HomeMy WebLinkAboutMayrides 9632 Enclave Generator App1' - 6"3' - 4"1' - 6"1' - 6 3/4"7' - 2 1/4"1' - 3 1/2"9 7/8"2' - 1 5/8"1' - 8 1/16"6 1/16"1' - 11 3/4"6 1/16"1' - 8"
6' - 4"1' - 6 3/4"9' - 10 1/2"1' - 6 3/4"13' - 0"9 1/16"9 1/8"7 3/16"2' - 1 5/8"6' - 3 5/8"1' - 3 3/4"5' - 4 5/8"GEN SET CONTROL
MIN (2) 3/4" PIPE W/SPACE TO ADD
COUPLERS TO BOTH PIPES
(2) 20A 120V STRANDED WIRE CIRCUITS
MIN (2) 1" PIPE W/SPACE TO ADD
COUPLERS TO BOTH PIPES
240V FROM ATS
MULTIPLE WIRES FOR 350A
NO TRIMING WIRES
CONDUITS: (1) 3" (2) 2 1/2"
W/SPACE TO ADD COUPLERS
GAS INLET LOCATION
NO SLAB CUT OUT
RUN LP IN HARDPIPE ON TOP
OF SLAB FASTEN PER CODE
CUMMINS 80KW 350A BREAKER
CUL DE SAC
GOLF COURSE
COOLING AIR INLET
CLEARENCE 36"
FROM END OF UNIT
COOLING AIR OUTLET
CLEARENCE 36"
FROM END OF UNIT
FINISHED SLAB HEIGHT MIN. 8" ABOVE SOD
SLAB MIN. 6" THICK 3000# CONCRETE FIBERMESH
ELECTRICAL RISER
TO FPL TRANSFORMER
(2) 2 1/2" CONDUIT
W/ (3) 350 MCM THHN CU
W/ (3) 350 MCM THHN CU
(2) 2 1/2" CONDUIT
IN EACH (VERIFY w/ FPL)
(1) 2" CONDUIT
W/ (3) 3/0 THHN CU
& (1) #6 CU GRND
#1 CU TIED TO EXISTING
GROUNDING ELECTRODE
CONDUCTOR & (2) 3/4" x 10'
COPPER GRND RODS MIN. 8' APART
IN EACH
METER
"MDP"
1∅
400A
120/240V120/240V
200A
1∅
"A""B"
1∅
200A
120/240V
NTS
400A
ATS
WITH
DISC.
TO STANDBY GENERATOR
(1) 3" CONDUIT
W/ (4) 2/0 THHN CU, (2) 1/0 THHN CU
& (1) #2 CU GRND W/CONTROL
WIRING
INSTALL & CONNECT (1) 10'
COPPER GROUNDING ROD
TO GENERATOR CHASIS
GROUNDING LUG
ScaleVILLADELTA CONSTRUCTION CORP. LLC CRC 058035THE DESIGN PROFESSIONAL OF RECORD (ENGINEER AND/OR ARCHITECT) ASSUMES ALL RESPONSIBILITY OF THE SPECIFICATIONS CONTAINED HERE IN. IT IS THE CLIENT'S AND/OR CONTRACTOR'S RESPONSIBILITY TO VERIFY THE FINAL PLANS AND MEASUREMENTS. ALL CHANGES FROM THIS POINT FORWARD WILL NEED A SIGNED CHANGE ORDER BEFORE ANY ADDITIONAL WORK OR MODIFICATIONS WILL BE MADE. ALL WRITTEN CHANGE ORDERS SUPERCEED THE DRAWINGS. THE DRAWINGS ARE CONCEPTUAL DESIGNS AND MAY VARY FROM THE FINISHED PROUCT. THESE DRAWINGS ARE THE PROPERTY OF THE DISIGNER AND SHALL NOT BE REPRODUCED, MODIFIED OR ALTERED WITHOUT PRIOR WRITTEN CONSENT. THESE DRAWINGS WILL REMAIN THE PROPERTY OF THE DESIGNER EVEN IF THEY ARE NOT USED IN THE CONSTRUCTION OF THIS PROJECT. COPYRIGHTT 2016 PRONTO PLANS, L.L.C._________________________________ ___________________________________CLIENT'S APPROVAL DATE CLIENT'S APPROVAL DATEAs indicated
10/8/2021 2:21:35 PM
E-49632 Enclave CirclePort Saint Lucie, FL 34986Thomas & Miriam Mayrides 1/2" = 1'-0"1Generator Pad
1/4" = 1'-0"2Generator w/Automatic Transfer Switch
SPECIFICATIONS AND
INSTALLATION MANUALS
SUBMITTED AS SEPARATE
PDF FILES