HomeMy WebLinkAboutApproved revsion ONeal Foundation Rev1 Set - 8.12.21-Signed (002)STRUCTURAL NOTES, SPECIFICATIONS AND GENERAL REQUIREMENTS DESIGN CRITERIA D-1 CODES: - FLORIDA BUILDING CODE 7TH EDITION (2020) - ASCE 7-16 "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES" D-2 DESIGN DEAD LOADS: ROOF 20 PSF 8" MASONRY WALL 55 PSF CONCRETE 150 PCF DESIGN LIVE LOADS: ROOF 20 PSF RESIDENTIAL AREAS 40 PSF D-3 SEISMIC: ZONE 0 D-4 PREPARE SITE IN ACCORDANCE WITH THE GEOTECHNICAL REPORT, PREPARED BY KSM ENGINEERING AND TESTING, JOB NO. 213143-b, DATED MAY 6, 2021. GENERAL NOTES G-1 REVIEW ALL PROJECT DOCUMENTS PRIOR TO FABRICATION AND START OF CONSTRUCTION. REPORT ANY DISCREPANCIES TO ARCHITECT OR STRUCTURAL ENGINEER PRIOR TO PROCEEDING WITH WORK. G-2 THE CONCRETE WALLS ARE NOT DESIGNED TO WITHSTAND TEMPORARY CONSTRUCTION LOADS. IT IS THE CONTRACTOR'S RESPONSIBILITY AT ALL TIMES TO MAINTAIN WALL STABILITY DURING THE CONSTRUCTION PHASE OF THIS PROJECT. G-3 IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROTECT EXISTING FACILITIES, STRUCTURES AND UTILITY LINES FROM ALL DAMAGE DURING CONSTRUCTION. G-4 NO STRUCTURAL MEMBER SHALL BE CUT, NOTCHED OR OTHERWISE REDUCED IN SIZE OR STRENGTH WITHOUT PRIOR APPROVAL IN WRITING FROM THE STRUCTURAL ENGINEER. G-5 COORDINATE STRUCTURAL AND OTHER DRAWINGS THAT ARE PART OF THE CONTRACT DOCUMENTS FOR ANCHORED, EMBEDDED OR SUPPORTED ITEMS WHICH MAY AFFECT THE STRUCTURAL DRAWINGS (I.E. MECHANICAL, ELECTRICAL, PLUMBING, DUCTWORK, ETC.) G-6 ALL DETAILS AND SECTIONS ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT EXCEPT WHERE A SEPARATE DETAIL IS SHOWN. G-7 THE INTENTION OF THE PLANS AND SPECIFICATIONS IS TO PROVIDE ALL NECESSARY DETAILS TO CONSTRUCT A COMPLETE STRUCTURE. WHEN SPECIFIC INFORMATION IS MISSING OR IS IN CONFLICT. THE CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. G-8 THE ENGINEER SHALL NOT BE RESPONSIBLE FOR LAYOUT, DIMENSIONAL ERRORS OR DISCREPANCIES RESULTING FROM THE REPRODUCTION AND USE OF CONTRACT DRAWINGS FOR ERECTION AND SHOP DRAWINGS. USE OF CONTRACT DRAWINGS REPRODUCED IN WHOLE OR ANY PART IN SHOP DRAWINGS SHALL NOT RELIEVE THE CONTRACTOR NOR SUBCONTRACTORS FROM THEIR RESPONSIBILITY TO ACCURATELY LAYOUT, COORDINATE, DETAIL, FABRICATE AND INSTALL A COMPLETE STRUCTURE. G-9 REVIEW ALL SHOP DRAWINGS FOR CONFORMANCE WITH THE CONTRACT DOCUMENTS AND FOR COMPLETENESS AND ANSWER ALL CONTRACTOR RELATED QUESTIONS. STAMP AND INITIAL ALL SHEETS PRIOR TO SUBMITTING SHOP DRAWINGS TO ARCHITECT/ENGINEER FOR REVIEW. NON-COMPLIANCE WITH THIS REQUIREMENT WILL RESULT IN REJECTION OF SUBMITTAL. G-10 ALL BOLTS, SCREWS, NUTS, WASHERS, NAILS & ETC. TO BE OF STAINLESS STEEL DEEP FOUNDATIONS -AUGER CAST PILE DF-1 AUGERCAST PILING SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE GEOTECHNICAL RECOMMENDATIONS AND INSTALLATION PROCEDURES CONTAINED IN THE GEOTECHNICAL REPORT, LISTED IN D-4. DF-2 ALL PILES SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE SOILS ENGINEER AND PROVIDE THE FOLLOWING SIZE AND CAPACITIES: PER REPORT PREPARED BY KSM ENGINEERING AND TESTING, JOB NO. 213143-b, DATED MAY 6, 2021. 14" DIA. AUGER CAST PILES 56 KIPS COMPRESSION (29 FT. LENGTH) DF-3 PILES SHOULD BE REINFORCED AS INDICATED IN "TYPICAL AUGERCAST PILING DETAIL". DF-4 GROUT SHALL BE PER AN APPROVED MIX DESIGN PROPORTIONED TO ACHIEVE A STRENGTH AT 28 DAYS OF 4000 PSI MINIMUM. GROUT SHALL HAVE A MAXIMUM FLOW RATE OF 15 SECONDS. SUBMIT PROPOSED MIX DESIGN WITH RECENT FIELD CURED OR LAB CURED CYLINDER TESTS FOR REVIEW PRIOR TO USE. DF-5 GROUT SHALL BE TESTED IN ACCORDANCE WITH ASTM STANDARDS UTILIZING 3"x6" CYLINDERS. TEST CYLINDERS SHALL BE MADE AND CURED IN ACCORDANCE WITH ASTM C31. DF-6 WHEN PILES ARE IN CLUSTERS OF TWO OR MORE, INDIVIDUAL PILES SHALL BE INSTALLED WITHIN 3" OF THE DESIGN LOCATION. THE CUMULATIVE LOCATION OF THE PILE GROUP CENTER OF GRAVITY SHALL NOT EXCEED 1\". SINGLE PILES SHALL BE INSTALLED WITHIN 1\" OF DESIGN LOCATION. VARIATION FROM PLUMB SHALL NOT EXCEED \" IN TWO FEET. DF-7 ADJACENT PILES SHALL NOT BE PLACED UNTIL THE MORTAR HAS REACHED ITS INITIAL SET IN ORDER THAT THERE WILL BE NO INTERCONNECTION BETWEEN ADJACENT PILES WHILE THE MORTAR IS IN THE FLUID STATE. DF-8 AN AS -BUILT SURVEY OF PILE LOCATIONS SHALL BE PERFORMED BY A FLORIDA REGISTERED LAND SURVEYOR. PILES SHALL BE LOCATED ON THE AS -BUILT DRAWINGS HORIZONTALLY AND VERTICALLY FROM THE COLUMN CENTERLINES. SUBMIT AS -BUILT DRAWINGS TO THE STRUCTURAL ENGINEER FOR APPROVAL. DF-9 CONTRACTOR IS RESPONSIBLE FOR ENGINEERING COSTS ASSOCIATED WITH REDESIGNS CAUSED BY IMPROPER PILE LOCATIONS. DF-10 WHERE THE PILE CUTOFF IS NEAR THE SURFACE OR ABOVE THE BOTTOM OF THE EXCAVATION METAL SLEEVES OR CASING OF THE PROPER DIAMETER AND AT LEAST 18 INCHES IN LENGTH SHALL BE PLACED AROUND THE PILE TOPS. (SPECIAL CONDITIONS MAY REQUIRE METAL SLEEVES OF ADDITIONAL LENGTH) DF-11 INSTALLATION OF PILING SHALL BE MONITORED BY A LICENSED GEOTECHNICAL ENGINEER. REPORTS OF WORK SHALL BE SUBMITTED FOR REVIEW. REPORT SHALL INCLUDE PILE DEPTH, PILE GROUT VOLUME, GROUT FACTOR, CONCRETE COVERAGE ON THE REINFORCING STEEL, GROUT DELIVERY DATES, MISCELLANEOUS OBSERVATIONS, AND OTHER INFORMATION AS REQUIRED. REINFORCED CONCRETE RC-1 ALL CONCRETE DESIGN AND PLACEMENT SHALL BE IN STRICT ACCORDANCE WITH THE ACI "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE," ACI 318-14. RC-2 PROVIDE (4) TEST CYLINDERS FOR EACH 50 C.Y. OF CONCRETE PLACED OR FRACTION THEREOF. RC-3 STRUCTURAL CONCRETE SHALL CONFORM TO ACI 301 SPECIFICATIONS AND SHALL DEVELOP THE FOLLOWING MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS: GRADE BEAMS AND PILING 4000 PSI COLUMNS AND WALLS 5000 PSI BEAMS AND SLABS 5000 PSI ALL OTHER CONCRETE 3000 PSI RC-4 USE REGULAR WEIGHT CONCRETE. RC-5 STRUCTURAL CONCRETE SHALL CONFORM TO ACI 301 AND HAVE THE FOLLOWING SLUMPS, WATER CEMENT RATIO & AGGREGATE REQUIREMENTS: LOCATION SLUMP W/C RATIO MAX. AGGREGATE GRADE BEAMS 4"+/-1" 0.48 ASTM #57 SLABS ON GRADE 4"+/-1" 0.48 ASTM #57 COLUMNS & WALLS 5"+/-1" 0.48 ASTM #57 BEAMS AND SLABS 5"+/-1" 0.45 ASTM #57 TIE BMS & TIE COL'S 5"+/-1" 0.45 ASTM #8 PEAROCK SUBMIT DESIGN MIXES FOR APPROVAL AT LEAST ONE WEEK PRIOR TO CONCRETE POUR. DESIGN MIX SUBMITTALS MUST INDICATE PROPOSED LOCATION OR TYPE OF USE. FAILURE TO DO SO WILL CAUSE DELAY AND/OR REJECTION OF SUBMITTALS. RC-6 MAXIMUM WATER TO CEMENT RATIO WHEN NO BACK-UP DATA IS AVAILABLE: a) 3000 PSI, 28 DAY COMPRESSIVE STRENGTH; W/C RATIO 0.58 MAXIMUM (NON -AIR ENTRAINED), 0.47 MAXIMUM (AIR ENTRAINED) RC-7 FLYASH, WHEN USED, SHALL BE LIMITED TO 20% OF THE CEMENTITIOUS MATERIAL. DO NOT USE FOR EXPOSED SLABS RC-8 SUBMIT COPIES OF CONCRETE MIX DESIGN TO ENGINEER FOR APPROVAL INFORMATION SHALL INCLUDE CEMENT CONTENT, WATER/CEMENT RATIO, SLUMP, ENTRAINED AIR, ADMIXTURE CONTENT AND QUANTITY. RC-9 ALL REINFORCEMENT SHALL BE FASTENED AND SECURED TOGETHER TO PREVENT DISPLACEMENT BY CONSTRUCTION LOADS OR THE PLACING OF CONCRETE RC-10 THE USE OF JITTERBUGS TO CONSOLIDATE CONCRETE WILL NOT BE PERMITTED. RC-11 ALL PUMPED CONCRETE WITH #57 AGGREGATE IS TO CONTAIN A HIGH RANGE WATER REDUCING AGENT. MINIMUM SIZE OF DISCHARGE TO BE 4" I.D. RC-12 A 2" I.D. DISCHARGE MAY BE USED WITH #8 AGGREGATE. USE PLASTICIZER ADMIXTURE IF NECESSARY TO INCREASE SLUMPS BEYOND THAT NOTED ABOVE. RC-14 ALL REINFORCING STEEL SHALL BE DETAILED, FABRICATED AND INSTALLED IN ACCORDANCE WITH ACI 318 AND ACI DETAILING MANUAL, ACI-315 LATEST EDITION. RC-15 REINFORCEMENT WITH RUST, MILL SCALE OR A COMBINATION OF BOTH SHALL BE CONSIDERED SATISFACTORY, PROVIDED THE MINIMUM DIMENSIONS (INCLUDING HEIGHT OF DEFORMATIONS) AND WEIGHT OF A HAND -WIRE -BRUSHED TEST SPECIMEN ARE NOT LESS THAN APPLICABLE SPECIFICATION REQUIREMENTS IN THE ASTM STANDARDS REFERENCE IN ACI 318. REINFORCING BARS SHALL CONFORM TO ASTM A-615, GRADE 60, LATEST REVISION, WITH SUPPLEMENT (S1), MARKED "S". RC-16 ALL SLABS ON GRADE SHALL REINFORCED WITH: 4" SLAB ON GRADE: 6"X6"- 1.4x1.4 WELDED WIRE REINFORCEMENT (WWR) LOCATED IN THE MIDDLE TO UPPER PORTION OF THE SLAB. W.W.R. SHALL BE SUPPORTED WITH APPROVED MATERIALS OR SUPPORTS NOT EXCEEDING 3 FT OR IN ACCORDANCE WITH MANUFACTURER SPECIFICATIONS. RC-17 WELDED WIRE FABRIC TO COMPLY WITH ASTM A1064 SHEETS ONLY, NO ROLLS. INSTALL ON BRICKS OR BOLSTERS, AT MID -DEPTH OF THE SLAB. RC-18 LAP CONTINUOUS REINF. AS NOTED IN LAP SPLICE SCHEDULE OR MIN 40 BAR DIA. LAP CONT. BOTTOM STEEL OVER SUPPORT AND CONT. TOP STEEL AT MIDSPAN UNLESS OTHERWISE SPECIFIED. RC-19 TERMINATE ALL DISCONTINUOUS TOP BARS WITH STANDARD 90 DEGREE HOOK (PLACED VERTICALLY) UNLESS NOTED OTHERWISE. RC-20 PROVIDE CONCRETE COVER OVER REINFORCEMENT AS FOLLOWS, UNLESS OTHERWISE NOTED: MINIMUM COVER: LOCATION AND CONDITION: A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH ALL BARS 3" B. CONCRETE EXPOSED TO EARTH OR WEATHER #6 OR GREATER 2" #5 OR SMALLER 1-1/2" C. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND 1. SLABS, WALLS, AND JOISTS #11 OR SMALLER 3/4" #14418 1-1/2" 2. BEAMS AND COLUMNS: (PRIMARY REINFORCEMENT, TIES, STIRRUPS, AND SPIRALS) ALL BARS 1-1/2" D. SLABS ON GRADE: SINGLE MAT, TOP 1/2 TO 1/3 OF THICKNESS RC-21 SLEEVE ALL PENETRATIONS THROUGH BEAMS AND SLABS INDIVIDUALLY. CORE DRILLING WILL NOT BE PERMITTED. SUBMIT LOCATION AND SIZE OF SLEEVES THROUGH BEAMS TO ENGINEER FOR REVIEW PRIOR TO CASTING CONCRETE. WHERE PIPING PENETRATES CONCRETE BEAMS, PLACE TWO #3 STIRRUPS @ 3" O.C. EACH SIDE OF PIPE, UNLESS OTHERWISE NOTED. RC-22 NO REINFORCING BARS SHALL BE CUT TO ACCOMMODATE THE INSTALLATION OF ANCHORS, EMBEDS OR OTHER ITEMS. RC-23 USE THE STRUCTURAL DRAWINGS INCLUDING REVISIONS AND ADDENDA IN CONJUNCTION WITH REVIEWED SHOP DRAWINGS FOR PLACEMENT OF REINFORCING. RC-24 AT CHANGES IN DIRECTION OF CONCRETE WALLS, BEAMS & STRIP FOOTINGS, PROVIDE CORNER BARS OF SAME SIZE AND QUANTITY UNLESS NOTED OTHERWISE AS HORIZONTAL STEEL. RC-25 ALL EMBEDDED ITEMS SHALL BE SECURELY TIED IN PLACE PRIOR TO CONCRETE PLACEMENT. RC-26 THE GENERAL CONTRACTOR IS RESPONSIBLE FOR FOR PROVIDING THE CONSTRUCTION OF ALL FORMWORK IN ACCORDANCE WITH ACI 347. RC-27 PLACE CONCRETE PER ACI 304. USE INTERNAL MECHANICAL VIBRATION FOR ALL CONCRETE. LIMIT MAXIMUM FREE FALL DROP OF CONCRETE TO 6-0" FOR #57 AGGREGATE AND 8'-0" FOR #8 AGGREGATE. ALL PRECAUTIONS SHOULD BE TAKEN TO AVOID SEGREGATION OF CONCRETE DURING PLACEMENT. RC-28 FOOTING SIZES SHOWN ARE FOR FOOTINGS CONSTRUCTED WITH SIDE FORMS. IF SOIL MATERIAL CAN HOLD A VERTICAL SHAPE, IT CAN BE USED AS AN EARTH FORM PROVIDED FOOTING WIDTH IS INCREASED 1" IN EACH HORIZONTAL DIRECTION. ALL SLOUGHED MATERIAL SHALL BE REMOVED FROM EXCAVATION BEFORE AND DURING PLACEMENT OF CONCRETE. RC-29 PLACEMENT OF CONDUIT AND PIPES IN CONCRETE SHALL CONFORM TO ACI 318, SECTION 20.7 GRADE BEAM SCHEDULE MARK BEAM SIZE REINFORCEMENT STIRRUPS REMARKS WI T DEPTH TOP OF BEAM ELEVATION TOP BARS "C" OR "E" BARS LEFT "C" OR E" BARS RIGHT SOT BARS uDu BARS SIZE TYPE SPACING GB1 24" 24" VARIES 346 346 #3 12" O.C. GB2 24" 24" VARIES 346 346 #3 8" O.C. GB3 24" 24" VARIES 346 346 #3 8" O.C. GB4 24" 24" VARIES 346 346 #3 16" O.C. NOTES: 1. STIRRUPS CAN BE DISCONTINUED WITHIN MIDDLE 1/3 OF SPAN 2. BEAM DEPTH IS ADJUSTABLE. SET BOTTOM OF BEAM AT A MINIMUM OF 6" BELOW GRADE. 24" MINIMUM BEAM DEPTH. ** CONTRACTOR TO VERIFY ALL BEAM SIZES PRIOR TO CONSTRUCTION REPORT ANY DISCREPANCIES TO ENGINEER 0.25 LN-1 CONTINUOUS IF SHOWN "T" BARS a as 4 a 4 / "B" BARS U) GREATER OF 0.33 LN-1 U) UJ OR 0.33 LN-2 OR Q z CONTINUOUS IF SHOWN "B" BARS CONTINUOUS OVER _J U GRADE BEAMS UNLESS SPLICE REQ'D H "T" BARS a 4 a a 4 a a a � a 4 a 4 2" CLR W/ VAPOR BARRIER ° a a a4 3" CLR W/O VAPOR BARRIER "M" BARS a 4 a a 4 e LN-1 BAR DESIGNATION: 4T16 WHERE 4 INDICATES SIZE OF REINFORCING BAR MIN MIN 6" / T LOCATION OF BAR (T=TOP, B=BOTTOM, M=MIDDLE) 16 INDICATES BAR SPACING IN INCHES TYPICAL STRUCTURAL SLAB ON GRADE REINFORCEMENT MIN 6" LN-2 LAP SPLICE LENGTHS BAR NO. fc' 3 4 5 6 7 8 9 10 COMPRESSION LAP SPLICE 3000 12 15 19 23 27 30 34 39 CLASS A TENSION LAP SPLICE 3000 13 17 21 25 36 42 47 53 4000 11 15 18 22 32 36 41 46 5000 10 13 16 20 28 32 36 41 CLASS B TENSION LAP SPLICE 3000 16 22 27 33 47 54 61 68 4000 14 19 23 28 41 47 53 59 5000 13 17 21 25 37 42 47 53 a 4 LN-3 CANT STRUCTURAL -ENGINEERING- MK STRUCTURAL ENGINEERING 587 WEST EAU GALLIE BLVD SUITE 201 MELBOURNE, FL 32935 P: 321.600.0672 OR 321.574.2702 www.mkstructural.com Certificate of Authorization#: CA 27800 project number MK21-152 O' N EAL RESIDENCE 38 SOVEREIGN WAY FT PIERCE, FL 32949 issued for date PERMIT SET 06/16/2021 This document is the property of MK Structural Engineering. MK Structural Engineering retains all rights therein, including copyrights. It is not to be reproduced or copied in whole or in part. It is not to be used on any other project and is to be returned upon request. It may only be used in a manner consistent with MK Structural Engineering's rights while MK Structural Engineering is providing services for the specific project identified or referred to herein or extensions thereto. It may not be used for any other purpose except with the express written agreement of, and compensation to, MK Structural Engineering. Unauthorized use will be prosecuted pursuant to the copyright laws. scale AS NOTED sheet title STRUCTURAL NOTES seal/signature ®a0%pII0IIpp�®® P,RAM _® No.601133 ° m �1 MICHAEL A. KALAJIAN ° �o M e FL. REG. ND. #601 3''3 %®� pDATE: AEJG 12, 2021°°��® ® 00 ° STATE OF AL Registered Engineer: Michael A. Kalajian Registered Engineer License: PE 60133 sheet number S1 SCALE 1/2"=V-0" drawn bv: NMC checked bv: MAK by MK Structural Engineering, LLC. all rights reserved. WHEN PLOTTED AT FULL SIZE THIS SHEET MEASURES 24" x 36" co STRUCTURAL ENGINEERING- MK STRUCTURAL ENGINEERING 587 WEST EAU GALLIE BLVD A B C T2'- E F SUITE 201 MELBOURNE, FL 32935 P: 321.600.0672 OR 321.574.2702 www.mkstructural.com 20' 4" 4'-4" 7 _g 10$' 14'-5$" g _4" 5'-2" 4'-6" 10" 10' 6" k TCertificate of Authorization#: CA 27800 project number MK21-152 O'NEAL 0 RESIDENCE 9 0 38 SOVEREIGN WAY FT PIERCE, FL 32949 14" DIA ot Joe issued for date PERMIT SET 06/16/2021 (1)#7 This document is the property of MK Structural Engineering. °? MK Structural Engineering retains all rights therein, including `n 14" DIA. AUGER CAST copyrights. It is not to be reproduced or copied in whole or in PILING, SEE DETAIL A/S2. part. It is not to be used on any other project and is to be returned upon request. It may only be used in a manner TYPICAL consistent with MK Structural Engineering's rights while MK Structural Engineering is providing services for the specific TOP OF PILE project identified or referred to herein or extensions thereto. e e It may not be used for any other purpose except with the a 4 express written agreement of, and compensation to, MK a Structural Engineering. Unauthorized use will be prosecuted a pursuant to the copyright laws. 4 revisions 56 KIPS COMPRESSION, d 14" DIA AUGER CAST PILE e ° item description p date W/ 5,000 PSI GROUT-4 FIELD ° J� REVISIONS 08/12/21 d ° N 5 _ a Z W J a X O 4 e d a DISCONTINUE #7 BAR AT 5'-0" ° 4 ABOVE BOTTOM OF PILE scale M N 44 ° ° AS NOTED d e 4 e sheet title PILE LAYOUT ad PLAN L, PILE TIP ih 7 N �ITYPICAL PILE DETAIL SCALE 1/2"=1'-0" seal/signature CID 7. 11, 48 g ®®�p84�OVO4�04p NPAM ° °° o �,prEN,9,p00, ° � m °EO m No. 60133 ° MICHAEL A. KALAJIAN 60' of a #2D21o��® -DATE ALJG 1D2 °°40Ro®�'°°°°°°°O�� ®�, PILE LAYOUT PLAN SCALE: 1/4"=V-0" Registered Engineer: Michael A. Kalajian Registered Engineer License: PE 60133 sheet number S2 drawn by: NMC checked by: MAK by MK Structural Engineering, LLC. all rights reserved. WHEN PLOTTED AT FULL SIZE THIS SHEET MEASURES 24" x 36" 04' 0" GRADE BEAM PLAN 1NDATION WORK SHALL NOT BEGIN UNTIL %L ARCHITECTURAL DRAWINGS AND OTHER gSTRUCTION DOCUMENTS ARE REVIEWED FHE ENGINEER OF RECORD TO VERIFY 1NDATION DESIGN. FOUNDATIONS ARE 3JECT TO CHANGE BASED ON 'ERSTRUCTURE LOADS PROVIDED IN 2. VERIFY ALL WINDOW AND DOOR OPENING LOCATIONS WITH FINAL ARCHITECTURAL PLANS SCALE: 1 /4"=1'-0" STRUCTURAL ENGINEERING MK STRUCTURAL ENGINEERING 587 WEST EAU GALLIE BLVD SUITE 201 MELBOURNE, FL 32935 P: 321.600.0672 OR 321.574.2702 www.mkstructural.com Certificate of Authorization#: CA 27800 project number MK 21-152 O' N EAL RESIDENCE 38 SOVEREIGN WAY FT PIERCE, FL 32949 issued for date PERMIT SET 06/16/2021 This document is the property of MK Structural Engineering. MK Structural Engineering retains all rights therein, including copyrights. It is not to be reproduced or copied in whole or in part. It is not to be used on any other project and is to be returned upon request. It may only be used in a manner consistent with MK Structural Engineering's rights while MK Structural Engineering is providing services for the specific project identified or referred to herein or extensions thereto. It may not be used for any other purpose except with the express written agreement of, and compensation to, MK Structural Engineering. Unauthorized use will be prosecuted pursuant to the copyright laws. scale AS NOTED sheet title GRADE BEAM PLAN seal/signature NRAM No. 60133 MICHAEL . ALAJIAN e A FL. REG. ND. #6013.t -E)ATE: ALJG 1 2, 2021 ® CO STATE OF �92 ® ®e DNQL e®®® Registered Engineer: Michael A. Kalajian Registered Engineer License: PE 60133 sheet number S3 drawn bv: NMC checked bv: MAK by MK Structural Engineering, LLC. all rights reserved. WHEN PLOTTED AT FULL SIZE THIS SHEET MEASURES 24" x 36" CONTINUE E LAP 8" MA; FORM AND CURE GRADE BEA 6vu STEP IN BEAM v TYPICAL STEP IN GRADE BEAM GARAGE GRADE BEAM #5 AROUND DEPRESSION #5 Z-BAR TOP @ 12" O.C. AT DEPRESSIONmom 001F ° 6" STRUCTURAL SLAB All - TYPICAL SLAB DEPRESSION SCALE 3/4"=1'-0" TOP OF SLAB SEE PLAN SCALE 3/4"=1'-0" STRUCTURAL SLAB TOP OF SLAB SEE PLAN SCALE 3/4"=V-0" I:e3:7\el PILE OR COLUMN StJPPnRT TERMINATE ALL LONGITUDINAL RADE BEAM REINF W/ 90° HOOK HOOK PILE REINF IN TYPICAL GRADE BEAM CORNER 10" VERIFY W/ DOOR MANUF. '*G% GARAGE GRADE BEAM STRUCTURAL SLAB, SEE INTERIOR GRADE BEAM TOP OF SLAB SEE PLAN J �gH U U H U SCALE 3/4"=V-0" TOP OF SLAB h SEE PLAN SEE SCALE 3/4"=V-0" SCALE 3/4"=V-0" GRADE BE TYPICAL GRADE BEAM INTERSECTION GRADE BEAM, SEE EXTERIOR GRADE BEAM STEP IN SLAB STRUCTURAL SLAB, SEE SCALE 3/4"=V-0" TOP OF SLAB SEE PLAN J �Q U J U U U SCALE 3/4"=V-0" SCALE 3/4"=V-0" J U J GRA FOR ALL PILES THAT TERMINATE IN GRADE BEAMS, HOOK PILE REINF W/90° HOOK IN DIRECTION OF GRADE BEAM GRADE BEAM, SEE SCHEDULE FOR REINF BEAM WIDTH a a a STRUCTURALSLAB, SEE PLAN FOR REINF AUGER CAST PILE TYPICAL PILE CONNECTION STEP IN SLAB TOP OF SLAB SEE PLAN J Q �a U J C0 H U SCALE 3/4"=V-0" 8" MAc FORM GRADE BEAM FROM SOIL IF SURFACE UNEXPOSED GRAD SCALE 3/4"=V-0" 8" MASONRY WALL BY OTHERS U w EXTERIOR GRADE BEAM STRUCTURAL SLAB, SEE FOUNDATION PLAN • a d a a a ° , a 4 a a o� GRADE BEAM, SEE PLAN STEP IN SLAB AUGERCAST PILE 1 >m .Q >co FOP OF SLAB SEE PLAN J � Q UJ U) STRUCTURAL �ENGINEERING— MK STRUCTURAL ENGINEERING 587 WEST EAU GALLIE BLVD SUITE 201 MELBOURNE, FL 32935 P: 321.600.0672 OR 321.574.2702 www.mkstructural.com Certificate of Authorization#: CA 27800 TOP of project number SEE PLA MK 21-15 2 O' N EAL RESIDENCE 38 SOVEREIGN WAY FT PIERCE, FL 32949 SCALE 3/ issued for date PERMIT SET 06/16/2021 This document is the property of MK Structural Engineering. MK Structural Engineering retains all rights therein, including copyrights. It is not to be reproduced or copied in whole or in part. It is not to be used on any other project and is to be returned upon request. It may only be used in a manner consistent with MK Structural Engineering's rights while MK Structural Engineering is providing services for the specific project identified or referred to herein or extensions thereto. It may not be used for any other purpose except with the express written agreement of, and compensation to, MK Structural Engineering. Unauthorized use will be prosecuted pursuant to the copyright laws. scale AS NOTED SCALE 3/4"=V-0" sheet title FOUNDATION DETAILS seal/signature NRAM ®®�p84�OVO4/OOp No. 60133 e � e MICHAEL A. KALAJIAN ° a lJ °° FL. REG. ND. #601 3t oDATE: ALJG 1 2, 2D211 ® OO ° STATCF OF Registered Engineer: Michael A. Kalajian Registered Engineer License: PE 60133 sheet number S4 drawn by: NMC checked by: MAK by MK Structural Engineering, LLC. all rights reserved. WHEN PLOTTED AT FULL SIZE THIS SHEET MEASURES 24" x 36"