Manual S Compliance Report Job: Lot 28Block I Waterston...
wrightsofto p p Date:
Entire House By- DCS
DEL AIR HTG, A/C & REFRIG. INC
531CODISCOWAY,,SANFORD,FL32771 Phore:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM
For: ADAMS HOMES
5340 Lugo Street, Fort Pierce, FL 34951
Design Conditions
Outdoor design DB:
90.4OF
Sensible gain:
26392
Btuh Entering coil DB: 76.4°F
Outdoor design WB:
77.4OF
Latent gain:
4767
Btuh Entering coil WB: 63.2°F
Indoor design DB`.
75.0 cF
Total gain:
31159
Btuh
Indoor RH:
50%
Estimated airflow:
1167
cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype:
SpIitASHP
Manufacturer:
Carrier
Model: 25HBC537AP03+FX4DNF037L00
Actual airflow:
1167
cfm
Sensible capacity:
28185
Btuh
1071% of load
Latent capacity:
5115
Btuh
1071% of load
Total capacity:
33301
Btuh
1070%of load SHR: 85%
Heating Equipment
Design Conditions
Outdoor design DB:
41.0 cF
Heat loss: 28571 Btuh Entering coil DB: 69.5°F
Indoor design DB:
70.0 cF
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: SpIitASHP
Manufacturer: Carrier
Model: 25HBC537AP03+FX4DNF037L00
Actual airflow: 1167
cfm
Output capacity: 31707
Btuh
111 % of load Capacity balance: 36 OF
Supplemental heat required:
0
Btuh Economic balance: -99 OF
Backup equipment type:
Elec strip
Manufacturer:
Model:
Actual airflow: 1167
cfm
Output capacity: 7.6
kW 91
% of load Temp. rise: 20 OF
_ Meets all requirements ofACCA Manual S.
Wrightsoft" 2021-May-06 11 33:15
�, �•�b- �� Righ1-Sute®Uriversa1202121.0.02RSU23828
i1CCA
...aterstone1820BGL\Lot28BIk1Waterstone18208GL.nQ CaIc=MJB FrorrtDoorfaces: E Page 1
-- wrightsoft° Component Constructions Job: Lot 28 Block 1 Waterstone...
Entire House Date:
By: DCS
DEL AIR HTG, A/C & REFRIG. INC
531CODISCOWAY, SANFORD,FL32771Phone:407-333-2665Fax: 407-333-3853 Web:WWW.DELAIR.COM
For: ADAMS HOMES
5340 Lugo Street, Fort Pierce, FL 34951
Location:
St Lucie Co Inti, FL, US
Indoor:
Indoor temperature (OF)
Heating
70
Cooling
75
Elevation: 26 ft
Latitude: 28 °N
Design TD (OF)
Relative humidity (%)
29
30
15
50
Outdoor: Heating
Dry bulb (OF) 41
Cooling
Moisture difference (gr/lb)
2.4
56.9
Daily range (`F) -
90
15 (L )
Infiltration:
Method
Simplified
Wet bulb (OF) -
Wind speed (mph) 15.0
77
7.5
Construction quality
Fireplaces
Average
0
Construction descriptions
or
Area
U-value
Insul R
Htg HTM
Loss Cig HTM
Gain
ft�
Btuh4PF
ftz°FBtuh
BUM
Stuh
BtutVft�
Btuh
Walls
1613-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum
n
20
0.049
19.0
1.42
board int fnsh
28
2.59
52
a
20
0.049
19.0
1.42
28
2.59
52
s
20
0.049
19.0
1.42
28
2.59
52
w
20
0.049
19.0
1.42
28
2.59
52
Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" board int fnsh
all
80
0.049
19.0
1.42
114
2.59
207
gypsum
n
611
0.201
4.1
5.83
3561
4.06
2481
e
126
0.201
4.1
5.83
736
4.06
513
s
534
0.201
4.1
5.83
3113
4.06
2168
w
317
0.201
4.1
5.83
1846
4.06
1286
all
1588
0.201
4.1
5.83
9257
4.06
6448
Partitions
12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int
fnsh, 2'k4" wood frm, 16" o.c. stud
Windows
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, 1/8" n
thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang s
(5.3 ft window ht, 0.83 ft sep.); 6.67 It head ht W
all
2A-2ov: 2 glazing, clr low-e outr, air gas, vni frm mat, cir innr, 1/4" gap, 1/8" n
thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang
(5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, 1/8" e
thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.33 It overhang
(5.3 ft window ht, 3.9 ft sep.); 6.67 It head ht
2A-2ov: 2 glazing, cir low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" e
thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.33 It overhang
(5.3 ft window ht, 5.3 It sep.); 6.67 ft head ht
1 -Of&- wrightsoft-
N Right-Sute®Uriversal 2021 21.0.02 RSU23828
aterstorel820BGL\Lot28BIklWaterstonel82OBGL.np Calc=MJ8 FrontDoorfaces: E
270
0.091
13.0
2.64
713
1.31
354
33
0.330
0
9.57
313
8.52
279
49
0.330
0
9.57
469
8.52
418
33
0.330
0
9.57
313
22.4
733
114
0.330
0
9.57
1095
12.5
1430
16
0.330
0
9.57
156
8.52
139
16
0.330
0
9.57
156
21.6
353
16
0.330
0
9.57
156
21.6
353
2021-May-061123:15
Page I.
2B-2fv: 2 glazing, dr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" e
7 0.330
thk; NFRC rated (SHGC=0.31); 9 ft overhang (1.4 ft window ht, 0.5 ft
sep.); 6.67 ft head ht
2B-2fv: 2 glazing, dr low-e outr, air gas, vnl fret mat, dr innr, 1/4" gap, 1/8" a
14 0.330
thk; NFRC rated (SHGC=0.31); 50% drapes, medium; 9 ft overhang (6.8
ft window ht, 2 ft sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" s
7 0.330
thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang
(3.2 ft window ht, 0.83 ft sep.); 6.67 ft headht
10C-v: 2 glazing, clr low-e outr, air gas, vnl frm mat; dr innr, 1/4" gap, 1/8" w
18 0.550
thk; NFRC rated (SHGC=0.70); 11.5 ft overhang (6.7 ft window ht, 0.5 ft
sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" w
33 0.330
thk; NFRC rated (SHGC=0.23);, 50% drapes, medium; 11.5 ft overhang
(5.3 ft window ht, 0.5 ft sep.); 0.67 ft head ht
Doors
11 JO: Door, mtl fbrgl type a
20 0.600
Ceilings
16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 5/8"
1835 0.032
gypsum board int fnsh
Floors
22A-tpl: Bg floor, light dry soil, on grade depth 212 0.989
wrightsoft-
a..W,.•�•» Rigft-Sute®Uriversa12021 21.0.02 RSU23828
AM aterstone1820BGL\Lot28BIk1Waterstone1820BGL:np Calc=MJ8 Frord Door faces: E
0 9.57
67
11.6
81
0 9.57
130
13.6
185
0 9.57
66
8.52
59
0 16.0
285
16.2
289
0 9.57
313
8.52
279
6.3
17.4
355
17.6
359
30.0
0.93
1703
1.69
3100
0
28.7
6080
0
0
2021 -May-06 1123:15
Page 2
-�- wrightsoft® Project Summary
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Ptnne:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM
Proiect Information
Job: Lot 28 Block 1 Waterston...
Date:
By- DCS
For:
ADAMS HOMES
5340 Lugo Street, Fort Pierce,
FL 34951
Notes:
JA8-18-15
Change to 3.0 ton 2/16/16 S. Finch_
L. S. 5-6-21 VWK
Design Information
Weather: St Lude Co Intl, FL, US
Winter Design
Conditions
Summer Design Conditions
Outside db
Inside db
41 OF
70 OF
Outside db
Inside db
90
OF
Design TD
29 OF
Design TD
75
15
OF
Daily range
L
Relative humidity
50
%
Moisture difference
57
grAb
Heating Summary
Sensible Cooling Equipment Load
Sizing
Structure
Ducts
24350 Btuh
Structure
20615
Btuh
Central vent (0 cfm)
4220 Btuh
0 Btuh
Ducts
Central vent (0 cfm)
5777
0
Btuh
Btuh
none
Humidification
0 Btuh
Blower
0
Btuh
Piping
0 Btuh
Equipment load
28571 Btuh
Use manufacturer's data
Infiltration
Rate/swin multipplier
EquipmenKens1 le load
1.00
26392
Btuh
Method
Construction quality
Simplified
Average
Latent Cooling Equipment Load Sizing
Fireplaces
0
Structure
3364
Btuh
Ducts
1403
Btuh
Central vent (0 cfm)
0
Btuh
Area (ft2)
Heatingg Cooling
1820 1820
(none)
Equipment latent load
4767
Btuh
Volume (ft3)
18350 18350
Air Changes/hour
Equiv. AVF (cfm)
0.38 0.20
116
Equipment Total Load (Sen+Lat)
31159
Btuh
61
Req. total capacity at 0.75 SHR
2.9
ton
Heating Equipment Summary
Cooling Equipment Summary
Make Carrier
Trade CARRIER
Make Carrier.
Trade CARRIER
Model 25HBC537AP03
AHRI ref 204837926
Cond 25HBC537AP03
Coil FX4DNF037L00
Efficiency
8.5 HSPF
AHRI ref 204837926
Efficiency 12.5 EER,16
SEER
Heating Input
Heating output
34600 Btuh @ 47°F
Sensible cooling
Lateritcooling
26250
8750
Btuh
Btuh
Temperature rise
Actual airflow
27 OF
1167 cfm
Total cooling
Actual airflow
35000
1167
Btuh
cfm
Airflowfactor
Static pressure
0.041 cfm/Btuh
0.30 in H2O
Airflowfactor
Static pressure
0.044
0.30
cfm/Btuh
in H2O
Space thermostat
Capacity balance point = 36 °F
Load sensible heat ratio
0.85
Backup:
Input = 8 kW, Output = 25920 Btuh,100 AFUE
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
-Fk- wrightne ft 2021-May-061133:15 Aft.w Right-Srite®Uriversal'2021 21.0.02 RSU23828 Page 1
aterslorel820BGL�Lot28BIk1Waterstorel820BGL.nQ Calc=MJ8 Frorft Door faces: E
-1- wrightsofts Right-JO Worksheet
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM
Job: Lot 28 Block 1 Waterstone182...
Date:
By: DCS
1
2
Room name
E>posed wall
Entire House
BDRM2
3
Room height
212.0 ft
10.0 ft d
36.0 ft
10.0 ft heaUwol
4
5
Room dimensions
Room area
1 835.0 iR
169.0 ft z 13.0 x 13.0 ft
Ty
Construction
number
U-value
(Btuh/ft-'o
Or
HTM
(Bluhfft2)
Area (ftz)
Load
Area (112)
Load
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/PiS
Heat
Cool
Gross
N/P/S
Heat
Cool
6
__.-__. _._.� __
W .. -- _ .16E-19ad_ -_. __ . _ _ . _"__ 0 049
Blkwall, stucco e# 0201
2A-2ov 0.330
.___-..
_._n
n
_ --
. _ _--1:4_2
5.83
_.._.-_
, T. 259
4.06
_ _
_.__ 20
660
-_- _
_ ._ 20
611
-
.._^ ..28
3561
-,_
_� 52
2481
_ _0
130
_ _
130
0 _ _�0
758
, �0
528
n
957
852
33
0 313
279
0
0 0
0
__.... 2A-2ov _0330
16B 19ad, _ _ _. _... _0.049
- -
e
957
1.42
852
' 2.59
----- -.16
- _ - -0
.. ..._ 156
__.. .. 139
_ 0
---
- - --0_0
_ 0
Blk well, stucco e# 0.201
2A-2ov 0.330
e
a
_
5,83
957
4.06
21.62
. _ _20
200
16
_ -_ . __20__
126
0
736
156
_ ._52
513
353
__ . _ _ 0
0
0
_ _ ._.. 0
0
0
_ ___ ._ _ 0
0
0
_ _ ,0
0
0
2A-2ov 0.330
a
957
21.62
16
0
156
353
0
0
0
0
213-2ty 0.330
a
957
11.58
7
7
67
81
0
0
0
0
2B-21v 0230
a
957
1359
14
11
130
185
0
0
0
0
----D ._._ -_ 0.600__e.._
---0.049
_s_.
,._17.40
..__17.58
259
_,._ _20
20
20._
20
_.._355._
359-_-.__..._0
52
_____. ___0.P__
0
0
W Blk well, stucco e# 0.201
2A-2ov 0.330
.
s
s
_. _.1A2
5.83
957
.
4.06
852
590
7
534
7
.=_,_ :28.-
3113
a ---
2168
- - 0
100
-- -` 0
100
v 0.
583
_ _.... ___0
406
2A-2ov
66
59
0
0
0
0
_ 0.330
s-
957
852
49
_ 49
469
418
0
0
0
0
W . _ 16B-19ad ; . _ _; _. 0049
Blk well, stucco e# 0.201
-W
w
142
5.83
`, 259
4.06
._ ..: 20
400
-- 20
317
_- ._. 28
1946
_ - 52
1286
- 0
130
- - --0
114
'- ' .A
663
- _ -0
461
10C-v 0550
w
1525
1620
18
18
285
2A-2ov 0350
2A-2ov_
w
w-
957
22.43
8.52
33
2
33.
313
289
733
0
16
0
1
0
156
0
367
_ .__._._0330
12C-Osw--- -__ _ _ _ --.-0091
.
_.
-- -2
2.64
_.,.._
. 121
.__.._.-._33
270,
U_."_-..
_.__27Q
-313
713
__--- 279
--- --__ -0
_ _.___..0
_ 0
0
C _ _ 16&30ad,_• ., __. _ 0032
09ti9--_-__6080
:-
0.93
1 69
_ ,1835
_ . 1835
1703
_____354
._,..3100
---_. __0
,._ _._ 169
._-----___0
.- _ ._. 1.69
.. 157
_____0
_ - 286
6
c) AED exajrsion
893
103
Envelope loss/gain
20647
14530
3349
2150
12
a) Infiltration
b) Room ventilation
3704
1035
691
193
0
0
0
0
13
Internal gains: Oocupants@
230
5
1150
0
0
Appliances/other
3900
300
Subtotal (lines6 to 13)
24350
20615
4040
2643
Less external load
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
15
Subtotal
Duct loads
24350
20615
0
4040
0
2643
17 %
28 %
4220
5777
17%
28 %
700
741
Total room load
Air required (dm)
28571
26392
4740
3384
1167
11671
194
150
Calculations approved bvACCAto meet all requirements of Manual J 8th Ed
�}+- wrigF�tsoTt^ �A Rigid-Sute®Universal 2021 21.0.02 RSU23828 2021-May-061123:15
Page 1
aterstone1820BGL\Lot28BIk1Waterstone1820BGL.rrp Calc=MJ8 FrontDoorfaces: E
-�- wrightsoft• Right-M Worksheet Job: Lot 28 Block 1 Waterstone182...
Entire House Date:
DEL AIR HTG, A/C & REFRIG. INC By: DCS
531CODISCOWAY, SANFORD,FL32771Phone:407-333-2665Fax: 407-333-3853 Web:WWW.DELAIR.COM
1 Room name BATH BDRM3
2 E)posed wall 6.0 It 13.0 ft
3 Room height 10.0 ft heaUmol 10.0 ft heaUmol
4 Room dimensions 13.0 x 6.0 ft 13.0 x 13.0 it
5 Room area 78.0 ftz 169.0 ftz
Ty Construction U-value Or HTM Area (ftz) Load Area z
number (Bluhfttz cq (Btuh/ftz) or perimeter ft(ft) Load
() (Btuh ) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
- - _ _ _
6 W 16619ad. _OA49 _ _n _ _ 1.42 _259 _ 0 _ _,` . 0 ..- - - 0 - -0 --- 0 - Q -__ -0
Elk aell, stucco ext 0201 n 5.83 4.06 60 60 350 244 _ 130 114 663 461
2A 2ov 0330 n 957 852 0 0 0 0 0 0 0 0
2A-2ov_.. - -, - -- 0.330 . n_ 957 _ 852 . --- --0 -- 0 0 - -- - 0 - ... - -16 0 _ .v -156 _._.. -_ 139
_..,
1.42 259 _ _ :0, _. _� 4 . _ ._ _. _0 ...__ _ _ 0 ._. _.:. _ ..9 _ _ .__ _0 __-----_ _ 0
Elk %tell, stucco ext 0.201 a 5.83 4.06 0 0 0 0 0 0 0 0
2A-2ov 0.330 a 957 21.62 0 0 0 0 0 0 0 0
2A-2ov 0.330 a 957 21.62 0 0 0 0 0 0 0 0
28-2fv 0330 a 9.57 11.58 0 0 0 0 0 0 0 0
2E-2M- 0.330 a 957 1359 0 0 0 0 0 0 0 0
11J0 _ .__ _0.600 - e._ 17.40 =- 17,58 . _ _. _ , 0 ....___ 0 - 0 0 .. _ 0 ---. _-_ _0 _. ..._ ._0. _.._.. _.._.. Q
W ...._ -16B 19ad.. ._0048 .:.s. 1,42 . .._;259 .-.: -_0 :...._-._0 _-. 0 .. .... _.-.-0 _. .... 0
Blk v,all, stucco e)d 0.201 s 5.83 4.06 0 0 0 0 0 0 0 0
2A-2ov 0.330 s 9.57 852 0 0 0 0 0 0 0 0
2A-2ov 0.330 s 957 852 0 0 0 0 0 0 0 0
_..-- - _ ._. _w. _ _ - -
16&19ad_ _ _.._ - -_. __0049 _ w_ _ 1., 259 _ _ 0 0 - 9 __.`0 ,,0 _ .._ 0 _ -__ 0 . -- __ 0
VVV���lll Blk wall, stucco ext 0.201 w 5.83 4.06 0 0 0 0 0 0 0 0
10C-v 0550 w 15.95 1620 0 0 0 0 0 0 0 0
2A-2ov 0.330 w 957 22.43 0 0 0 0 0 0 0 0
-- 2A-2ov_._ .-_ _ - 0.330 -w 957-...._8.52 - -.0 0
- - -- - - � - 0 --- ---- 0 0 - . 0 A
P . _ . 12C Osw-_--- - _ _. ._._0,091 _.- -----„_2,64 A 1,31- _ --- _-_0 ---.._ ,_ 0 . .-__- __0 . __._-_0 ---- _--_0 .-.._ ..-__0 -0
C- 16B 30ad : _.._. _ .. _. 0.032 - - -• 0.93 _.__ 1..69 78 78 _ _ 72 132 _._ .. 169 _._. _.. 1_69 157 286
F: _-_ . W( 0.989 - 28.68 _ ->0.00 - 78 -- _8 172 . -0 169 . -13 373 . -- - 0
6 c) AED excu sion -18
-56
Envelope loss/gain 594 357 1349 830
12 a) Infiltration 115 32 249 70
b) Room ventilation 0 01 0 0
13 Internal gains: Occupants@ 230 0 p 0 0
Appliancesrother 0 300
Subtotal (lines 6 to 13) 709 389 1598 1200
Less e#ernalload 0 0 0 0
Less transfer 0 0
0 0
Redistribution 0 0 0 0
14 Subtotal 709 389 1598 1200
15 Dud loads 17% 28 % 123 109 17 % 28 % 277 336
Total room load 832 498 1 T1875 1536
Air required (cim) 34 22 77 68
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed
�'f wrigtitsol<t^ �A Right-Sute®Universal 2021 21.0.02 RSU238282021-May-061133:15
...aterstone1820BGL\Lot28Blk1Waterstone1820BGL.np CaIc=MJ8 FrontDoorfaces: E Page
-�- wrightsoff Right-JO Worksheet
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3R53 Wah• W W W nrl nio enen
Job: Lot 28 Block 1 Waterstone182...
Date:
By: DCS
1
2
Room name
F�osedvIdl
DIN ING
DINING/FOYER FOYER
DENBDRM4
3
4
Room height
Room dimensions
ft
10.0 ft heat/mol
3.1.0 8
10.0 ft heat/cool
5
Room area
1.0 x 276.0 ft
13.0 x 13.0 ft
276.0 ftz
169.0 ftz
Ty
Construction
number
U-value
13tuh/ tz_
( fl
Or
HTM
(Btuh/ftz)
Area (ft)
Load
Area (ftz)
Load
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
I Cool
Gross
N/P/S
He
Cool
Gross
N/P/S
Heat
I Cool
- 4�_vu4y n 1'9L259 0 0 0 00.
Blk v�all stu000 ext 0 201 n 5.83 4 06 110 77 451 314 130 130 758 528
2A 2ov 0.330 n 957 852 33 0 313 279 0 0 0 0
2A 2ov _. 0 330 n_ 957 852 0 0 0 0 0 0 0 0
11 W 16&19ad_049 . en. .- 1.42 F, _2 59 0 0 0 .,' 0 0 ' Q - 0 0 Blk viell, stucco e# _ F Y0201 e 5 83 4.06 _ ;_ 70 29 _ 169 118 .k 130 97 567 395
2A-20v 0.330 a 9.57 21.62 0 0 0 0 16 0 156 353
2A-20v 0230 a 9.57 21.62 0 0 0 0 16 0 156 353
2B-2N 0.330 a 957 11.58 7 7 67 81 0 0 0 0
2B-2fv 0.330 a 9.57 1359 14 11 130 185 0 0 0 0
11,10 0.600 ,e _ 17.40 _ 17 58 _. 20 20 355 359 0
16B19ad- x w 0049.s_. 142 259 .,._ -,0 ___ _ 0 0 0, :.._ 0 _:..__.0 W Blk wall, stucco ext 0.201 s 5.83 4.06 0 0 ^0 0 50 50 291 203
2A-2ov 0.330 s 9.57 852 0 0 0 0 0 0 0 0
2A 2ov 0.330 s 957 852 0 0 0 0 0 0 0 0
16619atl' 0.049 . H- ._ 1„42 2S9 0 0 0 0 _ 0 _ c_0
VVV���lll Blk wall, stucco ext 0201 w 5 83 4.06 0 f ...T. ' 0 '0 -0 0 0 ._' .'.._.O 4:: o
10C-v 0550 w 15S5 1620 0 0 0 0 0 0 0 0
2A-2ov 0.330 w 957 22.43 0 0 0 0 0 0 0 0
0.330 w 957 8.52 _, 0 0 0 _„ 0 0 0 0 0
OA91 .._:w4 2,64 13I 70 . .,.. _ 70 __ ...,185 _92 ...R .. 00'_.0.
C 166 30ad _0 032 y... 023 1.69 276 276 256 . _ _ 466 169 , _ 169 157 , _. 286
7 _ . .
S,_... _....
6 c) AED excursion 100 116
Envelopeloss/gain 2642 1793 2975 2234
12 a) Infiltration 345 97 595 166
b) Room ventilation
0 0 0 0
13 Internal gains: Oocupantspa 230 1 230 0 0
Appliancestother 0
300
Subtotal (lines6 to 13) 2988 2120 3570 2700
Less external load 0 0 0 0
Less transfer
Redistribution 0 0 0 0
14 Subtotal 0 0 0 0
2988 2120 3570 2700
151
5 Duct loads 17% 28% 518 594 17% 28% 619 757
Total room load 3506 2714
Air required (cfm) 506 714 4189 3457
1
171 153
- Calculations proved bvACCAto meet all requirements of Manual J 8th Ed
2021-May-0611:33:15
Right-Sute®Udversal 2021 21:0.02 RSU23828
aterstone1820BGL\Lot28BIk1Waterstone1820BGL.np Calc=MJ8 FrontDoorfaces: E Page
-+'- wrightsoft°
Right-JO Worksheet
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM
1
2
Room name
Exposed wall
FAMILY RM
4
Room height
Room dimensions
13.0 It3
10.0 ft
heaV000l
5
Room area
13.0 x 22.0
286.0 ft2
ft
Ty
Construction
number
LlAdue
(Btuh/ft-9
Or
HTM
(Btuh/ft2)
Area (112)
Load
or perimeter (ft)
(Btuh)
Job: Lot 28 Block 1 Waterstone182...
Date:
By: DCS
MSTR BDRM
41.0 It
10.0 It heattwol
14.0 x 17.0 it
238.0 112
Area (ft2) Load
or perimeter (ft) (Btuh)
-Ul
Heat
Cool
6 W :_
VBlk
16619ad W._..
vdl, stucco ext
2A 2ov
_w :..0 049
0.201
W n
n
_u 1422
5 83
_ 259
4.06
..
0
28
0
0
0 100
100
583
0
406
0,330
n
957
852
0
0
0
0
0
0
2A 2ov
0.330
9
n
e.
957
8.52
0
0
0_
0
0,
0 0
0 0
0
Blk mall, stucco ext
2A-2ov
.._0,0
0.201
0,330
_
a
a
iA?
�5b3
957
_ ._ 259
4.06
21.62
w 20
-- 20
O J
0
. 28
0
0
__ 52
0
0
_.._ , .w0
0
0
. __
0
0
0; -0'-
0 0
.0
0
2A-2ov
0,330
a
957
21.62
0
0
0
0
0
0 0
0
2B-2fv
2B-2fv
0230
a
9.57
11.58
0
0
0
0
0
0 0
0 0
0
0
11J0
0.330
a
957
13.59
0
0
0 0
0
0 0
0
-,__
16B 1.9ad £--w=.._.
0600
F,, ," [9
_ ,e
_-'s.
1740
142
1758
,,.. 259
20
0
0 0
28
_-,_ 0
-, 0
Blk wall, stucco ext
2A-2ov
0.201
0,330
s
5.83
957
4.06
0
_ ..: _._.20
0 0
_5,2
0
__. 0
170
_ . _0
154
_ ,__ . w A
896
624
2A 2ov
s
852
0
0
0
0
0
0
0
W-..._,B
11k 19a
0230
0049;w_
s
957
142
852
0
0
_ 0
0
16
16
156
0
139
lk ald�
ml, stucco ext
10C-v
0.201
0550
w
w
_...
5.83
15.95
_.y259
4.06
1620
130
18
79
18
463
285
323
289
_
140
0
124
0
721
502
2A 2ov
2A2ov
0.330
w
w,
957
22.43
852
0
33
0
0
0
16
1
0
156
0
367
C
.._.
Osw4�
16B•30ad
_02W
0091131
_,._957
p
33
- 313
w
279
0
0
0
0
�_0
0
___ 0.
_
F _ _..
__ ,
22A WI .. _. _. _ :
0032
0 989
; `,`
0.93
8.68_0.00
_ 1 69
286
286
286
13
265
483
238
238
_ 221
--
._ _
402
-7
.. _373
: ...�
_:. _ 238
_'~ L h 41
1-
- 0
..
-
,
.,
,..
.�
._
,
v,.
... ..... .. ......
.ram , �.... , _
..,.
,.. _
�. __.
.. .a __
7 ... _.....
.._._..-......_.
,._.__......_
.._.. ,.,..__
' ,,,,..___
.._..-_.'_
_.... __.._
6
c) AED exaarsion
1024
16
Envelopeloss/gain
1813
2605
3909
2456
12
a) Infiltration
b) Room ventilation
403
113
787
220
0
0
0
0
13
Internal gains: Occupants@ 230
3
690
1
Appliances/other
230
600
600
Subtotal (lines 6 to 13)
2216
4007
4696
3506
Less e)dernal load
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
0
06
15
Duct loads
17%
28%
2210
384
4000
1123
179/.
28%
469
814
3506
982
Total room load
Airrequired (dm)
2606
5227
510
5225
4488
8
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed
*^ wrigl�tsoft- A Right-Sute81.1dversa12021 21.0:02 RSU23828 2021-May-061133:15 aterstonelB20BGL\Lot28BIk1Waterstorel820BGL.rLp Calc=MJ8 FrontDoorfaces: E Page 4
-�- wrightsoft®
Right-M Worksheet
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM
1
Room name
M
BATH
'
2
3
Exposed wall
Room height
ft
4
Room dimensions
10.0 ft heaUcool
5
Room area
1.0 x 119.0 It
Job: Lot 28 Block 1 Waterstone182...
Date:
By: DCS
M WIC
Oft
10.0 It heaU000l
7.0 x 7.0 It
.....,,
4y.0 IF
Ty
Construction
number
U-value
(Btuh/ft-`)
Or
HTM
(Btuh/ftz)
Area (ftz)
Load
Area (ft2)
Load
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6 W
16B 19a�1_?
Blkwall,stuccneM
2A-2ov
OA49
0.201
.. 0
n
1,42
5.83
�y2,59
4.06
_a _ .0
0"
0
_ 0
_.� _r _:
0 '� 0
0 ��`' p
p
p
0
p - -0
0 _ _----- .0,
0
0.330
n
957
852
0
0
0 0
0
2A 2ov
16B-_19,s
, 0330
n
me:_.0.
957
852
0
_0
0 _ 0
0
0
0 _0
O
0 0
Blkwall,stucoo ext
2A-2ov
0.201
0,330
a
a
5.83
957
4.06
21.62
0
0
0
0
0.v,_ 0
0 0
00
0
___ _•._
0 0
n,_0
0
2A`2ov
0,330
a
957
21.62
0
0
0 0
0
0 0
0
2B-2fv
2B-2fv
0.330
a
957
11.58
0
0
0 0
0
0 0
0
11J0 _,
0230
600
a
@
9.57
17.40
13.59
1758
0
0
0
0
0 0
0
0
0
0
W.0
16619ad'�.. _
Blk gall, stucco ext
2A-2ov
y;0
. 0049_,s`
0.201
_
s
7-42
5.83
_
w�2�9
4.06
_ __
._u,. :.; 0
120
_.A_ __ 0_,
113
x. 0'
659
0 0
�._= ._ 0
459
_ __ _ 0
:- v _ , 0
0
0
0
0
0
_ _ 0
0
___ 0
:_ Q
0
0.330
s
957
852
7
7
66
59
0
2A 2ov
0.330
s
9.57
852
0
0
0
0
0
0
0
0
W._. .._16B19aii_259
1 O v�ell, stucco ext
10C-v
_.
0.201
0550
w
w
5.83
15.95
4.06
1620
0
0
0
0
_0
0
0
0
0
0
0
0
0
0
0.
o.
2A-2ov
0.330
w
957
22.43
0
0
0
0
0
0
0
0
0
0
C
2A 2oy_, _.
0 330
_w,
9.57
___264
852
, 1,31
0
_', 0
0
0
0
0
0
.. _ ,--- , _0
0
. _ _ w._. p
0
0
F
16B30ad
22Atpl:_
0032
0989
0.93
8.
169
'000
119
119
110
201
_ 49
49
45
_..
83
_. .119
W _.�;`.12
_.M 344�f�
__ 0v
, 49.E
�_.0_.._
_0
.
_
_
Hr
,.
,
4
.
6
c) AED excursion
35
4
Envelope losstgain
1180
684
45
79
12
a) Infiltration
b) Room ventilation
230
64
0
0
0
0
0
0
13
Internal gains: Oocupants@ 230
0
0
Applianoestother
0
0
0
0
Subtotal (lines 6 to 13)
1410
748
45
79
Less external load
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
0
0
0
0
15
Duct loads
17%
28%
1410
244
748
210
45
79
17%
28 %
8
22
Total room load
Air required (cfm)
1655
958
52
1011
68
421
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed
- wrigF�tsoft� Riga-Sute®Uriversal 2021 21.0.02 RSU23828 2021 -May-06 1133:15
aterstone1820BGL\Lot28Blk1 Waterstore1820BGL.np Calc= W8 Front Doorfaces: E Page 5
-�- wrightsoft, Right-M Worksheet
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM
Job: Lot 28 Block 1 Waterstone182...
Date:
By: DCS
2
Room name Exloosed wall
KrrCHENMOOK
LAUNDRY
3
4
Room height
Room dimensions
29.0 ft
10.0 ft heaU000l
6.0 ft
10.0 It heaHwol
5
Room area
246.0 ftz 1.0 x 246.0 It
6.0 x 6.0 ft
36.0 ftz
Ty
Construction
number
U-value
(Btuhfltz q
Or
HTM
(Bluh/ftz)
Area (ftz)
Load
Area (ftz)
Load
or perimeter (ft)
(Btuh)
I or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P5
Heat
Cool
6
V)1
Blk well, stucco ex<
2A 2ov
0.201
0.330
n
5B3
4.06
----
0 0
0 ' 0
-
O
0
0 -
0 0
1�.-�G
n
957
8.52
0 0
0 0
0
D
2A_2oy_ _ _ _
Blk well, stucco eM
- .__ - - -
0.201
a
_ 1,42
5.83
._ . ,_259
4.06
. _4
- - -0
0 0
__ .
0 - 0
0 0
-�
- --
-- _-.__..
0 -- -
0 0
0 - -- _ 0
2A-2ov
0.330
a
957
21.62
0 0
0
0
0 0
0
2A-2ov
0.330
a
957
21.62
0
0
0 0
0
2B-2fv
0 0
0 0
0
0 0
0
26-21v
0.330
0330
a
a
957
9.57
11.58
1359
0 0
0 0
0 0
0
0
0
0
16B19ad_
__ 0.600
e__
. - 17.40
1.42
1758
_ 0
_._--.___. 0
-
-- 0
0 0
_ 0
0
_ 0
0
_0
0
0
0
0
-- .0
Blk well, stu000 ext '
2A-2ov
---0,049
6.201
0230
_._s_
s
.,..
5.83
,:__2,59.
4.06
- . __0
150
._.._._. 0
117
0.
684
_. 0
476
_ 0
0
0
_ -'p
0
' p
0
2A-2ov
s
957
852
0
0
0
0
0
0
0
0
W
-
0.330
-
_ -0049
s
_ 957
1.42
852
;
33
p
_ . _. _ 33
313
_ --
279
_. _ -.---
0
_-- -- .
_. 0
0
0
_ --
Blk well, stucco ext
10C-v
-
O'201
0550
_,w
w
w
- _
5.83
15.95
,259
4.06
1620
._ _..
0
0
0
0
- "0
0
0
0
0
0
0
0
0
0
" ' 0
0
2A-2ov
2A 2ov.
0.330
w
957
22.43
0
0
0
0
0
0
0
0
_...
C
-
16630ad
_._.__764
852
--140
0
. 0
._.__
_8
_
•-_ 0 ,
91
.-.__002.98390
.
-__-
-_-- -957
--0
28.68
__
-6.
_246
_A.__
2
_
6
_----_-_•--,_0
332A
_-_-
- .__-
-
...-___..-012C0
__--__._36
__.__._-_„_._
6
c) AED excursion
-118
33
Envelope loss/gain
2426
1236
364
106
12
a) Infiltration
b) Room ventilation
288
80
0
0
0
0
0
0
13
Internal gains: Occupants@ 230
0
0
0
Applianoesrother
0
1200
600
Subtotal (lines 6 to 13)
2714
2516
364
706
Less extemal load
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
0
0
0
0
15
Duct loads
17°/
28%
2714
470
2516
705
17 %
28 %
364
63
706
198
Total room load
Air required (dm)
3184
3221
417
04
940
Calculatons approved bvACCA to meet all requirements of Manual J 8th Ed
,` �� wr➢ghlsoTt^ �A Right-Sute®Uriversa12021 21.0.02 RSU23828 2021-May-061133:15
aterstone1820BGL\Lot28BIk1Waterstone1820BGL.rLp Calc=MJ8 FrontDoorfaces: E Page
-1- wrightsoft® Duct System Summary
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM
For: ADAMS HOMES
5340 Lugo Street, Fort Pierce, FL 34951
Job: Lot 28 Block 1 Waterston...
Date:
By: DCS
External static pressure
Heating
0.30 in H2O
Cooling
0.30 in H2O
Pressure losses
0.06
in H2O
0.06 in H2O
Available static pressure
0.24
in H2O
0.24 in H2O
Supply/return available pressure
0.120/0.120
in H2O
0.120/0.120 in H2O
Lowest friction rate
0.212
in/100ft
0.212 in/100ft
Actual air flow
1167
cfm
1167 cfm
Total effective length (TEL)
113 ft
Name
Design
(Btuh)
Htg
(cfm)
Cig
(cfm)
Design
FR
Diam
(in)
H x W
(in)
Duct
Mat
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
BATH 2
h 832
34
22
0.278
4.0
Ox 0
VI Fx
16.3
70.0
BDRM 2
h 4740
194
150
0.258
8.0
Ox 0
VIFx
22.9
70.0
BDRM3
h 1875
77
68
0.305
6.0
Ox0
VIFx
8.6
70.0
DENBDRM4
h 4189
171
153
0.288
7.0
Ox0
VIFx
13.2
70.0
DINING/FOYER
h 3506
143
120
0.314
7.0
Ox 0
MR
6.5
70.0
FAMILYRM
c 5130
106
227
0.233
8.0
Ox 0
VIFx
17.9
85.0
sti
KrrCHEN1NOOK
c 3221
130
142
0.228
7.0
Ox 0
VIFx
20.1
85.0
sti
LAUNDRY
c 904
17
40
0.223
4.0
Ox 0
VIFx
22.7
85.0
sti
M. BATH
h 1655
68
42
0.224
5.0
Ox 0
VI Fx
22.2
85.0
sti
M. WIC
c 101
2
4
0.225
4.0
Ox 0
VIFx
21.9
85.0
sti
MSTRBDRM
h 5510
225
198
0.212
8.0
Ox0
VIFx
28.2
85.0
sti
Name
Trunk
Type
Htg
(cfm)
Cig
(cfm)
Design
FIR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Duct
Material
Trunk
sti
PeakAVF
549
655
0.212
612
14.0
0 x 0
VInIFIX
: * wrightsoft® 2021-May-061133:16
M ,.•, Right-Sute®Uriversal 2021 21.0.02 RSU23828
aterstone1820BGL\Lot28Blk1Waterstone1820BGL.np Calc=MJ8 FrontDoorfaces: E Page1
Name
Grille
Size (in)
Htg
(Cfm)
Clg
(cfm)
TEL
(ft)
Design
FIR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Mat
Trunk
rb1
Ox 0
1167
1167
0
0
0
0
Ox 0
VIFx
wrightsofta 2021-May-0611:33:16
Rigtd-Sute®Udversal 2021 21.0.02 RSU23828JCCK Page 2
aterstone1820BGL\Lot28BIk1Waterstone1820BGL.nQ Calc=MJ8 FrontDoorfaces: E
2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Lot 28 Block 1 Waterstone 1820 BGL Builder Name: ADAMS HOMES
Street: 5340 Lugo Street Permit Office:
City, State, Zip: Fort Pierce , FL , 34951 Permit Number:
Y
Owner: Jurisdiction: 661000
w
Design Location: FL, ST_LUCIE CO INTL
=
U
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
requirements
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
Breaks or joints in the air barrier shall be sealed.
Ceiling/attic
The air barrier in any dropped ceiling/soffit shall be aligned with
the insulation and any gaps in the air barrier shall be sealed.
The insulation in any dropped ceiling/soffit
Access openings, drop down stairs or knee wall doors to
shall be aligned with the air barrier.
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
Knee walls shall be sealed.
with a material having a thermal resistance of R-3
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/doorjambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
(including
The air barrier shall be installed at any exposed edge of
insulation.
Floor framing cavity insulation shall be installed to
above -garage
maintain permanent contact with the underside of
and cantilevered
subfloor decking, or floor framing cavity insulation
floors)
shall be permitted to be in contact with the top side
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawispace wall
.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
as.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the finished surface.
thermal envelope shall be air tight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
Shower/tub
on exterior wall
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
a. In addition. insoectinn
lates and w;;Il, or
of Inn wain shau ha „ tk--',...:..:...... _r'__ .
_ _.._.. ..,.,, u— Fl vial l la ul
5/6/2021 11:43 AM EnergyGauge® USA 7.0.d0 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
FORM R405-2020
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the
Residential Simulated Performance Alternative shall include:
❑ This checklist
❑ Form R405-2020 report
❑ Input summary checklist that can be used for field verification (usually four pages/may be greater)
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page)
❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4
allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to
comply with Section C402.5
❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed
2020 Duct Leakage Test Report - Performance Method (usually one page)
5/6/2021 11:42:53 AM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Buildina Code. Enerav Con_qPrvatinn 7th 1=r itinn
Jurisdiction: 661000
Permit #:
Job Information -
Builder: ADAMS HOMES Community: Lot: 28-1
Address: 5340 Lugo Street
City: Fort Pierce State: FL Zip: 34951
Air. Leakage TeStr Results Passing reggltS,MUSt meet either -the Performance; Prescriptive, or ER1 Method
OPRESCRIPTIVE METHOD The building or dwelling unifshall be tested Jand verified.as_having an air leakage rate of not exceeding 7 air"
changes per.hour at a.pressure of-02'inch w.g: (50 Pascals) in'Climate Zones 1,and 2.-'
;$Q ,PERFORMANCE or ERI METHODrThe build !n6 ordweiling unitshall be tested and verified as, having an air leakage rate of!not exceeding'
the,selected;ACH(50).4ue,"as shown on Form R405-2020 (Performance),,or R406 2020 (ERI), section labeled as infiltration;.sub section ACH50.
- ACH(50) specified on Form'R405 2020 Energy Ca/c (Perforrriancej or-R406-2020 (ERO: ',' 7.000
x 60 _ 18200 = Method for calculating building volume:
CFM(50) Building Volume ACH(50)
Q Retrieved from architectural plans
F� PASS
Code software calculated
ElWhen ACH(50) is less than 3, Mechanical Ventilation installation Q Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester:
Printed Name of Tester:
License/Certification #:
Date of Test:
Issuing Authority:
5/6/2021 11:43:49 AM EnergyGaugeO USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 7th Edition (2020)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
F7RESS: 5340 Lugo Street Permit Number:
Fort Pierce , FL , 34951
tvtAuvUH i UKY KtQUIKEMENTS -See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
SECTION R402 BUILDING THERMAL ENVELOPE
❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and
R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
5/6/2021 11:43 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential,
R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
R403.1 Controls.
SECTION R403 SYSTEMS
R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system,
including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise
sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire
system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn =
duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41"C)
or below 55°F (13"C) shall be insulated to a minimum of R-3.
R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are
installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall
be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for
circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The
controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no
demand for hot water.
R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when heated water is used in the occupancy.
5/6/2021 11:43 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3'% inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to 60°C).
R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of
combustion types of service water -heating systems to be turned off.
R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TMA, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment.
❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based
on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation
methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the
outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design
conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other
factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical
ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have
an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is
installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN FFFIrArV
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMU IV
(CFM)
HRV or ERV
Any
1.2 cfm/watt
Any
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916
5/6/2021 11:43 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
2. calculated total sensible load but not less than 80 percent of that load.
When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
El R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403.
R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -Fred heaters shall not be equipped with continuously burning ignition pilots.
R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
5/6/2021 11:43 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5
R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
El efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
R403.11 Portable spas (Mandatory). The energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
nR403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements:
1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house
is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day.
2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air.
3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13,
conform to the following requirements:
1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct.
2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct.
3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an
efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
5/6/2021 11:43 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5