HomeMy WebLinkAboutPROJECT INFORMATION: Manual S Compliance Report Job: Lot 183 Phase 3 Watersto... wrightsoft Date: Entire House By: FLETCH DEL -AIR HEATING & AIR CONDITIONING w 531 CODISCO WAY, SANFORD, FL 32771 Phom:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM License: CMC 1249777 Project• • w For: ADAMS HOMES 5322 Vespera Street, Fort Pierce, FL 34951 Cooling Equipment Design Conditions Outdoor design DB: 90.4 OF Sensible gain: 21876 Btuh Entering coil DB: 77.7°F Outdoor design WB: 77.4OF Latentgain: 4380 Btuh Entering coil WB: 63.9°F Indoor design DB: 75.0 OF Total gain: 26256 Btuh Indoor RH: 50% Estimated airflow: 947 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNB031 L00 Actual airflow: 947 cfm Sensible capacity: 22839 Btuh 104% of load Latent capacity: 4511 Btuh 103% of I oad Total capacity: 27349 Btuh 1040% of load SHR: 84% Design Conditions Outdoor design DB: 41.0 OF Heat loss: 24382 Btuh Indoor design DB: 70.0 OF Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNB031 L00 Actual airflow: 947 ' cfm Output capacity: 26646 Btuh 109% of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 947 cfm Output capacity: 5.9 kW 83%of load Temp. rise: 19 OF Meets all requirements of ACCA Manual S. Entering coil DB: 69.0OF Capacity balance: 37 OF Economic balance: -99 OF y � wrightsoft® 2021-JU-1515:55:48 �� Rig11-Sdte®Uriversal2021 21.0.07 RSU23828 Page 1 �'�...rstone1512BGRS\Lot183Pfs3Waterstore1512BGRS.nQ CaIc=MJ8 Hoisefaces: S • Job: Lot 183 Phase 3 Watersto... •- wrightsoft® Component Constructions Date: Entire House By. FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM License: CMC 1249777 iLroject intormation For: ADAMS HOMES 5322 Vespera Street, Fort Pierce, FL 34951 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Inti, FL, US Indoor temperature (T) 70 75 Elevation: 26 ft Design TD (T) 29 15 Latitude: 28 ON Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (grflb) 2.4 56.9 Dry bulb (T) 41 90 Infiltration: Daily range (T) - 15 (L ) Method Simplified Wet bulb (T) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions or Area u-value tnsul R Htg HTM Loss Cig HTM Gain ' W Btuh/ftz°F ftz°FBtuh Bluh/fF Btuh Btuh/ft' Btuh Walls Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh n 267 0.201 4.1 5.83 1555 4.06 1083 e 323 0.201 4.1 5.83 1884 4.06 1313 se 8 0.201 4.1 5.83 46 4.06 32 s 112 0.201 4.1 5.83 650 4.06 453 sw 8 0.201 4.1 5.83 46 4.06 32 W 434 0.201 4.1 5.83 2529 4.06 1762 all 1151 0.201 4.1 5.83 6711 4.06 4675 Partitions 12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int 278 0.091 13.0 2.64 734 1.31 364 fnsh, 2'lx4"wood frm, 16" o.c. stud Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1 /4" gap, 1/8" n 30 0.330 0 9.57 287 8.52 256 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 6.7 ft overhang (5 ft window ht, 0.83 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1 /4" gap, 1/8" n 23 0.330 0 9.57 222 8.52 198 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang (5.25 ft window ht, 0.83 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1 /4" gap, 1/8" n 33 0.330 0 9.57 313 8.52 279 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang (5.3 ft window ht, 0.83 ft sep.); 6.67 ft head ht 10C-v: 2 glazing, dr low-e outr, air gas, vnl frm mat, dr innr, 1 /4" gap, 1/8" a 18 0.550 0 16.0 285 16.2 289 thk; NFRC rated (SHGC=0.70); 13 ft overhang (6.7 ft window ht, 1.3 ft sep.); 6.67 ft head ht 2A-2om: 2 glazing, clr outr, air gas, mtl no brk frm mat, dr low-e innr, 14' e 7 0.330 0 9.57 66 23.2 159 ' gap, 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1 ft overhang (3.17 ft window ht, 0.83 ft sep.); 6.67 ft head ht wrightsoft- 2021-Jt1-1515:55.48 .w •�• a•. �"• , gym• m Right-Slite®Uriversal 2021 21.0.07 RSU23828 ACCK Page 1 rstone1512BGRS\Lot183Phs3Waterstone1512BGRS.rLp Calc=MJB Housefaces: S 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr, innr, 1/4" gap, 1/8" se 10 0.330 0 9.57 96 15.8 158 • thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1 ft overhang (5 ft s 15 0.330 0 9.57 144 8.34 125 window ht, 1 ft sep.); 6.67 ft head ht sw 10 0.330 0 9.57 96 15.8 158 all 35 0.330 0 9.57 335 12.6 441 2B-2fv: 2 glazing, dr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" s 3 0.320 0 9.28 28 9.57 29 thk; NFRC rated (SHGC=0.31); 50% drapes, medium; 7.33 ft overhang (1 ft window ht, 0.75 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" w 10 0.330 0 9.57 93 22.8 223 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang (3.17 ft window ht, 1 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" w 16 0.330 0 9.57 156 23.0 376 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang (5.3 ft window ht, 1111 sep.); 6.67 ft head ht Doors 11 JO: Door, mtl fbrgl type s 20 0.600 6.3 17.4 350 17.6 353 11 DO: Door, wd so type n 18 0.390 0 11.3 202 11.4 204 Ceilings 1613-30ad: Attic ceiling, asphalt shingles roof mat, r,30 cell ins, 1/2" 1580 0.032 30.0 0.93 1467 1.69 2670 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 192 0.989 0 28.7 5519 0 0 1 - wrightsc ft® 2021-JU-151555:48 �A .�,•t•a•,.b�«...,,�mam Right-Sute®Uriversa1202121.0.07RSU23828 Paget rstone1512BGRS\I.ot183Pts3Waterstone1512BGRS.np Calc=W8 Hoisefaces: S m Project Summary wrightsoft 1 rY Job: Lot 183 Phase 3 Watersto... Date: Entire House By. FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Licerse: CMC 1249777 Project• • For: ADAMS HOMES 5322 Vespera Street, Fort Pierce, FL 34951 Notes: RVSD 8-17-15 JA L. S. 7-15-21 VWK Design Information Weather: St Lude Cc Inti, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 19506 Btuh Structure 14602 Btuh Ducts 4875 Btuh Ducts 7274 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh none (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 24382 Btuh Use manufacturer's data y Rate/swin multiplier 1.00 Infiltration EquipmenKensiple load 21876 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2548 Btuh Ducts 1832 Btuh Central vent (0 cfm) 0 Btuh Heating Cooling Area (none) (ft2) 151151g Equipment latent load 4380 Btuh Volume (ft3) 13571 13571 Air changes/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 26256 Btuh Equiv. AVF (cfm) 86 45 Req. total capacity at 0.75 SHR 2.4 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER Trade CARRIER Model 25HBC530AP03 Cond 25HBC530AP03 AHRI ref 204840289 Coil FX4DNB031 L00 AHRI ref 204840289 Efficiency 8.5 HSPF Efficiency 12.5 EER,15 SEER Heating Input Sensible cooling 21300 Btuh Heating output 28200 Btuh @ 470F Latentcooling 7100 Btuh Temperature rise 27 OF Total cooling 28400 Btuh Actual air flow 947 cfm Actual air flow 947 cfm Airflowfactor 0.039 cfm/Btuh Air flow factor 0.043 cfm/Btuh Static pressure 0.40 in H2O Static pressure 0.40 in H2O Space thermostat Load sensible heat ratio 0.83 Capacity balance point = 37 OF IBackup: t = 6 kW, Output = 20238 Btuh,100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed C -rk 2021-JU-151555:48 Bight-Sute®Uriversa12021 21.0.07 RSU23828 Page 1 rstone1512BGRS\Lot183Pts3Waterstore1512BGRS.nQ Calc=MJ8 Horsefaces: S - wrightsoftt Right-M Worksheet Jab: Lot 183 Phase 3 Waterston 1... Entire House Date: DEL -AIR HEATING &AIR CONDITIONING By: FLETCH 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM License: CMC 1249777 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Entire House 192.4 ft 9.0 ft 1516.0 ftz WIC 8.0 ft 83 ft heaVcool 1.0 x 41 B ft 41 B ftz Ty Construction number U-value (Btuhfit -fl Or HTM (BtuhRtz) Area (ft2) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (it) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PiS Heat Cool 6 1 1 _ -- yI Vy L—�G R C BlkHell,stu000eid -- 2A 2ov 2A-2ov Blk wall, stucco ext 10C-v 2A2om BlkMl stuccoeM .2A2ov___.. _.� _ _. Blk Ml, stucco eM 2A-2ov 213-2ty 11J0 Blkvall,stu000eiQ- _ Blk u%all, stuao ext 2A-2ov 2A 2ov 12C-0sv .1I __.__ ___ _...._.. 1613-30ad - 0201" 0330 ;,0330 0.201 0550 0201 _ _; ,0330 0.201 0230 0320 0.600 __ --0201 0201 0330 0330 0091 ..__.__0390 0.032 n583 n , n a a e_ se :wse s s s _ s sw w w w - .w.n_ 957 9S7 5.83 1525 957 �5.83 _957_ 5.83 957 928 17.40 : 583 957. 5.83 9S7 9.57 264 11 39 0.93 4:06 8S2 852 __ 852 4.06 1620 2320 4.06 .. -1581 4.06 834 957 17.58 4A6 1581. 4.06 22B3 22.98 131 _ 11.43 1.69 `,353 30 23 348 18 7 18 _ .. 10 150 15 3 20 460 10 16 296 _____,_ _18 1580 1516 -267 0 0 0 323 18 0 8 _.. __ 1 112 13 3 20 434 0 0 06. ___._4 18 1580 _ 192 �T1555 287 222 , 313 1884 285 66 ._ u 96 650 144 28 350 _ 98 2529 93 156 1083 256 ', 198 .m_279 1313 289 159 y 0 0" 0 , - _ 0 0 0 0 0 0 0 . 0 0 0 -' 0 0 0 0 0 0 0 ._. _. 17 0 0 0 _0 0_a 0 0 0 4 169 0 40 0 � o 0 -'# '--0 0 0 0 ,._0 12 0 0 0 __�._,_O 0 0 0 _ _ 84 73 _Q. �. 158 453 125 29 353 1762 223 376 - 364 ._.:_-._204 2670 _ _., ...,MO 3 0 0 0 _ .0 0 0 0 .0. 43 _ .__ 0 3 0 0 0 , v_,0 __ 0 0 _ _. 0 _ .�'0 43 734 '_.__.. _202 1467 excursion 0 c) AED -5 16 Envelope losstgain 16767 10516 455 163 12 a) Infiltration b) Room ventilation 2739 0 766 0 6 0 2 0 13 Internal gains: Occupantspa 230 Applianoes/other 4 920 2400 0 0 0 Subtotal (lines6 to 13) 19506 14602 461 165 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 25 % 50 % 0 0 0 19506 4875 0 0 0 14602 7274 259/6 50 % 0 0 0 461 115 0 0 0 165 82 Total room load Air required (cfm) 24382 9471 21876 947 576 221 247 11 Calculations approved byACCAto meet all requirements of Manual J 8th Ed -*- wr➢gf�tso4ft^ A _ RigM-Sute®Universal 2021 21.0.07 RSU23828 2021-JU-151555:48 ...rslone1512BGRS1Lot183Phs3Waterstore1512BGRS.rtp CaIc=MJB House faces: S Page 1 -�- wrightsoft° Right-M Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Pfone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM License: CIVIC 1249777 Job: Lot 183 Phase 3 Waterston 1... Date: By: FLETCH 1 2 3 4 5 Room name WATH Exposed wall 175 It Room height 8.7 ft heatbool Room dimensions 1.0 x 136.0 It Room area 136.0 ft2 WC 4.0 It 9.0 It heat/cool 1.0 x 20.3 It 202 ft2 Ty Construction number U-value (Btuhft2 F� Or HTM Area (ft') Load (Btu"2) or perimeter (ft) (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/Pi3 Heat Cool Gross N/P/S Heat Cool 6 11 V)! R C BIk wall, stucco eM 2A 2ov 2A 2ov 2A-2ov, ,�.�_ _ '� 0.201 0.33o 0230 ____QX0 0201 0550 0.330 0201 ..__.a0.330 0.201 0.330 0.320 0.600 yU201 _._ �_0330 0201 0.330 0,330 "0091 _0.390 0 032 '- 0 0" 0 32 0 0 0 0 0 0 0 .__ 0 ___ 0 0 ._ - 0 0, 0 22 .___-. 20• µ0 0 0 32 0 0 01 0 0 0 0 _ -0 0 0 0 0 0 - y 22 _4 7. - 0 0 0 187 0 0 -y0 0 0 0 0 O 0 0 0 �y, w 0 �21 �_:115, _.. p 0 0: 130 0 0 76 0 0 0 0 , 0 0 0 0 38 � a : n ` n n _ n_Y a a �e_ 6 .,se_ s s s s `_S sw: w w w ` - .n._ 53 957 957 _9.57_0 5,83 15.95 957 583 _._._:957. 5.83 957 928 17AO 5.83 _._.957 5,83 957 957 2.1i4 0.93 4.06 0 852 0 852 0 4.06 96 1620 0 2320 7 4.06 - 0 _. 15.8.1 .u,0 4.06 6 8,34 0 957 0 1758 0 4A6 __ :1581 .__ _M O 4.06 0 22.83 0 22.98 0 131 44 1.69 147 0,._.1_ M.J% - 0 0 0 0 0 0 a _ y 89 y' " 520 0 0 0 66 0 0 _ .,�_._._0 _0 6 32 0 0 0 0 0 0 w_ 0 0 0 0 0 0 0 0 44 __- 116 147 136 . _., . 18 . _. b02 M } 0 0 0 362 0 159 - 0 22 0 0 0 ; 0 _-- _._-0 0 0 0 T" _ _58 248 .,_ 0 Blk wall, stucco ext 1OC-v 2A 2om_ BIkviall,i5oo. oeM 2A2ov_._.._,__,__._ . Blk wall, stucco ext 2A-2ov 2B-2fv 11J0 Blkwall,stu000ext _2A2oy --__ Blk wall, stucco ext 2A-2ov 2A 2ov 12G Osw 16B-30ad _ 6 c) AED excursion 26 -5 Envelope lossrgain 1372 876 322 163 12 a) Infiltration b) Room ventilation 207 0 58 0 65 0 18 0 13 Internal gains: Occupants@ 230 0 Appliancestother 0 0 0 0 0 Subtotal (lines6 to 13) 1578 933 387 181 14 151 Less extemalload Less transfer Redistribution Subtotal Dud loads 25 % 0 0 0 1578 50%1 394 0 .0 0 933 465 25% 50 % 0 0 0 387 97 0 0 0 181 90 Total room load Air required (dm) 1973 -n 1398 61 484 19 271 12 Calculations approved byACCAto meet all requirements of Manual J 8th Ed "�- wr➢ghtsoft^ A RigH-SriteOUriversal2021 21.0.07 RSU23828 2021-JU-1515P.age42 -➢ rstone1512BGRS\LotiB3Phs3Waterstone1512BGRS.np Calc=MJ8 Housefaces: S -�- wrightsoft® Right-JO Worksheet Job: Lot 183 Phase 3 Waterstone 1... Entire House Date: DEL -AIR HEATING & AIR CONDITIONING By: FLETCH 531 CODISCO WAY SANFORD, R_ 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM License: CIVIC 1249777 1 2 3 4 5 Room name Bposecivall Room height Room dimensions Room area MBR 35b It 8.6 ft heat/000l 135 x 165 It 222.8 ft' LAU 6.0 ft 8.0 It heaf/oocl 1.0 x 56.0 ft 56.0 ft2 Ty Construction number U-value (Btuh/ftzf Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 BI'k viall, stucco ext 2A-2ov Blk mall, stu000 ext 10C-v 2A2om �._ BIk viell, sN000 _ext___ .2A2ov:___----.:_ .._._w::0330 Blk %all, stu000 ext 2A-2ov 213-2fv 11J0 glkxell,sW000eM, Blk wall, stu000 eM 2A-2ov 2A-2ov 12C Osw _.. ._.______ 1613-30ad �.._. 0 201 0.330 'v 0.201 0550 0330 0201 0201 0330 0320 0.600, '' `0201 0.201 0330 0.330 - - 0091 ---.0390_-n_. 0.032 __...:.0989—;_•„--�28_68 n n a a __e- se _•ee:..._-_:_957 s s s s sw w w w - r, 5.83 957 9S7 5..83 15.95 957 5.ti9 5.83 957 928 17.40 5,83 5.83 957 957 264 -. ..1131,__ 93 0..69 4.06 - T�852 852 4.06 1620 2320 408 _ _„_.15b1 4.06 834 957 17.58 4'.O6 4.06 22b3 22.98 13'1 1143 1 0,00 116 , 33 _._._. 0 132 0 0 0 _ _'._0 0 0 0 0 — _ - 0 .___ Q 44 0 0 0 ._. 0 238 ___-::.'223 84 _�, 0 w__ 0 132 0 0 0 _: _0 0 0 0 0 0 44 0 0 0 ._'__0 238 _-----�36-r�_,�1018:.__-__�_0�_ 488 _u ' _ 0 313 769 0 0 � 0 _.-.;5.0 0 0 0 _ 0 0 __0 256 0 0 0 .__. __0 221 340 01 0 w._ ' 279 536 0 0 0 0 0 0 0 _ _ .__ 0 0 __�0 179 0 0 0 _.'_<_.. 0 _ 402 .y0' _ 0 �_ J_0 0 0 0 0 w- 0 0 0 0 0 _ t1 __—A 0 R _ _�._0 0 0 0 0 ' � 0 ` _ _d._0 0 0 0 0 - 0 0 0 ._ 0 56 _ - 0 0 _ . _� 0 0 0 0 �..___u _:0..__. 0 0 0 0 —_- 0 0 0 0 ._. _ _ .127 Q 52 , .0 0 0 0 0 _ 0 ____0 0 0 0 __ 0 �0 -- ---- 0 0 0 63 95 V Y` (L�� V)/ R _-_. __11D0:� C F_ 0 0 _ 0 _.__ _0'__---:::0_:__— 56 �56,w excursion _75 -21 6 c) AED Envelope losstgain 3065 1660 351 137 12 a) Infiltration b) Room ventilation 595 0 166 0 0 0 0 0 13 Internal gains: Occupants@ 230 Applianoes/other 1 230 600 0 0 600 Subtotal (lines 6 to 13) 3660 2656 351 737 14 151 Less external load Less transfer Redistribution Subtotal Duct loads 25 % 50 % 0 0 0 3660 915 0 0 0 2656 1323 25 % 50 % 0 0 0 351 88 0 0 0 737 367 Total room load Air required 4575 178 3979 172 438 17 1104 48 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -*- wrigtitso�f�t^ Right-Sute®Uriversal 2021 21.0.07 RSU23828 2021 16 151 Page 3 rstone1512BGRS\Lot183PFs3Waterstone1512BGRS.np Calc=MJ8 Housefaces: S 9 - wrightsoft, Right-M Worksheet Job: Lot 183 Phase 3 Waterston 1... Entire House Date: DEL -AIR HEATING & AIR CONDITIONING By: FLETCH 531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM License: CMC 1249777 1 2 3 4 5 Room name Exposedwall Room height Room Room dimareensions BR3 31.9 it 8.0 it heat/000l 1.0 x 162.0 ft 162.0 ftz BATH2 6D it 8.9 ft heat/cool 9.5 x 6.0 ft 57.0 ftz Ty Construction number U-value (Btuhlftz Or HTM (BtuhRlz) Area (ftz) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (it) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 _ VN L--G R L--D C _ Blk viall, siuoco ext:, 2A 2ov 2A 2ov 2A 2ov_ . _ _ Blk Nall, stucco ext 1013-v 2A 2om Blkvell,stuomext . Blk viall, stucco ext 2A-2ov 26-2ty 11J0� Blk vsll, sluaoo ext Blk vsll, stucco ext 2A-2ov 2A-2ov 12C Osw `M 11 D0 _ 16B-30ad — ---- 0 201 0M6 ' 0.330 0330 w 0201 0550 _�-- 0330 0201 0.201 0.330 0320 0.600 0201 0 330 m0.201 0230 0230 ,bb9 0 390 0032 --. -n n n _., nn a a a :se s s s s W sw . w w w w ^ -_ ri -_ -----r- — 5 83 957 957 957 5.83 1525 _� 957 563 5.83 957 928 17.40 5.83 957 5.83 957 957 2.64 1131 023 4.06-, 852 852 ,_8;52 4.06 1620 __ 2320 4.06 _15.81 4.06 834 957 1758 4.06 15. 81 4.06 22,83 22.98 13Y 1193 169 _ OAO 0 0 0 44 0 Y 0 0 0 44 0 _____ 0 8 _ .__..__.1 53 13 0 0 8 1 - 108 0 0 0 0 162 0 0 0 256 0 __ _ 0 46 _ , 96 309 144 0 0 46 96 630 0 0 0 0 150 ' p 0- 0 � _179 0 0 rv— 32 u__.__._158 215 125 0 0 32 ' _ _158 439 0 0 w O .�0 274 '� „0 0 0 ' " 0 0 __,___� 0 b ___mom;__. _.0 8 0 0 0 0 =— 48 0 0 _ O _': 62 _57 ' 7- 0 0 0 0 0 _ 0 0 0 '"— 0 0 0 `p 49 0 0 0 —0 — — 280 0 0 ,0 '-- 0- 56 0 0 -- ` 0 0 0 ;`�"'-'-'0 34 0 0 0 0 �. _ Q 195 0 _. _ 0 ._ .._ 0 1d5 ____0 18 _ __,10 68 15 0 0 18 - 10 108 0 0 0 0 162 '—'_162 8 0 0 0 0 48 0 0 _0 __0 _ _ 62 exairsion 6n c) AED 48 ^-10 Envelope loss/gain 2688 1563 558 324 12 a) Infiltration b) Room ventilation 520 0 145 0 115 0 32 0 13 Internal gains: Occupants@ 230 Applianoes/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 3208 1709 673 356 14 151 Less extemal load Less transfer Redistribution Subtotal Dud loads 25 % 50%1 0 0 0 3208 802 0 0 0 1709 851 25 % 50 % 0 0 0 673 168 0 0 0 356 177 Total room load Air required (clm) 4010 156 2560 111 841 33 533 23 Calculations approved bvACCAto meet all requirements of Manual J 8th Ed - wrigF�tso_ft^ Right-SuteGUriversal 2021 21.0.07 RSU23828 2021-Jt1-1515:55:48 Page 4 ...rstone1512BGRS1Lot183Pfs3Waterstone15Y2BGRS.nQ CaIc=MJB Hoisetaces: S - wrightsofta Right-JO Worksheet Job: Lot 183 Phase 3 Waterston 1... Entire House Date: DEL -AIR HEATING & AIR CONDITIONING By: FLETCH 531 CODISCO WAY, SANFORD, FL32771 Phone:407.333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COMLicerse:CMC1249777 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area BR2 11.0 it 8.6 it heat/000l 14.0 x 11.0 ft 154.0 ft2 Krr 10.0 it 8.7 It heat/000l 1.0 x 120.8 it 120.8 ftz Ty Construction number U-value (Btuh/tz-f Or HTM (Btuhlft2) Area (ftz) or perimeter (ft) Load (13 h) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 Vj! —' y1 R rD_ C � y�all, stucco ext 2ovey _ Blk Mall, stucco end 1oC-v Blk wall, siu000 ext FeY 2A2ov' __ __.__M Blk vdl, stucco e)d 2A-2ov 213-2N 11J0 - Blk v all stucco e# 2A2ovy__r _'-_ 2A-2ov 2A-2ov 12C Osw .1100 1613-36ad 0201 0.330 _____0330 0201 0550 0.330 0201 __.sv.._0330 0201 0230 0320 0.600 0 201 ._0.330 ___'-sw 0230 0230 0 091 0390 0032 n ,. n � � 9.57 _,. 957 5.83 15.95 957 5.83 _. 957_ 5B3 957 928 17AO 5 83 9:57 957 957 2.64 11.31 0.93 .07 -852 852 4.06 1620 2320 4D6 .,._:15BA 4D6 8.34 957 1758 4.06 _ 1581 22B3 22.98 131 , 11..43 1.69 , : 0 0 0 0 0 0 _v_o 0 0 0 0 0 -_ -- — 0 16 0 0 164 1.54 p . Q 0 0 0 0 _ ::, _0 0 0 0 0 0 --_. _ 0_ 0 0 0 0 164 11 p0 __.:w ' - Q 0 0 0 _ 0 a 0 0 0 0 0 0 ._:_.�,_0__ 0 156 0 _M b. r0.µ 152 O 0 0 0 0 0 0 0 0 0 _� -0: o 0 0 0 0 �' 0 0 0 0 0 _ :Q 0 0 0 0 0 0 0 0 0 0 _409 93 0 0 _ .:.0 121 _ o 0 0 0 0 1) 0 0 0 0 T_ 0 a a e. se ,sse_ s s s s sw w w _ n _Q 0 0 0 0 _ 0 0 0 0 0 _�_Q. 10 0 0 y 0 130 0 376 - 0 _ a 0. 277 0 0 p -- 0 130 285 223 0 0 __': 'o. 219 6 c) AED exairsion 189 78 Envelope losstgain 1042 1133 910 805 12 a) Infiltration b) Room ventilation 179 0 50 0 163 0 46 0 13 Internal gains: Occupants@ 230 Appliances/other 0 0 0 0 0 1200 Subtotal (lines 6 to 13) 1221 1183 1073 2051 14 151 Less external load Less transfer Redistribution Subtotal Duct loads 25 % 50%1 0 0 0 1221 305 0 0 0 1183 589 25% 50% 0 0 0 1073 268 0 0 0 2051 1022 Total room load Air required (cfm) 1526 59 1772 77 1341 52 3073 133 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed wrightso t^ .�-rw A Right-Sute®Uriversal 2021 21.0.07 RSU23828 2021-JB-151 PaSe 5 rstorx1512BGRStLot183Phs3Waterstone1512BGRS.rLp Calc=MJ8 Hosefaces: S g - wrightsoft® Right-JO Worksheet Job: Lot 183 Phase 3 Waterston 1... Entire House Date: DEL -AIR HEATING &AIR CONDITIONING By: FLETCH 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM License: CIVIC 1249777 1 3 4 5 Room name osed wall Room height Room dimensions Room area DIN 280 ft heat/000l 8.8 ft 1.0 x 119.0 It 119.0 ftz GRT/FOY/HALLS 10.0 ft 345 ft heat/cool 1.0 x 426.5 It 426.5 ftz Ty Construction number U-value (Btuh/ftz-IF) Or HTM (Btuh/ftz) Area (ftz) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/8 Heat Cool Gross N/P/S Heat Cool 6 1 1 Vjl G _._ V�1 L —G C F-- Blk;viell,stucaoeM 2A 2ov 2A 2ov 2A2ov = Blk wall, stucco ext 10C-v 2A tom BIk vall, stucco eM .2A2ov__ _M .__ ._ Blk wall, stucco ext 2A-2ov 2B-2fv 11Jo Blk yell, stuaca ext 2A 2ov �__.._ Blk wall, stucco ext 2A-2ov 2A 2ov 11 D0 16B 30ad �?Qch ---- 0201 0.330 0 330 0330 0.201 0550 0.330 0 201 ___.._0230._se_ 0.201 0.330 0.320 0.600 0201 _ _ _ 0201 0.201 0.330 0230 _.._ 0 091 0290 0032 ---- 0989 '. n� ' n n . a a a y se s s s s sw _ e sw w w w _ n _ � z`5',8 957 957 .,.. _ 957 5,83 1525 957 5 83 _.____95Z 5.83 9.57 928 17.40 5 83 _ 9.57 5.83 957 9.57 2:64 1131 0.93 28,68 4.06 852 8i52 ___,852 4.06 1620 2320 - - 4.06 7581 4.06 8.34 957 1758 4.06 1. 5 4.06 2223 22.98 131 1143 1 69 000 -" 86 0 23 M __ _ 0 44 18 0 0 ____.._._...0 0 0 0 - 0 0 92 0 0 0 0 129 _.119 • 73 0 0 _ 0 �_, 26 18 0 426 0 ' 222 _. 0 152 285 0 ;." 297 0 198 106 289 0 30 , 0 0 0 0 110 01 0 .__. _ 0 0 0 0 ' 641 287 0 _�. _._,_ 0 0 0 0 b 244 0 28 350 0. 0 0 0 322 202 396 ^ 447� : „'256 0 0 0 0 0 '0 170 0 29 3.53 A. 0 0 -_ 0 _ .,160 _204. 72_1 0 ..__._0 0 0 0 0 0 . 92 0 0 0 0 129 __...�28 0 _. 0 0 0 0 0 0 _ 536 0 0 !, 0 0 120 ;"" _803 ' 0 .�.„. _ ,0..__ 0 0 0 0 0 374 0 0 . _ 0 - 0 219 0 65 0 3 20 "" 0 0 0 0 140 18 427 �- 0 42 0 3 20 , 0 y 0 0 _ 0 Y 122 ' 18 427 _.. 6 c) AED excursion -50 -80 Envelope loss/gain 2545 1432 3460 2260 12 a) Infiltration b) Room ventilation 473 0 132 0 417 0 117 0 13 Internal gains: Occupants@ 230 Appliances/other 1 230 0 2 460 0 Subtotal (lines 6 to 13) 3018 1794 3877 2836 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 25 % 50 % 0 0 0 3018 754 0 0 0 1794 894 25 % 50% 0 0 0 3877 969 0 0 0 2836 1413 Total room load Air required (cim) 3772 1471 2688 116 4846 188 4249 184 Calculations approved byACCAto_meet all requirements of Manual J 8th Ed -�- wrigF�tsof't" __ Right-Sute®Uriversal 2021 21.0.07 RSU23828 2021-JLI-1515:55.48 e 6 rstone1512BGRS1Lot183Pts3Waterstone1512BGRS,nQ Calc=MJ8 Housefaces: S g -�- wrightsoft® Duct System Summary Job: Lot 183 Phase 3 Watersto... Date: Entire House By: FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM License: CMC 1249777 iLroject intormation For: ADAMS HOMES 5322 Vespera Street, Fort Pierce, FL 34951 External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170/0.170 in H2O 0.359 in/100ft 947 cfm 95 ft Supply Branch Detail Table Cooling 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.359 in/100ft 947 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Mal Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH2 h 841 33 23 0.379 4.0 Ox 0 VIFx 19.7 70.0 BR2 c 1772 59 77 0.408 6.0 Ox 0 VIFx 13.3 70.0 BR3 h 4010 156 111 0.359 7.0 Ox 0 VIFx 24.7 70.0 DIN h 3772 147 116 0.370 7.0 Ox 0 VIFx 22.0 70.0 GRT/FOY/}iALLS h 4846 188 184 0.458 8.0 Ox 0 VIFx 4.3 70.0 KIT c 3073 52 133 0.406 6.0 Ox 0 VIFx 13.7 70.0 LAU c 1104 17 48 0.456 4.0 Ox 0 \AFx 4.6 70.0 MBATH h 1973 77 61 0.430 5.0 Ox 0 VIFx 9.0 70.0 MBR h 4575 178 172 0.411 8.0 Ox 0 VIFx 12.8 70.0 WC h 484 19 12 0.417 4.0 Ox 0 VIFx 11.5 70.0 W lc h 576 22 11 0.453 4.0 Ox 0 VI Fx 5.0 70.0 Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mal Trunk rb2 Ox 0 947 947 0 0 0 0 Ox 0 VI Fx -0 id- wrightsoft° edRight-Sute®Universal 202121.0.07RSU23828 ...rstone1512BGRS1Lot1B3Pfs3Waterstore1512BGRS.rrp Calc=MJB Hoisefaces: S 2021-JU-151555:49 Page 1 2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 183 Phase 3 Waterstone 1512 BGRS Builder Name: ADAMS HOMES Street: 5322 Vespera Street Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 w , Design Location: FL, ST_LUCIE_CO_INTL U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/door jambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace wall . Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac 3s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be airtight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exteriorwalls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids a. In addition, inspection of log we shall be in accordance with the provisions of ICC-400. 7/15/2021 4:10 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S orper exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage" then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 7/15/2021 4:09:51 PM EnergyGauge@ USA 7.0.00-.FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th ,Edition Jurisdiction: 661000 Permit #: Job Information. Builder: ADAMS HOMES Community: Lot: 183-3 Address: 5322 Vespera Street City: Fort Pierce State: FL Zip: 34951 Air Leakage Test Results Passing results must meet either. the Performance, Prescriptive, or ERI Method O PRESGRIPTIUE METHOD -The building ;or dwelling .'unit shall'be tested'and verified as having anair'leakage rate'of,rf6t exceeding 7 air ' changes per hour at apressure,of•0.2`inbh w.g (50'Pascals) in'Glimate Zones9 and 2. 0 ' PERFORMANCE or ERI METHOD -The building or dwelling unit shall be tested;and verified;as having an air leakage rate of not=exceeding the selected ACH(50) value, as shown on Form R405 2020 (P'erformance) or R406-2020 (ERI);,section abeled'as infiltration,sub-section ACH50`. ACH(50) specified, on, Form' R405-20201Energy Ca/c (Performance): or R,406-2020 (ERQ: 7.000 x 60 _ 13608 = Method for calculating building volume: CFM(50) Building Volume ACH(50) Q Retrieved from architectural plans F-1 PASS • Code software calculated When ACH(50) is less than 3, Mechanical Ventilation installation Q Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Printed Name of Tester: License/Certification #: Date of Test: Issuing Authority: 7/15/2021 4:10:47 PM EnergyGaugeO USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 5322 Vespera Street Permit Number: Fort Pierce , FL , 34951 MANDATORY REQUIREMENTS - See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) ❑display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, *shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 7/15/2021 4:10 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airnow rate when tested in accordance with ASHRAE 193. R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the. outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C) or below 55°F (13°C) shall be insulated to a minimum of R-3. R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. ❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 7/15/2021 4:10 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'% inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60°C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of combustion types of service water -heating systems to be turned off. R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. ❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. ❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMUIV (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 7/15/2021 4:10 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) ElR403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40oF (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 7/15/2021 4:10 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5 QR403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. ❑ R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. F1 R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 7/15/2021 4:10 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 5