September 21, 2021
St. Lucie County
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34992
Re: Roofing specification prepared for the St. Lucie County Building Department for the
structure located at, 9803 S. Ocean Drive, Jenson Beach, FL 34957
Manufacturer:
Petersen Aluminum Corporation
Profiles:
Snap -Clad Aluminum Standing Seam, N0A# 18.1023.13
Code:
FBC 2020; Section R 905
Wind Speed:
165 MPH; Ultimate Design Wind Speeds
Exposure:
D
Mean Roof Height:
15'- 0" Maximum
Pitch:
4/12 Minimum
Required Design Pressure:
Zonel: -79.8 Zone 2: -100.6 Zone3: -118.8
Maximum Uplift Pressure:
-153.5
Fasteners:
Panels shad be installed along the rib with SNAP CLAD Clips secured
with #10 x 1.5" pancake head screws (2 per clip); the screws shall be of
sufficient length to penetrate through the sheathing a min. of 3/16".
The female rib of panel is snapped over the male rib of panel. Panel
clips shall be spaced a max. distance of 6" o.c.
Underlayment:
Polyglass Roof Underiayment, FL# 5259.1
Roof Decking:
Existing 5/8" plywood sheathing to be nailed w/8d x 2" ring shank
@ 6" O.C. thru out zone 1, 4" O.C. perimeter, and 6" C.C. field zone 2,
and 4" O.C. thru out zone 3.
The above approved, as per Florida Building Code Compliance acceptances, 2020 Florida Building Code,
and the Manufacturer's recommendations.