HomeMy WebLinkAboutPRODUCT EVALUATION REPORTMetal Roof and Wall Systems PRODUCT EVALUATION REPORT PBR PANEL FLORIDA BUILDING CODE 7TH EDITION (2020) FLORIDA PRODUCT APPROVAL FL 11819.5-R4 STRUCTURAL COMPONENTS ROOF DECK Prepared For: MBCI, part of the Cornerstone Building Brands family. 14031 West Hardy Houston, TX 77064 Telephone: (844) 327-1748 Fax: (281) 445-8110 Prepared By: Bala Sockalingam, Ph.D., P.E. Florida Professional Engineer #62240 1216 N Lansing Ave., Suite C Tulsa, OK 74106 Telephone: (918) 492-5992 FAX: (866) 366-1543 This report consists of Evaluation Report (3 Pages including cover) Installation Details (1 Page) Report No. C2422-5 Date: 12.16.2020 �ft3 �&-ft W% 0 �wm 1. 0 Metal Roof and Wall Systems PRODUCT EVALUATION REPORT PBR PANEL FLORIDA BUILDING CODE 7TH EDITION (2020) FLORIDA PRODUCT APPROVAL FL 11819.5-R4 STRUCTURAL COMPONENTS ROOF DECK Prepared For: w oP&wz o Qz���-,°oQ MBCI, part of the Cornerstone Building Brands f ily. Wo0< uW 14031 West Hardy QC o U � � og�,¢Q��� Houston, TX 77064 Q Z ov0" LD 0 Telephone: (844) 327-1748 o ;9WwLLoo Fax: (281) 445-8110 > W w0o<.WF� m w gg � � Prepared By: C9 EN Wes= Bala Sockalingam, Ph.D., P.E. oZ° oU- � z Florida Professional Engineer #62240 W a Z o z c"'i a z z 1216 N Lansing Ave., Suite C ®W g �o=Z Wo Tulsa, OK 74106 0- . w L* ldwO0o Telephone: (918) 492-5992 p a ¢ w mW}z~"� o]Z-rZmoU�J FAX: (866) 366-1543 U (0000t.L(L U- m v This report consists of Evaluation Report (3 Pages including cover) Installation Details (1 Page) Report No. C2422-5 Date: 12.16.2020 FL 11819.5-R4 C2422-5 12.16.2020 Page 2 of 3 Manufacturer: MBCI, part of the Cornerstone Building Brands family. Manufacturing Houston: 14031 West Hardy, Houston, TX 77064 Locations: Atlanta: 2280 Monier Ave., Lithia Springs, GA 30122 Adel: 1600 Rogers Road, Adel, GA 31620 Product Name: PBR Panel Panel Description: 36" wide coverage with (4) 1-1/4" high ribs Materials: Min. 29 ga., 80 ksi steel or min. 24 ga., 50 ksi steel. Galvanized coated steel (ASTM A653) or Galvalume coated steel (ASTM A792) or painted steel (ASTM A755). Corrosion resistant as per FBC 2020 Section 1507.4.3. Support Description: Min. 16 ga., 50 ksi steel section. (Must be designed by others) Slope: 1/2:12 or greater in accordance with FBC 2020 Section 1507.4.2. Requires applied lap sealant for roof slopes less than 3:12. Uplift Pressure: 29 ga.: -55 sf at panel span of 48 o.c. with one fastener at each rib. (Factor of Safety = 2) 26 ga.: -80 sft�,panel spaiof4�8o�cvui;�thne fasterier�ateachrb: 24 ga.: -90 psf at panel span of 48 S. with one fastener at each ri 22 ga.: -142.5 psf at panel span of 48 o.c. with two fasteners at each rib. Panel Attachment: 1/4"-14 x 1-1/4" long self -drilling screws with washer. Fasteners are corrosion resistant as per FBC 2020 Section 1507.4.4. At panel ends 7"-5"-7" o.c. across panel width At intermediate 12" o.c. across panel width for 29, 26 and 24 ga. panels 7"-5"-7" o.c. across panel width for 22 ga. panels Sidelap Attachment: 1/4"-14 x 7/8" long self -drilling screws with washer at 20" o.c. Fasteners are corrosion resistant as per FBC 2020 Section 1507.4.4. Test Standards: Roof assembly tested in accordance with ASTM E1592-01 `Test Method for Structural Performance of Sheet Metal Roof and Siding Systems by Uniform Static Air Pressure Difference' and FM 4471 Section 5.4 `Resistance to Foot Traffic'. Test Equivalency: The test procedure in ASTM E1592-01 comply with test procedure prescribed in ASTM E1592-05(2012). Code Compliance: The product described herein has demonstrated compliance wi , `BC 2020 Section 1507.4. FL 11819.5-R4 C2422-5 12.16.2020 Page 3 of 3 Product Limitations: Design wind loads shall be determined for each project in accordance with FBC 2020 Section 1609 or ASCE 7-16 using allowable stress design. The maximum panel span listed herein shall not be exceeded. The design pressure for reduced panel span may be computed using rational analysis prepared by a Florida Professional Engineer or based on MBCI load span table. This evaluation report is not applicable in High Velocity Hurricane Zone. Fire classification is not within scope of this Evaluation Report. Refer to FBC 2020 Section 1505 and current approved roofing materials directory or ASTM E108/UL790 report from an accredited laboratory for fire ratings of this product. Supporting Documents: ASTM E1592 Test Reports Force Engineering & Testing, Inc. 07-0045T-07 A, B, E, F, Reporting Date 4/3/2007 FM 4471 Test Report Force Engineering & Testing, Inc. 07-0172T-17, Reporting Date 9/21/2017 O D 1/2' 12' 3B' 12' - 2 1/2' ------------ --------------------------------- 12-14 x i 1/4 LDNG-UFE SELF- DTBLLER W/WASHER [FASTENER 131 PBR PANEL FASTENER PATTERN Lows uFE Um (AT INTERMEDIATE SUPPORTS) ,MM j410 20' D.C. TAPE STJILER 35' APPLICA N f- P N1ND --� PBR PANEI'SIDE LAP DETAIL 2 1/2' _ 7' 5' 7' 5' 7' .2 1/2' ---------------------------------- PBR PANEL FASTENER PATTERN (AT PANEL ENDS) SIDESPNLESS NOTED) tm F52-B fT{09F t S4'O3 PER�FtORIDA� PROD UGTAPPROYAL. S ope o iWor : m§aRinitall il3ln�a ai Repraceroo rpan' er al !� FRAME CROSS SECTION: FRAME LINE 2 3 4 5 6 0 0 V. taw