 15 416 0 49 14 402 0
6 c) AED excursion 53 -12
Envelope loss/gain 1029 637 891 358
12 a) Infiltration 251 67 242 64
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)1280 704 1133 422
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 8 14 0 0
14 Subtotal 1288 718 1133 422
15 Duct loads 35%46%446 331 35%46%392 195
Total room load 1734 1049 1526 617
Air required (cfm)Air required (cfm)84 55 74 33
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-17 12:40:34Right-Suite® Universal 2021 21.0.05 RSU29066 Page 4...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Right-J® Worksheet 3/16/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Master Bed 2 Bath 2
2 Exposed wall 28.5 ft 7.5 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft14.0x14.5 ft7.5x7.5
5 Room area 203.0 ft²56.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 75 75 236 151
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 10.0910.09 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 145 123 386 247 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 13.7413.74 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 22 0 403 609 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 140 140 441 282 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 21.0721.07 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 203 203 201 366 56 56 56 102
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 203 29 817 0 56 8 215 0
6 c) AED excursion 50 -8
Envelope loss/gain 2249 1554 507 245
12 a) Infiltration 493 131 130 34
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 500 0
Subtotal (lines 6 to 13)2742 2185 637 279
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 148 75 0 0
14 Subtotal 2890 2261 637 279
15 Duct loads 35%46%1000 1044 35%46%220 129
Total room load 3890 3304 857 408
Air required (cfm)Air required (cfm)188 174 41 22
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-17 12:40:34Right-Suite® Universal 2021 21.0.05 RSU29066 Page 5...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Right-J® Worksheet 3/16/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Family Room Pantry
2 Exposed wall 19.0 ft 0 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft19.0x15.0 ft5.0x3.0
5 Room area 285.0 ft²15.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 190 174 550 351 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 10.0910.09 16 0 294 157 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 13.7413.74 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 21.0721.07 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 285 285 282 514 15 15 15 27
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 285 19 545 0 15 0 0 0
6 c) AED excursion -44 -1
Envelope loss/gain 1671 979 15 26
12 a) Infiltration 329 87 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 2 460 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)2000 1527 15 26
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 133 116 -15 -26
14 Subtotal 2133 1643 0 0
15 Duct loads 35%46%738 758 35%46%0 0
Total room load 2872 2401 0 0
Air required (cfm)Air required (cfm)139 127 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-17 12:40:34Right-Suite® Universal 2021 21.0.05 RSU29066 Page 6...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Right-J® Worksheet 3/16/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Lin Bath
2 Exposed wall 0 ft 8.5 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft5.0x3.0 ft8.5x5.5
5 Room area 15.0 ft²46.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 85 78 246 157
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 7 0 115 79
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 10.0910.09 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 13.7413.74 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 21.0721.07 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 15 15 15 27 47 47 46 84
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 15 0 0 0 47 9 244 0
6 c) AED excursion -1 -10
Envelope loss/gain 15 26 652 311
12 a) Infiltration 0 0 147 39
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)15 26 799 350
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -15 -26 21 37
14 Subtotal 0 0 820 386
15 Duct loads 35%46%0 0 35%46%284 178
Total room load 0 0 1103 565
Air required (cfm)Air required (cfm)0 0 53 30
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-17 12:40:34Right-Suite® Universal 2021 21.0.05 RSU29066 Page 7...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Right-J® Worksheet 3/16/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bed 3 Bed 2
2 Exposed wall 24.5 ft 18.5 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft13.5x11.0 ft13.5x10.5
5 Room area 148.5 ft²141.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 135 135 425 272 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 10.0910.09 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 13.7413.74 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 80 80 252 161
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 110 94 297 190 105 89 282 180
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 16 0 262 439 16 0 262 439
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 21.0721.07 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 149 149 147 268 142 142 141 256
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 149 25 703 0 142 19 531 0
6 c) AED excursion 143 147
Envelope loss/gain 1835 1312 1467 1183
12 a) Infiltration 424 113 320 85
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 250 250
Subtotal (lines 6 to 13)2259 1674 1787 1518
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 13 24 26 45
14 Subtotal 2272 1698 1813 1564
15 Duct loads 35%46%787 784 35%46%628 722
Total room load 3059 2482 2441 2286
Air required (cfm)Air required (cfm)148 131 118 120
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-17 12:40:34Right-Suite® Universal 2021 21.0.05 RSU29066 Page 8...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Right-J® Worksheet 3/16/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name M Hall 2 Kitchen
2 Exposed wall 4.5 ft 3.0 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft4.5x7.0 ft14.5x10.0
5 Room area 31.5 ft²145.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 10.0910.09 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 30 30 95 60
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 13.7413.74 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 45 24 75 48 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 21 21 79 79 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 21.0721.07 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 32 32 31 57 145 145 144 262
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 32 5 129 0 145 3 86 0
6 c) AED excursion -6 -70
Envelope loss/gain 314 178 324 252
12 a) Infiltration 78 21 52 14
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 2 460
Appliances/other 0 1700
Subtotal (lines 6 to 13)391 199 376 2426
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -391 -199 164 103
14 Subtotal 0 0 540 2529
15 Duct loads 35%46%0 0 35%46%187 1168
Total room load 0 0 727 3697
Air required (cfm)Air required (cfm)0 0 35 195
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-17 12:40:34Right-Suite® Universal 2021 21.0.05 RSU29066 Page 9...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Right-J® Worksheet 3/16/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Hall Foyer
2 Exposed wall 0 ft 30.0 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft106.0x1.0 ft14.5x15.5
5 Room area 106.0 ft²224.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 10.0910.09 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 155 85 267 171
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 13.7413.74 0 0 0 0 22 22 403 308
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 48 48 177 179
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 21.0721.07 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 145 145 426 212
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 106 106 105 191 225 225 223 406
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 106 0 0 0 225 30 860 0
6 c) AED excursion -5 -38
Envelope loss/gain 105 186 2355 1237
12 a) Infiltration 0 0 268 71
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)105 186 2624 1308
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -105 -186 0 0
14 Subtotal 0 0 2624 1308
15 Duct loads 35%46%0 0 35%46%908 604
Total room load 0 0 3532 1912
Air required (cfm)Air required (cfm)0 0 170 101
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-17 12:40:34Right-Suite® Universal 2021 21.0.05 RSU29066 Page 10...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Right-J® Worksheet 3/16/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Living Room WIC
2 Exposed wall 20.0 ft 17.0 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft14.0x19.0 ft3.5x13.5
5 Room area 266.0 ft²47.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 10.0910.09 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 13.7413.74 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 35 35 110 71
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 190 142 447 286 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 21.0721.07 48 34 905 1011 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 10 10 29 15 135 135 397 197
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 266 266 264 480 47 47 47 85
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 266 20 574 0 47 17 488 0
6 c) AED excursion 613 -10
Envelope loss/gain 2219 2405 1041 342
12 a) Infiltration 329 87 61 16
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 2 460 0 0
Appliances/other 900 0
Subtotal (lines 6 to 13)2548 3853 1102 358
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 26 45 0 0
14 Subtotal 2573 3898 1102 358
15 Duct loads 35%46%891 1799 35%46%381 165
Total room load 3464 5697 1483 524
Air required (cfm)Air required (cfm)167 300 72 28
2021-Mar-17 12:40:35
Right-Suite® Universal 2021 21.0.05 RSU29066 Page 1
...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Duct System Summary 3/16/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Chhay Residence, Air Conditioning UnlimitedFor:
TBD Carlton, Fort Pierce, FL 34983
CoolingHeating
External static pressure in H2O0.70in H2O0.70
Pressure losses in H2O0in H2O0
Available static pressure in H2O0.70in H2O0.70
Supply / return available pressure 0.350 / 0.350 in H2O in H2O0.350 / 0.350
Lowest friction rate in/100ft0.368in/100ft0.368
Actual air flow cfm1500cfm1500
Total effective length (TEL) ft190
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st1100.040.3VlFx0x05.00.49936641103hBath
st3125.063.1VlFx0x04.00.3722650857hBath 2
st1100.037.8VlFx0x06.00.5081451412286cBed 2
st1100.041.4VlFx0x06.00.4951571773059hBed 3
st1100.047.3VlFx0x05.00.47576831436hFamily Room
st1100.039.0VlFx0x05.00.50476831436hFamily Room-A
80.07.8VlFx0x07.00.7971212043532hFoyer
st1100.041.5VlFx0x07.00.495234423697cKitchen
75.010.2VlFx0x07.00.8221801002849cLiving Room
st1100.041.4VlFx0x07.00.4951801002849cLiving Room-A
st2100.018.6VlFx0x05.00.590661001734hM Bath
st2100.018.5VlFx0x05.00.5901031111921hMaster Bed
st3125.064.4VlFx0x06.00.3701041131945hMaster Bed 2
st3125.065.0VlFx0x06.00.3681041131945hMaster Bed 2-A
st2100.023.0VlFx0x05.00.5691031111921hMaster Bed-A
st2100.019.0VlFx0x04.00.5881633566hTackle Room
st2100.021.1VlFx0x05.00.57833861483hWIC
st3125.064.3VlFx0x05.00.37039881526hWIC 2
2021-Mar-17 12:40:35
Right-Suite® Universal 2021 21.0.05 RSU29066 Page 2
...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st3 Peak AVF 363 274 0.368 822 9.0 0x0 VinlFlx st1
st1 Peak AVF 1054 1177 0.368 843 16.0 0x0 VinlFlx
st2 Peak AVF 441 322 0.569 809 10.0 0x0 VinlFlx
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb7 0x 3080 240 0 0 0 0 x0 0 VlFx
rb6 0x 1660 152 0 0 0 0 x0 0 VlFx
rsb1 0x 6940 859 0 0 0 0 x0 0 VlFx
rb4 0x 3130 248 0 0 0 0 x0 0 VlFx
rb3 0x 1410 145 0 0 0 0 x0 0 VlFx
rb2 0x 1770 157 0 0 0 0 x0 0 VlFx
2021-Mar-17 12:40:35
Right-Suite® Universal 2021 21.0.05 RSU29066 Page 1
...uments\Wrightsoft HVAC\TBD Carlton PSL Prop.rup Calc = MJ8 Front Door faces: N
1440Job:Manual S Compliance Report 3/16/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Chhay Residence, Air Conditioning UnlimitedFor:
TBD Carlton, Fort Pierce, FL 34983
Cooling Equipment
Design Conditions
°F77.3Entering coil DB:Btuh30313Sensible gain:°F90.4Outdoor design DB:
°F64.5Entering coil WB:Btuh10424Latent gain:°F77.4Outdoor design WB:
Btuh40737Total gain:°F75.0Indoor design DB:
cfm1500Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
GSX16S481A+ASPT49D14AModel:Goodman Mfg.Manufacturer:
cfm1500Actual airflow:
% of load117Btuh35464Sensible capacity:
% of load91Btuh9508Latent capacity:
%79SHR:% of load110Btuh44972Total capacity:
Heating Equipment
Design Conditions
°F67.3Entering coil DB:Btuh34590Heat loss:°F41.0Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Elec stripEquipment type:
Model:Manufacturer:
cfm1500Actual airflow:
°F50Temp. rise:% of load91kW9.2Output capacity:
Meets all requirements of ACCA Manual S.
Job #: 1440
Performed by Chris Bateman for:
Chhay Residence
TBD Carlton
Fort Pierce, FL 34983
Air Calcs, LLC
7550 Hidden Hammock Ln
Vero Beach, FL 32966
Phone: 772.800.8413
vickilynne@aircalcs.com
Scale: 1 : 147
Page 1
Right-Suite® Universal 2021
21.0.05 RSU29066
2021-Mar-17 12:40:50
...ft HVAC\TBD Carlton PSL Prop.rup
N
Level 1
Garage
Tackle Room
Master Bed
M Hall
M Bath
WIC 2
Master Bed 2
Bath 2
Family Room
Pantry
Lin
Bath
Bed 3Bed 2
M Hall 2
Kitchen
Hall
Foyer
Living Room
WIC
6'0"W x 8'0"H
4'4"W x 5'2"H
H/W
4'4"W x 5'2"H
3'0"W x 5'2"H
2'2"W x 3'2"H
3'0"W x 5'2"H3'0"W x 5'2"H
6'0"W x 8'0"H
3'0"W x 2'0"H
2'8"W x 8'0"H
3'0"W x 5'2"H
12 x 8
177 cfm12 x 8
145 cfm
12 x 12
177 cfm
12 x 12
145 cfm
8 x 8
111 cfm
8 x 8
111 cfm
10 x 6
100 cfm
10 x 6
64 cfm
8 x 4
50 cfm
12 x 12
313 cfm
8 x 8
113 cfm
8 x 8
113 cfm
8 x 8
83 cfm
8 x 8
83 cfm
12 x 12
166 cfm
20 x 20
859 cfm
12 x 12
308 cfm
18 x 18
10 x 10
180 cfm10 x 10
180 cfm
80 CFM
4" Duct
4" Exhaust Vent
50 CFM
4" Duct
4" Exhaust Vent
80 CFM
4" Duct
4" Exhaust Vent
12 x 12
234 cfm14 x 8
204 cfm
10 x 6
88 cfm
10 x 6
86 cfm
8 x 4
33 cfm
4 "
4 "
4 "
10 "
4 "
16 x 16
5 "
5 "
5 "
5 "
7 "
16 "
7 "
7 "
6 "
7 "
6 "
5 "
5 "
5 "
9 "
16 x 16
6 "
6 "
5 "
4 "
16 "
12 "
10 "
12 "
16 "
DUCTS IN THE GARAGE AND
DUCTS PENETRATING THE
WALLS OR CEILINGS
SEPARATING THE DWELLING
FROM
THE GARAGE SHALL BE
CONSTRUCTED OF A MINIMUM
NO.
26 GAGE (0.48 MM) SHEET
STEEL, 1 INCH MINIMUM RIGID
NONMETALLIC CLASS 0 OR
CLASS 1 DUCT BOARD, OR
OTHER APPROVED MATERIAL
AND SHALL HAVE NO
OPENINGS INTO THE GARAGE