PRODUCT EVALUATION REPORT
PBR PANEL
FLORIDA BUILDING CODE 7TH EDITION (2020)
FLORIDA PRODUCT APPROVAL
FL 11819.5-R4
STRUCTURAL COMPONENTS
ROOF DECK
Prepared For:
MBCI, part of the Cornerstone Building Brands family.
14031 West Hardy
Houston, TX 77064
Telephone: (844) 327-1748
Fax: (281) 445-8110
Prepared By:
Bala Sockalingam, Ph.D., P.E.
Florida Professional Engineer #62240
1216 N Lansing Ave., Suite C
Tulsa, OK 74106
Telephone: (918) 492-5992
FAX: (866) 366-1543
This report consists of
Evaluation Report (3 Pages including cover)
Installation Details (1 Page)
Report No. C2422-5
Date: 12.16.2020
�ft3 �&-ft W% 0 �wm 1.
0
Metal Roof and Wall Systems
PRODUCT EVALUATION REPORT
PBR PANEL
FLORIDA BUILDING CODE 7TH EDITION (2020)
FLORIDA PRODUCT APPROVAL
FL 11819.5-R4
STRUCTURAL COMPONENTS
ROOF DECK
Prepared For:
w
oP&wz o
Qz���-,°oQ
MBCI, part of the Cornerstone Building Brands f
ily.
Wo0< uW
14031 West Hardy
QC o
U � �
og�,¢Q���
Houston, TX 77064
Q Z
ov0" LD 0
Telephone: (844) 327-1748
o
;9WwLLoo
Fax: (281) 445-8110
>
W
w0o<.WF�
m
w
gg
�
�
Prepared By:
C9
EN Wes=
Bala Sockalingam, Ph.D., P.E.
oZ° oU-
� z
Florida Professional Engineer #62240
W
a Z o z c"'i a z z
1216 N Lansing Ave., Suite C
®W
g
�o=Z Wo
Tulsa, OK 74106
0- .
w
L* ldwO0o
Telephone: (918) 492-5992
p
a
¢
w
mW}z~"�
o]Z-rZmoU�J
FAX: (866) 366-1543
U
(0000t.L(L U- m
v
This report consists of
Evaluation Report (3 Pages including cover)
Installation Details (1 Page)
Report No. C2422-5
Date: 12.16.2020
FL 11819.5-R4
C2422-5
12.16.2020
Page 2 of 3
Manufacturer: MBCI, part of the Cornerstone Building Brands family.
Manufacturing Houston: 14031 West Hardy, Houston, TX 77064
Locations: Atlanta: 2280 Monier Ave., Lithia Springs, GA 30122
Adel: 1600 Rogers Road, Adel, GA 31620
Product Name: PBR Panel
Panel Description: 36" wide coverage with (4) 1-1/4" high ribs
Materials: Min. 29 ga., 80 ksi steel or min. 24 ga., 50 ksi steel. Galvanized coated
steel (ASTM A653) or Galvalume coated steel (ASTM A792) or painted
steel (ASTM A755). Corrosion resistant as per FBC 2020 Section
1507.4.3.
Support Description: Min. 16 ga., 50 ksi steel section. (Must be designed by others)
Slope: 1/2:12 or greater in accordance with FBC 2020 Section 1507.4.2.
Requires applied lap sealant for roof slopes less than 3:12.
Uplift Pressure: 29 ga.: -55 sf at panel span of 48 o.c. with one fastener at each rib.
(Factor of Safety = 2) 26 ga.: -80 sft�,panel spaiof4�8o�cvui;�thne fasterier�ateachrb:
24 ga.: -90 psf at panel span of 48 S. with one fastener at each ri
22 ga.: -142.5 psf at panel span of 48 o.c. with two fasteners at each rib.
Panel Attachment: 1/4"-14 x 1-1/4" long self -drilling screws with washer. Fasteners are
corrosion resistant as per FBC 2020 Section 1507.4.4.
At panel ends 7"-5"-7" o.c. across panel width
At intermediate 12" o.c. across panel width for 29, 26 and 24 ga. panels
7"-5"-7" o.c. across panel width for 22 ga. panels
Sidelap Attachment: 1/4"-14 x 7/8" long self -drilling screws with washer at 20" o.c. Fasteners
are corrosion resistant as per FBC 2020 Section 1507.4.4.
Test Standards: Roof assembly tested in accordance with ASTM E1592-01 `Test
Method for Structural Performance of Sheet Metal Roof and Siding
Systems by Uniform Static Air Pressure Difference' and FM 4471
Section 5.4 `Resistance to Foot Traffic'.
Test Equivalency: The test procedure in ASTM E1592-01 comply with test procedure
prescribed in ASTM E1592-05(2012).
Code Compliance: The product described herein has demonstrated compliance wi , `BC
2020 Section 1507.4.
FL 11819.5-R4
C2422-5
12.16.2020
Page 3 of 3
Product Limitations: Design wind loads shall be determined for each project in accordance
with FBC 2020 Section 1609 or ASCE 7-16 using allowable stress
design. The maximum panel span listed herein shall not be exceeded.
The design pressure for reduced panel span may be computed using
rational analysis prepared by a Florida Professional Engineer or based
on MBCI load span table. This evaluation report is not applicable in
High Velocity Hurricane Zone. Fire classification is not within scope of
this Evaluation Report. Refer to FBC 2020 Section 1505 and current
approved roofing materials directory or ASTM E108/UL790 report
from an accredited laboratory for fire ratings of this product.
Supporting Documents: ASTM E1592 Test Reports
Force Engineering & Testing, Inc.
07-0045T-07 A, B, E, F, Reporting Date 4/3/2007
FM 4471 Test Report
Force Engineering & Testing, Inc.
07-0172T-17, Reporting Date 9/21/2017
O
D 1/2'
12'
3B'
12' - 2 1/2'
------------ ---------------------------------
12-14 x i 1/4 LDNG-UFE SELF-
DTBLLER W/WASHER [FASTENER 131 PBR PANEL FASTENER PATTERN
Lows uFE Um (AT INTERMEDIATE SUPPORTS)
,MM j410 20' D.C.
TAPE STJILER
35'
APPLICA N f-
P N1ND --�
PBR PANEI'SIDE LAP DETAIL
2 1/2' _ 7' 5' 7' 5' 7' .2 1/2'
----------------------------------
PBR PANEL FASTENER PATTERN
(AT PANEL ENDS)
SIDESPNLESS NOTED)
tm
F52-B
fT{09F t S4'O3 PER�FtORIDA�
PROD UGTAPPROYAL.
S ope o iWor : m§aRinitall
il3ln�a ai
Repraceroo rpan' er
al
!� FRAME CROSS SECTION: FRAME LINE 2 3 4 5 6
0
0
V.
taw