HomeMy WebLinkAbout36-44 DAB 2021M iAM l•DADE MIAMI-DADS covrlTY
PRODUCT CONTROL SECTION
11805 SW 26 Street, Room 208
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474
BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) www.miamidade.gov/economy
DAB Door Company, Inc.
12195 NW 981h Avenue
Hialeah Gardens, FL 33018
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER-Product Control Section to be
used in Miami -Dade County and otherareaswhere allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall notbe valid afterthe expiration date statedbelow. The Miami -Dade County Product Control Section (In
Miami -Dade County) and/or the AHJ (in areas other than Miami -Dade County) reserve the right to have this product or
material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the
manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use o f
such product or material within their jurisdiction. RER reserves the right to revoke this acceptance, if it is determined
by Miami -Dade County Product Control Section that this product or material fails to meet the requirements of the
applicable building code.
This product is approved as described herein and has been designed to comply with the Florida Building Code, including
the High Velocity Hurricane Zone.
DESCRIPTION: Hurricane Master® Model 824/811 Steel Sectional Garage Door 16ft-2in Wide with
Window Lite Option (DP +36.0, —44.0 PSF)
APPROVAL DOCUMENT: Drawing No. 02-21, titled "24 GA. Roll Formed Steel Sectional Garage
Door", dated 09/10/2002, with revision M dated 07/20/2020, sheets 1 through 5 of 5, preparedby Al-Farooq
Corporation, signed and sealed by Jalal Farooq, P.E., bearing the Miami -Dade County Product Control
revision stamp with the Notice of Acceptance number and expiration date by the Miami -Dade County
Product Control Section.
MISSILE IMPACT RATING: Large and Small Missile Impact Resistant
LABELING: A permanent label with the manufacturer's name or logo, manufacturing address, model/series
number,the positive and negative design pressure rating, indicate impactrated if applicable, installation
instruction drawing reference number, approval number (NOA), the applicable test standards, and the
statement reading `Miami -Dade County Product Control Approved' is to be located on the door's side track,
bottom angle, or inner surface of a panel.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product orprocess. Misuse of this NOA as an endorsement ofanyproduct, for
sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of
this NOA shall be cause for termination and removalofNOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA revises NOA # 20-0107.06 and consists of this page 1 and evidence pages E-1, E-2, E-3 and E-4,
as well as approval document mentioned above.
The submitted documentation was reviewed by Carlos M. Utrera, P.E.
MIAMMdIADrz NOA-No. 20-0901.25
Expiration Date: July 21, 2025
Approval Date: December 03, 2020
Page 1
DAB Door Company, Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
1. EVIDENCE SUBMITTED UNDER PREVIOUS NOA's
A. DRAWINGS "Submitted under NOA # 17-1018.12"
1. Drawing No. 02-21, titled "24 GA. Roll Formed Steel Sectional Garage Door", dated
09/10/2002, with last revision K dated 03/09/2015, sheets 1 through 5 of 5, prepared by A1-
Farooq Corporation, signed and sealedby Javad Ahmad, P.E.
B. TESTS "Submitted underNOA #11-0414.12"
1. Test Report on Uniform Static Air Pressure Test, Loading and Forced Entry Te st per FBC,
TAS 202-94, of "DAB 824 Sectional Residential Garage Door" prepared by Hurricane
Engineering & Testing Inc., Report No. HETI-07-4200, dated 05/02/2007, signed and sealed
by Candido F. Font, P.E.
2. Test Report on Large Missile Impact Test per FBC, TAS 201-94 and Cyclic Wind Pre ssure
Test per FBC, TAS 203-94, of"DAB 824 Sectional Residential Garage Door", prepared by
Hurricane Engineering & Testing Inc., Report No. HETI-11-3204, dated 01/20/2011, signed
and sealed by Candido F. Font, P.E.
3. Test Report on Tensile Test perASTM E8-08 of"Sectional Residential Door (skin)", prepared
by Hurricane Engineering & Testing Inc, Report No. HETI-11-T100, dated 01/21/2011,
signed and sealed by Candido F. Font, P.E.
"Submitted under NOA # 05-0228.02"
4. Test Report on Large Missile Impact Test and Cyclic Wind Pressure Test, of "Sectional
Residential Door with Windows", prepared by Hurricane Engineering & Testing Inc., Report
No. HETI 03-1328, dated 07/15/2003, signed and sealed by Rafael E. Droz-Seda, P.E.
5. Test Report on Uniform Static Air Pressure Test, of "Sectional Residential Door" prepared by
Hurricane Engineering& Testing Inc., Report No. HETI 03-1329, dated 07/15/200 3, signed
and sealed by Rafael E. Droz-Seda, P.E.
6. Test Report on Tensile Test perASTM E-8 of "Sectional Residential Door (skin)", prepared
by Hurricane Engineering & Testing Inc, Report No. HETI 03-T078, dated 10/31/2003,
signed and sealed by Rafael E. Droz-Seda, P.E.
"Submitted under NOA # 03-0210.04"
7. Test report on Salt Spray (Corrosion) Test per ASTM B 117 of a painted G-40 steel p anels,
prepared by Celotex Corporation, Test Report No. 258592, dated 08/17/1998, signed by W. A.
Jackson, P.E.
C. CALCULATIONS "Submitted under NOA # 14-0814.10"
1. Anchor verification calculations prepared by Al-Farooq Corporation, date d 0 9/2 2/2014 an d
07/24/2014, signed and sealed by Javad Ahmad, P.E.
Carlos M. Utrera, P.E.
Product Control Examiner
NOA-No. 20-0901.25
Expiration Date: July 21, 2025
Approval Date: December 03, 2020
E - 1
DAB Door Company, Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
C. CALCULATIONS (font.)
"Submitted under NOA # 11-0414.12"
2. Anchor verification calculations prepared by Al-Farooq Corporation, complying with F. B. C
2007, dated 04/07/2011, signed and sealed by Javad Ahmad, P.E.
3. Anchor verification calculations prepared by Al-Farooq Corporation, complying with F. B. C
2007, dated 12/19/2008, signed and sealed by Humayoun Farooq, P.E.
"Submitted under NOA # 09-0128.02"
D. QUALITY ASSURANCE
1. Miami -Dade Department of Regulatory and Economic Resources (RER).
E. MATERIAL CERTIFICATIONS
1. Notice of AcceptanceNo.13-0717.01, issuedto SABIC Innovative Plastics, for their Lexan
Sheet Products, approved on 11/28/2013 and expiring on 07/17/2018.
2. Notice of Acceptance No. 14-0311.08, issued to Insulfoam, LLC, for their Insulfoam
Expanded Polystyrene Insulation, approved on 08/14/2014 and expiring on 11/29/2017.
3. Notice of Acceptance No.11-0926.07, issued to Dyplast Products, LLC, for their Expanded
Polystyrene Block Type Insulation, approved on 11 /10/2011 and expiring on 0 1/11/2017.
4. Notice of Acceptance No.11-0926.06, issued to Dyplast Products, LLC, for their Dyp last
ISO-C 1 Polyisocyanurate Insulation, approved on 11/10/2011 and expiring on 01 /11/2017.
5. Notice of Acceptance No.10-1129.04, issued to CellofoamNorth America Inc, for their
Expanded Polystyrene Block Insulation, approved on 02/24/2011 and expiring on 02/24/2016.
"Submitted under NOA # 05-0228.02"
6. Test Report on Accelerated Weathering Using Xenon Arc Light Apparatus Test per ASTM
G155 of "PVC Extrusion Material", prepared by Hurricane Engineering & Testing, Inc.,
Report No. HETI 04-A002, dated 09/27/2004, signed and sealed by Rafael E. Droz-Seda, P.E.
7. Test Reports on Tensile Test per ASTM D638 of "PVC Extrusion Material", prepared by
Hurricane Engineering & Testing Inc., Report No. HETI 04-T251, dated 11/29/2004 signed
and sealed by I. Ghia, P.E.
8. Test Report on Self -Ignition Temperature Test, Rate of Burn Test and Smoke Density Test of
"REHAU non -foam PVC extrusion material", prepared by ETC Laboratories, Report No. 04 -
761-15019.0, dated 05/06/2004, signed and sealed by J. L. Doldan, P.E.
F. STATEMENTS "Submitted underNOA # 14-0814.10"
1. Statement letter of code conformance to the 51 edition (2014) FBC and no financial interest
issued by Al-Farooq Corporation, dated 05/13/2014, signed and sealed by Javad Ahmad, P.E.
Carlos M. Utrera, P.E.
Product Control Examiner
NOA-No. 20-0901.25
Expiration Date: July 21, 2025
Approval Date: December 03, 2020
E-2
DAB Door Company, Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUB
2. EVIDENCE SUBMITTED IN PREVIOUS NOA # 20-0107.06
A. DRAWINGS "Submitted under NOA #17-1018.12"
1. Drawing No. 02-21, titled "24 GA. Roll Formed Steel Sectional Garage Door", dated
09/10/2002, with revision L dated 10/03/2017, sheets 1 through 5 of 5, prepared by
Al-Farooq Corporation, signed and sealed by Javad Ahmad, P.E.
B. CALCULATIONS
1. None.
C. QUALITY ASSURANCE
1. Miami Dade Department of ,Regulatory and Economic Resources (RER).
D. MATERIAL CERTIFICATIONS
1. Notice of Acceptance No.17-0221.06, issued to Insulfoam, LLC, for their Insulfoam
Expanded Polystyrene Insulation, expiring on 11/29/2022.
2. Notice of Acceptance No.16-1108.04, issued to Dyplast Products, LLC, for their
Dyplast ISO-C1 Polyisocyanurate Insulation, expiring on 01/11/2022.
3. Notice of Acceptance No.15-1203.04, issued to Cellofoam North America Inc, for
their Expanded Polystyrene Block Insulation, expiring on 02/24/2021.
4. Notice of Acceptance No.15-0915.08, issued to SABIC Innovative Plastics, for their
Lexan Sheet Products, expiring on 07/17/2018.
E. STATEMENTS
1. Statement letter of code conformance to the 6th edition (2017) FBC, prepared by Al
Farooq Corporation, dated 12/23/2019, signed and sealed by Javad Ahmad, P.E.
F. OTHER
1. This NOA renews NOA #17-1018.12.
Carlos M. Utrera, P.E.
Product Control Examiner
NOA-No. 20-0901.25
Expiration Date: July 21, 2025
Approval Date: December 03, 2020
E-3
DAB Door Company, Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
3. NEW EVIDENCE SUBMITTED.
A. DRAWINGS
1. Drawing No. 02-21, titled "24 GA. Roll Formed Steel Sectional Garage Door", dated
09/10/2002, with revision M dated 07/20/2020, sheets 1 through 5 of 5, prepared by Al-
Farooq Corporation, dated 11/16/2020, signed and sealed by Jalal Farooq, P.E.
B. TESTS
1. None.
C. CALCULATIONS
1. None.
D. QUALITY ASSURANCE
1. Miami Dade Department of Regulatory and Economic Resources (RER).
E. MATERIAL CERTIFICATIONS
1. Notice of Acceptance No. 19-0129.06, issued to Insulfoam, LLC, for their Insulfoam
Expanded Polystyrene Preformed Block Type I Insulation, expiring on 11/29/2022.
2. Notice of Acceptance No. 17-1207.04, issued to Dyplast Products, LLC, for their
Dyplast ISO-C1 Polyisocyanurate Rigid Foam Insulation, expiring on 01/11/2022.
3. Notice of Acceptance No. 18-0918.06, issued to Plaskolite, LLC, for their TUFFAK
Polycarbonate Sheets, approved on 01/15/2018 and expiring on 8/27/2022.
F. STATEMENTS
1. Letter of conformance to FBC 2020 (7t' Edition) and FBC 2017 (6th Edition),
prepared by Al Farooq Corporation, dated 07/15/2020, signed and sealed by Jalal
Farooq, P.E.
Carlos M. Utrera, P.E.
Product Control Examiner
NOA-No. 20-0901.25
Expiration Date: July 21, 2025
Approval Date: December 03, 2020
E - 4