HomeMy WebLinkAboutProject Information. . Manual S Compliance Report Job: Lot 28Block I Waterston... wrightsofto p p Date: Entire House By- DCS DEL AIR HTG, A/C & REFRIG. INC 531CODISCOWAY,,SANFORD,FL32771 Phore:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM For: ADAMS HOMES 5340 Lugo Street, Fort Pierce, FL 34951 Design Conditions Outdoor design DB: 90.4OF Sensible gain: 26392 Btuh Entering coil DB: 76.4°F Outdoor design WB: 77.4OF Latent gain: 4767 Btuh Entering coil WB: 63.2°F Indoor design DB`. 75.0 cF Total gain: 31159 Btuh Indoor RH: 50% Estimated airflow: 1167 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Sensible capacity: 28185 Btuh 1071% of load Latent capacity: 5115 Btuh 1071% of load Total capacity: 33301 Btuh 1070%of load SHR: 85% Heating Equipment Design Conditions Outdoor design DB: 41.0 cF Heat loss: 28571 Btuh Entering coil DB: 69.5°F Indoor design DB: 70.0 cF Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Output capacity: 31707 Btuh 111 % of load Capacity balance: 36 OF Supplemental heat required: 0 Btuh Economic balance: -99 OF Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1167 cfm Output capacity: 7.6 kW 91 % of load Temp. rise: 20 OF _ Meets all requirements ofACCA Manual S. Wrightsoft" 2021-May-06 11 33:15 �, �•�b- �� Righ1-Sute®Uriversa1202121.0.02RSU23828 i1CCA ...aterstone1820BGL\Lot28BIk1Waterstone18208GL.nQ CaIc=MJB FrorrtDoorfaces: E Page 1 -- wrightsoft° Component Constructions Job: Lot 28 Block 1 Waterstone... Entire House Date: By: DCS DEL AIR HTG, A/C & REFRIG. INC 531CODISCOWAY, SANFORD,FL32771Phone:407-333-2665Fax: 407-333-3853 Web:WWW.DELAIR.COM For: ADAMS HOMES 5340 Lugo Street, Fort Pierce, FL 34951 Location: St Lucie Co Inti, FL, US Indoor: Indoor temperature (OF) Heating 70 Cooling 75 Elevation: 26 ft Latitude: 28 °N Design TD (OF) Relative humidity (%) 29 30 15 50 Outdoor: Heating Dry bulb (OF) 41 Cooling Moisture difference (gr/lb) 2.4 56.9 Daily range (`F) - 90 15 (L ) Infiltration: Method Simplified Wet bulb (OF) - Wind speed (mph) 15.0 77 7.5 Construction quality Fireplaces Average 0 Construction descriptions or Area U-value Insul R Htg HTM Loss Cig HTM Gain ft� Btuh4PF ftz°FBtuh BUM Stuh BtutVft� Btuh Walls 1613-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum n 20 0.049 19.0 1.42 board int fnsh 28 2.59 52 a 20 0.049 19.0 1.42 28 2.59 52 s 20 0.049 19.0 1.42 28 2.59 52 w 20 0.049 19.0 1.42 28 2.59 52 Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" board int fnsh all 80 0.049 19.0 1.42 114 2.59 207 gypsum n 611 0.201 4.1 5.83 3561 4.06 2481 e 126 0.201 4.1 5.83 736 4.06 513 s 534 0.201 4.1 5.83 3113 4.06 2168 w 317 0.201 4.1 5.83 1846 4.06 1286 all 1588 0.201 4.1 5.83 9257 4.06 6448 Partitions 12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2'k4" wood frm, 16" o.c. stud Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, 1/8" n thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang s (5.3 ft window ht, 0.83 ft sep.); 6.67 It head ht W all 2A-2ov: 2 glazing, clr low-e outr, air gas, vni frm mat, cir innr, 1/4" gap, 1/8" n thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang (5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, 1/8" e thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.33 It overhang (5.3 ft window ht, 3.9 ft sep.); 6.67 It head ht 2A-2ov: 2 glazing, cir low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" e thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.33 It overhang (5.3 ft window ht, 5.3 It sep.); 6.67 ft head ht 1 -Of&- wrightsoft- N Right-Sute®Uriversal 2021 21.0.02 RSU23828 aterstorel820BGL\Lot28BIklWaterstonel82OBGL.np Calc=MJ8 FrontDoorfaces: E 270 0.091 13.0 2.64 713 1.31 354 33 0.330 0 9.57 313 8.52 279 49 0.330 0 9.57 469 8.52 418 33 0.330 0 9.57 313 22.4 733 114 0.330 0 9.57 1095 12.5 1430 16 0.330 0 9.57 156 8.52 139 16 0.330 0 9.57 156 21.6 353 16 0.330 0 9.57 156 21.6 353 2021-May-061123:15 Page I. 2B-2fv: 2 glazing, dr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" e 7 0.330 thk; NFRC rated (SHGC=0.31); 9 ft overhang (1.4 ft window ht, 0.5 ft sep.); 6.67 ft head ht 2B-2fv: 2 glazing, dr low-e outr, air gas, vnl fret mat, dr innr, 1/4" gap, 1/8" a 14 0.330 thk; NFRC rated (SHGC=0.31); 50% drapes, medium; 9 ft overhang (6.8 ft window ht, 2 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" s 7 0.330 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang (3.2 ft window ht, 0.83 ft sep.); 6.67 ft headht 10C-v: 2 glazing, clr low-e outr, air gas, vnl frm mat; dr innr, 1/4" gap, 1/8" w 18 0.550 thk; NFRC rated (SHGC=0.70); 11.5 ft overhang (6.7 ft window ht, 0.5 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" w 33 0.330 thk; NFRC rated (SHGC=0.23);, 50% drapes, medium; 11.5 ft overhang (5.3 ft window ht, 0.5 ft sep.); 0.67 ft head ht Doors 11 JO: Door, mtl fbrgl type a 20 0.600 Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 5/8" 1835 0.032 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 212 0.989 wrightsoft- a..W,.•�•» Rigft-Sute®Uriversa12021 21.0.02 RSU23828 AM aterstone1820BGL\Lot28BIk1Waterstone1820BGL:np Calc=MJ8 Frord Door faces: E 0 9.57 67 11.6 81 0 9.57 130 13.6 185 0 9.57 66 8.52 59 0 16.0 285 16.2 289 0 9.57 313 8.52 279 6.3 17.4 355 17.6 359 30.0 0.93 1703 1.69 3100 0 28.7 6080 0 0 2021 -May-06 1123:15 Page 2 -�- wrightsoft® Project Summary Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Ptnne:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Proiect Information Job: Lot 28 Block 1 Waterston... Date: By- DCS For: ADAMS HOMES 5340 Lugo Street, Fort Pierce, FL 34951 Notes: JA8-18-15 Change to 3.0 ton 2/16/16 S. Finch_ L. S. 5-6-21 VWK Design Information Weather: St Lude Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db Inside db 41 OF 70 OF Outside db Inside db 90 OF Design TD 29 OF Design TD 75 15 OF Daily range L Relative humidity 50 % Moisture difference 57 grAb Heating Summary Sensible Cooling Equipment Load Sizing Structure Ducts 24350 Btuh Structure 20615 Btuh Central vent (0 cfm) 4220 Btuh 0 Btuh Ducts Central vent (0 cfm) 5777 0 Btuh Btuh none Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 28571 Btuh Use manufacturer's data Infiltration Rate/swin multipplier EquipmenKens1 le load 1.00 26392 Btuh Method Construction quality Simplified Average Latent Cooling Equipment Load Sizing Fireplaces 0 Structure 3364 Btuh Ducts 1403 Btuh Central vent (0 cfm) 0 Btuh Area (ft2) Heatingg Cooling 1820 1820 (none) Equipment latent load 4767 Btuh Volume (ft3) 18350 18350 Air Changes/hour Equiv. AVF (cfm) 0.38 0.20 116 Equipment Total Load (Sen+Lat) 31159 Btuh 61 Req. total capacity at 0.75 SHR 2.9 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Trade CARRIER Make Carrier. Trade CARRIER Model 25HBC537AP03 AHRI ref 204837926 Cond 25HBC537AP03 Coil FX4DNF037L00 Efficiency 8.5 HSPF AHRI ref 204837926 Efficiency 12.5 EER,16 SEER Heating Input Heating output 34600 Btuh @ 47°F Sensible cooling Lateritcooling 26250 8750 Btuh Btuh Temperature rise Actual airflow 27 OF 1167 cfm Total cooling Actual airflow 35000 1167 Btuh cfm Airflowfactor Static pressure 0.041 cfm/Btuh 0.30 in H2O Airflowfactor Static pressure 0.044 0.30 cfm/Btuh in H2O Space thermostat Capacity balance point = 36 °F Load sensible heat ratio 0.85 Backup: Input = 8 kW, Output = 25920 Btuh,100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -Fk- wrightne ft 2021-May-061133:15 Aft.w Right-Srite®Uriversal'2021 21.0.02 RSU23828 Page 1 aterslorel820BGL�Lot28BIk1Waterstorel820BGL.nQ Calc=MJ8 Frorft Door faces: E -1- wrightsofts Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 28 Block 1 Waterstone182... Date: By: DCS 1 2 Room name E>posed wall Entire House BDRM2 3 Room height 212.0 ft 10.0 ft d 36.0 ft 10.0 ft heaUwol 4 5 Room dimensions Room area 1 835.0 iR 169.0 ft z 13.0 x 13.0 ft Ty Construction number U-value (Btuh/ft-'o Or HTM (Bluhfft2) Area (ftz) Load Area (112) Load or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/PiS Heat Cool Gross N/P/S Heat Cool 6 __.-__. _._.� __ W .. -- _ .16E-19ad_ -_. __ . _ _ . _"__ 0 049 Blkwall, stucco e# 0201 2A-2ov 0.330 .___-.. _._n n _ -- . _ _--1:4_2 5.83 _.._.-_ , T. 259 4.06 _ _ _.__ 20 660 -_- _ _ ._ 20 611 - .._^ ..28 3561 -,_ _� 52 2481 _ _0 130 _ _ 130 0 _ _�0 758 , �0 528 n 957 852 33 0 313 279 0 0 0 0 __.... 2A-2ov _0330 16B 19ad, _ _ _. _... _0.049 - - e 957 1.42 852 ' 2.59 ----- -.16 - _ - -0 .. ..._ 156 __.. .. 139 _ 0 --- - - --0_0 _ 0 Blk well, stucco e# 0.201 2A-2ov 0.330 e a _ 5,83 957 4.06 21.62 . _ _20 200 16 _ -_ . __20__ 126 0 736 156 _ ._52 513 353 __ . _ _ 0 0 0 _ _ ._.. 0 0 0 _ ___ ._ _ 0 0 0 _ _ ,0 0 0 2A-2ov 0.330 a 957 21.62 16 0 156 353 0 0 0 0 213-2ty 0.330 a 957 11.58 7 7 67 81 0 0 0 0 2B-21v 0230 a 957 1359 14 11 130 185 0 0 0 0 ----D ._._ -_ 0.600__e.._ ---0.049 _s_. ,._17.40 ..__17.58 259 _,._ _20 20 20._ 20 _.._355._ 359-_-.__..._0 52 _____. ___0.P__ 0 0 W Blk well, stucco e# 0.201 2A-2ov 0.330 . s s _. _.1A2 5.83 957 . 4.06 852 590 7 534 7 .=_,_ :28.- 3113 a --- 2168 - - 0 100 -- -` 0 100 v 0. 583 _ _.... ___0 406 2A-2ov 66 59 0 0 0 0 _ 0.330 s- 957 852 49 _ 49 469 418 0 0 0 0 W . _ 16B-19ad ; . _ _; _. 0049 Blk well, stucco e# 0.201 -W w 142 5.83 `, 259 4.06 ._ ..: 20 400 -- 20 317 _- ._. 28 1946 _ - 52 1286 - 0 130 - - --0 114 '- ' .A 663 - _ -0 461 10C-v 0550 w 1525 1620 18 18 285 2A-2ov 0350 2A-2ov_ w w- 957 22.43 8.52 33 2 33. 313 289 733 0 16 0 1 0 156 0 367 _ .__._._0330 12C-Osw--- -__ _ _ _ --.-0091 . _. -- -2 2.64 _.,.._ . 121 .__.._.-._33 270, U_."_-.. _.__27Q -313 713 __--- 279 --- --__ -0 _ _.___..0 _ 0 0 C _ _ 16&30ad,_• ., __. _ 0032 09ti9--_-__6080 :- 0.93 1 69 _ ,1835 _ . 1835 1703 _____354 ._,..3100 ---_. __0 ,._ _._ 169 ._-----___0 .- _ ._. 1.69 .. 157 _____0 _ - 286 6 c) AED exajrsion 893 103 Envelope loss/gain 20647 14530 3349 2150 12 a) Infiltration b) Room ventilation 3704 1035 691 193 0 0 0 0 13 Internal gains: Oocupants@ 230 5 1150 0 0 Appliances/other 3900 300 Subtotal (lines6 to 13) 24350 20615 4040 2643 Less external load 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 15 Subtotal Duct loads 24350 20615 0 4040 0 2643 17 % 28 % 4220 5777 17% 28 % 700 741 Total room load Air required (dm) 28571 26392 4740 3384 1167 11671 194 150 Calculations approved bvACCAto meet all requirements of Manual J 8th Ed �}+- wrigF�tsoTt^ �A Rigid-Sute®Universal 2021 21.0.02 RSU23828 2021-May-061123:15 Page 1 aterstone1820BGL\Lot28BIk1Waterstone1820BGL.rrp Calc=MJ8 FrontDoorfaces: E -�- wrightsoft• Right-M Worksheet Job: Lot 28 Block 1 Waterstone182... Entire House Date: DEL AIR HTG, A/C & REFRIG. INC By: DCS 531CODISCOWAY, SANFORD,FL32771Phone:407-333-2665Fax: 407-333-3853 Web:WWW.DELAIR.COM 1 Room name BATH BDRM3 2 E)posed wall 6.0 It 13.0 ft 3 Room height 10.0 ft heaUmol 10.0 ft heaUmol 4 Room dimensions 13.0 x 6.0 ft 13.0 x 13.0 it 5 Room area 78.0 ftz 169.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area z number (Bluhfttz cq (Btuh/ftz) or perimeter ft(ft) Load () (Btuh ) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool - - _ _ _ 6 W 16619ad. _OA49 _ _n _ _ 1.42 _259 _ 0 _ _,` . 0 ..- - - 0 - -0 --- 0 - Q -__ -0 Elk aell, stucco ext 0201 n 5.83 4.06 60 60 350 244 _ 130 114 663 461 2A 2ov 0330 n 957 852 0 0 0 0 0 0 0 0 2A-2ov_.. - -, - -- 0.330 . n_ 957 _ 852 . --- --0 -- 0 0 - -- - 0 - ... - -16 0 _ .v -156 _._.. -_ 139 _.., 1.42 259 _ _ :0, _. _� 4 . _ ._ _. _0 ...__ _ _ 0 ._. _.:. _ ..9 _ _ .__ _0 __-----_ _ 0 Elk %tell, stucco ext 0.201 a 5.83 4.06 0 0 0 0 0 0 0 0 2A-2ov 0.330 a 957 21.62 0 0 0 0 0 0 0 0 2A-2ov 0.330 a 957 21.62 0 0 0 0 0 0 0 0 28-2fv 0330 a 9.57 11.58 0 0 0 0 0 0 0 0 2E-2M- 0.330 a 957 1359 0 0 0 0 0 0 0 0 11J0 _ .__ _0.600 - e._ 17.40 =- 17,58 . _ _. _ , 0 ....___ 0 - 0 0 .. _ 0 ---. _-_ _0 _. ..._ ._0. _.._.. _.._.. Q W ...._ -16B 19ad.. ._0048 .:.s. 1,42 . .._;259 .-.: -_0 :...._-._0 _-. 0 .. .... _.-.-0 _. .... 0 Blk v,all, stucco e)d 0.201 s 5.83 4.06 0 0 0 0 0 0 0 0 2A-2ov 0.330 s 9.57 852 0 0 0 0 0 0 0 0 2A-2ov 0.330 s 957 852 0 0 0 0 0 0 0 0 _..-- - _ ._. _w. _ _ - - 16&19ad_ _ _.._ - -_. __0049 _ w_ _ 1., 259 _ _ 0 0 - 9 __.`0 ,,0 _ .._ 0 _ -__ 0 . -- __ 0 VVV���lll Blk wall, stucco ext 0.201 w 5.83 4.06 0 0 0 0 0 0 0 0 10C-v 0550 w 15.95 1620 0 0 0 0 0 0 0 0 2A-2ov 0.330 w 957 22.43 0 0 0 0 0 0 0 0 -- 2A-2ov_._ .-_ _ - 0.330 -w 957-...._8.52 - -.0 0 - - -- - - � - 0 --- ---- 0 0 - . 0 A P . _ . 12C Osw-_--- - _ _. ._._0,091 _.- -----„_2,64 A 1,31- _ --- _-_0 ---.._ ,_ 0 . .-__- __0 . __._-_0 ---- _--_0 .-.._ ..-__0 -0 C- 16B 30ad : _.._. _ .. _. 0.032 - - -• 0.93 _.__ 1..69 78 78 _ _ 72 132 _._ .. 169 _._. _.. 1_69 157 286 F: _-_ . W( 0.989 - 28.68 _ ->0.00 - 78 -- _8 172 . -0 169 . -13 373 . -- - 0 6 c) AED excu sion -18 -56 Envelope loss/gain 594 357 1349 830 12 a) Infiltration 115 32 249 70 b) Room ventilation 0 01 0 0 13 Internal gains: Occupants@ 230 0 p 0 0 Appliancesrother 0 300 Subtotal (lines 6 to 13) 709 389 1598 1200 Less e#ernalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 709 389 1598 1200 15 Dud loads 17% 28 % 123 109 17 % 28 % 277 336 Total room load 832 498 1 T1875 1536 Air required (cim) 34 22 77 68 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed �'f wrigtitsol<t^ �A Right-Sute®Universal 2021 21.0.02 RSU238282021-May-061133:15 ...aterstone1820BGL\Lot28Blk1Waterstone1820BGL.np CaIc=MJ8 FrontDoorfaces: E Page -�- wrightsoff Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3R53 Wah• W W W nrl nio enen Job: Lot 28 Block 1 Waterstone182... Date: By: DCS 1 2 Room name F�osedvIdl DIN ING DINING/FOYER FOYER DENBDRM4 3 4 Room height Room dimensions ft 10.0 ft heat/mol 3.1.0 8 10.0 ft heat/cool 5 Room area 1.0 x 276.0 ft 13.0 x 13.0 ft 276.0 ftz 169.0 ftz Ty Construction number U-value 13tuh/ tz_ ( fl Or HTM (Btuh/ftz) Area (ft) Load Area (ftz) Load or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat I Cool Gross N/P/S He Cool Gross N/P/S Heat I Cool - 4�_vu4y n 1'9L259 0 0 0 00. Blk v�all stu000 ext 0 201 n 5.83 4 06 110 77 451 314 130 130 758 528 2A 2ov 0.330 n 957 852 33 0 313 279 0 0 0 0 2A 2ov _. 0 330 n_ 957 852 0 0 0 0 0 0 0 0 11 W 16&19ad_049 . en. .- 1.42 F, _2 59 0 0 0 .,' 0 0 ' Q - 0 0 Blk viell, stucco e# _ F Y0201 e 5 83 4.06 _ ;_ 70 29 _ 169 118 .k 130 97 567 395 2A-20v 0.330 a 9.57 21.62 0 0 0 0 16 0 156 353 2A-20v 0230 a 9.57 21.62 0 0 0 0 16 0 156 353 2B-2N 0.330 a 957 11.58 7 7 67 81 0 0 0 0 2B-2fv 0.330 a 9.57 1359 14 11 130 185 0 0 0 0 11,10 0.600 ,e _ 17.40 _ 17 58 _. 20 20 355 359 0 16B19ad- x w 0049.s_. 142 259 .,._ -,0 ___ _ 0 0 0, :.._ 0 _:..__.0 W Blk wall, stucco ext 0.201 s 5.83 4.06 0 0 ^0 0 50 50 291 203 2A-2ov 0.330 s 9.57 852 0 0 0 0 0 0 0 0 2A 2ov 0.330 s 957 852 0 0 0 0 0 0 0 0 16619atl' 0.049 . H- ._ 1„42 2S9 0 0 0 0 _ 0 _ c_0 VVV���lll Blk wall, stucco ext 0201 w 5 83 4.06 0 f ...T. ' 0 '0 -0 0 0 ._' .'.._.O 4:: o 10C-v 0550 w 15S5 1620 0 0 0 0 0 0 0 0 2A-2ov 0.330 w 957 22.43 0 0 0 0 0 0 0 0 0.330 w 957 8.52 _, 0 0 0 _„ 0 0 0 0 0 OA91 .._:w4 2,64 13I 70 . .,.. _ 70 __ ...,185 _92 ...R .. 00'_.0. C 166 30ad _0 032 y... 023 1.69 276 276 256 . _ _ 466 169 , _ 169 157 , _. 286 7 _ . . S,_... _.... 6 c) AED excursion 100 116 Envelopeloss/gain 2642 1793 2975 2234 12 a) Infiltration 345 97 595 166 b) Room ventilation 0 0 0 0 13 Internal gains: Oocupantspa 230 1 230 0 0 Appliancestother 0 300 Subtotal (lines6 to 13) 2988 2120 3570 2700 Less external load 0 0 0 0 Less transfer Redistribution 0 0 0 0 14 Subtotal 0 0 0 0 2988 2120 3570 2700 151 5 Duct loads 17% 28% 518 594 17% 28% 619 757 Total room load 3506 2714 Air required (cfm) 506 714 4189 3457 1 171 153 - Calculations proved bvACCAto meet all requirements of Manual J 8th Ed 2021-May-0611:33:15 Right-Sute®Udversal 2021 21:0.02 RSU23828 aterstone1820BGL\Lot28BIk1Waterstone1820BGL.np Calc=MJ8 FrontDoorfaces: E Page -+'- wrightsoft° Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM 1 2 Room name Exposed wall FAMILY RM 4 Room height Room dimensions 13.0 It3 10.0 ft heaV000l 5 Room area 13.0 x 22.0 286.0 ft2 ft Ty Construction number LlAdue (Btuh/ft-9 Or HTM (Btuh/ft2) Area (112) Load or perimeter (ft) (Btuh) Job: Lot 28 Block 1 Waterstone182... Date: By: DCS MSTR BDRM 41.0 It 10.0 It heattwol 14.0 x 17.0 it 238.0 112 Area (ft2) Load or perimeter (ft) (Btuh) -Ul Heat Cool 6 W :_ VBlk 16619ad W._.. vdl, stucco ext 2A 2ov _w :..0 049 0.201 W n n _u 1422 5 83 _ 259 4.06 .. 0 28 0 0 0 100 100 583 0 406 0,330 n 957 852 0 0 0 0 0 0 2A 2ov 0.330 9 n e. 957 8.52 0 0 0_ 0 0, 0 0 0 0 0 Blk mall, stucco ext 2A-2ov .._0,0 0.201 0,330 _ a a iA? �5b3 957 _ ._ 259 4.06 21.62 w 20 -- 20 O J 0 . 28 0 0 __ 52 0 0 _.._ , .w0 0 0 . __ 0 0 0; -0'- 0 0 .0 0 2A-2ov 0,330 a 957 21.62 0 0 0 0 0 0 0 0 2B-2fv 2B-2fv 0230 a 9.57 11.58 0 0 0 0 0 0 0 0 0 0 0 11J0 0.330 a 957 13.59 0 0 0 0 0 0 0 0 -,__ 16B 1.9ad £--w=.._. 0600 F,, ," [9 _ ,e _-'s. 1740 142 1758 ,,.. 259 20 0 0 0 28 _-,_ 0 -, 0 Blk wall, stucco ext 2A-2ov 0.201 0,330 s 5.83 957 4.06 0 _ ..: _._.20 0 0 _5,2 0 __. 0 170 _ . _0 154 _ ,__ . w A 896 624 2A 2ov s 852 0 0 0 0 0 0 0 W-..._,B 11k 19a 0230 0049;w_ s 957 142 852 0 0 _ 0 0 16 16 156 0 139 lk ald� ml, stucco ext 10C-v 0.201 0550 w w _... 5.83 15.95 _.y259 4.06 1620 130 18 79 18 463 285 323 289 _ 140 0 124 0 721 502 2A 2ov 2A2ov 0.330 w w, 957 22.43 852 0 33 0 0 0 16 1 0 156 0 367 C .._. Osw4� 16B•30ad _02W 0091131 _,._957 p 33 - 313 w 279 0 0 0 0 �_0 0 ___ 0. _ F _ _.. __ , 22A WI .. _. _. _ : 0032 0 989 ; `,` 0.93 8.68_0.00 _ 1 69 286 286 286 13 265 483 238 238 _ 221 -- ._ _ 402 -7 .. _373 : ...� _:. _ 238 _'~ L h 41 1- - 0 .. - , ., ,.. .� ._ , v,. ... ..... .. ...... .ram , �.... , _ ..,. ,.. _ �. __. .. .a __ 7 ... _..... .._._..-......_. ,._.__......_ .._.. ,.,..__ ' ,,,,..___ .._..-_.'_ _.... __.._ 6 c) AED exaarsion 1024 16 Envelopeloss/gain 1813 2605 3909 2456 12 a) Infiltration b) Room ventilation 403 113 787 220 0 0 0 0 13 Internal gains: Occupants@ 230 3 690 1 Appliances/other 230 600 600 Subtotal (lines 6 to 13) 2216 4007 4696 3506 Less e)dernal load Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 0 06 15 Duct loads 17% 28% 2210 384 4000 1123 179/. 28% 469 814 3506 982 Total room load Airrequired (dm) 2606 5227 510 5225 4488 8 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed *^ wrigl�tsoft- A Right-Sute81.1dversa12021 21.0:02 RSU23828 2021-May-061133:15 aterstonelB20BGL\Lot28BIk1Waterstorel820BGL.rLp Calc=MJ8 FrontDoorfaces: E Page 4 -�- wrightsoft® Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM 1 Room name M BATH ' 2 3 Exposed wall Room height ft 4 Room dimensions 10.0 ft heaUcool 5 Room area 1.0 x 119.0 It Job: Lot 28 Block 1 Waterstone182... Date: By: DCS M WIC Oft 10.0 It heaU000l 7.0 x 7.0 It .....,, 4y.0 IF Ty Construction number U-value (Btuh/ft-`) Or HTM (Btuh/ftz) Area (ftz) Load Area (ft2) Load or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 16B 19a�1_? Blkwall,stuccneM 2A-2ov OA49 0.201 .. 0 n 1,42 5.83 �y2,59 4.06 _a _ .0 0" 0 _ 0 _.� _r _: 0 '� 0 0 ��`' p p p 0 p - -0 0 _ _----- .0, 0 0.330 n 957 852 0 0 0 0 0 2A 2ov 16B-_19,s , 0330 n me:_.0. 957 852 0 _0 0 _ 0 0 0 0 _0 O 0 0 Blkwall,stucoo ext 2A-2ov 0.201 0,330 a a 5.83 957 4.06 21.62 0 0 0 0 0.v,_ 0 0 0 00 0 ___ _•._ 0 0 n,_0 0 2A`2ov 0,330 a 957 21.62 0 0 0 0 0 0 0 0 2B-2fv 2B-2fv 0.330 a 957 11.58 0 0 0 0 0 0 0 0 11J0 _, 0230 600 a @ 9.57 17.40 13.59 1758 0 0 0 0 0 0 0 0 0 0 W.0 16619ad'�.. _ Blk gall, stucco ext 2A-2ov y;0 . 0049_,s` 0.201 _ s 7-42 5.83 _ w�2�9 4.06 _ __ ._u,. :.; 0 120 _.A_ __ 0_, 113 x. 0' 659 0 0 �._= ._ 0 459 _ __ _ 0 :- v _ , 0 0 0 0 0 0 _ _ 0 0 ___ 0 :_ Q 0 0.330 s 957 852 7 7 66 59 0 2A 2ov 0.330 s 9.57 852 0 0 0 0 0 0 0 0 W._. .._16B19aii_259 1 O v�ell, stucco ext 10C-v _. 0.201 0550 w w 5.83 15.95 4.06 1620 0 0 0 0 _0 0 0 0 0 0 0 0 0 0 0. o. 2A-2ov 0.330 w 957 22.43 0 0 0 0 0 0 0 0 0 0 C 2A 2oy_, _. 0 330 _w, 9.57 ___264 852 , 1,31 0 _', 0 0 0 0 0 0 .. _ ,--- , _0 0 . _ _ w._. p 0 0 F 16B30ad 22Atpl:_ 0032 0989 0.93 8. 169 '000 119 119 110 201 _ 49 49 45 _.. 83 _. .119 W _.�;`.12 _.M 344�f� __ 0v , 49.E �_.0_.._ _0 . _ _ Hr ,. , 4 . 6 c) AED excursion 35 4 Envelope losstgain 1180 684 45 79 12 a) Infiltration b) Room ventilation 230 64 0 0 0 0 0 0 13 Internal gains: Oocupants@ 230 0 0 Applianoestother 0 0 0 0 Subtotal (lines 6 to 13) 1410 748 45 79 Less external load Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 0 0 0 0 15 Duct loads 17% 28% 1410 244 748 210 45 79 17% 28 % 8 22 Total room load Air required (cfm) 1655 958 52 1011 68 421 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed - wrigF�tsoft� Riga-Sute®Uriversal 2021 21.0.02 RSU23828 2021 -May-06 1133:15 aterstone1820BGL\Lot28Blk1 Waterstore1820BGL.np Calc= W8 Front Doorfaces: E Page 5 -�- wrightsoft, Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 28 Block 1 Waterstone182... Date: By: DCS 2 Room name Exloosed wall KrrCHENMOOK LAUNDRY 3 4 Room height Room dimensions 29.0 ft 10.0 ft heaU000l 6.0 ft 10.0 It heaHwol 5 Room area 246.0 ftz 1.0 x 246.0 It 6.0 x 6.0 ft 36.0 ftz Ty Construction number U-value (Btuhfltz q Or HTM (Bluh/ftz) Area (ftz) Load Area (ftz) Load or perimeter (ft) (Btuh) I or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P5 Heat Cool 6 V)1 Blk well, stucco ex< 2A 2ov 0.201 0.330 n 5B3 4.06 ---- 0 0 0 ' 0 - O 0 0 - 0 0 1�.-�G n 957 8.52 0 0 0 0 0 D 2A_2oy_ _ _ _ Blk well, stucco eM - .__ - - - 0.201 a _ 1,42 5.83 ._ . ,_259 4.06 . _4 - - -0 0 0 __ . 0 - 0 0 0 -� - -- -- _-.__.. 0 -- - 0 0 0 - -- _ 0 2A-2ov 0.330 a 957 21.62 0 0 0 0 0 0 0 2A-2ov 0.330 a 957 21.62 0 0 0 0 0 2B-2fv 0 0 0 0 0 0 0 0 26-21v 0.330 0330 a a 957 9.57 11.58 1359 0 0 0 0 0 0 0 0 0 0 16B19ad_ __ 0.600 e__ . - 17.40 1.42 1758 _ 0 _._--.___. 0 - -- 0 0 0 _ 0 0 _ 0 0 _0 0 0 0 0 -- .0 Blk well, stu000 ext ' 2A-2ov ---0,049 6.201 0230 _._s_ s .,.. 5.83 ,:__2,59. 4.06 - . __0 150 ._.._._. 0 117 0. 684 _. 0 476 _ 0 0 0 _ -'p 0 ' p 0 2A-2ov s 957 852 0 0 0 0 0 0 0 0 W - 0.330 - _ -0049 s _ 957 1.42 852 ; 33 p _ . _. _ 33 313 _ -- 279 _. _ -.--- 0 _-- -- . _. 0 0 0 _ -- Blk well, stucco ext 10C-v - O'201 0550 _,w w w - _ 5.83 15.95 ,259 4.06 1620 ._ _.. 0 0 0 0 - "0 0 0 0 0 0 0 0 0 0 " ' 0 0 2A-2ov 2A 2ov. 0.330 w 957 22.43 0 0 0 0 0 0 0 0 _... C - 16630ad _._.__764 852 --140 0 . 0 ._.__ _8 _ •-_ 0 , 91 .-.__002.98390 . -__- -_-- -957 --0 28.68 __ -6. _246 _A.__ 2 _ 6 _----_-_•--,_0 332A _-_- - .__- - ...-___..-012C0 __--__._36 __.__._-_„_._ 6 c) AED excursion -118 33 Envelope loss/gain 2426 1236 364 106 12 a) Infiltration b) Room ventilation 288 80 0 0 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 Applianoesrother 0 1200 600 Subtotal (lines 6 to 13) 2714 2516 364 706 Less extemal load Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 0 0 0 0 15 Duct loads 17°/ 28% 2714 470 2516 705 17 % 28 % 364 63 706 198 Total room load Air required (dm) 3184 3221 417 04 940 Calculatons approved bvACCA to meet all requirements of Manual J 8th Ed ,` �� wr➢ghlsoTt^ �A Right-Sute®Uriversa12021 21.0.02 RSU23828 2021-May-061133:15 aterstone1820BGL\Lot28BIk1Waterstone1820BGL.rLp Calc=MJ8 FrontDoorfaces: E Page -1- wrightsoft® Duct System Summary Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM For: ADAMS HOMES 5340 Lugo Street, Fort Pierce, FL 34951 Job: Lot 28 Block 1 Waterston... Date: By: DCS External static pressure Heating 0.30 in H2O Cooling 0.30 in H2O Pressure losses 0.06 in H2O 0.06 in H2O Available static pressure 0.24 in H2O 0.24 in H2O Supply/return available pressure 0.120/0.120 in H2O 0.120/0.120 in H2O Lowest friction rate 0.212 in/100ft 0.212 in/100ft Actual air flow 1167 cfm 1167 cfm Total effective length (TEL) 113 ft Name Design (Btuh) Htg (cfm) Cig (cfm) Design FR Diam (in) H x W (in) Duct Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 832 34 22 0.278 4.0 Ox 0 VI Fx 16.3 70.0 BDRM 2 h 4740 194 150 0.258 8.0 Ox 0 VIFx 22.9 70.0 BDRM3 h 1875 77 68 0.305 6.0 Ox0 VIFx 8.6 70.0 DENBDRM4 h 4189 171 153 0.288 7.0 Ox0 VIFx 13.2 70.0 DINING/FOYER h 3506 143 120 0.314 7.0 Ox 0 MR 6.5 70.0 FAMILYRM c 5130 106 227 0.233 8.0 Ox 0 VIFx 17.9 85.0 sti KrrCHEN1NOOK c 3221 130 142 0.228 7.0 Ox 0 VIFx 20.1 85.0 sti LAUNDRY c 904 17 40 0.223 4.0 Ox 0 VIFx 22.7 85.0 sti M. BATH h 1655 68 42 0.224 5.0 Ox 0 VI Fx 22.2 85.0 sti M. WIC c 101 2 4 0.225 4.0 Ox 0 VIFx 21.9 85.0 sti MSTRBDRM h 5510 225 198 0.212 8.0 Ox0 VIFx 28.2 85.0 sti Name Trunk Type Htg (cfm) Cig (cfm) Design FIR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk sti PeakAVF 549 655 0.212 612 14.0 0 x 0 VInIFIX : * wrightsoft® 2021-May-061133:16 M ,.•, Right-Sute®Uriversal 2021 21.0.02 RSU23828 aterstone1820BGL\Lot28Blk1Waterstone1820BGL.np Calc=MJ8 FrontDoorfaces: E Page1 Name Grille Size (in) Htg (Cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat Trunk rb1 Ox 0 1167 1167 0 0 0 0 Ox 0 VIFx wrightsofta 2021-May-0611:33:16 Rigtd-Sute®Udversal 2021 21.0.02 RSU23828JCCK Page 2 aterstone1820BGL\Lot28BIk1Waterstone1820BGL.nQ Calc=MJ8 FrontDoorfaces: E 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 28 Block 1 Waterstone 1820 BGL Builder Name: ADAMS HOMES Street: 5340 Lugo Street Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 w Design Location: FL, ST_LUCIE CO INTL = U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. The insulation in any dropped ceiling/soffit Access openings, drop down stairs or knee wall doors to shall be aligned with the air barrier. unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. Knee walls shall be sealed. with a material having a thermal resistance of R-3 per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors (including The air barrier shall be installed at any exposed edge of insulation. Floor framing cavity insulation shall be installed to above -garage maintain permanent contact with the underside of and cantilevered subfloor decking, or floor framing cavity insulation floors) shall be permitted to be in contact with the top side of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawispace wall . Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall Shower/tub on exterior wall The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids a. In addition. insoectinn lates and w;;Il, or of Inn wain shau ha „ tk--',...:..:...... _r'__ . _ _.._.. ..,.,, u— Fl vial l la ul 5/6/2021 11:43 AM EnergyGauge® USA 7.0.d0 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 5/6/2021 11:42:53 AM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Buildina Code. Enerav Con_qPrvatinn 7th 1=r itinn Jurisdiction: 661000 Permit #: Job Information - Builder: ADAMS HOMES Community: Lot: 28-1 Address: 5340 Lugo Street City: Fort Pierce State: FL Zip: 34951 Air. Leakage TeStr Results Passing reggltS,MUSt meet either -the Performance; Prescriptive, or ER1 Method OPRESCRIPTIVE METHOD The building or dwelling unifshall be tested Jand verified.as_having an air leakage rate of not exceeding 7 air" changes per.hour at a.pressure of-02'inch w.g: (50 Pascals) in'Climate Zones 1,and 2.-' ;$Q ,PERFORMANCE or ERI METHODrThe build !n6 ordweiling unitshall be tested and verified as, having an air leakage rate of!not exceeding' the,selected;ACH(50).4ue,"as shown on Form R405-2020 (Performance),,or R406 2020 (ERI), section labeled as infiltration;.sub section ACH50. - ACH(50) specified on Form'R405 2020 Energy Ca/c (Perforrriancej or-R406-2020 (ERO: ',' 7.000 x 60 _ 18200 = Method for calculating building volume: CFM(50) Building Volume ACH(50) Q Retrieved from architectural plans F� PASS Code software calculated ElWhen ACH(50) is less than 3, Mechanical Ventilation installation Q Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Printed Name of Tester: License/Certification #: Date of Test: Issuing Authority: 5/6/2021 11:43:49 AM EnergyGaugeO USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods F7RESS: 5340 Lugo Street Permit Number: Fort Pierce , FL , 34951 tvtAuvUH i UKY KtQUIKEMENTS -See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 5/6/2021 11:43 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential, R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41"C) or below 55°F (13"C) shall be insulated to a minimum of R-3. R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. ❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 5/6/2021 11:43 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'% inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60°C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of combustion types of service water -heating systems to be turned off. R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TMA, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. ❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN FFFIrArV FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU IV (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 5/6/2021 11:43 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. El R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -Fred heaters shall not be equipped with continuously burning ignition pilots. R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 5/6/2021 11:43 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5 R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal El efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. R403.11 Portable spas (Mandatory). The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. nR403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 5/6/2021 11:43 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5