HomeMy WebLinkAboutProject InformationI
Manual S Compliance Report Job: Lot44 Block 1 Waterston...
wrightsoft® p Date: 06.07.12
Entire House By: FLETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
For:
ADAMSHOMES
5435 Lugo Street, Fort Pierce, FL 34951
Cooling Equipment
Design Conditions
Outdoor design DB: 90.4OF
Sensible gain: 20279
Btuh Entering coil DB: 76.2OF
Outdoor design WB: 77.4OF
Latent gain: 4018
Btuh Entering coil WB: 63.2°F
Indoor design DB: 75.0 OF
Total gain: 24297
Btuh
Indoor RH: 50%
Estimated airflow: 947
cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype: SpIitASHP
Manufacturer: Carrier
Model: 25HBC530AP03+FX4DNB031 L00
Actual airflow: 947
cfm
Sensible capacity: 21039
Btuh 1040% of load
Latent capacity: 5956
Btuh 148% of load
Total capacity: 26995
Btuh 111 % of load SHR: 78%
Design Conditions
Outdoor design DB: 41.0 °F Heat loss: 22296 Btuh Entering coil DB: 69.6 °F
Indoor design DB: 70.0 cF
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype: SpIitASHP
Manufacturer: Carrier Model: 25HBC530AP03+FX4DNB031 L00
Actual airflow: 947 cfm
Output capacity: 26646 Btuh 120% of load Capacity balance: 35 OF
Supplemental heat required: 0 Btuh Economic balance: -99 of
Backup equipment type: Elec strip
t Manufacturer: . Model:
Actual airflow: 947 cfm
Output capacity: 6.6 kW 101 % of load Temp. rise: 22 OF
Meets all requirements ofACCA Manual S
-*- wrightsoft® 2021-May-061551:12
�� >,,.�- �,e ••,e, m�M Rig11-SUte8Uriversal2021 21.0.02 RSU23828
Page 1
...aterstore1780BGR\Lot4461k1 Waterstone1780BGR.rLip Calc= MJ8 House faces: SE
wri htsoft® Component Constructions Job: Lot 44 Block 1 Waterston...
9 Entire House Date: FLET H
By: LETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-339-2665 Fax:407-333-3853 Web: W WW.DEL-AIR.COM
"Project•
•
For:
ADAMS HOMES
5435 Lugo Street, Fort Pierce, FL 34951
Design
Conditions
Location:
St Lude Cc Intl, FL, US
Indoor:
Indoor temperature (°F)
Heating
70
Cooling
75
Elevation: 26 ft
Latitude: 28 ON
Design TD (OF)
29
15
Outdoor:
Heating Cooling
Relative humidity (%)
Moisture difference (gr4b)
30
2.4
50
56.9
Dry bulb (T)
41 90
Infiltration:
Daily range (OF)
Wet bulb (OF)
- 15 (L
- 77
) Method
Simplified
Wind speed (mph)
15.0 7.5
Construction quality
Fireplaces
Average
0
Construction descriptions Or Area tl-value Insul R Htg HTM Loss Clg HTM Gain
ft� Btuh/ftz°F ftz°F/Btuh Btuh/W StO Rh,h/W RhA
Walls
16B-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum
board int fnsh
Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh
Partitions
12C-Osw., Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int
fnsh, 2'k4" wood frm, 16" o.c. stud
ne
30
0.049
19.0
1.42
43
2.59
78
se
30
0.049
19.0
1.42
43
2.59
78
sw
30
0.049
19.0
1.42
43
2.59
78
nw
30
0.049
19.0
1.42
43
2.59
78
all
120
0.049
19.0
1.42
171
2.59
310
ne
291
0.201
4.1
5.83
1698
4.06
1183
e
17
0.201
4.1
5.83
99
4.06
69
se
68
0.201
4.1
5.83
399
4.06
278
s
17
0.201
4.1
5.83
99
4.06
69
sw
383
0.201
4.1
5.83
2232
4.06
1555
nw
269
0.201
4.1
5.83
1571
4.06
1094
all
1046
0.201
4.1
5.83
6098
4.06
4247
250
0.091
13.0
2.64
660
1.31
328
Windows
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
ne
thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang
sw
(5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht
nw
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
all
e
thk; NFRC rated (SHGC=0.21); 50%drapes, medium; 1.3 ft overhang
se
(5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht
s
all
1 OC-m: 2 glazing, dr low-e outr, air gas, mtl no brk frm mat, clr innr, 1/4"
nw
gap, 1/8" thk; NFRC rated (SHGC=0.70); 14.33 ft overhang (6.7 ft window
ht, 0.8 ft sep.); 6.67 ft head ht
Doors
11 JO: Door, mtl fbrgl type
11 DO: Door, wd sc type
33
0.330
0
9.57
313
17.7
579
49
0.330
0
9.57
469
15.7
768
33
0.330
0
9.57
313
17.7
579
114
0.330
0
9.57
1095
16.8
1925
12
0.330
0
9.57
114
20.9
249
23
0.330
0
9.57
224
14.7
345
12
0.330
0
9.57
114
8.22
98
47
0.330
0
9.57
452
14.7
693
18
0.550
0
16.0
285
39.5
706
se 20 0.600 6.3 17.4 350 17.6 353
n 18 0.390 0 11.3 202 11.4 204
wrightsoft" 2021-May-061551:12
� • •�••�^•w�-.,�-o.m Rigk-Sute®universal 2021 21.0.02 RSU23828 Page 1
aterstore1780BGR\Lot44BIk1 Waterstone1780BGR.rLp Calc= W8 House faces: SE
Ceilings
1613-30ad:Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" 1972 0.032
gypsum board int fnsh
Floors
22A-tpl: Bg floor, light dry soil, on grade depth 189 0.989
'fk- wrightsoft,
RigM-Sute®Uriversa1202721.0.02RSU23828
aterstone1780BGR1Lot44Blk1 Waterstone1780BGR.nQ Calc= W8 House faces: SE
30.0 0.93 1830 1.69 3332
0 28.7 5425 0 0
2021-May-06 1551:12
Page 2
wri htsoft® Project Summary Job. Lot44 Block 1 Waterston...
9 Date: 06.07.i2
Entire House By: FLETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W WW.DEL-AIR.COM
Project• •
For: ADAMSHOMES
5435 Lugo Street, Fort Pierce, FL 34951
Notes: L. S. 5-6-21 VWK
Desicin Information
Weather: St Lude Cc Infl, FL, US
Winter Design Conditions
Summer Design Conditions
Outside db 41
Inside db 70
OF
OF
Outside db
Inside db
90
OF
OF
Design TD 29
OF
Design TD
75
15
OF
Daily range
L
Relative humidity
50
%
Moisture difference
57
gr/lb
Heating Summary
Sensible Cooling Equipment Load
Sizing
Structure 19749
Ducts
Btuh
Structure
16184
Btuh
2548
Central vent (0 cfm) 0
Btuh
Btuh
Ducts
Central vent (0 cfm)
4095
0
Btuh
Btuh
none
Humidification 0
Btuh
Blower e)
0
Btuh
Piping 0
Btuh
Equipment load 22296
Btuh
Use manufacturer's data
y
Infiltration
Rate/swingg multi�pplier
Equipmentsensible load
1.00
20279
Btuh
Method Simplified
Construction quality Average
Latent Cooling Equipment Load Sizing
Fireplaces
0
Structure
2830
Btuh
Ducts
1188
Btuh
Central vent (0 cfm)
0
Btuh
Heatingg
Area (ft2) 1780
Coolin
1 It
(none)
Equipment latent load
4018
Btuh
Volume (ft3) 15760
15760
Air changes/hour 0.38
Equiv. AVF (cfm) 100
0.20
53
Equipment Total Load (Sen+Lat)
24297
Btuh
Req. total capacity at 0.75 SHR
2.3
ton
Heating Equipment Summary
Cooling Equipment Summary
Make Carrier
Trade CARRIER
Make Carrier
Trade CARRIER
Model 25HBC530AP03
AHRI ref 204840289
Cond 25HBC530AP03
Coil FX4DNB031 L00
Efficiency 8.5 HSPF
AHRI ref 204840289
Efficiency 12.5 EER,
15 SEER
Heating Input
Heating output 28200
Btuh Qa 47OF
Sensible cooling
Latentcooling
21300
7100
Btuh
Btuh
Temperature rise 27
Actual airflow 947
OF
cfm
Total cooling
Actual airflow
28400
947
Btuh
cfm
Airflowfactor 0.042
Static pressure 0.40
cfm/Btuh
in H2O
Airflowfactor
Static pressure
0.047
0.40
cfm/Btuh
in H2O
Space thermostat
Capacity balance point = 35 OF
Load sensible heat ratio
0.83
Backup:
Input = 7 kW, Output = 22460 Btuh, 100 AFUE
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
- wrigiltsoft- 2021-May-0615:51:12
Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 1
aterstone17808GR\Lot44BIk1Waterstone1780BGR.rp Calc=W8 Housefaces:SE
-�- wrightsoft- Right-JO Worksheet
Entire House
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Job: Lot 44 Block 1 Waterstone 17...
Date: 06.07.12
By. FLETCH
1
Room name
Entire House
LAU
2
3
Exposed wall
Room height
1892 ft
7.0 ft
4
Room dimensions
8.8 it
8.0 ft heaUcool
5
Room area
17920 ftz
7.0 x 7.0 It
49.0 ftz
Ty
Construction
U-value
Or
HTM
Area
(ftz)
Load
Area
(ftz)
Load
number
(Btuh/tz`F)
(Btuh/112)
or perimeter
(ft)
(Btuh)
or perimeter
(ft)
(Btuh)
Heat
Cool
Gross
N/PS
Heat
Cool
Gross
N/P/S -
Heat
Cool
6
W..
Vt/
-_
16 walks-_._ ._ _
Blk wall, stu000 e)d
- -
. 0001
0201
-
_ne.
ne
1.83
5.83
_259
4.06
. _ 30
324
-
, 30
291
-
1698
1183
0
_ ...
2A 2ov
0,330
ne-
957
17.70
33
0
313
579
0 0
0
11
yV�//
Y -
Blk MI, stucoo e)d
-^ _
0.
a
_._^
5B3
4.06
. 29
_ ._ t
17
__.. __._._9s
. _ . _.._.69
0
__ _„__ O
0
_._.
-_ 0
0
--._ 0,
0
_- -- , -_O
-_WC
2A-2ov _. - ---- ----
-_-•-- 0330
-A,
- _957
---20.92
------12
._._. 1
.,' 114
W �-
16B 19ad
Blkwsll stu000ext
2A 2ov
_._- 0049
0201
0.330
se.
se
_1-42
5.83
2.59
4.66
30
112
30
- _....W 68
__-_._ -_ 43
399
---_ __ _249
78
r -"278
_., _.. 0
0
0
- ' p
. _ _.,__0
'" 6
0
0
se
957
14.75
23
6
224
345
. 0
0
0
0
W
Blk mall, stun o e)d
__._-0600
0201
__se...___17.40.-_
s
5.83
1758.'_..:..:
4.06
20._.__..___
29
20
17
___"__-350,'___
99
_-353._:�
69
_ _0
0
__0
0
_.� �.
0
_._---_0.
-G
2A-2ov
_. _ 0.330
. s __
_._,_ . 12
_.. .-_ 12
_._. _ ... 114
98
0
0
0
0
0
Blk well, stucoo e)d
0.201
-sw-
sw
"-- 1.42,
5.83
.. _:.2.59
4.06
-.._ _. ___.30
432
_.,..----30
383
__..-_ 43
2232
_.._
�- _-:78
1555
_ _
-- 0
0
- .- _.. -0
0
__.__-_.0
0
0.
2A-2ov_ _ -_- - . _._-._.. _
.._ . .0,330
. svv_.
957
15.67
49
12
768
0
0
0
0
Blk vtall, stucco e)d
10C-m
.0.049
0.201
0550
_.nvv
nw
1.42
5.83
_
• �259
4.66
- -- _.
_--- 30
320
. _ - - -
_ __.... 30
269
_469
. .._. 43
1571
- -._ _ _78
1094
-- -- -_--
0
_
0
0
0
0
nw
15.95
3950
18
0
285
706
0
0
0
0
2A 2ov -
0230
nw
957
17.70
33
0
313
579
0
0
0
0
._ .-_ 50•
C
-
16B 30ad
_--_--_0.390
0032
n
11.31.
0.93
11.43
1.69
__ 18
1972
___18
1972
-202
____2Q4
.............18
... _, 48
--- .202
.. _204
FA
WI _-- - - • _
_ . -b 989
.
28,68
189
1830
_ -- _ 5425
3332
. _._ _. 0
49
_ -. -,. 49
49
- - -
-_ 7
- - 45
_ .. .;201
83
_
0
6
c) AED excursion
477
-26
Envelopeloss/gain
16568
12575
549
311
12
a) Infiltration
3181
889
0
0
b) Room ventilation
0
0
0
0
13
Internal gains Oocupants@ 230
4
920
0
0
Applianoesrother
1800
600
Subtotal (lines 6 to 13)
19749
16184
549
911
Less extemal load
0
0
Less transfer
0
0
0
0
0
0
Redistribution
0
0
0
0
14
15
Subtotal
Duct loads
19749
16184
549
911
13%
25%1
2548
4095
13%
251%
71
230
Total room load
Air required (ofm)
22296
20279
620
1141
947
9471
47
26
53
Calculations approved bvACCAto meet all requirements of Manual J 8th Ed
- wr➢gf�tsoTt- Right-Su2021-May-061551:12
te®Uriversal 2021 21.0.02 RSU23828 Page 1
aterstore1780BGR\Lot44BIk1Waterstone1780BGR.np Calc=MJ8 Housefaces:SE
wrightsoft- Right-JO Worksheet
Entire House
DEL -AIR HEATING &AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax:407-333-3853 Web: WWW.DEL-AIR.COM
Job: Lot 44 Block 1 Waterston 17
Date: 06.07.12
By- FLETCH
1 Room name
2 Exposed wall
BR3
BATH2
4FRoom
Room height
dimensions
26.0 It
8.0 ft heaVcool
8.0 it 0 ft heaticool
5
Room area
1.0 x 146.5 it
146.5
9.0 x 6.0 ft
ft2
54.0 ft 2
Ty
Construction
number
LI-value
(Btuh/ft-IF)
or
HTIVI
(Btu"2)
Area (ft)
Load
Area (ft2)
Load
or (it)
perimeter
(Btuh)
I or perimeter (ft)
(13tuh)
-
Heat
Cool
Gross
N/P)S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
6 k.19ad
Blk vd], stucco e)d
9
ne
-ne
5,B3
4.06
104
88
511
356
-0
0 - 0
_0
4.
2-A-2ov
0230
ne
957
17.70
16
0 156
289
0
0
0
0
0
0
0 -6
-6
0 0
it
W
1613-19ad
_0
61 k vi6J I'ih
2A-2ov'
0.049
0330
- se
- se
so,
1.42
957
259
7
' 14.75
0 0
0
A
0
0
0 0
0 0
0
0
0
D
0 0
0 0
0
0
0
6
_11i Q_.,
Blk mi,_kk�e�
-Q.600
0.201
_sP
s
5.83
_,,17.5�8
4.06
0
0
0
0
0
0
0
.2A-2oy
0,330
- s
9.57
- 822
0
_0
0
0
0
0
0;
0
-16B-119ad
Blk vdI, 966o6 _6�j'
0.049
- .,
0.201
- SK
sw
1.42
5.83
250
4.66
0
_0
0
0
-0
0
__
0
-0
0
__0
2A-2ov
0.330
_Eky.
957
15.67
0
0
0
0
0
0
0
0
0
V�i
Blk vdl, stucco e)d
loc-m
0.201
-ow-
nw
_!A�
5.83
:�.69
4.06
0
0
0
0
0
------- �b
0
0
-0
0
055
nw
1525
39.50
0
0
0
0
0
0
0
2A-2ov
0,330
nw
957
17.70
0
0
0
0
0
0
0
0
0
D
C
-11D0
_0390
__n
0
'0..
�P, —
--a
-- 0.032
9989
0.93
_8
1.69-------
- __._ -
147
�6
136
1._1_.__
248
-0
54
64
54
_56
- -
91
- ---- --
-----
__,000
----- --- ---
_9
-0
6
c) AED excursion
-14
-3
—
Envelope loss/gain
1823
10151
50
89
12
a) Infiltration
242
68
0
0
b) Room ventilation
0
0
13
Internal gains Occupants@ 230
0
0
0
Appliancestother
0
0
0
—
Subtotal (lines 6 to 13)
2066
1082
50
89
Less external load
0
0
Less transfer
0
0
Redistribution
0
0
0
0
14
Subtotal
0
0
0
0
15
Duct loads
13%
25%
2066
266
1082
274
13%
25%
50
6
89
22
Total room load
Air required (cfm)
2332
1356
57
111
991
1
-rid- Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
Riglt-SLite@ Uriversal 2021 21.0.02 RSU23828 2021-May-06 15:51:12
aterstorie1780BGR1Lot44BIk1Waterstone1780BGR.rLp Calc=MJ8 Housefaces:SE Page 2
-�- wrightsoft, Right-JO Worksheet
Entire House
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Plune:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Job: Lot 44 Block 1 Waterston 17...
Date: 06.07.12
By: FLETCH
1
Room name
BR2
MBR
2
3
wall
Room height
13.0 ft
325 it
4
Room dimensions
8.0 ft heaticool
8.0 ft heat/cool
5
Room area
137.5 ft 1.0 x 137.5 ft
z
1.0 x 270.5 ft
270.5 ft z
Ty
Construction
number
U-value
(BtuhHtzfl
Or
HTM
(BtuhRt2)
Area (ftz)
Load
Area (ft2)
Load
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
I Cool
Gross
N/PiS
Heat
Cool
Gross
N/PiS
Heat
Cool
6
W -
Vll
16619ad. -.4
Blk gall, stucco ext
, _ _.__OA49
0.201
_ __
_ ne
ne
_... _
. _ 1.42
- 5B3
_.._259
4.06
_
,.._.� _
104
__
0 -� _
' 88
_.
0 _
511
-
0 0--,
1 l 356
_
__ _�_0
-
0 ._� `p'
w-
--•._-_ -0
LL
_.G
2A-2ov
0.330
ne
9.57
17.70
16
0 156
289
116
116
676
471
11
V+l
Blkulell,stu000exf
' 0201
e
` 5.83
- 4.06
_,._
0 -_,__ _,_0
�.__ _ ,,__o
._____ __ o
_0
0
0 0
o _ ,_--.- O
0
- -- _-• o
_-_G
W
2A2py__- __-
16B 19ad
0330
_,-_e_-_
_ -9.57
__._20.92
__--_:
0 ___.._..�,
0 ___ ._. _0.
_:Q
0
_
Blku+ell sU6iie#
2A 2ov
0049
0201
0.330
__se_
se
,, se
__ -_1.42
583
957
259
406
-14.75
.._____
0 0
0 __, 0
__ ___ U
0 0
___ .__._0
___ "0
_9
0 h ._ _0
0 0
-- -_ �0
0
__. ____0.
0 0:
0
0
0
0 0
0
Blk wall, stucco eid
0.,500,--se_
0201
s
-,_17.44_i7.58
523
4.06
-,_.._ _ 0
� 0
_,....^,r_0.
0
0
0
__0
0
.__c._" 0
0
W_--.
16�19ad_-
0.330
...
--s -
--- _957,
_.._.. 822
_-_ 0
- -
0.
_ .__ ._-.0
_..,...._.._ Q
0
0
0
0
0
0
0
0
_ _ _ _
Blk Nsll, stuoo ext
__ 0049
0 201
_ sw
sw
... 1,42
5.83
"2$9
4.06
._. _.. _ 0
0
-0_0
Q
_
_. p
0
0
-0
0
-._-.
2A2ov_ ..
i6B 19ad
0.330
_�_
.. _, 957
- 15.67
0
0
,__. _ 0
0
0
0
V)1
_
Blk v all, stu000 eM
10C-m
-.-__0:049
0 201
0.550
.-nw
nw
1.42
5.83
___2:59
4.06
0
0
_
._ 0
0
_ _ - _0
0
-� _ 0
0
_0
_. _____0
144
_. _..__0
_.._ �0
111
_____.. __0.__
------ --0-
649
__ _0
--- ----.-
452
2A
nw
15.95
3950
0
0
0
0
0
0
0
0
q
2ov
12COsw
0.330
_0091
nw
957
2.64
y 17.70
131
0
0'
0
0
0
0
0
0
_. 33
0
- _0
31
;. - 13
579
' D.
C
11D0
166-30ad '--
0390
_n_
-.-__11,31
1143
0
__. 0.__
__.._0,
__0.
_ ____
0.
F - ...
22A- I
W . _ _. _
0032
989
__
;
0.93
28.68
1.69
0.00
138
_ _
138
13
_ 128
•- 232
_0
271
_ -
__0
271
____ _.__'0
2_
--
_458
_ .-0
ILL
-_ -
-_•.
,_ _:_...138
._ - _
-=-• - 373
-0
- -_271
_ - 33
_ -. _932
6
c) AED excursion
-10
250
Envelope loss/gain
1168
868
2822
2210
12
a) Infiltration
b) Room ventilation
242
68
606
169
0
0
0
0
13
Internal gains: OccupantsQa 230
0
0
1
Appliances/other
230
0
0
Subtotal (lines 6 to 13)
1410
935
3427
2609
Less extemalload
Lesstransfer
0
0
0
0
Redistribution
0
0
0
0
14
15
Subtotal
Duct loads
0
1410
0
935
0
3427
0
2609
13%
25 %
182
237
13 %
25%
442
660
Total room load
Air required (cfm)
1592
1172
3870
269
3153
68
55
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed
-*- wrigF�tsoft- Right-SriteOUriversal 2021 21.0.02 RSU23828 2021-May-061651:12
aterstore1780BGR1Lot44BlkiWaterslorel780BGR.nQ Calc=MJ8 Hosefaces:SE Page 3
-�+ wrightsoft- Right-M Worksheet Job: Lot44 Block 1 Waterston 17...
Entire House Date: 06.07.12
DEL -AIR HEATING & AIR CONDITIONING By: FLETCH
531CODISCOWAY, SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM
1
2
Room name
Exposed vyall
M3ATH
WIC
3
4
Room height
Room dimensions
21D ft
8.0 ft heat/cool
75 ft
8.1 ft heat/000l
5
Room area
116.0 ftz 1.0 x 116.0 It
1.0 x 87.0 ft
87.0 ftz
Ty
Construction
number
BUv cue
( z-'q
Or
HTM
Area (ftz) Load
Area (ftz)
Load
I or perimeter (ft) (Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/F/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
W ..'
-- ----
16B-19ad _
Blk well, stucco ext
--
__. 0049
0.201
-_ne
ne
142
5,83
259
4.06
.. _ ..
9 _ -
0
0 __... _
0
0 -,, _0
0 0
__ -. 0
0
_,-
2A 2ov
0.330
ne
9,57
17.70
0
0
0 0
0
0
0
0
0 0
i
y/
Blkwall,sluocoexd
0201
a
583
--
4.06
0
0 - -_-•_ `O
_._ ._.__ 0
-. --- - --.:0
. _O.O
0
0
1
i ., -G
W
2A 2ov ..__, _ . _..
16B 19ad
_. 0,330__
e_
_ _...:957
_._ 2092
. -
0 .. _-'_. _
0 °r -
0 _. 0
_ - -
0
0 :_.- 0
U
_
� ^
Blkvell stuomext
2A 2dv
0049
0201
0.330
_se
se
se
1.42
583
957
2.59
A:O6
14.75
` `
0
0
0 _0
0 __
_0.
0 D
0 _,...1
0
0 0
0 _ri___o.-__w_
- --
0
0
�D
11J0
0 0
0 0
0 0
0
0
_
W
. .__
Blk well, stu000 ext
0600
0.201
--se-
s
1]40
5.83
,1758
4.06
0
0 ;: 0
0
- - _ 6
0
_ _0
0
_ __ 0
0
- -
- - '0
_
2A 2ov
0.330
_ s
_9.57
822
0
0
0
_ 0
0
0
0
0
0
Blk wall, stuoco exd
0.049
0.201
_.sw
sw
1.42
5.83
4.06
56
56
326
..
227
_ _0
60
_
60
�..
2A-2ov_,
0,330
sw_
957
15.67
0
0,
0
0
350
244
W_
- - -
16B 19ad _ - -
0 049
_ riw-
- _ _ _
- -_ 1.42
- ,
2,59
_ .. _ 0
Q
0
0
0
0
-_. -0
_.._ 0
VL2Blk
wall, stucco e#
100-m
0.2~01
0550
nw
nw
5.83
15.95
4.06
3950
112
_
112
. _
653
- -
455
-
0
-.- . . r0
0
. - - - _-0._
0
- - 0-
0
2A2ov
,330
nw
957
17.70
0
0
0
0
0
0
0
0
0
-�.-_-_
Fi
12C Osiv '
0-..b.
091
-, .
2.64
131
0
0
0
0
0
0
0
0
_... 0
0
.. _ , 0
0
- 0
._-. .. 0
C
11DQ-- .. _.._:
16B-30ad
_. 0390
0.032
,r1._
._,. 11.31
0.93
_11„43-.
1.69
_. 0
-•___..___0
0
._'-,_.-_0._.
_.__0_.
__-_---o..---..
0
_,_.__._ o.
_. _
„0.60
116
116
108
196
88
....
87
88
_._-
-- ._ _ 81
215
148
----_
_0
.:... _ _
_8
_. ...
.0
16
c) AED exarsion
-28
12
Envelope loss/gain
1689
851
646
380
12
a) Infiltration
b) Room ventilation
391
109
140
39
0
0
0
0
13
Internal gains: Occupants@ 230
0
0
0
Appliancestother
0
0
0
Subtotal (lines6 to 13)
2081
960
786
419
Less exdemalload
0
0
Less transfer
0
0
Redistribution
0
0
0
0
14
Subtotal
0
0
0
0
15
Duct loads
130
25 %
2081
268
960
243
1300
251%
786
101
419
106
Total room load
Air required (dm)
349
2100
1256
887
525
56
38
25
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
1 * wrigtitsoit- Right-Su2021-May-061551:12
te®Uriversal 2021 21.0.02 RSU23828 aterstone1780BGR1Lot44Blk1 Waterstone1780BGR.np Calc= W8 House faces: SE Page 4
- wrightsoft' Right-JO Worksheet
Entire House
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Job: Lot 44 Block 1 Waterstone 17...
Date: 06.07.12
By: FLETCH
2 I Room name wajl FAMHALL(S) Krr
3 Room height 24.0 ft 30S ft
9S ft heaUcool 95 ft heaUeool
4 Room armensiorLs. 1.0 x 451.0 ft 1.0 x 290.0 ft 5 Room area
-
cau.0 nr
Ty
Construction
number
U-value
(Btuht-9
Or
HTM
(Btuhfltz)
Area (ftz)
Load
Area (ftz)
Load
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N1P/S
Heat
Cool
Gross
N/Pr5
Heat
Cool
6 W _ _
—
16B-19ad _._ ._. _ _._
Blk Hall, stucco e)d
_ _. _.._ 0 049
0201
ne
ne
.1.42
5.83
_
,-_259
4.06
30
_
. .:30
0 0
-
.. _ _. 78
0 0
. _ . _ _ _ _0
_ _ _ 0
_ _ _ __U
_ -- _ 0
_
G
2A2ov
_ 0330
ne
9S7
17.70
0 0
0 0
0
0
0
0 0
BlkNall,stuocoext
0201
_e.
_..._._._.
0 0
- .. _
0 0
0
--•__--
W
16B•19ad
,-._._._._0' M0
..._e _
_ _..:.,957.....
20.92
__0
.. _._ V.--0
_.._
..-.-___.0
_ ----,_0
0 _0
__ _.
Blk cell stucco ext
2A 2ov
-- 0.049
0261
0.330
se
se
1.42
5.83
9.57
2.59
4.66
_ 30
p
. 30
- 0
43
-- - -_ .. o
78
._.- _ _-0
..__.--
- --- - -0
-----
0
._ ; _20
- 0
__
0
se
14.75
0 0
0 0
0
0
0
0
_.
11J0.._.. _�
Elk gall, stucco eM
-..._...0.600...se
0.261
s
J7:40
5.83
_,_.175.8
4.06
=
0
00:
0
Q.- -0
0 0
— 20._.
__.._20__
_'3.50-
-
_.
2ov..,-_
0330
S -
--__ 957
0
0
0
0
0
0
w ._-..
16&19ad
Blk xell, stucco ext
0.049
0.201
_ sro
sw
_ 1,42
5113
-6�
__.._-259
4.06
_
...... 30..._....__30.--
128
- -
95
- -._4
-
556
..
____78,
387
0
96
0
-•.-.0
0
.__0
- ---0
-0:
2A 2ov..
_ 0.330
sw„
9.57
S
313
512
96
560
390
W --
16B 19ad-_ - -
- - 0049
_nw
_ _
- _--1,42
_..15.67
-
__.• ...33
- ....
- -
_._ _
_ I -
.. 0
_. _
._ . 0
0
_ ..._.._0
0
V)1
Blk Ml, stucco eM
10C-m
0201
0S50
nw
nw
5.83
15.95
4.06
3950
64
46
269
- - '
187
-0
0
-- --�
0
- - - -
0
0
Lr—�L
2A-2ov
04330
18
0
285
706
0
0
0
0
R -
_ ...
12C Osw
_
0.091
nw
-
9.57
_.
2.64
17.70
131
0
0
_ 0
0
- 0
0
0
- 0
0
� 108
0__
�108
� 0
� � �-� 0
L_p
C
11D0___
16B 30ad_
;._0.390
0 032
__n _
11211
0.93
11.43
_ _ .__. 0
, __.._.._.0
____._. __ 0
_ - _._ ._ _0
._ �_ _ 0
._.__.__0
285
142
WL
_._
1.69
538
538
- 499
_ 909
346
_
346
321
584
6
c) AED excursion
--79
464
Envelope losstgain
2780
3475
2506
1470
12
a) Infiltration
b) Room ventilation
727
203
317
89
0
0
0
0
13
Internal gains: Occupants@ 230
p
460
0
Applianoes(other
0
0
1200
Subtotal (lines 6 to 13)
3507
4138
2823
2759
Less external load
Lesstransfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
0
0
0
0
15
Duct loads
13 %
25 %
3507
452
4138
1047
1047
13 %
25 %
2823
364
2759
698
Total room load
Air required (cfm)
3452
959
185
3187
3457
135
161
Calculations approved bvACCAto meet all requirements of Manual J 8th Ed.
,� �-• wriigF�tsoTt^
Right-Sute®Uriversal 2021 21.0.02 RSU23828 2021-May-06 15:51:12
aterstone1780BGR\Lot44Blk1 Waterstone1780BGR.np Calc= MJ8 House faces: SE Page 5
- wrightsofta Right-JO Worksheet Job: Lot 44 Block 1 Waterston 17...
Entire House Date: 06.07.12
DEL -AIR HEATING & AIR CONDITIONING By: F ETCH
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
1
Room name
DIN/
DIN/FOY
2
F�osed wall
Room height
It
95 It heaUcool
4
Room dimensions
Room area
1.0 x 190.5 It
190.5 ftz
Ty
Construction
number
U-value
(Btuh/ftz--q
Or
HTM
(Btuh/ftz)
Area (ftz)
Load
Area
Load
or perimeter (ft)
(Btuh)
or perimeter
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
V�/
Blk usll, stucco e#
0049
0.201
._ne
ne
_J-42
5.83
_ ._259
4.06
_. " Q
0
_._._ 0.
0
_ -O
-0
0
- - . _O
.. _
...- ,._ w
__......
--
- - ..
- -- -.
_ ._...
-_ -T
L�
2A-2ov -
4 0 330
ne
957
17.70
0
0
0
0
Blknell,stu000e#-
0201
a
683
4.06
y29
_ "17
_99
6s.
.__._.._
W
1 t36 19ad
_.:__-._0330_,.q
0 049
.. __._9,57.-_._-2092
'1.?__
.__.___1.
___ .114
_.-----••249
--__-•----
- _
Sik wall, sluo�o e#
2A 2ov
0201
0.330
_ se
se
" se
_ 1.42
583
957
259
r4:06
14.75
0
72
" 23
0
--- 49
6
0
283
0
197
--
-
- "
_.
W
_ 11J0 _ ...___ -_ _
Blk wall, stucco e#
__ ..0.600
0.201
_._se
s
_17.40
5.83
4.06
29
- - - 17
224
Y 99
345
- 69
2A 2ov __,
16B
0330
-_ s
9,57
-_ 822
-_. - 12
12
'_
_ _ 114
98
BIk stucco e#
_0.049
0.201
_sw
sw
.. _1 -0
5.83
.__ 259
4.06
-- _0
92
. _ 0
76
.... _0
441
-_„ _ _.
._..- _._0
307
,
- `
- _ .
_- _
UV-__
ov
2A2ov
16B19ad
0.330__sw
__957-_t_-15.67
156
.
..0049
-nw
_-1_.42
, _' 2.69
___;_ 0
0
. p
___-„_256
l�1
tL-�G
BIk mall, stucco e#
10C-m
0201
0550
nw
nw
5.83
15.95
4.66
3950
0
-_..
0
_ _ _
0
----__- -0----
0
2A 2ov
0,330
0
0
0
0
12C Osw
0 091
nw
-
9.57
_
2.64
17.70
131
0
0
0
.. 0
0
. _ 0
0
0
.
C -
u.-
16B-30ad
0390
0032
: -n,
11.31
0.93
1143
._._ . 0
-. 0.__
1 69
227
227
210
383
---
6
c) AED excursion
-65
Envelope loss/gain
2534
1908
12
a) Infiltration
b) Roomventilation
516
144
0
0
13
Internal gains: Occupants@ 230
1
230
Applianoes/other
0
Subtotal (lines 6to 13)
3050
2282
Less external load
Less transfer
0
0
Redistribution
0
0
14
Subtotal
0
0
15
Duct loads
3050
2282
282
13 %
25 %
Total room load
Air required (dm)
3444
2860
146
134
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed
�-�- wrigf�tsoit- �A Right-Sute®Universal 2021 21.0.02 RSU23828 2021-May-06 15:51:12
aterstorLe1780BGR1Lot44Blk1 Waterstone17808GR.np Calc= MJ8 Hose faces: SE Page 6
- wrightsoft® Duct System Summary Job: Lot 44 Block 1 Waterston...
Date: 06.07.12
Entire House By: FLETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
For: ADAMS HOMES
5435 Lugo Street, Fort Pierce, FL 34951
External static pressure
Pressurelosses
Available static pressure
Supply / return available pressure
Lowest friction rate
Actual airflow
Total effective length (TEL)
Heating
0.40
in H2O
0.06
in H2O
0.34
in H2O
0.170 / 0.170
in H2O
0.312
in/100ft
947
cfm
109 ft
Cooling
0.40 in H2O
0.06 in H2O
0.34 in H2O
0.170 / 0.170 in H2O
0.312 in/100ft
947 cfm
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FIR
Diam
(in)
H x W
(in)
Duct
Mat
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
BATH2
c 111
2
5
0.460
4.0
Ox 0
VI Fx
3.9
70.0
BR2
h 1592
68
55
0.420
6.0
Ox 0
VIFx
11.0
70.0
BR3
h 2332
99
63
0.443
6.0
Ox 0
VIFx
6.7
70.0
DIWOY
h 3444
146
134
0.374
7.0
Ox 0
VIFx
20.9
70.0
FAMMALL(S)
c 5185
168
242
0.434
8.0
Ox 0
VI Fx
8.3
70.0
Krr
c 3457
135
161
0.381
7.0
Ox 0
VIFx
19.1
70.0
LAU
c 1141
26
53
0.456
4.0
Ox 0
VI Fx
4.5
70.0
MBATH
h 2349
100
56
0.312
6.0
Ox 0
VIFx
24.0
85.0
sti
MBR
h 3870
164
153
0.322
7.0
Ox 0
VIFx
20.7
85.0
sti
WIC
h 887
38
25 1
0.333
4.0
Ox 0
VIFx
17.1
85.0
st1
Supply Trunk Detail Table
Name
Trunk
Type
Htg
(cfm)
Clg
(cfm)
Design
FIR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Duct
Material
Trunk
sti
PeakAVF
302
233
0.312
553
10.0
0 x 0
VinlFlx
Return Branch Detail Table
Name
Grille
Size (in)
Htg
(cfm)
Clg
(cfm)
TEL
(ft)
Design
FIR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Mat
Trunk
rb2
Ox 0
947
947
0
0
0
0
Ox 0
VIFx
- wrightsoftD 2021-May-0615:51:13
Rigtd-Suite®Uriversa12021 21.0.02 RSU23828
Page 1
aterstore1780BGR\Lot44Blk1 Waterstore1780BGR.nQ Calc= MJ8 House faces: SE
2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Lot 44 Block 1 Waterstone 1780 BGR Builder Name: ADAMS HOMES
Street: 5435 Lugo Street Permit Office:
City, State, Zip: Fort Pierce , FL , 34951 Permit Number:
Y
Owner: Jurisdiction: 661000
Design Location: FL, ST LUCIE CO
W
=
—INTL
U
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
requirements
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
Breaks or joints in the air barrier shall be sealed.
Ceiling/attic
The air barrier in any dropped ceiling/soffit shall be aligned with
the insulation and any gaps in the air barrier shall be sealed.
The insulation in any dropped ceiling/soffit
Access openings, drop down stairs or knee wall doors to
shall be aligned with the air barrier.
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
Knee walls shall be sealed.
with a material having a thermal resistance of R-3
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/doorjambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
(including
The air barrier shall be installed at any exposed edge of
insulation.
Floor framing cavity insulation shall be installed to
above -garage
maintain permanent contact with the underside of
and cantilevered
subfloor decking, or floor framing cavity insulation
floors)
shall be permitted to be in contact with the top side
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace wall
.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
3s.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the finished surface.
thermal envelope shall be air tight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
behind nepina and w*rina
Shower/tub
on exterior
-extend
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
a. In addition, inspection
cover p
of loa walls shall ha ;fk ff,e ...:: .,
5/6/2021 4:04 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
FORM R405-2020
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the
Residential Simulated Performance Alternative shall include:
❑ This checklist
0 Form R405-2020 report
❑ Input summary checklist that can be used for field verification (usually four pages/may be greater)
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO: .
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page)
❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4
allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to
comply with Section C402.5
❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed
2020 Duct Leakage Test Report - Performance Method (usually one page)
5/6/2021 4:04:02 PM EnergyGauge@ USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
Duct Leakage Test Report
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
System 1
cfm25
System 2
cfm25
System 3
cfm25
Sum of others
cfm25
Total of all
cfm25
- 1780 = Qn
Total of all
Total Conditioned
systems
Square Footage
PASS [:]FAI L
Q Prescriptive, Method ,` cfm25 (,Total)
To qualify as"substantially.'leak free" On Total must be ,less- than or
equal to 0:04.if air handier -unit is installed. If -air handier unit i¬,.
Installed, Qn Total must`be less tf an ore qual#o.0.03. This,testing
method meets the requirements; in. accordance with Section R403 3.3,
Is the air handler uni't mstalled,during testing? E]YES
0 Performance/ERI...Method ' .cfm25`(Owt.or Total) .'
To,,qualtfy_usingthis method, On must not be�greater;than the.
proposed'duct:aeakageOn specified on Form 11405-2020 or R406.2020
Leakage Type selected'on Form;. Q6spec fled on Form.R405-2020 .
R405 2Q2Q.(EnergyCalc)Ior R4,06" 0' 20-' . (Ene'rgyCalc) or'R406-2020
' Proposed Qn 0.06
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section
553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (1), Florida Statutes.
Testing Company
Company Name: Phone:
I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the
selected compliance path as stated above, either the Prescriptive Method or Performance Method. .
Signature of Tester:
Printed Name of Tester:
License/Certification #:
Date of Test:
Issuing Authority:
5/6/2021 4:05:10 PM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Enerqy Conservation, 7th Edition
Jurisdiction: 661000 Permit #:
Job Information ,
Builder: ADAMS HOMES Community: Lot: 44-1
Address: 5435 Lugo Street
City: Fort Pierce
Air Leakage Test Results
State: FL Zip: 34951
Passing, results must meefeither the•Performance, Prescriptive, or ERI Method
0 PRESCRIPTIVE METHOD -The building or dwelling'unit shall be tested:and verified as having an air leakage rate of not exceeding 7 air,
changes.per hour at a pressure of 0.2 inch w.g, (50.Pascals)'inClimate,Zones 1 and 2:
Q PERFORMANCE or ERl METHOD -The ,building ordwelling unit shall be tested and verified as'havind an air leakage rate of not exceeding'
the selected ACH(50) value, as shown on Form R405-2020 (Performance) or R406-2020,(ERI), section labeled as infiltration, sub-sectionACH50.
ACH(50) specified.on Form R405-2020-Energy Ca1c (Performance) or R406 2020-(ERI): 7.000
x 60 _ 15664 = Method for calculating buildinq volume:
CFM(50) Building Volume ACH(50)
Q Retrieved from architectural plans
FIPASS 40 Code software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation Q Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company`
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester:
Printed Name of Tester:
License/Certification #:
Date of Test:
Issuing Authority:
5/6/2021 4:04:59 PM EnergyGaugeOO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 7th Edition (2020)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
F777577
5435 Lugo Street Permit Number:
Fort Pierce , FL , 34951
IVIARuA I UKY KtQUIKLMENT5 -See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory) The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
SECTION R402 BUILDING THERMAL ENVELOPE
❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and
R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (1) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
5/6/2021 4:04 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
R403.1 Controls. SECTION R403 SYSTEMS
R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. .
R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system,
including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise
sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire
system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn =
duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C)
or below 55°F (13°C) shall be insulated to a minimum of R-3.
R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are
installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall
be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for
circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The
controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no
demand for hot water.
R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when heated water is used in the occupancy.
5/6/2021 4:04 PM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 1407 (38°C to 60°C).
- R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of
combustion types of service water -heating systems to be turned off.
R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment.
❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based
on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation
methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the
outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design
conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other
factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical
ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have
an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is
installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
MINIMUM EFFICACY a
AIRFLOW RATE MAXIMU
(CFM)
(CFM/WATT)
(CFM)
HRV or ERV
Any
1.2 cfm/watt
Any
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916
5/6/2021 4:04 PM EnergyGauge® USA 7.0.00 -. FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS . (Continued)
❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
2. calculated total sensible load but not less than 80 percent of that load.
When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery. pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
5/6/2021 4:04 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5
QR403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements:
1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house
is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day.
2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air.
3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13,
conform to the following requirements:
1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct.
2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct.
3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6.
SECTION R404
ELECTRICAL POWER AND LIGHTING- SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an
efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
5/6/2021 4:04 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 5