Loading...
HomeMy WebLinkAboutProject InformationI Manual S Compliance Report Job: Lot44 Block 1 Waterston... wrightsoft® p Date: 06.07.12 Entire House By: FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM For: ADAMSHOMES 5435 Lugo Street, Fort Pierce, FL 34951 Cooling Equipment Design Conditions Outdoor design DB: 90.4OF Sensible gain: 20279 Btuh Entering coil DB: 76.2OF Outdoor design WB: 77.4OF Latent gain: 4018 Btuh Entering coil WB: 63.2°F Indoor design DB: 75.0 OF Total gain: 24297 Btuh Indoor RH: 50% Estimated airflow: 947 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNB031 L00 Actual airflow: 947 cfm Sensible capacity: 21039 Btuh 1040% of load Latent capacity: 5956 Btuh 148% of load Total capacity: 26995 Btuh 111 % of load SHR: 78% Design Conditions Outdoor design DB: 41.0 °F Heat loss: 22296 Btuh Entering coil DB: 69.6 °F Indoor design DB: 70.0 cF Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNB031 L00 Actual airflow: 947 cfm Output capacity: 26646 Btuh 120% of load Capacity balance: 35 OF Supplemental heat required: 0 Btuh Economic balance: -99 of Backup equipment type: Elec strip t Manufacturer: . Model: Actual airflow: 947 cfm Output capacity: 6.6 kW 101 % of load Temp. rise: 22 OF Meets all requirements ofACCA Manual S -*- wrightsoft® 2021-May-061551:12 �� >,,.�- �,e ••,e, m�M Rig11-SUte8Uriversal2021 21.0.02 RSU23828 Page 1 ...aterstore1780BGR\Lot4461k1 Waterstone1780BGR.rLip Calc= MJ8 House faces: SE wri htsoft® Component Constructions Job: Lot 44 Block 1 Waterston... 9 Entire House Date: FLET H By: LETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-339-2665 Fax:407-333-3853 Web: W WW.DEL-AIR.COM "Project• • For: ADAMS HOMES 5435 Lugo Street, Fort Pierce, FL 34951 Design Conditions Location: St Lude Cc Intl, FL, US Indoor: Indoor temperature (°F) Heating 70 Cooling 75 Elevation: 26 ft Latitude: 28 ON Design TD (OF) 29 15 Outdoor: Heating Cooling Relative humidity (%) Moisture difference (gr4b) 30 2.4 50 56.9 Dry bulb (T) 41 90 Infiltration: Daily range (OF) Wet bulb (OF) - 15 (L - 77 ) Method Simplified Wind speed (mph) 15.0 7.5 Construction quality Fireplaces Average 0 Construction descriptions Or Area tl-value Insul R Htg HTM Loss Clg HTM Gain ft� Btuh/ftz°F ftz°F/Btuh Btuh/W StO Rh,h/W RhA Walls 16B-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum board int fnsh Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh Partitions 12C-Osw., Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2'k4" wood frm, 16" o.c. stud ne 30 0.049 19.0 1.42 43 2.59 78 se 30 0.049 19.0 1.42 43 2.59 78 sw 30 0.049 19.0 1.42 43 2.59 78 nw 30 0.049 19.0 1.42 43 2.59 78 all 120 0.049 19.0 1.42 171 2.59 310 ne 291 0.201 4.1 5.83 1698 4.06 1183 e 17 0.201 4.1 5.83 99 4.06 69 se 68 0.201 4.1 5.83 399 4.06 278 s 17 0.201 4.1 5.83 99 4.06 69 sw 383 0.201 4.1 5.83 2232 4.06 1555 nw 269 0.201 4.1 5.83 1571 4.06 1094 all 1046 0.201 4.1 5.83 6098 4.06 4247 250 0.091 13.0 2.64 660 1.31 328 Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" ne thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang sw (5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht nw 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" all e thk; NFRC rated (SHGC=0.21); 50%drapes, medium; 1.3 ft overhang se (5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht s all 1 OC-m: 2 glazing, dr low-e outr, air gas, mtl no brk frm mat, clr innr, 1/4" nw gap, 1/8" thk; NFRC rated (SHGC=0.70); 14.33 ft overhang (6.7 ft window ht, 0.8 ft sep.); 6.67 ft head ht Doors 11 JO: Door, mtl fbrgl type 11 DO: Door, wd sc type 33 0.330 0 9.57 313 17.7 579 49 0.330 0 9.57 469 15.7 768 33 0.330 0 9.57 313 17.7 579 114 0.330 0 9.57 1095 16.8 1925 12 0.330 0 9.57 114 20.9 249 23 0.330 0 9.57 224 14.7 345 12 0.330 0 9.57 114 8.22 98 47 0.330 0 9.57 452 14.7 693 18 0.550 0 16.0 285 39.5 706 se 20 0.600 6.3 17.4 350 17.6 353 n 18 0.390 0 11.3 202 11.4 204 wrightsoft" 2021-May-061551:12 � • •�••�^•w�-.,�-o.m Rigk-Sute®universal 2021 21.0.02 RSU23828 Page 1 aterstore1780BGR\Lot44BIk1 Waterstone1780BGR.rLp Calc= W8 House faces: SE Ceilings 1613-30ad:Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" 1972 0.032 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 189 0.989 'fk- wrightsoft, RigM-Sute®Uriversa1202721.0.02RSU23828 aterstone1780BGR1Lot44Blk1 Waterstone1780BGR.nQ Calc= W8 House faces: SE 30.0 0.93 1830 1.69 3332 0 28.7 5425 0 0 2021-May-06 1551:12 Page 2 wri htsoft® Project Summary Job. Lot44 Block 1 Waterston... 9 Date: 06.07.i2 Entire House By: FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W WW.DEL-AIR.COM Project• • For: ADAMSHOMES 5435 Lugo Street, Fort Pierce, FL 34951 Notes: L. S. 5-6-21 VWK Desicin Information Weather: St Lude Cc Infl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 Inside db 70 OF OF Outside db Inside db 90 OF OF Design TD 29 OF Design TD 75 15 OF Daily range L Relative humidity 50 % Moisture difference 57 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 19749 Ducts Btuh Structure 16184 Btuh 2548 Central vent (0 cfm) 0 Btuh Btuh Ducts Central vent (0 cfm) 4095 0 Btuh Btuh none Humidification 0 Btuh Blower e) 0 Btuh Piping 0 Btuh Equipment load 22296 Btuh Use manufacturer's data y Infiltration Rate/swingg multi�pplier Equipmentsensible load 1.00 20279 Btuh Method Simplified Construction quality Average Latent Cooling Equipment Load Sizing Fireplaces 0 Structure 2830 Btuh Ducts 1188 Btuh Central vent (0 cfm) 0 Btuh Heatingg Area (ft2) 1780 Coolin 1 It (none) Equipment latent load 4018 Btuh Volume (ft3) 15760 15760 Air changes/hour 0.38 Equiv. AVF (cfm) 100 0.20 53 Equipment Total Load (Sen+Lat) 24297 Btuh Req. total capacity at 0.75 SHR 2.3 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Trade CARRIER Make Carrier Trade CARRIER Model 25HBC530AP03 AHRI ref 204840289 Cond 25HBC530AP03 Coil FX4DNB031 L00 Efficiency 8.5 HSPF AHRI ref 204840289 Efficiency 12.5 EER, 15 SEER Heating Input Heating output 28200 Btuh Qa 47OF Sensible cooling Latentcooling 21300 7100 Btuh Btuh Temperature rise 27 Actual airflow 947 OF cfm Total cooling Actual airflow 28400 947 Btuh cfm Airflowfactor 0.042 Static pressure 0.40 cfm/Btuh in H2O Airflowfactor Static pressure 0.047 0.40 cfm/Btuh in H2O Space thermostat Capacity balance point = 35 OF Load sensible heat ratio 0.83 Backup: Input = 7 kW, Output = 22460 Btuh, 100 AFUE Calculations approved byACCAto meet all requirements of Manual J 8th Ed. - wrigiltsoft- 2021-May-0615:51:12 Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 1 aterstone17808GR\Lot44BIk1Waterstone1780BGR.rp Calc=W8 Housefaces:SE -�- wrightsoft- Right-JO Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Job: Lot 44 Block 1 Waterstone 17... Date: 06.07.12 By. FLETCH 1 Room name Entire House LAU 2 3 Exposed wall Room height 1892 ft 7.0 ft 4 Room dimensions 8.8 it 8.0 ft heaUcool 5 Room area 17920 ftz 7.0 x 7.0 It 49.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuh/tz`F) (Btuh/112) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/PS Heat Cool Gross N/P/S - Heat Cool 6 W.. Vt/ -_ 16 walks-_._ ._ _ Blk wall, stu000 e)d - - . 0001 0201 - _ne. ne 1.83 5.83 _259 4.06 . _ 30 324 - , 30 291 - 1698 1183 0 _ ... 2A 2ov 0,330 ne- 957 17.70 33 0 313 579 0 0 0 11 yV�// Y - Blk MI, stucoo e)d -^ _ 0. a _._^ 5B3 4.06 . 29 _ ._ t 17 __.. __._._9s . _ . _.._.69 0 __ _„__ O 0 _._. -_ 0 0 --._ 0, 0 _- -- , -_O -_WC 2A-2ov _. - ---- ---- -_-•-- 0330 -A, - _957 ---20.92 ------12 ._._. 1 .,' 114 W �- 16B 19ad Blkwsll stu000ext 2A 2ov _._- 0049 0201 0.330 se. se _1-42 5.83 2.59 4.66 30 112 30 - _....W 68 __-_._ -_ 43 399 ---_ __ _249 78 r -"278 _., _.. 0 0 0 - ' p . _ _.,__0 '" 6 0 0 se 957 14.75 23 6 224 345 . 0 0 0 0 W Blk mall, stun o e)d __._-0600 0201 __se...___17.40.-_ s 5.83 1758.'_..:..: 4.06 20._.__..___ 29 20 17 ___"__-350,'___ 99 _-353._:� 69 _ _0 0 __0 0 _.� �. 0 _._---_0. -G 2A-2ov _. _ 0.330 . s __ _._,_ . 12 _.. .-_ 12 _._. _ ... 114 98 0 0 0 0 0 Blk well, stucoo e)d 0.201 -sw- sw "-- 1.42, 5.83 .. _:.2.59 4.06 -.._ _. ___.30 432 _.,..----30 383 __..-_ 43 2232 _.._ �- _-:78 1555 _ _ -- 0 0 - .- _.. -0 0 __.__-_.0 0 0. 2A-2ov_ _ -_- - . _._-._.. _ .._ . .0,330 . svv_. 957 15.67 49 12 768 0 0 0 0 Blk vtall, stucco e)d 10C-m .0.049 0.201 0550 _.nvv nw 1.42 5.83 _ • �259 4.66 - -- _. _--- 30 320 . _ - - - _ __.... 30 269 _469 . .._. 43 1571 - -._ _ _78 1094 -- -- -_-- 0 _ 0 0 0 0 nw 15.95 3950 18 0 285 706 0 0 0 0 2A 2ov - 0230 nw 957 17.70 33 0 313 579 0 0 0 0 ._ .-_ 50• C - 16B 30ad _--_--_0.390 0032 n 11.31. 0.93 11.43 1.69 __ 18 1972 ___18 1972 -202 ____2Q4 .............18 ... _, 48 --- .202 .. _204 FA WI _-- - - • _ _ . -b 989 . 28,68 189 1830 _ -- _ 5425 3332 . _._ _. 0 49 _ -. -,. 49 49 - - - -_ 7 - - 45 _ .. .;201 83 _ 0 6 c) AED excursion 477 -26 Envelopeloss/gain 16568 12575 549 311 12 a) Infiltration 3181 889 0 0 b) Room ventilation 0 0 0 0 13 Internal gains Oocupants@ 230 4 920 0 0 Applianoesrother 1800 600 Subtotal (lines 6 to 13) 19749 16184 549 911 Less extemal load 0 0 Less transfer 0 0 0 0 0 0 Redistribution 0 0 0 0 14 15 Subtotal Duct loads 19749 16184 549 911 13% 25%1 2548 4095 13% 251% 71 230 Total room load Air required (ofm) 22296 20279 620 1141 947 9471 47 26 53 Calculations approved bvACCAto meet all requirements of Manual J 8th Ed - wr➢gf�tsoTt- Right-Su2021-May-061551:12 te®Uriversal 2021 21.0.02 RSU23828 Page 1 aterstore1780BGR\Lot44BIk1Waterstone1780BGR.np Calc=MJ8 Housefaces:SE wrightsoft- Right-JO Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax:407-333-3853 Web: WWW.DEL-AIR.COM Job: Lot 44 Block 1 Waterston 17 Date: 06.07.12 By- FLETCH 1 Room name 2 Exposed wall BR3 BATH2 4FRoom Room height dimensions 26.0 It 8.0 ft heaVcool 8.0 it 0 ft heaticool 5 Room area 1.0 x 146.5 it 146.5 9.0 x 6.0 ft ft2 54.0 ft 2 Ty Construction number LI-value (Btuh/ft-IF) or HTIVI (Btu"2) Area (ft) Load Area (ft2) Load or (it) perimeter (Btuh) I or perimeter (ft) (13tuh) - Heat Cool Gross N/P)S Heat Cool Gross N/P/S Heat Cool 6 6 k.19ad Blk vd], stucco e)d 9 ne -ne 5,B3 4.06 104 88 511 356 -0 0 - 0 _0 4. 2-A-2ov 0230 ne 957 17.70 16 0 156 289 0 0 0 0 0 0 0 -6 -6 0 0 it W 1613-19ad _0 61 k vi6J I'ih 2A-2ov' 0.049 0330 - se - se so, 1.42 957 259 7 ' 14.75 0 0 0 A 0 0 0 0 0 0 0 0 0 D 0 0 0 0 0 0 0 6 _11i Q_., Blk mi,_kk�e� -Q.600 0.201 _sP s 5.83 _,,17.5�8 4.06 0 0 0 0 0 0 0 .2A-2oy 0,330 - s 9.57 - 822 0 _0 0 0 0 0 0; 0 -16B-119ad Blk vdI, 966o6 _6�j' 0.049 - ., 0.201 - SK sw 1.42 5.83 250 4.66 0 _0 0 0 -0 0 __ 0 -0 0 __0 2A-2ov 0.330 _Eky. 957 15.67 0 0 0 0 0 0 0 0 0 V�i Blk vdl, stucco e)d loc-m 0.201 -ow- nw _!A� 5.83 :�.69 4.06 0 0 0 0 0 ------- �b 0 0 -0 0 055 nw 1525 39.50 0 0 0 0 0 0 0 2A-2ov 0,330 nw 957 17.70 0 0 0 0 0 0 0 0 0 D C -11D0 _0390 __n 0 '0.. �P, — --a -- 0.032 9989 0.93 _8 1.69------- - __._ - 147 �6 136 1._­1_.__­ 248 -0 54 64 54 _56 - - 91 - ---- -- ----- __,000 ----- --- --- _9 -0 6 c) AED excursion -14 -3 — Envelope loss/gain 1823 10151 50 89 12 a) Infiltration 242 68 0 0 b) Room ventilation 0 0 13 Internal gains Occupants@ 230 0 0 0 Appliancestother 0 0 0 — Subtotal (lines 6 to 13) 2066 1082 50 89 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 0 0 14 Subtotal 0 0 0 0 15 Duct loads 13% 25% 2066 266 1082 274 13% 25% 50 6 89 22 Total room load Air required (cfm) 2332 1356 57 111 991 1 -rid- Calculations approved byACCA to meet all requirements of Manual J 8th Ed. Riglt-SLite@ Uriversal 2021 21.0.02 RSU23828 2021-May-06 15:51:12 aterstorie1780BGR1Lot44BIk1Waterstone1780BGR.rLp Calc=MJ8 Housefaces:SE Page 2 -�- wrightsoft, Right-JO Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Plune:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Job: Lot 44 Block 1 Waterston 17... Date: 06.07.12 By: FLETCH 1 Room name BR2 MBR 2 3 wall Room height 13.0 ft 325 it 4 Room dimensions 8.0 ft heaticool 8.0 ft heat/cool 5 Room area 137.5 ft 1.0 x 137.5 ft z 1.0 x 270.5 ft 270.5 ft z Ty Construction number U-value (BtuhHtzfl Or HTM (BtuhRt2) Area (ftz) Load Area (ft2) Load or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat I Cool Gross N/PiS Heat Cool Gross N/PiS Heat Cool 6 W - Vll 16619ad. -.4 Blk gall, stucco ext , _ _.__OA49 0.201 _ __ _ ne ne _... _ . _ 1.42 - 5B3 _.._259 4.06 _ ,.._.� _ 104 __ 0 -� _ ' 88 _. 0 _ 511 - 0 0--, 1 l 356 _ __ _�_0 - 0 ._� `p' w- --•._-_ -0 LL _.G 2A-2ov 0.330 ne 9.57 17.70 16 0 156 289 116 116 676 471 11 V+l Blkulell,stu000exf ' 0201 e ` 5.83 - 4.06 _,._ 0 -_,__ _,_0 �.__ _ ,,__o ._____ __ o _0 0 0 0 o _ ,_--.- O 0 - -- _-• o _-_G W 2A2py__- __- 16B 19ad 0330 _,-_e_-_ _ -9.57 __._20.92 __--_: 0 ___.._..�, 0 ___ ._. _0. _:Q 0 _ Blku+ell sU6iie# 2A 2ov 0049 0201 0.330 __se_ se ,, se __ -_1.42 583 957 259 406 -14.75 .._____ 0 0 0 __, 0 __ ___ U 0 0 ___ .__._0 ___ "0 _9 0 h ._ _0 0 0 -- -_ �0 0 __. ____0. 0 0: 0 0 0 0 0 0 Blk wall, stucco eid 0.,500,--se_ 0201 s -,_17.44_i7.58 523 4.06 -,_.._ _ 0 � 0 _,....^,r_0. 0 0 0 __0 0 .__c._" 0 0 W_--. 16�19ad_- 0.330 ... --s - --- _957, _.._.. 822 _-_ 0 - - 0. _ .__ ._-.0 _..,...._.._ Q 0 0 0 0 0 0 0 0 _ _ _ _ Blk Nsll, stuoo ext __ 0049 0 201 _ sw sw ... 1,42 5.83 "2$9 4.06 ._. _.. _ 0 0 -0_0 Q _ _. p 0 0 -0 0 -._-. 2A2ov_ .. i6B 19ad 0.330 _�_ .. _, 957 - 15.67 0 0 ,__. _ 0 0 0 0 V)1 _ Blk v all, stu000 eM 10C-m -.-__0:049 0 201 0.550 .-nw nw 1.42 5.83 ___2:59 4.06 0 0 _ ._ 0 0 _ _ - _0 0 -� _ 0 0 _0 _. _____0 144 _. _..__0 _.._ �0 111 _____.. __0.__ ------ --0- 649 __ _0 --- ----.- 452 2A nw 15.95 3950 0 0 0 0 0 0 0 0 q 2ov 12COsw 0.330 _0091 nw 957 2.64 y 17.70 131 0 0' 0 0 0 0 0 0 _. 33 0 - _0 31 ;. - 13 579 ' D. C 11D0 166-30ad '-- 0390 _n_ -.-__11,31 1143 0 __. 0.__ __.._0, __0. _ ____ 0. F - ... 22A- I W . _ _. _ 0032 989 __ ; 0.93 28.68 1.69 0.00 138 _ _ 138 13 _ 128 •- 232 _0 271 _ - __0 271 ____ _.__'0 2_ -- _458 _ .-0 ILL -_ - -_•. ,_ _:_...138 ._ - _ -=-• - 373 -0 - -_271 _ - 33 _ -. _932 6 c) AED excursion -10 250 Envelope loss/gain 1168 868 2822 2210 12 a) Infiltration b) Room ventilation 242 68 606 169 0 0 0 0 13 Internal gains: OccupantsQa 230 0 0 1 Appliances/other 230 0 0 Subtotal (lines 6 to 13) 1410 935 3427 2609 Less extemalload Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 15 Subtotal Duct loads 0 1410 0 935 0 3427 0 2609 13% 25 % 182 237 13 % 25% 442 660 Total room load Air required (cfm) 1592 1172 3870 269 3153 68 55 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed -*- wrigF�tsoft- Right-SriteOUriversal 2021 21.0.02 RSU23828 2021-May-061651:12 aterstore1780BGR1Lot44BlkiWaterslorel780BGR.nQ Calc=MJ8 Hosefaces:SE Page 3 -�+ wrightsoft- Right-M Worksheet Job: Lot44 Block 1 Waterston 17... Entire House Date: 06.07.12 DEL -AIR HEATING & AIR CONDITIONING By: FLETCH 531CODISCOWAY, SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM 1 2 Room name Exposed vyall M3ATH WIC 3 4 Room height Room dimensions 21D ft 8.0 ft heat/cool 75 ft 8.1 ft heat/000l 5 Room area 116.0 ftz 1.0 x 116.0 It 1.0 x 87.0 ft 87.0 ftz Ty Construction number BUv cue ( z-'q Or HTM Area (ftz) Load Area (ftz) Load I or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/F/S Heat Cool Gross N/P/S Heat Cool 6 W ..' -- ---- 16B-19ad _ Blk well, stucco ext -- __. 0049 0.201 -_ne ne 142 5,83 259 4.06 .. _ .. 9 _ - 0 0 __... _ 0 0 -,, _0 0 0 __ -. 0 0 _,- 2A 2ov 0.330 ne 9,57 17.70 0 0 0 0 0 0 0 0 0 0 i y/ Blkwall,sluocoexd 0201 a 583 -- 4.06 0 0 - -_-•_ `O _._ ._.__ 0 -. --- - --.:0 . _O.O 0 0 1 i ., -G W 2A 2ov ..__, _ . _.. 16B 19ad _. 0,330__ e_ _ _...:957 _._ 2092 . - 0 .. _-'_. _ 0 °r - 0 _. 0 _ - - 0 0 :_.- 0 U _ � ^ Blkvell stuomext 2A 2dv 0049 0201 0.330 _se se se 1.42 583 957 2.59 A:O6 14.75 ` ` 0 0 0 _0 0 __ _0. 0 D 0 _,...1 0 0 0 0 _ri___o.-__w_ - -- 0 0 �D 11J0 0 0 0 0 0 0 0 0 _ W . .__ Blk well, stu000 ext 0600 0.201 --se- s 1]40 5.83 ,1758 4.06 0 0 ;: 0 0 - - _ 6 0 _ _0 0 _ __ 0 0 - - - - '0 _ 2A 2ov 0.330 _ s _9.57 822 0 0 0 _ 0 0 0 0 0 0 Blk wall, stuoco exd 0.049 0.201 _.sw sw 1.42 5.83 4.06 56 56 326 .. 227 _ _0 60 _ 60 �.. 2A-2ov_, 0,330 sw_ 957 15.67 0 0, 0 0 350 244 W_ - - - 16B 19ad _ - - 0 049 _ riw- - _ _ _ - -_ 1.42 - , 2,59 _ .. _ 0 Q 0 0 0 0 -_. -0 _.._ 0 VL2Blk wall, stucco e# 100-m 0.2~01 0550 nw nw 5.83 15.95 4.06 3950 112 _ 112 . _ 653 - - 455 - 0 -.- . . r0 0 . - - - _-0._ 0 - - 0- 0 2A2ov ,330 nw 957 17.70 0 0 0 0 0 0 0 0 0 -�.-_-_ Fi 12C Osiv ' 0-..b. 091 -, . 2.64 131 0 0 0 0 0 0 0 0 _... 0 0 .. _ , 0 0 - 0 ._-. .. 0 C 11DQ-- .. _.._: 16B-30ad _. 0390 0.032 ,r1._ ._,. 11.31 0.93 _11„43-. 1.69 _. 0 -•___..___0 0 ._'-,_.-_0._. _.__0_. __-_---o..---.. 0 _,_.__._ o. _. _ „0.60 116 116 108 196 88 .... 87 88 _._- -- ._ _ 81 215 148 ----_ _0 .:... _ _ _8 _. ... .0 16 c) AED exarsion -28 12 Envelope loss/gain 1689 851 646 380 12 a) Infiltration b) Room ventilation 391 109 140 39 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 Appliancestother 0 0 0 Subtotal (lines6 to 13) 2081 960 786 419 Less exdemalload 0 0 Less transfer 0 0 Redistribution 0 0 0 0 14 Subtotal 0 0 0 0 15 Duct loads 130 25 % 2081 268 960 243 1300 251% 786 101 419 106 Total room load Air required (dm) 349 2100 1256 887 525 56 38 25 Calculations approved byACCA to meet all requirements of Manual J 8th Ed 1 * wrigtitsoit- Right-Su2021-May-061551:12 te®Uriversal 2021 21.0.02 RSU23828 aterstone1780BGR1Lot44Blk1 Waterstone1780BGR.np Calc= W8 House faces: SE Page 4 - wrightsoft' Right-JO Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Job: Lot 44 Block 1 Waterstone 17... Date: 06.07.12 By: FLETCH 2 I Room name wajl FAMHALL(S) Krr 3 Room height 24.0 ft 30S ft 9S ft heaUcool 95 ft heaUeool 4 Room armensiorLs. 1.0 x 451.0 ft 1.0 x 290.0 ft 5 Room area - cau.0 nr Ty Construction number U-value (Btuht-9 Or HTM (Btuhfltz) Area (ftz) Load Area (ftz) Load or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N1P/S Heat Cool Gross N/Pr5 Heat Cool 6 W _ _ — 16B-19ad _._ ._. _ _._ Blk Hall, stucco e)d _ _. _.._ 0 049 0201 ne ne .1.42 5.83 _ ,-_259 4.06 30 _ . .:30 0 0 - .. _ _. 78 0 0 . _ . _ _ _ _0 _ _ _ 0 _ _ _ __U _ -- _ 0 _ G 2A2ov _ 0330 ne 9S7 17.70 0 0 0 0 0 0 0 0 0 BlkNall,stuocoext 0201 _e. _..._._._. 0 0 - .. _ 0 0 0 --•__-- W 16B•19ad ,-._._._._0' M0 ..._e _ _ _..:.,957..... 20.92 __0 .. _._ V.--0 _.._ ..-.-___.0 _ ----,_0 0 _0 __ _. Blk cell stucco ext 2A 2ov -- 0.049 0261 0.330 se se 1.42 5.83 9.57 2.59 4.66 _ 30 p . 30 - 0 43 -- - -_ .. o 78 ._.- _ _-0 ..__.-- - --- - -0 ----- 0 ._ ; _20 - 0 __ 0 se 14.75 0 0 0 0 0 0 0 0 _. 11J0.._.. _� Elk gall, stucco eM -..._...0.600...se 0.261 s J7:40 5.83 _,_.175.8 4.06 = 0 00: 0 Q.- -0 0 0 — 20._. __.._20__ _'3.50- - _. 2ov..,-_ 0330 S - --__ 957 0 0 0 0 0 0 w ._-.. 16&19ad Blk xell, stucco ext 0.049 0.201 _ sro sw _ 1,42 5113 -6� __.._-259 4.06 _ ...... 30..._....__30.-- 128 - - 95 - -._4 - 556 .. ____78, 387 0 96 0 -•.-.0 0 .__0 - ---0 -0: 2A 2ov.. _ 0.330 sw„ 9.57 S 313 512 96 560 390 W -- 16B 19ad-_ - - - - 0049 _nw _ _ - _--1,42 _..15.67 - __.• ...33 - .... - - _._ _ _ I - .. 0 _. _ ._ . 0 0 _ ..._.._0 0 V)1 Blk Ml, stucco eM 10C-m 0201 0S50 nw nw 5.83 15.95 4.06 3950 64 46 269 - - ' 187 -0 0 -- --� 0 - - - - 0 0 Lr—�L 2A-2ov 04330 18 0 285 706 0 0 0 0 R - _ ... 12C Osw _ 0.091 nw - 9.57 _. 2.64 17.70 131 0 0 _ 0 0 - 0 0 0 - 0 0 � 108 0__ �108 � 0 � � �-� 0 L_p C 11D0___ 16B 30ad_ ;._0.390 0 032 __n _ 11211 0.93 11.43 _ _ .__. 0 , __.._.._.0 ____._. __ 0 _ - _._ ._ _0 ._ �_ _ 0 ._.__.__0 285 142 WL _._ 1.69 538 538 - 499 _ 909 346 _ 346 321 584 6 c) AED excursion --79 464 Envelope losstgain 2780 3475 2506 1470 12 a) Infiltration b) Room ventilation 727 203 317 89 0 0 0 0 13 Internal gains: Occupants@ 230 p 460 0 Applianoes(other 0 0 1200 Subtotal (lines 6 to 13) 3507 4138 2823 2759 Less external load Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 0 0 0 0 15 Duct loads 13 % 25 % 3507 452 4138 1047 1047 13 % 25 % 2823 364 2759 698 Total room load Air required (cfm) 3452 959 185 3187 3457 135 161 Calculations approved bvACCAto meet all requirements of Manual J 8th Ed. ,� �-• wriigF�tsoTt^ Right-Sute®Uriversal 2021 21.0.02 RSU23828 2021-May-06 15:51:12 aterstone1780BGR\Lot44Blk1 Waterstone1780BGR.np Calc= MJ8 House faces: SE Page 5 - wrightsofta Right-JO Worksheet Job: Lot 44 Block 1 Waterston 17... Entire House Date: 06.07.12 DEL -AIR HEATING & AIR CONDITIONING By: F ETCH 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM 1 Room name DIN/ DIN/FOY 2 F�osed wall Room height It 95 It heaUcool 4 Room dimensions Room area 1.0 x 190.5 It 190.5 ftz Ty Construction number U-value (Btuh/ftz--q Or HTM (Btuh/ftz) Area (ftz) Load Area Load or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�/ Blk usll, stucco e# 0049 0.201 ._ne ne _J-42 5.83 _ ._259 4.06 _. " Q 0 _._._ 0. 0 _ -O -0 0 - - . _O .. _ ...- ,._ w __...... -- - - .. - -- -. _ ._... -_ -T L� 2A-2ov - 4 0 330 ne 957 17.70 0 0 0 0 Blknell,stu000e#- 0201 a 683 4.06 y29 _ "17 _99 6s. .__._.._ W 1 t36 19ad _.:__-._0330_,.q 0 049 .. __._9,57.-_._-2092 '1.?__ .__.___1. ___ .114 _.-----••249 --__-•---- - _ Sik wall, sluo�o e# 2A 2ov 0201 0.330 _ se se " se _ 1.42 583 957 259 r4:06 14.75 0 72 " 23 0 --- 49 6 0 283 0 197 -- - - " _. W _ 11J0 _ ...___ -_ _ Blk wall, stucco e# __ ..0.600 0.201 _._se s _17.40 5.83 4.06 29 - - - 17 224 Y 99 345 - 69 2A 2ov __, 16B 0330 -_ s 9,57 -_ 822 -_. - 12 12 '_ _ _ 114 98 BIk stucco e# _0.049 0.201 _sw sw .. _1 -0 5.83 .__ 259 4.06 -- _0 92 . _ 0 76 .... _0 441 -_„ _ _. ._..- _._0 307 , - ` - _ . _- _ UV-__ ov 2A2ov 16B19ad 0.330__sw __957-_t_-15.67 156 . ..0049 -nw _-1_.42 , _' 2.69 ___;_ 0 0 . p ___-„_256 l�1 tL-�G BIk mall, stucco e# 10C-m 0201 0550 nw nw 5.83 15.95 4.66 3950 0 -_.. 0 _ _ _ 0 ----__- -0---- 0 2A 2ov 0,330 0 0 0 0 12C Osw 0 091 nw - 9.57 _ 2.64 17.70 131 0 0 0 .. 0 0 . _ 0 0 0 . C - u.- 16B-30ad 0390 0032 : -n, 11.31 0.93 1143 ._._ . 0 -. 0.__ 1 69 227 227 210 383 --- 6 c) AED excursion -65 Envelope loss/gain 2534 1908 12 a) Infiltration b) Roomventilation 516 144 0 0 13 Internal gains: Occupants@ 230 1 230 Applianoes/other 0 Subtotal (lines 6to 13) 3050 2282 Less external load Less transfer 0 0 Redistribution 0 0 14 Subtotal 0 0 15 Duct loads 3050 2282 282 13 % 25 % Total room load Air required (dm) 3444 2860 146 134 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed �-�- wrigf�tsoit- �A Right-Sute®Universal 2021 21.0.02 RSU23828 2021-May-06 15:51:12 aterstorLe1780BGR1Lot44Blk1 Waterstone17808GR.np Calc= MJ8 Hose faces: SE Page 6 - wrightsoft® Duct System Summary Job: Lot 44 Block 1 Waterston... Date: 06.07.12 Entire House By: FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM For: ADAMS HOMES 5435 Lugo Street, Fort Pierce, FL 34951 External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.312 in/100ft 947 cfm 109 ft Cooling 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.312 in/100ft 947 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH2 c 111 2 5 0.460 4.0 Ox 0 VI Fx 3.9 70.0 BR2 h 1592 68 55 0.420 6.0 Ox 0 VIFx 11.0 70.0 BR3 h 2332 99 63 0.443 6.0 Ox 0 VIFx 6.7 70.0 DIWOY h 3444 146 134 0.374 7.0 Ox 0 VIFx 20.9 70.0 FAMMALL(S) c 5185 168 242 0.434 8.0 Ox 0 VI Fx 8.3 70.0 Krr c 3457 135 161 0.381 7.0 Ox 0 VIFx 19.1 70.0 LAU c 1141 26 53 0.456 4.0 Ox 0 VI Fx 4.5 70.0 MBATH h 2349 100 56 0.312 6.0 Ox 0 VIFx 24.0 85.0 sti MBR h 3870 164 153 0.322 7.0 Ox 0 VIFx 20.7 85.0 sti WIC h 887 38 25 1 0.333 4.0 Ox 0 VIFx 17.1 85.0 st1 Supply Trunk Detail Table Name Trunk Type Htg (cfm) Clg (cfm) Design FIR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk sti PeakAVF 302 233 0.312 553 10.0 0 x 0 VinlFlx Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat Trunk rb2 Ox 0 947 947 0 0 0 0 Ox 0 VIFx - wrightsoftD 2021-May-0615:51:13 Rigtd-Suite®Uriversa12021 21.0.02 RSU23828 Page 1 aterstore1780BGR\Lot44Blk1 Waterstore1780BGR.nQ Calc= MJ8 House faces: SE 2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 44 Block 1 Waterstone 1780 BGR Builder Name: ADAMS HOMES Street: 5435 Lugo Street Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 Design Location: FL, ST LUCIE CO W = —INTL U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. The insulation in any dropped ceiling/soffit Access openings, drop down stairs or knee wall doors to shall be aligned with the air barrier. unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. Knee walls shall be sealed. with a material having a thermal resistance of R-3 per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors (including The air barrier shall be installed at any exposed edge of insulation. Floor framing cavity insulation shall be installed to above -garage maintain permanent contact with the underside of and cantilevered subfloor decking, or floor framing cavity insulation floors) shall be permitted to be in contact with the top side of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace wall . Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac 3s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall behind nepina and w*rina Shower/tub on exterior -extend The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids a. In addition, inspection cover p of loa walls shall ha ;fk ff,e ...:: ., 5/6/2021 4:04 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist 0 Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: . ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 5/6/2021 4:04:02 PM EnergyGauge@ USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Duct Leakage Test Report Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition System 1 cfm25 System 2 cfm25 System 3 cfm25 Sum of others cfm25 Total of all cfm25 - 1780 = Qn Total of all Total Conditioned systems Square Footage PASS [:]FAI L Q Prescriptive, Method ,` cfm25 (,Total) To qualify as"substantially.'leak free" On Total must be ,less- than or equal to 0:04.if air handier -unit is installed. If -air handier unit i&not,. Installed, Qn Total must`be less tf an ore qual#o.0.03. This,testing method meets the requirements; in. accordance with Section R403 3.3, Is the air handler uni't mstalled,during testing? E]YES 0 Performance/ERI...Method ' .cfm25`(Owt.or Total) .' To,,qualtfy_usingthis method, On must not be�greater;than the. proposed'duct:aeakageOn specified on Form 11405-2020 or R406.2020 Leakage Type selected'on Form;. Q6spec fled on Form.R405-2020 . R405 2Q2Q.(EnergyCalc)Ior R4,06" 0' 20-' . (Ene'rgyCalc) or'R406-2020 ' Proposed Qn 0.06 Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (1), Florida Statutes. Testing Company Company Name: Phone: I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected compliance path as stated above, either the Prescriptive Method or Performance Method. . Signature of Tester: Printed Name of Tester: License/Certification #: Date of Test: Issuing Authority: 5/6/2021 4:05:10 PM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Enerqy Conservation, 7th Edition Jurisdiction: 661000 Permit #: Job Information , Builder: ADAMS HOMES Community: Lot: 44-1 Address: 5435 Lugo Street City: Fort Pierce Air Leakage Test Results State: FL Zip: 34951 Passing, results must meefeither the•Performance, Prescriptive, or ERI Method 0 PRESCRIPTIVE METHOD -The building or dwelling'unit shall be tested:and verified as having an air leakage rate of not exceeding 7 air, changes.per hour at a pressure of 0.2 inch w.g, (50.Pascals)'inClimate,Zones 1 and 2: Q PERFORMANCE or ERl METHOD -The ,building ordwelling unit shall be tested and verified as'havind an air leakage rate of not exceeding' the selected ACH(50) value, as shown on Form R405-2020 (Performance) or R406-2020,(ERI), section labeled as infiltration, sub-sectionACH50. ACH(50) specified.on Form R405-2020-Energy Ca1c (Performance) or R406 2020-(ERI): 7.000 x 60 _ 15664 = Method for calculating buildinq volume: CFM(50) Building Volume ACH(50) Q Retrieved from architectural plans FIPASS 40 Code software calculated When ACH(50) is less than 3, Mechanical Ventilation installation Q Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company` Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Printed Name of Tester: License/Certification #: Date of Test: Issuing Authority: 5/6/2021 4:04:59 PM EnergyGaugeOO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods F777577 5435 Lugo Street Permit Number: Fort Pierce , FL , 34951 IVIARuA I UKY KtQUIKLMENT5 -See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory) The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (1) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 5/6/2021 4:04 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. . R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C) or below 55°F (13°C) shall be insulated to a minimum of R-3. R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. ❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 5/6/2021 4:04 PM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 1407 (38°C to 60°C). - R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of combustion types of service water -heating systems to be turned off. R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. ❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM MINIMUM EFFICACY a AIRFLOW RATE MAXIMU (CFM) (CFM/WATT) (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 5/6/2021 4:04 PM EnergyGauge® USA 7.0.00 -. FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS . (Continued) ❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. ❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections ❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. ❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery. pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 5/6/2021 4:04 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5 QR403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING- SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 5/6/2021 4:04 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 5