HomeMy WebLinkAboutAPPROVED Signed Energy Code (2)FORM R405-2020
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2020 Florida Buildings Code, Energy Conservation via the
Residential Simulated Performance Alternative shall include:
❑ This checklist
❑ Form R405-2020 report
❑ Input summary checklist that can be used for field verification (usually four pages/may be greater)
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1. 9 - one page)
❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4
allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to
comply with Section C402.5
❑ If Form R405 duct leakage type indicates anything other than "default leakage`, then a completed
2020 Duct Leakage Test Report - Performance Method (usually one page)
3/17/2021 9:27:30 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
FORM R405-2020
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: TBD Carlton PSL Prop
Street: TBD Carlton
City, State, Zip: Fort Pierce , FL , 34983
Owner: Chhay Residence
Design Location: FL, ST_LUCIE_CO_INTL
Builder Name: PSL Prop
Permit Office:
Permit Number:
Jurisdiction: St. Lucie
County: St. Lucie (Florida Climate Zone 2 )
1. New construction or existing New (From Plans) 10. Wall Type$2470.0 sgft.) Insulation Area
Detached a. Concrete Block - Ext Insul, Exterior R=4.1 2115.00 ft2
2. Single family or multiple family b. Interior Frame - Wood, Interior R=11.0 355.00 ft'
3. Number of units, if multiple family 1 c. N/A R= ft2
4. Number of Bedrooms 4 d. NIA R= 112
11. Ceiling Types (2155.0 sqft.) Insulation Area
5. Is this a worst case? Yes a. Under Attic (Vented) R=30.0 2155.00 ft2
6. Conditioned floor area above grade (ft2) 2155 b. N/A R= 112
c. NIA R= ft2
Conditioned floor area below grade (fl2) 0 R ft2
12. Ducts
7. Windows(167.6 sgft.) Description Area a. Sup: Attic, Ret: Attic, AH: Garage 6 859
a. U-Factor: SgI, U=0.65 63.50 ft2
SHGC: SHGC=0.21
Efficiency
b. U-Factor: SgI, U=0.58 59.36 ft2 13. Cooling systems kBg5 Or SEER:16 00
SHGC: SHGC=0.24 a. Central Unit
c. U-Factor: Sgl, U=0.62 44.78 ft2
SHGC: SHGC=0.22 14, Heating systems kBtulhr Efficiency
Area Weighted Average Overhang Depth: 3.995 ft. a. Electric Strip Heat 31 A COP:1.00
Area Weighted Average SHGC: 0,223
8. Skylights Area
c. U-Factor.(AVG) N/A (l2 15. Hot water systems
SHGC(AVG): N/A a. Electric Cap: 50 gallons
9. Floor Types (2153.7 sgft.) Insulation Area EF: 0.960
a. Slab -On -Grade Edge Insulation R=0.0 2153.70 ft2 b. Conservation features
b. N/A R= fP None
c. N/A R= ft2 16. Credits Pstat
Total Proposed Modified Loads: 64.84 PASS
Glass/Floor Area: 0.078 Total Baseline Loads: 64.92
I hereby certify that the plans and specifications covered by
this calculation are in compliance with the Florida Energy
Code.
PREPARED BY: CA44� g 2�L--
DATE: 3T02�
--
I hereby certify that this building, a es ad, is
with the Florida Energy Code. /
OWNER/AGENT.
DATE:
Review of the plans and
specifications covered by this
calculation indicates compliance
with the Florida Energy Code.
Before construction is completed
this building will be inspected for
compliance with Section 553.908
Florida Statutes.
BUILDING OFFICIAL:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure quanrres as
certified factory -sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 6.00 ACH50 (R402.4.1.2).
3/17/2021 9:27 AM 7.0.00 - FlaRes2020 FBC 7ih Edition (2020) Compliant Software Page 1 of 7
PROJECT
Title: TBD Carlton PSL Prop Bedrooms: 4 Address Type: Street Address
Building Type: User Conditioned Area: 2155 Lot #
Owner Name: Chhay Residence Total Stories: 1 Block/Subdivision:
# of Units: 1 Worst Case: Yes PlatBook:
Builder Name: PSL Prop Rotate Angle: 180 Street: TBD Carlton
Permit Office: Cross Ventilation: No County: St. Lucie
Jurisdiction: St. Lucie Whole House Fan: No City, State, Zip: Fort Pierce ,
Family Type: Detached FL , 34983
New/Existing: New (From Plans)
Comment:
CLIMATE
Design Temp Int Design Temp Heating Design Daily Temp
Design Location TMY Site 97.5 % 2.5 % Winter Summer Degree Days Moisture Range
FL, ST_LUCIE_CO_INTL FL_VERO_BEACH_MUNI 39 90 70 75 299 58 Medium
BLOCKS
Number Name Area Volume _ —.— —
1 Entire House 2155 21550
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms InfI ID FinishedCooledHeated
1 Tackle Room 36 360 No 0 1 Yes Yes Yes
2 Master Bed 236 2360 No 0 1 1 Yes Yes Yes
3 M Hall 26 260 No 0 1 Yes Yes Yes
4 M Bath 75 750 No 0 1 Yes Yes Yes
5 WIC 2 49 490 No 0 1 Yes Yes Yes
6 Master Bed 2 203 2030 No 0 1 1 Yes Yes Yes
7 Bath 2 56 560 No 0 1 Yes Yes Yes
8 Family Room 285 2850 No 2 1 Yes Yes Yes
9 Pantry 15 150 No 0 1 Yes Yes Yes
10 Lin 15 150 No 0 1 Yes Yes Yes
11 Bath 47 470 No 0 1 Yes Yes Yes
12 Bed 3 149 1490 No 0 1 1 Yes Yes Yes
13 Bed 142 1420 No 0 1 1 Yes Yes Yes
14 M Hall 2 32 320 No 0 1 Yes Yes Yes
15 Kitchen 145 1450 Yes 2 1 Yes Yes Yes
16 Hall 106 1060 No 0 1 Yes Yes Yes
17 Foyer 225 2250 No 0 1 Yes Yes Yes
18 Living Room 266 2660 No 2 1 Yes Yes Yes
19 WIC 47 470 No 0 1 Yes Yes Yes
3/17/2021 9:27 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 7
1iP]1A�
# Floor Type
Space
Perimeter
Perimeter R-Value
Area
Joist R-Value
Tile
Wood
Carpel
1 Slab -On -Grade Edge Insulatio
Tackle Room
6.5 it
0
35.8 ft'
____
1
0
0
2 Slab -On -Grade Edge Insulatio
Master Bed
31 ft
0
236.3 ft'
1
0
0
3 Slab -On -Grade Edge Insulatio
M Hall
1 it
0
26 ft'
____
1
0
0
4 Slab -On -Grade Edge Insulatio
M Bath
14.5 it
0
74.8 ft'
____
1
0
0
5 Slab -On -Grade Edge Insulatio
WIC 2
14 ft
0
48.8 ft'
____
1
0
0
6 Slab -On -Grade Edge Insulatio
Master Bed 2
28.5 ft
0
203 ft'
____
1
0
0
7 Slab -On -Grade Edge Insulatio
Bath 2
7.5 ft
0
56,3 ft'
____
1
0
0
8Slab-On-Grade Edge Insulatio
Family Room
19 ft
0
285 ft'
____
1
0
0
9 Slab -On -Grade Edge Insulatio
Pantry
1 ft
0
15 ft'
____
1
0
0
1OSlab-On-Grade Edge Insulatio
Lin
1 ft
0
15 ft'
1
0
0
11Slab-On-Grade Edge Insulatio
Bath
8.5 It
0
46.8 ft'
__--
1
0
0
12SIab-On-Grade Edge Insulatio
Bed 3
24.5 It
0
148.5 ft2
____
1
0
0
13SIab-On-Grade Edge Insulatio
Bed 2
18.5 it
0
141.8 ft'
____
1
0
0
14SIah-On-Grade Edge Insulatio
M Hall 2
4.5 it
0
31.5 W
____
1
0
0
15SIab-On-Grade Edge Insulatio
Kitchen
3 ft
0
145 ft'
____
1
0
0
16SIab-On-Grade Edge Insulatio
Hall
1 it
0
106 ft'
1
0
0
17SIab-On-Grade Edge Insulatio
Foyer
30 it
0
224.8 ft'
1
0
0
18SIab-On-Grade Edge Insulatio
Living Room
20 ft
0
266 ft'
____
1
0
0
19SIab-On-Grade Edge Insulatio
WIC
17 it
0
47.3 ft'
____
1
0
0
Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch
# Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg)
1 Hip Composition shingles 2409 ft' 0 W Medium N 0.8 No 0.9 No 0 26.57
/ ATTIC
V # Type Ventilation Vent Ratio (1 in) Area RBS IRCC
1 Full attic Vented 300 2155 ft' N N
3/17/2021 9:27 AM 7.0.00 - FlaRes2020 FBC 71h Edition (2020) Compliant Software Page 3 of 7
CEILING
_# Ceiling Type Space - R-Value Ins Type Area Framing Free Truss Type
1 Under Attic (Vented) Tackle Room 30 Blown 36 ft2 0.1 Wood
2 Under Attic (Vented) Master Bed 30 Blown 236 ft2 0.1 Wood
_ 3 Under Attic (Vented) M Hall 30 Blown 26 ft2 0.1 Wood
_ 4 Under Attic (Vented) M Bath 30 Blown 75 ft2 0.1 Wood
_ 5 Under Attic (Vented) WIC 2 30 Blown 491? 0.1 Wood
_ 6 Under Attic (Vented) Master Bed 2 30 Blown 203 ft2 0.1 Wood
7 Under Attic (Vented) Bath 2 30 Blown 56 ft2 0.1 Wood
_ 8 Under Attic (Vented) Family Room 30 Blown 285 ft2 0.1 Wood
_ 9 Under Attic (Vented) Pantry 30 Blown 15 ft2 0.1 Wood
Lin 30 Blown 15 ft2 0.1 Wood
_ 10 Under Attic (Vented) '
Bath 30 Blown 47 ft2 0.1 Woad
_ 11 Under Attic (Vented) '..
_ 12 Under Attic (Vented) Bed 3 30 Blown 149 1 0.1 Wood
13 Under Attic (Vented) Bed 2 30 Blown 142 W 0.1 Wood
14 Under Attic (Vented) M Hall 2 30 Blown 32 ft2 0.1 Wood
_ 15 Under Attic (Vented) Kitchen 30 Blown 145 ft2 0.1 Wood
_ 16 Under Attic (Vented) Hall 30 Blown 1061 0.1 Wood
_ 17 Under Attic (Vented) Foyer 30 Blown 225 ft2 0.1 Wood
18 Under Attic (Vented) 9
Livin Room 30 Blown 266 ft2 0.1 Wood
',...
19 Under Attic (Vented) WIC 30 Blown 47 ft2 0.1 Wood
WALLS
Adjacent Cavity Width Height Sheathing Framing Solar Below
T.o-�VaUSype--- Space R- a Ft In- �tJ Area-. tz-�ialue-Fraction--96sor,-Grade%-
_ 1 E=>W Tackle R Interior Frame - Wood Tackle Room 11 6 6 10 0 65.0 ft2 0 025 0.8 0
_ 2 S=>N Exterior Concrete Block - Ext InstMaster Bed 4.1 17 6 10 0 175.0 ft2 0 0 0,3 0
_ 3 W=>E Exterior Concrete Block - Ext InsdUaster Bed 4.1 13 6 10 0 135.0 ft2 0 0 0.3 0
_ 4 N=>S Exterior Concrete Block - Ext Insul M Bath 4.1 8 0 10 0 80.0 ft2 0 0 0.3 0
_ 5 W=>E Exterior Concrete Block - Ext Insul M Bath 4.1 6 6 10 0 65.0 ft2 0 0 0.3 0 '......
_ 6 N=>S Exterior Concrete Block - Ext Insul WIC 2 4.1 6 6 10 0 65.0 f 2 0 0 0.3 0
_ 7 E=>W Exterior Concrete Block - Ext Insul WIC 2 4.1 7 6 10 0 75.0 ft2 0 0 0.3 0
_ 8 E=>W Exterior Concrete Block - Ext InWhster Bed 2 4.1 14 6 10 0 145.0 ft2 0 0 0.3 0 '..
_ 9 S=>N Exterior Concrete Block - Ext In3dhster Bed 2 4.1 14 0 10 0 140.0 IE 0 0 0.3 0
_ 10 N=>S Exterior Concrete Block - Ext Insul Bath 2 4.1 7 6 10 0 75,0 ft2 0 0 03 0
_ 11 N=>S Exterior Concrete Block - Ext IngAmily Room 4.1 19 0 10 0 190,0 ft2 0 0 0.3 0
_ 12 N=>S Exterior Concrete Block - Ext Insul Bath 4.1 8 6 10 0 85.0 ft2 0 0 0.3 0
_ 13 N=>S Exterior Concrete Block - Ext Insul Bed 3 4.1 13 6 10 0 135.0 ft2 0 0 0.3 0
14 W=>E Exterior Concrete Block - Ext Insul Bed 3 4.1 11 0 10 0 110.0 ft2 0 0 0.3 0
_ 15 S=>N Exterior Concrete Block - Ext Insul Bed 2 4.1 8 0 10 0 80.0 ft2 0 0 0.3 0
_16 W=>E Exterior Concrete Block - Ext Insul Bed 2 4A 10 6 10 0 105.0 ft2 0 0 0.3 0
17 S=>N Exterior Concrete Block - Ext InsulM Hall 2 4.1 4 6 10 0 45.0 ft2 0 0 0.3 0
_ 18 E=>W Exterior Concrete Block - Ext Insul Kitchen 4.1 3 0 10 0 30.0 ft2 0 0 0.3 0
_ 19 E=>W Exterior Concrete Block - Ext Insul Foyer 4.1 15 6 10 0 155.0 W 0 0 0.3 0
20 S=>N Tackle R Interior Frame - Wood Foyer 11 14 6 10 0 145.0 ft2 0 0.25 0.8 0
21 W=>E Exterior Concrete Block - Ext Insblving Room 4.1 19 0 10 0 190.0 ft2 0 0 0.3 0
3/17/2021 9:27 AM
7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 7
FORM R405-2020
INPUT
SUMMARY CHECKLIST REPOKI
WALLS
Adjacent Cavity Width Height Sheathing Framing Solar Below
Oral TI �I.�e-, Space R_Value- Fr in _F_L--In-- Qrea R_velue_._Fraction--Absor_-Crade%-
22 S=>N Tackle R Interior Frame - Wood Living Room 11 1 0 10 0 10.0 ft' 0 0.25 0.8 0
23 S=>N Exterior Concrete Block- Ext Insul WIC 4.1 3 6 10 0 35.0 ft' 0 0 0.5 0
24 E=>W Tackle R Interior Frame - Wood WIC 11 13 6 10 0 135.0 ft' 0 0.25 0.8 0
DOORS
# Ornt
Door Type
Space
P
Storms U-Value
Ft
Width
In
Height
Ft In
Area
1 S=>N
2 E=>W
Insulated
Insulated
M Hall 2
Foyer
None .13
None .13
2
6
8
8
8
21.3 W
48 ft'
WINDOWS
Orientation shown is the
entered orientation => changed to Worst Case.
/ Wall
V # Ornt ID
_ 1 W=>E 3
_ 2 W=>E 5
3 E=>W 8
_ 4 N=>S 11
_ 5 N=>S 12
_ 6 W=>E 14
_ 7 W=>E 16
_ 8 E=>W 19
9 W=>E 21
Frame
Metal
Metal
Metal
Metal
Metal
Metal
Metal
Metal
Metal
Panes
low-E Single
Low-E Single
Low-E Single
Low-E Single
Low-E Single
low-E Single
Low-E Single
Low-E Single
Low-E Single
NFRC
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
U-Factor SHGC Imp Area
0.58 0.24 Y 15.5 fP
0.58 0.24 Y 6.0 112
0.62 0.22 Y 22A ft'
0.65 0.21 Y 15.5 ft'
0.58 0.24 Y 6.9 ft'
0.58 0.24 Y 15.5 ft'
0.58 0.24 Y 15.5 ft2
0.62 0.22 Y 22.4 ft'
0.65 0.21 Y 48.0 ft'
Overhang
Depth Separation
1 it 0 in 1 ft 0 in
1 it 0 in 1 ft 0 in
1 ft 0 in 1 It 0 in
1 ft 0 in 1 it 0 in
1 it 0 in 1 ft 0 in
1 ft 0 in 1 ft 0 in
1 ft 0 in 1 ft 0 in
8 ft 5 in 1 it 0 in
8 it 0 in 1 ft 0 in
Int Shade
Drapes/blinds
Drapes/blinds
Drapeslblinds
None
Drapes/blinds
Drapes/blinds
Drapes/blinds
Drapes/blinds
None
Screening
Exterior 5
Exterior 5
Exterior 5
None
Exterior 5
Exterior 5
Exterior 5
Exterior 5
None
GARAGE
# Floor Area
1 382.8 ft'
Ceiling Area
382.8 ft'
Exposed Wall Perimeter Avg. Wall Height
64 it 8 it
Exposed Wall Insulation
1
INFILTRATION
# Scope
Method
SLA
CFM 50- ELA EgLA
ACH
ACH 50
1 Wholehouse Proposed ACH(50)
.000381
2155 118.23 221.96
.1184
6
HEATING SYSTEM
# System
1 Electric
Type
Strip Heat/
Subtype
None
Speed Efficiency
COPA 31.37
Capacity
kBtu/hr
Block
1
Ducts
sys#1
3/1712021 9:27 AM
7.0.00 - FlaRes2020 FBC 7ih Edition (2020) Compliant Software Page 5 of 7
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
COOLING SYSTEM
_#--System Type
1 Central Unit/
Subtype
Split
Subtype _Efficiency
Singl SEER: 16
Capacity
45 kBtu/hr
Air Flow
cfm
SHR Block
0.7 1
Ducts
sys#1
HOT WATER SYSTEM
# _System Type
1 Electric
SubType
None
Location
Garage
EF
0.96
Cap — Use
50 gal 60.9 gal
SetPnt
120 deg
Conservation
None
SOLAR HOT
WATER SYSTEM
Collector
Storage
FSEC
Cert # Company Name
System Model # Collector Model
# Area
Volume—
FEF
—
W
None None
DUCTS
---- Supply ----
# Location R-Value Area
---- Return ----
Location Area
Leakage Type
Air
Handler
CFM 25
TOT
CFM25 OUT ON RLF
--
H#
Heatt C
Cool
1 Attic
6 859 ft2
Attic
859 ft'
Default Leakage
Garage
(Default)
(Default)
1 1
TEMPERATURES
Programabl(feX,jThermostat:
CApr(feiling Fans:Jan
1�Y Feb((X,(
Cooing [ ]Jan [ ] Feb
Ven
[X] Mar
€
Apr
I Merr
[ May
Junfr Jul
rl Jun rl Jul
(r
[X� Aug
ff
[X� Sep
f (fX,�Nov
Oct [X]
Nov
H Dec
Dec
Thermostat Schedule: HERS 2006 Reference
Schedule Type 1
2
3
4
Hours
5 6 — 7
_8
9
10
11
12
Cooling (WD) AM
PM
Cooling (WEH) PAM
M
Heating (WD) PM
Heating (WEH) PM
78
80
78
78
66
68
68
78
80
78
78
66
68
68
78
78
78
78
66
68
68
78
78
78
78
66
68
68
—
78 78
78 78
78 78
78 78
66 68
68 68
68 68
78
78
78
78
68
68
68
78
78
78
78
68
68
68
80
78
78
78
68
68
68
80
78
78
78
68
68
68
80
78
78
78
68
66
66
80
78
78
78
68
66
66
MASS
Mass Type
Default(8 Ibs/sq.ft.
Default(8 Ibs/sq.ft.
Default(8 ibs/sq.ft.
Default(8 Ibs/sq.ft.
Default(8 Ibs/sq.ft,
Default(8 Ibs/sq.ft.
Default(8 ibs/sq.ft.
Default(8 Ibs/sq.ft.
Default(8 lbs/sq.ft,
Default(8 lbs/sq.ft.
Default(8 Ibs/sq.ft.
--
Area
0 ft2
ft'
ft2
ft'
ft'
ft'
ft'
ft'
ft2
ft2
fE
--
Thickness —Furniture
0 ft
it
ft
ft
it
ft
ft
ft
ft
It
It
Fraction
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
Space_
Tackle Room
Master Bed
M Hall
M Bath
WIC 2
Master Bed 2
Bath 2
Family Room
Pantry
Lin
Bath
—_
Default(8 Ibs/sq.ft.
3/1712021 9:27 AM
7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 6 of 7
FORM
MASS
Mass Type Area Thickness Furniture Fraction Space
Default(8 Ibs/sq.ft. ft' ft 0.3 Bed 2
Default(8 Ibs/sq.ft. ft2 it 0.3 M Hall 2
Default(8 lbs/sq.ft. ft' it 0.3 Kitchen
Default(8 lbs/sq.ft. ft' ft 0.3 Hall
Default(8 lbs/sq.ft. W it 0.3 Foyer
Default(8 Ibs/sq.ft. ft' ft 0.3 Living Room
3/17/2021 9:27 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 7 of 7
FORM R405-2020
11:19WARRM
IMMM OUR
ESTIMATED ENERGY PERFORMANCE INDEX* = IUU
The lower the EnergyPerformance Index, the more efficient the home.
TBD Carlton, Fort Pierce, FL, 34983
Insulation Area
1. New construction or existing New (From Plans) 10 a Colncrete Block - Ext'I sul, Exterior R=4.1 2115.00 fP
2. Single family or multiple family Detached b. Interior Frame - Wood, Interior R=11.0 355.00 ft'
3. Number of units, if multiple family 1 c. N/A R= ft'
4. Number of Bedrooms 4
d. N/A R= fi
11. Ceiling Type and insulation level Insulation Area
5. is this a worst case? Yes a. Under Attic (Vented) R=30.0 2155.00 fP
bN/A R= ft'
6. Conditioned floor area (ft') c. N/A R= ft'
2155 ,
7. Windows" Description Area 12. Ducts, location & insulation level R ft`
a. U-Factor: Sgl, U=0.65 63.50 ft' a. Sup: Attic, Ret: Attic, AH: Garage 6 859
SHGC: SHGC=0.21
b. U-Factor: Sgi, U=0.58 59.36 ft' kBtu/hr Efficiency
13. Cooling systems y
SHGC: SHGC=0.24
c. U-Factor: Sgl, U=0.62 44.78 ft'
a. Central Unit 45.0 SEER:16.00
SHGC: SHGC=0.22
d. U-Factor: NIA fP 14, Heating systems kBtulhr Efficiency
SHGC: a. Electric Strip Heat 31.4 COP:1.00
Area Weighted Average Overhang Depth: 3,995 ft.
Area Weighted Average SHGC: 0.223
Area 15. Hot water systems Cap: 50 gallons
8. Skylights Description a. Electric
a. U-Factor(AVG): N/A ft' EF: 0.96
SHGC(AVG): N/A b. Conservation features
9. Floor Types Insulation Area None
a. Slab -On -Grade Edge Insulation R=0.0 2153,70 fl' Credits (Performance method) Pstal
b. N/A R= ft'
a N/A R= ft'
I certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded)
in this home before final inspection. Oth rwise, a p w EPL Display Card will be completed
based on installed Code complia e res.
Builder Signature: ��_"i�� Date: frj'
Address of New Home: 'j- City/FL Zip:I% PLVC F(
;3Y483
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code,
Energy Conservation, contact the Florida Building Commission's support staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
3/17/2021 9:27 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 7th Edition (2020)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: TBD Carlton Permit Number:
Fort Pierce FL 34983
MANDATORY REQUIREMENTS -See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory).The building offcial shall require that an energy performance level (EPL)
display card be completed and certifed by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and effciencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
SECTION R402 BUILDING THERMAL ENVELOPE
❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and
R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturers instructions and the criteria listed in Table R402.4.1.1, as applicable io the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNETIICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted 6y either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infltralion control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if Installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑ R402.4.2 Fireplaces. New wood -burning freplaces shall have tight -fitting Flue dampers or doors, and outdoor combustion air. Where
using tight-Fltting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
❑R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
AAMA/ WDMA/CSA 1/01/I.S.21A440 by an accredted, ndependent laboratory and listed andLlabeled by the manufacturerng to NFRC 400 or
Exception: Site -built windows, skylights and doors.
3/17/2021 9:27 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS _ (Continued)
R402.4.4 Rooms containing fuel burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the roam shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 L/s) when tested in accordance wish ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls.
R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSIlRESNET/ICC 380 by either individuals as defned in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rol ding thet aoufacturegs a c ha dle renclo a el if installed at the time'of the test. AllWegistersshall be tapedsor o henvise
sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire
system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn =
duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code offcial.
R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C)
or below 55°F (13°C) shall be insulated to a minimum of R-3.
❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are
installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall
be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibifed. Controls for
circulating hot water system pumps shall start the pump based on the identifcation of a demand for hot water within [he occupancy. The
controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no
demand for hot water.
❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems s a
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when heated water is used in the occupancy.
3/17/2021 9:27 AM EnergyGauge®USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software
Page 2 of 5
MANDATORY REQUIREMENTS -
Continued
❑ R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 1A inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1A Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
❑
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100OF to 140OF (38°C to 60°C).
R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall he provided to permit the power supplied to
❑ electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burners) of
combustion types of service water -heating systems to be turned off.
❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table 0404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
❑ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
❑ R403.6 Mechanical ventilation (Mandatory). The building shall he provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment.
❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based
on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation
methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the
outdoor and indoor units (if split system) shall be submitted along with the sensible and total
cooling
s focapacities
uture at the
desiexpansiongn other
conditions described in Section R302.1. This Code does not allow designer safety factors, pr
factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical
ventilation such as standard kitchen and bathroom exhaust systems, New or replacement heating and cooling equipment shall have
an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is
installed. TABLE R403.6.1
ruAnur Ai NIPHTu ATION SYSTEM FAN EFFICACY MUM
Wnvr.o-nvuo
' FAN LOCATION
„
AIRFLO C RATE MINIMUM
MIN�CFM/WATT) EFFICACYa
AIRFLOW RATE MAXIMU
Any
1.2 cfm/watt
HRV or ERV
EEEAny
Any
2.8 cfm/watt
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
Bathroom, utility room
For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916
3/17/2021 9:27 AM EnergyGauge®USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
❑R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values far entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return ducts) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by aFlorida-registered engineer, in attached single- and multiple -family units, the capacity o
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7,1.
❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or healing to the major entertainment areas.
2, A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is failing and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
❑ R403.10.1 Heaters. The electric power to heaters shall 6e controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
❑ shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
3/17/2021 9:27 AM EnergyGauge®USA 7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 4 of 5
❑ R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with avapor-retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat Toss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pooi
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
❑ R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
❑ R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements:
1. The minimum rated efficiency of the dehumidifer shall be greater than 1.7 liters/ kWh if the total dehumidi0er capacity for the house
is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for fhe house is greater than or equal to 75 pints/day.
2. The dehumidifer shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air.
3. Any dehumidifer unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
❑
R403.13.1 Ducted dehumidifiers.
Ducted dehumidifers shall,
in addition to conforming
to the requirements of Section
R403.13,
conform to the following requirements:
1. If a ducted dehumidifer is confgured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct.
2. If a ducted dehumidifer is confgured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifer supply duct between the dehumidifer and central supply duct.
3. A ducted dehumidifer shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an
effcacy of at least 45tumens-per-watt or shall utilize lamps with an efficacy of not less than 65 tumens-per-watt.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
3/17/2021 9:27 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 5
2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: TBD Carlton PSL Prop Builder Name: PSL Prop
Street: TBD Carlton Permit Office:
City, State, Zip: Fort Pierce FL, 34983 Permit Number:
U
w
Owner: Chhay Residence Jurisdiction: St. Lucie
=
U
Design Location: FL, ST_LUCIE_CO_INTL
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
requirements
Breaks orjoints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
Ceiling/attic
the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
Walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
with a material having a thermal resistance of R-3
sealed.
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/doorjambs and framing, and
skylights and framing shall be sealed.
and doors
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
The barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
Floors
air
maintain permanent contact with the underside of
(including
insulation,
subfloor decking, or floor framing cavity insulation
above -garage
shall be permitted to be in contact with the top side
and cantilevered
of sheathing, or continuous insulation installed on
Floors)
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
Crawl space walls
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace wall
.
Duct shafts, utility penetrations, and flue shafts opening to
Shafts, penetrations
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
cavities shall be filled by insulation that on
Narrow cavities
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spa
s.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
uidng
Recessed lighfixturesin theICI
ght
shall be sealed to the finished surface.
shall be aacle
thermal envelope and tilted.
Batt insulation shall be cut neatly to fit around wiring
Plumbing and wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sealed in a manner that is recommended by the manufacturer.
sprinklers
Caulking or other adhesive sealants shall not be used to fill voids
1 between .. ri _,__..,.�.�__._..;_;...,�,.a 11cnnn
a. In addition, inspection or tog woos snau ee ui d�w;Ua�IU� .•���I kS 1� r��•�•�••� -• •-- I--
3/17/2021 9:28 AM EnergyGauge®USA 7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction: St. Lucie
Permit #:
Job Information
Builder PSL Prop Community: Lot: NA
Address: TBD Carlton
State: FL Zip: 34983
City: Fort Pierce
Leakage Test l Results' Passing results must meet either the Performance, Prescriptive, or ERI Method
FAir
METHOD -The building or dwelling unit shall be tested'. and verified as having an air leakage rate of not exceeding 7 air
OPRESCRIPTIVE
changes per hour at a pressure of 0.2 inch w.g. (50 Pascals) in Climate Zones 1 and 2.
Q PERFORMANCE or ERI METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding
labeled as infiltration, sub -section ACH50.
the selected' ACH(50) value, as shown on Form R405-2020 (Performance) or. R406 2020 (ERI), section
ACH(50) specified on Form R405 2020-Energy Calc (Performance) or R406-2020 (ERI): 6.000
60 = 2.486346E30 = Method for calculatingnraanse
x
CFM(50) Building Volume ACH(50) O Retrieved from arc❑PASS
Code software calWhen
ACH(50) is less than 3, Mechanical Ventilation installationQ Field measured an
must be verified by building department.
2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
individuals licensed as set forth in Section
hall be conducted by either individuals as defned in Section 553.993(5) or (7), Florida Statues.or
the test shall be signed by the party conducting the test and
)(f), (g), or (i) or an approved third party. A written report of the results of
of all penetrations of the building thermal envelope.
rTesting
to thecode official. Testing shall be performed at any time after creation
sting:r
doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infltration
windows and
easures.
intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
2. Dampers including exhaust,
measures.
3. Interior doors, if installed at the time of the test, shall be open.
shall be closed and sealed.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators
be turned off.
5. Heating and cooling systems, if installed at the time of the test, shall
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Phone:
Company Name:
Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
I hereby verify that the above
Energy Conservation requirements according to the compliance method selected above.
Date of Test:
Signature of Tester:
Printed Name of Tester:
License/Certification #: Issuing Authority:
3117/2021 9:28:06 AM EnergyGaugeOO USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1