HomeMy WebLinkAboutFire Alarm System Plansi CD �e i W 0 Lu CRISTELLE CAY CONDOMINIUM -SAILFISH BLDG. � 7 FIRE ALARM SYSTEM GENERAL NOTES 1, ALL WALL -MOUNTED VISUAL SIGNALING APPLIANCES SHALL BE MOUNTED SUCH THAT THE ENTIRE LENS IS NOT LESS THAN 80 IN. (2.03m) AND NOT GREATER THAN 96 IN. ABOVE THE FINISHED FLOOR (A.F.F.) PER NFPA 72 2016 CH. 1&5.5 ALL WALL MOUNTED AUDIBLE DEVICES SHALL BE A MINIMUM OF 90" A.F.F. TO THE TOP OF DEVICE PER NFPA 72 2016 (SECTION 18.4.8.1). AREAS HAVING MORE THAN 2 STROBES IN THE FIELD OF VIEW SHALL BE SYNCHRONIZED PER NFPA 72, SECTION 18.5.5.4.2. 2. SMOKE DETECTORS AND HEAT DETECTOR LOCATIONS ARE BASED ON SMOOTH CEILING WITH MAXIMUM HEIGHT OF 10 FEET UNLESS OTHERWISE NOTED. 3. STROBE LOCATION IS BASED ON 10 FOOT CEILING HEIGHT AND ARE INSTALLED ACCORDING TO NFPA 72 REQUIREMENTS UNLESS OTHERWISE NOTED. ANY DEVICES ON CEILINGS OVER 10 FT. WILL BE DERATED PER NFPA 72. 4. CENTER OF MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" ABOVE FLOOR LEVEL. 5. ALL EQUIPMENT SHALL BE U.L. LISTED. 6. ALL WIRING SHALL BE IN ACCORDANCE WITH N.E.C. AND AUTHORITIES HAVING JURISDICTION. 7. ALL JUNCTION BOXES SHALL BE SIZED IN ACCORDANCE WITH THE N.E.C. 8. ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT REQUIRE SERVICING, TROUBLE SHOOTING, ETC. 9. DO NOT DEVIATE FROM CONDUIT RUNS AS SHOWN ON FLOOR PLANS WITHOUT PRIOR APPROVAL FROM SYSTEM SUPPLIER. FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITIONAL PARTS, ENGINEERING, ETC. THAT ARE A RESULT OF CONDUIT RUN DEVIATIONS SHALL BE THE SOLE RESPONSIBILITY OF ELECTRICAL CONTRACTOR. 10. DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR -FLOW, NOR CLOSER THAN 3 FEET (900mm) FROM AN AIR SUPPLY DIFFUSER. 11. ALL DUCT SMOKE DETECTORS SHALL BE MOUNTED BY THE MECHANICAL: OR ELECTRICAL CONTRACTOR. DUCT DETECTORS EXPOSED TO THE WEATHER SHALL BE WEATHER PROTECTED BY THE MECHANICAL CONTRACTOR. ALL AIR VELOCITY TESTING SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR. 12. ALL 120 VAC POWER REQUIREMENTS FOR THE FIRE ALARM SYSTEM SHAI-L BE FURNISHED BY THE ELECTRICAL CONTRACTOR AND SHALL MEET ALL REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. 13. ALL FIRE ALARM DEVICE BACK BOXES, FIRE ALARM TERMINAL CABINETS, GUTTERS, JUNCTION BOXES AND ASSOCIATED SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. REFER TO FIRE ALARM SYMBOL LIST AND/OR MOUNTING DETAILS FOR ADDITIONAL INFORMATION. SYSTEM SUPPLIER PROVIDED BACK BOXES SHALL BE INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. 14, SMOKE DETECTOR TESTING SHALL BE ACCOMPLISHED WITH SMOKE OR LISTED AEROSOL APPROVED BY THE MANUFACTURER PER NAFP 72, AS ACCEPTABLE BY THE A.H.J. 15. ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION. THE FIRE ALARM CONTROL PANEL TO SUPERVISE THE ANNUNCIATOR PANEL, ALL INITIATING AND INDICATING DEVICE CIRCUITS. 16. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE LOOPED THROUGH DEVICES. 17. POINT AND COMMON ANNUNCIATION AND T-TAPPING ARE PROHIBITED. (T-TAPPINGON ADDRESSABLE STYLE 4 SLC LOOPS). 18. THE ALARM SYSTEM SHALL HAVE AN AUDIBILITY OF NOT LESS THAN 15dB ABOVE AMBIENT NOISE LEVELS, BUT NOT LESS THAN 75dB THROUGHOUT AREA OF ALARM. TESTING SHALL BE ACCOMPLISHED WITH A dB METER. WHERE APPLICABLE, AUDIBLE TONE WILL BE TEMPORAL PATTERN. 19. FIRE ALARM SIGNAL SHALL MEET ANSI S3.41. AUDIBILITY EMERGENCY EVACUATION SIGNAL (TEMPORAL PATTERN) 20. ALL CONDUITS ARE 3/4" UNLESS OTHERWISE NOTED. 21. ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED PER MANUFACTURERS SPECIFICATIONS. 22. SYSTEM SHALL BE FURNISHED AND INSTALLED BY AN AUTHORIZED DISTRIBUTOR. 23. TAMPER PROOF SCREWS OR OTHER APPROVED MECHANICAL MEANS SHALL BE USED ON ALL COVERS OF EXTERIOR ELECTRICAL JUNCTION BOXES IN LIEU OF ELECTRICAL SUPERVISION OF THE COVERS. PER THE 2016 NFPA 72 23.8.5.11.1. 24. ELECTRICAL POWER SERVICE SHALL BE ON A DEDICATED BRANCH CIRCUIT(S) AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED (CIRCUIT BREAKERS SHALL BE LOCKED IN THE ON POSITION WITH AN APPROVED MECHANICAL CLIP). CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT-" THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT. 25. UPON COMPLETION OF ALL INSTALLATION AND TESTING, THE CONTRACTOR SHALL PROVIDE TO THE AUTHORITY HAVING JURISDICTION AND THE BUILDING OWNER A COMPLETED AND SIGNED NFPA 72 CERTIFICATE OF COMPLETION. 2& SECTION 17.7.1.11.3 OF THE 2016 EDITION OF NFPA 72 STATES THAT "WHERE DETECTION IS NOT REQUIRED DURING CONSTRUCTION, DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER ALL OTHER CONSTRUCTION TRADES HAVE COMPLETED CLEANUP." 27. IN -BUILDING PUBLIC SAFETY RADIO SYSTEM ENHANCEMENT, IF REQUIRED, SHALL BE FURNISHED AND INSTALLED BY OTHERS. PROJECT SCOPE OF WORK 1. INSTALLATION OF NEW FIRE ALARM CONTROL PANEL & BOOSTER PANEL. 2. INSTALLATION OF NEW FIRE ALARM SYSTEM INITIATION DEVICES, (SMOKE DET., HEAT DET., PULL STATIONS, INTERFACE MODULES) 3. INSTALLATION OF NEW FIRE ALARM SYSTEM AUDIBLE/VISUALS, & VISUAL DEVICES. 4. MONITOR MODULES FOR CONNECTIONS TO WATERFLOW SW., TAMPER SW., TO BE PROVIDED. CONNECTIONS BY OTHER. 5. 120VAC POWER CONNECTION TO BE PROVIDED BY DEDICATED CIRCUIT. 6. CELLULAR COMMUNICATOR TO BE PROVIDED FOR CENTRAL STATION MONITORING. 7. PROGRAMMING OF FIRE ALARM SYSTEM TO OPERATE AS SHOWN IN SEQUENCE OF OPERATIONS. APPLICABLE CODES / STANDARDS PARTIAL LIST OF APPLICABLE NFPA STANDARDS NFPA 72-National Fire Alarm Codes (2016 Edition) NFPA 101-Life Safety Code (2018 Edition) 2020 Florida Fire Prevention Code 7th Edition FIRE ALARM SYSTEM FORT PI ERC E, FIL 34981 TOTALALARM STANDBY CURRENTALARM CURRENTPER CURRENT PER PERUNIT UNIT(AMPS) ..UNIT (AMPS) (AMPS) OPTICA SMOKE DET HEAT OR � � �' !It#r #rrr r r # #Irr �INTELLIGENT CC) DETECTOR ACTION t rr! t r rrr r r rlt�lr # rr rr, MODULEINPUT rrr# # r rt '! ! ttt�tt rrr•,rr�'� MODULE® 0,000396i rrr .r r #r1.«r rrr rr ,CONTROL (r;« � _ r#�ri 1 r!# r rrrr rlrr CONTROL RELAY 0.0000751 0.000075 0.000075 ! 000075 TOTALALARM TOTAL ► CCURRENT (AM• 1 .' • REQUIRED TOTAL SYSTEM STANDBY REQUIRES ALARM TIME TOTAL SYSTEM REQUIRED ALARM CAPACITY (AI1P REQUIRED STANDBY TIME (HOURS) STANDBY CURRENT CAPACITY ALARM CURRENT (MINUTES) HOURS) (AMPS) (AMP (AMPS) OURS) 24.00 0.178029 1 4.27 1 15.00 1 0.276639 1 0.07 REQUIRED ALARM TOTAL REQUIRED REQUIRED BATTERY 2 X 12 VOLT BATTERIES INSTALLED REQUIRED STANDBY CAPACITY (AMP HOURS) CAPACITY (AMP SAFETY FACTOR CAPACITY CAPACITY (AMP AMP/HR RATING PART# HOUR) (AMP UQUES) 7.00 12V 7A 4.27 0.07 4.34 20% FRCP BATTERY CALCULATIONS PROJECT CRISTELLE CAY CONDOMINIUM - SAILFISH BLDG. , �/ -- /st Fires & Security,,C. Life Safet), Powered BY Service ADDRESS 4810OCEAN PALMS DR. CITY,ST,ZIP FORT PIERCE, FL 34981 STANDBY 11• s 04ALARMTOTALALARM CURRENT >+ CURRENTPER CURRENTPER PER UNIT a ).. sUNIT(AMPS) . .: I -REMOTE -POWER SUPPLY �G �GENESIS HORN/STROBEOUTDOOR �� # !rlt## r i!�!!1#• ! « :1ri FREQUENCYGENESIS LOW 1 0000 00000001 t 0 4032000i TOTAL STANDBY , CURRENT CURRENT ' 0.0 70000 " Irl1- REQUIRED TOTALSYSTEM STANDBY REQUIRES TOTALSYSTEM REQUIRED ALARM CAPACITY (AMP REQUIRED STANDBY TIME (HOURS) STANDBY CURRENT CAPACITY ALARMTIME ALARM CURRENT HOURS) (AMPS) (AMP (MINUTES) (AMPS) HOURS) 24.00 1 0,070000 1 1.68 1 15.00 1 6.230000 1 1.56 REQUIRED STANDBY CAPACITY (AMP HOURS) REQUIRED ALARM CAPACITY (AMP TOT AL REQUIREDSAFETY i. FACTOR REQUIRED BATTERY 2 X 12 VOLT BATTERIES INSTALLED C4 F AtlY`t" CAPACITY (AMP AMP/HRRATING PART# HOUR) MP HOURS) 7.00 12V7A 1.68 1,56 3.2" 20% 3.$9 BPS BATTERY CALCULATIONS 333 Bayview AvenueAmityville,pars(New York 11701 For Sales and icL(8 Repairs, Starl-ink SLE-LTEV-CFB-PS Fire Alarm For Technical Sernce, (800) 645-9440 a visR us at htto:fltech.naocosecuritv.coml IVAPCO (Note. T�hiclytradedronNASDAQuftPro NSSCsontY) Communicator Standby Battery Calculations ONAPGo2019 W12335LF 4/1f Standby Current Calculations for the model SLE-LTEV-CFB-PS Fire Alarm Communicator: • Standby Battery Capacity: ...................................... 7AH • Standby Current Draw of Communicator: ............. 85mA • De -rating Factor: ...................................................... 0.80 Standby Time (Hours) = Battery Capacity x 0.80 = 65.9 Hours Communicator Current Draw Examples: 4 AH battery = (4AH / 0.085A) x 0.80 = 37.6 Hours 7 AH battery = (7AH / 0.085A) x 0.80 = 65.9 Hours CELLULAR COMMUNICATOR BATTERY CALCULATIONS PROJECT NAME PANEL NAC Circuit 2 3 4 co z 0 U) W It CV U c� co Z _ U U cn W = N J t W0 00 J z �C 0 0 -1W 0 W z LU = Ed a = u- a Q Q Uwe W rn a U) W W Z c� z W RECEIVED •dry C! i Y , %_'s � '�.• w F � �..'�,� t a.. i � .. 1 P ... �. si �- r 1 EtAI �Sffire & Securttyrwc, Life Safety Powered By Service CRISTELLE CAY • saBLDG. * taken from NEC Chapter 9 Table 8 ** calculated for resistance over 2 conductors Wire AWG & Type Ohms Per 1000 Ft. * Length(ft) One -Way 14ga Solid 3.19 200 14ga Solid 3.19 510 14ga Solid 3.19 530 tarting Actual Volts Ccv %Drop oltage Ohms** EOL 24.0 1.28 23.74 1.06 24.0 3.25 17.75 26.03 24.0 3.38 17.51 27.05 0 STp�REV� " Total ,rerrt {A 1.92 DATE: 1-92 EL E 14ga Solid 3.19 550 24-0 1 3.51 17.26 1 28.07 1.92 BATE:zI Maximum Current per NAC Circuit = 2.500 Amps PLUNis: BPS MODEL 10/A I AVAIL AMP 1 101 PERCENT USED 1 60% pQ►TE' I MECK: NAC-1 G4AVRF-75-110 GENESIS LED G4 HORN STROBEi75/110 CD 41 Alarm: mA 50 f, . . >.. .. mA Current Subtotals: mA G4AVWF-75-110 GENESIS LED G4 HORN STROBE175/110 CD 2 Alarm: mA 50 r mA 100 WG4WF-HVMC-35 GENESIS HORN-STROBEtWP OUTDOOR\RED135cd 2 Alarm: mA p ; mA 238 476 G4LFWN-H GENESIS LOW FREQUENCY HORN 12 Alarm: mA , , 4 �,.. � x_,�, mA 112 1344 Current Subtotals: mA w G4AVWF-75-110 GENESIS LED G4 HORN STROBE175/110 CD 2 Alarm: ►rA 50 " mA 100 GENESIS HORN-STROBEIW'P OUTDOOR\REM35cd 2 Alarm: mA GENESIS LOW FREQUENCY HORN 12 Alarm mA , ' WG4WF-HVMC-35 238 mA 476 G4LFWN-H 112, ,` ¢.,; EA 1344 £`r:sXk _,,rent jbtotals i ti G4AVWF-75-110 GENESIS LED G4 HORN STROBE`75,m 110 CD 2 Alarm. A 50 " �;°', , `"tA • =; n.='-, mA 100 476 WG4WF-HVrAC-35 GENESIS HORN-STROBEIWP OUTDOOMREM35ccl _ 2 Alarm: mA 238 G4LF1l N-H GENESIS LOW FREQUENCY HORN 12 Alarm: mA 112 = x`" mA 1344 •; Current Subtotals: n-A 1920 BPS VOLTAGE DROP CALCULATIONS IDATE� CO 0 z tC) 00 .. 1 a- LLI zW W ~ EL z ELI W W 000 N Drawing Nurn 1 OF 5 NOTES: F 120V SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX QTY HEIGHT FACP FIRE ALARM CONTROL PANEL i01000 1 PROVIDED 66" A.F.F. BPS REMOTE BOOSTER POWER SUPPLY BPS10A 1 4" SQUARE 1-1/2" DEEP 66" A.F.F. SD PITCAL SMOKE DETECTOR W/BASE SSIGA -SB4 3 1-1/2""UDEEP ARE CEILING OHD HEAT DETECTOR SIGA-HRD 2 4" SQUARE 1-1/2" DEEP VERIFY IN FIELD SIGA-COD/ 1 4" SQUARE CEILING CO INTELLIGENT CO DETECTOR SIGA-SB4 1-1/2" DEEP p DOUBLE ACTION PULLSTATION SIGA-278 3 1 GANG 1-1/2" DEEP 48" A.F-F- CT1 SINGLE INPUT MODULE SIGA-CT1 11 1 GANG STANDARD VERIFY IN FIELD CT2 DUAL INPUT MODULE SIGA-CT2 5 1 GANG STANDARD VERIFY IN FIELD CONTROL RELAY MODULE SIGA-CR 3 1 GANG STANDARD VERIFY IN FIELD (RH HIGH POWER CONTROL RELAY MODULE SIGA-CRH 1 4" SQUARE 2-1/8" DEEP VERIFY IN FIELD ❑'� WEATHERPROOF. DOUBLE ACTION PULLSTATION MPSR2-S45W-GE 6 PROVIDED 48" A.F.F. vp HD WEATHERPROOF, HEAT DETECTOR/BASE AP-P 302-AW-135/ 3 PROVIDED CEILING FHS HORN STROBE G4AVWF 10 1 GANG STANDARD 80" A.F.F. WEATHERPROOF HORN STROBE WG4WF-HVMC 6 4 OUTDOOR RATED 80" A.F.F. HS PROVIDED =LF H LOW FREQUENCY HORN G4LFWN-H 36 4" SQUARE 2-1 8" DEEP 80" A.F.F. O TAMPER SWITCH F.B.O 5 ----- --_-- OWATERFLOW SWITCH F.B.O 4 ----- ----- DOC SYSTEM RECORD DOCUMENTS SS000689 1 ����� ����� on VOLTAGE SURGE PROTECTOR ASCO 237 3 «LL CELL DIALER SLE-LTEV-CFB-PS 1 PROVIDED VERIFY IN FIELD DEVICE QUANTITIES REFLECT OVERALL PROJECT FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F DEVICE # B-1-, HS 75 CD .-- CANDELLARATING DEVICE SYMBOL r DEVICE ADDRESS SD 001 FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL OR EQUIVALENT B (SLC DATA LOOP) 18-2 FPL OR EQUIVALENT ALL CONDUITS 3/4" EMT. MINIMUM UNLESS OTHER WISE NOTED. 40% FILLED MAX. LIVING RM.� LIVING RM. LIVING RM. j 7, I BEDROOM BEDROOM I BEDROOM l ,- ; 2A 2 B 2 C I I :� 1i 1-Ja 1v' sssii F ;- I , r : o l f ICE CL. +, -- - - - - - - _- _ TT -T - I - - i z- r KI71CHEN_ - — ��TCHEN �} - � �' _— � i +-�ITCH�N i W.I,C W i .I. )Ji C'L I I 1F P C : , 1 _ C L. } C L I _ phl i -'_:•—: J.__. ___ r '...it if \ - - -- - -- ; 4-11 \ s - -- -- - I 0 t { j I R—Yr �. I `~rI -__BATHBA - HBATH OATH BAT - j_- GL.-,C BEDROOM } , E TRY BEDROOM BEDROOM � BEDROOM , BEDROOM � NR ;ELEV - - -- -- ., I l -, ' -- BEDROOM _� 4P R - _lE'7 C I --- - --, -�- , - Io _•iY'�Iht -- L- TIS1E2s It 1 R., HALLWAY EXACT LOCATION T.B.D 4fi I)A. �I�_ - -- - - 1i;Nhn -.-. - , __ - .FROM cE 'RAGE DATA OOP IA H E aA _., ,,, 2ND FLOOR — DEVICE LAYOUT N s SCALE: 1/8" = 1'-0" 7p_lc w Lr---------j (ACT LOCATION EXACT LOCATION T.B.D T.B.D _ (� r I _ — — _ J BACK FLOW PREVENTER NTHOUSE) 0 w z E- C114 0 J Q U co O 2 H Q p 0 r;, q� LL p = U co z O co w N 0 CV U 00 Z LU r-+ J *k J >HLL W n C) U) LLi U U a�i "c J W U F- � J O Z U O r W U _wjQ W_j ;;zD w w -� =mom < a 0- a Z z w CID Ia Cl Co < LL_ Ljj Q z LLl LLJ LU F_ CL L 11 Ise O U- 0 z Cv 06 0 LL. w Li1 Q z < w Of w E GARAGE FLOOR — DEVICE LAYOUT N s SCALE: 1 /8" = 1'-0" 4 w NOTES: 120V SINGLE STATION SMOKE DETECTOR a (SUPPLIED & INSTALLED BY OTHERS) FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX CITY HEIGHT FACP FIRE ALARM CONTROL PANEL 101000 1 PROVIDED 66" A.F.F. BPS REMOTE BOOSTER POWER SUPPLY BPS10A 1 4" SQUARE 1-1/2" DEEP 66" A.F.F. SD PITCAL SMOKE DETECTOR W/BASE SIGA-OSD/ SIGA-SB4 3 4" SQUARE 1-1/2" DEEP CEILING OHD HEAT DETECTOR SIGA-HRD 2 4" SQUARE 1-1/2" DEEP VERIFY IN FIELD 1 4" SQUARE CEILING 0 INTELLIGENT CO DETECTORSIGA-COD/ SIGA-SB4 1-1/2" DEEP p DOUBLE ACTION PULLSTA11ON SIGA-278 3 1 GANG 1-1/2" DEEP 48" A.F.F. CTt SINGLE INPUT MODULE SIGA-CT1 11 1 GANG STANDARD VERIFY IN FIELD CT2 DUAL INPUT MODULE SIGA-CT2 5 1 GANG STANDARD VERIFY IN FIELD Q CONTROL RELAY MODULE SIGA-CR 3 1 GANG STANDARD VERIFY IN FIELD ❑� HIGH POWER CONTROL RELAY MODULE SIGA-CRH 1 4" SQUARE 2-1/8" DEEP VERIFY IN FIELD ❑P r WEATHERPROOF, DOUBLE ACTION PULLSTATION MPSR2-S45W-GE 6 PROVIDED 48" A.F.F. HD WEATHERPROOF, HEAT DETECTOR/BASE 302-AW-135/AP-P 3 PROVIDED CEILING HS HORN STROBE G4AVWF 10 1 GANG STANDARD 80" A.F.F. WEATHERPROOF HORN STROBE WG4WF-HVMC 6 OUTDOOR RATED 80" A.F.F. HS PROVIDED I H I� LJt LOW FREQUENCY HORN G4LFWN-H 36 ARE 2-1 8"UDEEP 80" A.F.F. O TAMPER SWITCH F.B.O 5 - / -- ----- OWATERFLOW SNATCH F.B.O 4 ----- ----- DOC SYSTEM RECORD DOCUMENTS SS000689 1 ----- ----- ua VOLTAGE SURGE PROTECTOR ASCO 237 3 ---- ----- umw CELL DIALER SLE-LTEV-CFB-PS 1 PROVIDED VERIFY IN FIELD DEVICE QUANTITIES REFLECT OVERALL PROJECT FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F CKT # DEVICE # B-1-1 HS 1 75 CD o CANDELLA RATING DEVICE SYMBOL SD 001 — DEVCE ADDRESS FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL OR EQUIVALENT B (SLC DATA LOOP) 18-2 FPL OR EQUIVALENT ALL CONDUITS 31,C EMT. MINIMUM UNLESS OTHER WISE NOTED. 40% FILLED MAX. LIVING RM, r BEDROOM PHA B-4-13 B-4-12 LFIF - �' H H i i I 1 • i KITCHEN— -i lI 13 ATH H B-4-14 j , LF L. BEDROOM E RY STAIR i ' I I CL. 47Kt2 I EOL.5 I - Cif - - i J BATH LIVING RM. BEDROOM B-4-9 1 1 1 B WICk r WIC r LIVING RM. BEDROOM i B-4 5 h .rn PHC r� !LF it l I! t C - 1 -- r I , �� !I � 7� ---K1TCH N C� 7 �i J 3 1 �I TH L BATH _. -4-3 H ly L.lrl • x 71 BEDROOM LF LF EN TRY I , r BEDROOM BEDROOM BEDROOM E ELEV ' B� ! - - BEDROOM I r �C4 �' y: �a' g-4-1� _ - Ji �� / .F is si �C. ��rn STAIR 2 ' HS - _ , HALLWAY 35CD - , FA RISER _ - 1 _ { r. EXACT LOCATION I TAD F 7�,R%( ry a;t I Rr N. : E 4TH FLOOR (PENTHOUSE) - DEVICE LAYOUT N S SCALE: 1/8" = 1'-0" 7pc w \-BPS NAC4 FROM GARAGE FLOOR .,CDATA LOOP FR , L C DATA LOOPTO " <,,)F - : LIVING RM. it -1 ! LIVING RM. LIVING RM. BEDROOM BEDROOM �1 BEDROOM r 3A B-3-13 B-3-12 El -! B-3-5 B-3-4 ' - LF LF _ LF ':Lf i --- If iLF H H H H ' H H 1 ; it- \.. C. _.. C.L. - CL - 1L } KI CHEiN - 4' = KITCHENf - C, _j _ IC W.IC W- C�. .�� CL.'' C..ry�L ;L i.. i 7 k i i I Y - -' - i DElr T i ATH BATH ATH' BAT; rBATH - BATHIj BATH „ __, \ - __ _._ B-3-14 - LF- — - _ 25 B-3 11 , ^' s a H i': __ H - B-3-6 HL _ BEDROOMLF ENTRY. BEDROOM I / _' H t � I� �:' •' '` BEDROOM i ENTRY I BEDROOM �� ;� Ii BEDROOM E RY,;:. � ELEV ' E OM : STAIR a �J . = CL. -- - CL :i AIR 2 1Ki - _ a HS - - - :H JS*�� E� , -,K c, HS HS HALLWAY FA RISER EOL 675CD8� B-3-15 - 35CD _ L CD __ _ - _ ...` EXACT LOCATION -_ f } T.B D I L 1.. ( I47Kii{f i P 47 �I E01 ! 5 4 ' i r L ,_I , I —I E 3RD FLOOR - DEVICE LAYOUT N S SCALE: 1/8" = 1'-0" w -BPS NAC3 FROM GARAGE FLOOR SLC DATA 3 O !ND FLOOR __SLC DATA LOOP ll1 P_)1 (PE_ T-HO13SE) 0 J Q z ~ W CID Z Y f!J O o' Fw- < =� W U zoo J *k J W a- J W �WU U a,(n ` J 0 Z W Up-j W LJLI �Z � w � -' 1.U) < g F- LL CL U 00 a g°'O cn a W _ W z - z W cn I ME 000 s) �l- I.I.. 0- LLj � 0 z 3 F-m 0 LLj 0 W 0 0 I1_ cNd Ct m 0 F_ @L W — — — — — — — — — — — — — — — — — SHUNTTRIP H — STATUS SHUNT TRIP FIREHAT ALTERNATE PRIMARY ?" —__ I F 1 _ Tat +r L-------------------- J ELEVATOR CONTROL E ROOF DEVICE LAYOUT N S 'SCALE: 1/8" = 1'-0" w FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BAf:KBOX QTY HEIGHT FACP FIRE ALARM CONTROL PANEL i01000 1 PPCV'DED 66" A.F.F. BPS REMOTE BOOSTER POWER SUPPLY BPS10A 1 4" SDI, ARE 4' SO AlDEE Ei6" A F". F. SD PITCAL SMOKE DETECTOR W BASE / SIGA-OSD/ SIGA-SB4 3 4" SQUARE 1-1/2" DEEP C_ILING HD HEAT DETECTOR SIGA-HRD 2 4" SQUARE 1-1/2" DEEP VERIFY IN =1ELD ~ SIGA-COD/ 1 4" SQUARE CEILING CO INTELLIGENT CO DETECTOR SIGA-SB4 1-1/2" DEEP �p DOUBLE ACTION PULLSTATION SIGA-278 3 1_1/2",NG DEEP 48" A.F.F. CTl SINGLE INPUT MODULE SIGA-CT1 11 1 GANG STANDARD VERIF`' IN ='ELD - CT2 DUAL INPUT MODULE SIGA-CT2 5 1 GANG STANDARD VERI Y IN FIELD CR CONTROL RELAY MODULE SIGA-CR 3 1 GANG STANDARD RI IN PELD CRH HIGH POWER CONTROL RELAY MODULE SIGA-CRH 1 4" SQUARE 2-1,/8" DEEP Fti N FIELD WEATHERPROOF, DOUBLE ACTION PULLSTATION MPSR2-S45W-GE 6 PROVIDED 48 A.F.F. HD WEATHERPROOF, HEAT DETECTOR/BASE 302-AW-135/AP-P 3 PROVIDED COILING HS HORN STROBE G4AVWF 10 1 GANG STANDARD HS WEATHERPROOF HORN STROBE WG4WF-HVMC 6 OU DRORRATED L� LOW FREQUENCY HORN G4LFWN-H 36 4" SQUARE 2-1,/8" DEEP 5;-11 q.F,F. OTAMPER SWITCH F.B.O 5 ------ --- -- V WATERFLOW SWITCH F.B.O 4 - --- ----- DOG SYSTEM RECORD DOCUMENTS SS000689 1 -- --- -� - Esc" VOLTAGE SURGE PROTECTOR ASCO 237 3 -- --- ----- CELL DIALER SLE-LTEV-CFB-PS 1 PROVIDED ER! ` IN FIELD DEVICE QUANTITIES REFLECT OVERALL PROJECT — FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F Cl It DEVICE # B-1-1 HS 1 75 CD �—CANDELLA RATING DEVICE SYMBOL rDEVICE ADDRESS SD 001 FIRE ALARM WIRE LEGEND — WIRE TAG WIRE USE A (NAC) 14-2 FPL OR EQUIVALENT B (SLC DATA LOGE-; 18-2 FPL OR EQUIVALENT ALL CONDUITS 3/4" EM-, MINIMUM UNLESS OTHER WISE tiC` 4O7 -LLED MAX. -- DATA. � c� SYSTEM OUTPUTS O� c�= p1k' O OJO� Al O -3P �Q- V Q V Q V Q V A A SYSTEM INPUTS A B C D E F G H I J K L M N 0 1. MANUAL FIRE ALARM BOXES • • • • • 2• SMOKE DETECTOR • • • • • 3. SMOKE DETECTOR — 1ST FL ELEV. LOBBY. • • • • • • 4. HEAT DETECTOR — ELEV. LOBBY. • • • • • • 5. CO OETCTOR 10 • 6. HEAT DETECTOR • • • • • 7. WATERFLOW • • • • • 8. SPRINKLER CONTROL VALVE (TAMPER SWITCH) • • • • 9. FIRE ALARM AC POWER FAILURE • • 10. FIRE ALARM SYSTEM LOW BATTERY • _• • • 11. OPEN CIRCUIT • • • 12. GROUND FAULT • • • 13. NOTIFICATION APPLIANCE CIRCUIT SHORT • • • SEQUENCE OF OPERATION NOTES: 1. FIRE ALARM CONTROL PANEL SHALL BE ANALOG ADDRESSABLE TYPE. 2. INITIATING DEVICE CIRCUIT SHALL BE CLASS "B". 3. NOTIFICATION APPLIANCE CIRCUIT SHALL BE CLASS "B". —-————————— — — — — —— — SHUNT TRIP PRIMARY ALTERNATE FIREHAT SHUNT TRIP STATUS I I __. _ _-___. 1. __ I 1 +-___—_._-, ti y, IT A C) I I jn Iz j L•--------------- ----J ELEVATOR CONTROL J. BOX ROOF ROOF LF If 1 A WwP —�-- H S 7 HST H H H H H H 1 B 75CD I 3 C 15KO wP LF LF LF LF LF EOL. H S 75cd H S H H H H H H 75 D 3 CD EXACT LOCATION T.B.D I1 i2 K_t? r r F Cf I Ol_. a fi J. BOX f — — — j L---��---J 4TH FLOOR 4TH FLOOR 1A H S TScdH� 1B,1A 75CD1 I 35 D I —_I 1 OL. qP LF LF LF LF LF EOL. H S H S H H H 15cd 35C0 H H H 75CD I 35CD EXACT LOCATION T.B.D --- --�� F 47K 47Kt` I 04'` `?4. �7K0 1 � _. —_ ------ �4 — �.—_ -- --- — J. BOX _ I I i I L — — ---J 3RD FLOOR 3RD FLOOR 1A _ - - - - - --- ! ---- - - a LF ;4 - 1 1 r — i -I -- r---- 1B 2A I Li u- =41 F3 5. 3 r E3 _oi [ P-- _ EXACT LOCATION T.B.D 47KO 147K , � I !-I D p 47 KO } b� EOL, a �, ,�_ EEL. Ft � ' � J. BOX L 2ND FLOOR lI U J. BOX I, 'o — - F' Lr ; L.'7 7:7f 2ND FLOOR Li EXACT LOCATION EXACT LOCATION �2) T.B.D T.B.D ® 1B I ----—_--_. SUf, <' ..._ _.._.... I 1 y :L I 14a t2 + m"�I a7K I - r p ' F _ L. BPS-1 DA ` WIRELESS CELL SIGNAL I I I DEDICATED C�/,TO CENTRAL STATION. © _ a. _.H"TxY-FAucT CELLULAR GROUND er>�1xs sAtnTCOMMUNICATOR suR DEDICATED I -31 I I L { �) # 12THHN M. __ ____ _.___"� STARLINK FIRE 72ovnc L �SLE—LTEV—CFB—PS (GREEN) � BACK FLOW L — — -- — — — J _ PREVENTER DEDICATED i01000GD 120VAC�—I SUR FACP GROUND (1) # 12THHN GARAGE FLOOR = (GREEN) RISER DIAGRAM GARAGE FLOOR 0 z w F- c' J .� Q W r Z Y 0 w ¢ Z a 0 U cn z 0 w o- 00 z w -M J_ it J w ;--i 2 > U- o_ U U U) U = ry _J , W U U J 0 z cC U O J W 2i F- W 3: U w J J ww Q LIJ J Q m N = J O 0- U co � a °' 0 a ., U) oc w w z 0 z w ca j 0-s uj U_ LU LIJ ED t-- 0 Ci CD ( Co EST 10 1000 MOUNT EST SIGA SERIES MODULES SIGH-CT1/CT2, SIGA-CR, SIGA-MM1 SIGH-WTM. TO STANDARD SINGLE GANG 1/1-2' DEEP ELECTRICAL BOX. THE TERMINALS WILL ACCEPT #14AWG WIRE. COMPATIBLE ELECTRICAL BOX EDL 4OHM MOUNT EST SIGH SERIES MODULES SIGH-CT1/CT2, SIGH-CR, SIGA-MM1 SIGA-WTM. TO STANDARD SINGLE GANG 1/1-2- DEEP ELECTRICAL BOX. THE TERMINALS WILL ACCEPT #14AWG WIRE. COMPATIBLE ELECTRICAL BOX NIIIATM NDEVVICE NIMIWG DEVICE INPUT 1 INPUT 2 / EDL 4OHM MOUNT EST SIGA SERIES MODULES SIGA-CTt CT2, SIGA-CR, SIGA-MM1 SIGA-WTM. TO STANDARD SINGLE GANG 1/1-2' DEEP ELECTRICAL BOX. THE TERMINALS WILL ACCEPT #14AWG WIRE. COMPATIBLE ELECTRICAL BOX 0 z J F- CCN Ui o co i O a s H 0 o Q Gr O w U i--�1 TB2 B 7 r- ,. 0 SIGA-CT1 A. ® OPTIONALLED o SELF-ADHESIVE ° FRENCH LABEL 1 10 VAC (NON —LIMITED) POWER LIMITED ONLY ° TB1 0' 0' WALL PLATE, WHITE 0 GANG) •ew ww s u as +>• _ FROM FACP .._ ___ _ 1- u o o w OR PIOUS DATA N(-) L CEILING MOUNTED SMOKE/HEAT DETECTOR 24" MIN HANDICAP BEDROOM STROBE I riwl MORE THAN TWO APPLIANCES IN THE SAME ROOM OR ADJACENT SPACE WITHIN THE FIELD OF VIEW SHALL FLASH IN SYNCHRONIZATION. o 0 T u Tr w DO NOT USE HOLES FIRE ALARM DEVICE MOUNTING GUIDE �3' (MIN) cEluBG_ A/C SUPPLY DIFFUSER ACCEPTABLE HkRE--� AUDIOVISUAL DO NOT INSTALL & VISUAL -ONLY IN THIS AREA DEVICES CEILING MOUNTED NOTIFICATION DEVICE. WALL MOUNTED SEE PLAN FOR LOCATION. SMOEK/HEAT DETECTOR- 96" MAX (NFPA. ADA) TO THE BOTTOM. ABOVE FINISHED FLOOR TO TOP OF LENS 5'-0 MAX FROM EXIT DOOR MANUAL J PULL MAGNETIC FIRE STATION DOO HOLDER PHONE JACK 5" DUCT I C DETECTOR DOOR 80" MIN (NFPA, ADA REMOTE TEST WIDTH LESS 3" ABOVE FINISHED FLOOR TO BOTTOM OF LENS o ® • FNISHED FLOOR IMPORTANT NOTE NOT ALL DEVICES SHOWN ON THIS DETAIL APPLY TO THIS PROJECT. SEE THE PLAN VIEW LAYOUT OF THE FIRE ALARM SYSTEM TO VERIFY WHICH DEVICES APPLY, AND WHICH DO NOT. STROBE OR SPEAKER/STR F O O IKY A.F.F. OR E O 6' BELOW CEILING (WHICHEVER IS LOWER) PULL STATION O 48' AF.F. O ADA HEIGHT REQUIREMENTS NO SCALE 12" (MAX) 48" MAX (NFPA, ADA) 42" MIN (NFPA) a o MEASUREMENTS SHOWN ARE if T TO THE TOP OF PULL HANDLE NOTE FIRE DEVICE MOUNTING DETAIL CHECK WITH MANUFACTURE'S INSTALLAnON SHEET N.T.S. FOR THE EXACT ROUGH -IN HEIGHTS, LOCATION OF BACK BOXES, AND WIRING REQUIREMENTS. WIRE STRIPPING GUIDE STRIP 1 /4" FROM THE ENDS OF ALL WIRES THAT CONNECT TO THE TERMINAL BLOCKS OF THE MODULE. 1 /4" DO NOT EXPOSE MORE THAN 1 /4" SIGA—CT1 MOUNTING DETAIL N.T.S. ...._~_.. TO NEXT am DuK-) DEVICE SINGLE INPUT MODULE WIRING DIAGRAM N.T.S. TYPICAL SPEAKER OCT. EDL 4OHM TB4 to • T83 SIGA-CC1 TIED m A!/OYUI HOOWL AC1� 8 T 8 8 4 3 2 1 TBi 0 0 0 0 T81 TO NEXT DEVICE OR _ RISM 00-1 EOL RESISTOR FROM FACP FROM FACP I r,-"�;.*:-_ OR PREVIOUS TO NEXT DEVICE DEVICE �A _ oA� aUX-) SINGLE INPUT RISER MODULE WIRING DIAGRAM N.T.S. COVER RELEASE SCREW COMPATIBLE ELECTRICAL BOX T82 J a SIGA-278 BACK o PLATE 0 0 TBt 4 s 2 t ° TOGGLE SWITCH e FROM FACP OR TO NEXT PREVIOUS DATA - l DATA art(-) DEVICE GLASS ROD DEVICE RELEASE LEVER MANUAL PULL STATION SINGLE MODEL — SIGA-278 STAGE WIRING DIAGRAM N.T.S. INSTALL EST SIGA SERIES 270/270 MANUAL PULL STATION USING STANDARD 1-1/2'(3amm) DEEP CONCRETE SLAB BACK BOX e'. lke 3 4" EMT CONDUIT J / � DETECTOR TYPICAL HEAT DETECTOR/SMOKE DETECTOR MOUNTED ON CONCRETE OR GYPSUM CEILING NOT TO SCALE - 3/4" EMT CONDUIT BACK BOX 0, SIGA—CT2 MOUNTING DETAIL N.T.S. SIGA-CC 1 LED rm am AAW BDAaAI e 7 e s 4 s 2 1 TB1TO 0 0 0 0 TB1 DEVICE OR NEXT _ RIBER art(-1 DE EOL RESISTOR FROM FACP ; 1 i I FROM FACP - DATA' + ,_...-.__ OR TO NEXT PREVIOUS DM - l pm-) DEVICE DEVICE SINGLE INPUT RISER MODULE WIRING DIAGRAM N.T.S. TB2 a T a s SIGA-CT2 Dan as OPTIONAL SELF-ADHESIVE NOMMIL FRENCH LABEL (SUPPLIED) TB7 + s z t 0 0 WALL PLATE, WHITE / (i GANG) i Sw.TA iN(+) . CATA MT(,) FACPL--_..._ ....._..___.. _.__...;-.. OR TO NEXT PREVIOUS DATA N(-) LTA MIT(-) DEVICE DEVICE AM-07-06-052197-00 DUAL INPUT MODULE WIRING DIAGRAM N.T.S. SAfPLOW TUBE SOCKET SOCKET E•wlsL tu•E I� i ��e— ®\- T„m DUCT DETECTOR HOUSING DIAGRAM N.T.S. [rJ]� [ril iriJi [r�l 3 • [r�7 [r'� � I��hr;� 1�■dd� [r� • [r�7 Iuyutl�rauuTA© IuNuu�uuuu0 • [ram] • [r�l -• •. [raj [U7;� wlor.T THE CBxaICTS m P10oA a)taWeLE DATA ULVfj+) TO NEXT DATA OUT(-) DEVICE REMOTE BOOSTER POWER SUPPLIES MOUNTING DETAIL (BPS10A) N.T.S. NEW VISUAL ALARM DEVICE DRYWALL TYPICAL VISUAL DEVICE INSTALLATION ON GYPSUM WALL NOT TO SCALE - SIGA-AB4GT, ® p p ® SIGA-AB4G LF: SIGA-AB4G, SIGA-AB4G-LF: JUMPER CUTS OUTPUT MODE DEFAULT = FIRE VOLUME SETTING CUT/REMOVE JUMPER FOR DEFAULT = HIGH FIRE PLUS CO CUT/REMOVE JUMPER FOR SIGA-AB4G: LOW dB ® ® TONE SETTING DEFAULT = TEMPORAL DATA DATA- SIG+ Sic- OUT IN DATA+ IN/OUT CUT/REMOVE JUMPER FOR STEADY O SIGA-AB4GT: NOT USED 24 VDC IN _ FROM POWER SUPPLY In 24 VDC OUT OR PREVIOUS BASE + > + TO NEXT BASE OR EOL RELAY DATA IN DATA OUT FROM SIGNATURE CONTROLLER TO NEXT SIGNATURE DEVICE OR PREVIOUS DEVICE'll+ AUDIBLE SOUNDER BASES FIRE MODE AB4GT, A134G, A134G-LE SOUNDER BASES - NOT TO SCALE - 54 SIGA—CR MOUNTING DETAIL N.T.S. #10 SHEET i SCRE° (2f) TB2 v a T a SIGA-CR 0 m o OPTIONAL aowLn SELF-ADHESIVE s t FRENCH LABEL TBt 0 0 (SUPPLIED) WALL PLATE, WHITE (1 GALNc) 1111(+) I CAFA L`JT(+} FROM FRCP-,•--DATA \ OR TO N PREVIOUS-) l °ug -) DEVICES ��4//IIIYYY MINE CONTROL RELAY MODULE WIRING DIAGRAM N.T.S. DETECTOR MOUNT BASE TO 4' SQUARE STANDARD ELECTRICAL BOX 1-1/2" DEEP. TAMPER -RESIST LEVER ARM Co -BREAK OFF TO DISABLE - (LOCATED ON BASE) ACCESS SLOT FOR TAMPER -RESIST MECHANISM M D SD / HD SIGA—OSD/PS/HRS MOUNTING DETAIL N.T.S. CONTACTS SHOWN WHEN RELAY IS DE -ENERGIZED ax (H) (N) H+—FSD N E.S.T. SIGA-CR I POWER 1112 P.',' • NOTE: ALSO USED FOR ELEVATOR SHUNT TRIP, RECALL AND FAN SHUTDOWN Le to ao0MM TBI mn, n�rn B B DATA IW+) WTA OUT(,) FROM FACP-------- _.,._..,a... OR TO NEXT PREVIOUS DATA N(-) DATA OUR-) DEVICE DEVICE CONTROL RELAY MODULE WIRING DIAGRAM DETAIL #5 (n z O U) w o aCM0 Z w M a - J_ 4# J w Q (� V U) _JI = N J t w U U p J Z w O J w w LU J D Q v�� a Q LL Q W rn Q o w w 0 UJ 1 co Co LL- < CL_ w 0 Q z Lli w w k- Imo.Ll- 00 OO F- LLB w8 w z w w w U