Loading...
HomeMy WebLinkAbout9803 S Ocean Dr engineeringArchitectonic Inc September 21, 2021 St. Lucie County Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34992 Re: Roofing specification prepared for the St. Lucie County Building Department for the structure located at, 9803 S. Ocean Drive, Jenson Beach, FL 34957 Manufacturer: Petersen Aluminum Corporation Profiles: Snap -Clad Aluminum Standing Seam, N0A# 18.1023.13 Code: FBC 2020; Section R 905 Wind Speed: 165 MPH; Ultimate Design Wind Speeds Exposure: D Mean Roof Height: 15'- 0" Maximum Pitch: 4/12 Minimum Required Design Pressure: Zonel: -79.8 Zone 2: -100.6 Zone3: -118.8 Maximum Uplift Pressure: -153.5 Fasteners: Panels shad be installed along the rib with SNAP CLAD Clips secured with #10 x 1.5" pancake head screws (2 per clip); the screws shall be of sufficient length to penetrate through the sheathing a min. of 3/16". The female rib of panel is snapped over the male rib of panel. Panel clips shall be spaced a max. distance of 6" o.c. Underlayment: Polyglass Roof Underiayment, FL# 5259.1 Roof Decking: Existing 5/8" plywood sheathing to be nailed w/8d x 2" ring shank @ 6" O.C. thru out zone 1, 4" O.C. perimeter, and 6" C.C. field zone 2, and 4" O.C. thru out zone 3. The above approved, as per Florida Building Code Compliance acceptances, 2020 Florida Building Code, and the Manufacturer's recommendations. irl'.9ff�d r10 .Re`i�ectfu IV su mit' eri AR96098 806 Delaware Avenue Tel: 772 460 7751 www.architectonicinc.com Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 1