HomeMy WebLinkAboutAPPROVED, MS86155-OP445084-ROBERTMCCLELLAN-MS86155FINALDESIGNStamped (1)(1)COVER PAGE
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-1
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
COVER PAGE
SYSTEAD INFORADATION
MODULE HANWHA Q.PEAK DUO BLK-G6+/AC 340
INVERTER ENPHASE IQ7PLUS-72-2-US
RACKING ROOFTECH RT-MINI & ECOFASTEN CLICKFIT
2-RAIL SYSTEM
SYSTEM SIZE (DC)8.16 KW
LOCATION 27.4191605,-80.3477459
HANWHA Q.PEAK DUO BLK-G6+/AC 340
340 WATT MODULE
68.5'' X 40.5'' X 1.57''(SEE DATASHEET)
BUILDING INFORMATION/B.O.M.
# STORIES 1/15
ROOF AREA 2453.34
P.V. AREA 462
ROOFING TYPE ASPHALT SHINGLES
ROOF PITCH 10
# RAILS 12
# L-FOOT ATTACHMENTS 35
# MODULES 24
# INVERTERS 24
# SKIRTS 7
# ENPHASE COMBINER BOXES 1
EATON 60A FUSIBLE SOLAR AC
DISCONNECT 1
40A FUSES 2
125A LINE TAPS 2
PLAN KEY
PV-1 COVER PAGE
PV-2 SITE PLAN
PV-3 PANEL SPECIFICATION
PV-3.1 PANEL LOAD TESTING RESULTS
PV-3.2 INVERTER SPECIFICATION
PV-3.3 COMBINER BOX SPECIFICATION
PV-3.4 JUNCTION BOX SPECIFICATION
PV-3.5 ATTACHMENT DETAIL
PV-3.6 STRUCTURAL CALCULATION
PV-3.7 SEALANT SPECIFICATION
PV-3.8 SEALANT SPECIFICATION CONT.
PV-4 THREE LINE DIAGRAM
PV-4.1 ELECTRICAL NOTES
PV-4.2 EQUIPMENT LABELS
PV-5 STRUCTURAL CERTIFICATION
STRUCTURAL STATEMENT:
THE EXISTING STRUCTURE IS ADEQUATE TO SUPPORT THE NEW LOADS IMPOSED BY THE PHOTOVOLTAIC MODULE
SYSTEM INCLUDING UPLIFT & SHEAR.EXISTING RAFTER SIZES & DIMENSIONS CONFORM TO 7TH EDITION 2020
FLORIDA RESIDENTIAL CODE, 7TH EDITION 2020 FLORIDA BUILDING CODE SECTION 1512 THROUGH 1525 AND
SECTION 1616 THROUGH 1626 FOR HIGH VELOCITY HURRICANE ZONES.
GENERAL NOTES:
THIS PV SYSTEM HAS BEEN DESIGNED TO MEET THE MINIMUM DESIGN STANDARDS FOR BUILDING AND OTHER
STRUCTURES OF THE ASCE 7-16, 7TH EDITION 2020 FLORIDA RESIDENTIAL CODE, 7TH EDITION 2020 FLORIDA
BUILDING CODE, 7TH EDITION 2020 FLORIDA FIRE PREVENTION CODE, NEC 2017 AND ALL LOCAL CODES &
ORDINANCES.
ROOF SHALL HAVE NO MORE THAN TWO LAYERS OF COVERING IN ADDITION TO THE SOLAR EQUIPMENT.
INSTALLATION OF SOLAR EQUIPMENT SHALL BE FLUSH MOUNTED, PARALLEL TO AND NO MORE THAN 6-INCHES
ABOVE THE SURFACE OF THE ROOF FOR SLOPED ROOF AND NO MORE THAN 10-INCHES ABOVE THE SURFACE OF
THE ROOF FOR FLAT ROOF.
ANY PLUMBING VENTS ARE NOT TO BE CUT OR COVERED FOR SOLAR EQUIPMENT INSTALLATION. ANY
RELOCATION OR MODIFICATION OF THE VENT REQUIRES A PLUMBING PERMIT AND INSPECTION.
ALL DESIGN, CALCULATIONS ARE PERFORMED BY DANIEL DUNZIK REGISTERED ARCHITECT. FLORIDA STATE
STATUTE 471.003(3) PROVIDES THAT LICENSED ARCHITECTS ARE EXEMPTED FROM THE PROVISIONS OF
CHAPTER 471 ENGINEERING AND NOT PRECLUDED FROM PERFORMING ENGINEERING SERVICES FOR INTEGRATED
SYSTEMS AND SERVICES THAT ARE INCIDENTAL TO THE DESIGN CONSTRUCTION OR ALTERATION OF BUILDINGS
AND STRUCTURES FOR HUMAN HABITATION.
INVERTER PLACEMENT:
SYSTEM UTILIZES "ENPHASE" MICRO-INVERTERS WITH RAPID SHUTDOWN CONTROL LOCATED ON THE BACK SIDE
OF EACH MODULE.
FSEC CERTIFICATION STATEMENT:
PER FL. STATUE 377.705 , I, MINA A. MAKAR PE# 86753, CERTIFICATE OF AUTHORIZATION #33404, AN
ENGINEER LICENSED PURSUANT TO CHAPTER 471,CERTIFY THAT THE PV ELECTRICAL SYSTEM AND ELECTRICAL
COMPONENTS ARE DESIGNED AND APPROVED USING THE STANDARDS CONTAINED IN THE MOST RECENT
VERSION OF THE FLORIDA BUILDING CODE. FBC 2020
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
1 / 15
SCALE: 1/8" = 1'-0"
SITE PLAN
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-2
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
NOTE:
1. ROOF COVERING MATERIAL IS COMPOSED OF
2. EXACT ATTACHMENT LOCATION AND QUANTITY OF ATTACHMENTS ARE BASED ON EXISTING RAFTER LOCATIONS OBTAINED FROM FIELD
MEASUREMENTS. . THE LOCATION AND QUANTITY OF ATTACHMENTS MAY VARY BASED ON RAFTER LAYOUT START POINT, SPACING
VARIATIONS AND ROOFING TYPE. VERIFY IN THE FIELD ALL RAFTER LOCATIONS AND ADJUST LAYOUT AS REQUIRED. A TILE ROOF WILL
PRODUCE A STAGERED ATTACHMENT LAYOUT BECAUSE OF EXISTING STAGERED TILE JOINT LOCATIONS
3. EXISTING RESIDENCE EQUIPPED WITH SMOKE/CO DETECTOR IN AND OUTSIDE OF ALL SLEEPING ROOMS HARDWIRED AND
INTERCONNECTED AS PER FEDERAL LAW
ASPHALT SHINGLES
SITE PLAN
SYMBOL LEGEND
MAIN SERVICE PANEL
UTILITY METER
SKYLIGHT
VENT
CHIMNEY
SUB-PANEL
MSP
SP
M
SOLAR
AC
DISC
UDC
LC
N3R
CB
SOLAR AC DISCONNECT
LOAD CENTER
NEMA 3R BOX W/ ENVOY-S
COMBINER BOX
PIPE VENT
FAN
SATELLITE DISH
MODULE
FIRE SETBACKS
PITCH DIRECTION
UTILITY DISCONNECT
MIN 3'x3' GROUND ACCESS
POINT
WIND PRESSURE ZONE LINES
ROOF PANEL COUNT TILT AZIMUTH SHADING
R1 24 10°89°92%
RAFTER SPACING
24" O.C. (TYP)
TOTAL SQUARE FOOTAGE OF ROOF: 2454 SQFT
SQUARE FOOTAGE OF SOLAR ARRAY:462 SQFT
PERCENTAGE OF SOLAR ROOF COVERAGE: 18.85%
18" RIDGE SETBACK SHALL BE REQUIRED
CLAMPING MAX SPACING IN ZONE 1 48" O.C
AND IN ZONE 2 AND ZONE 3 48" O.C
51'-5"
51'-5"
58'-1"58'-1"FRONT OF RESIDENCEPLACID AVEMSP
M
SOLAR
AC
DISC
ELECTRICAL EQUIPMENT
CB
PZ1
PZ1
PZ1
PZ1
PZ1
PZ1
PZ1
PZ1
PZ1
PZ1
PZ1
PZ1
PZ1
PZ2e
PZ2e
PZ2e
PZ2e
PZ2e
PZ2e
PZ2e
PZ2e
PZ2e
PZ2e
PZ2n
PZ2n
PZ2n
PZ2n
PZ2rPZ2r
PZ2rPZ2r
PZ2rPZ2r
PZ2rPZ2r
PZ3rPZ3r PZ3e
PZ3e
PZ3e PZ3e
PZ3r
PZ3r
PZ2 PZ2
PZ3
PZ3 PZ3
PZ3
PZ3
PZ3
PZ3
PZ3
5'-1"
5'-1"5'-1"5'-1"5'-1"5'-1"5'-1"
5'-1"
10'-2"10'-2"
10'-2"10'-2"
5'-1"
5'-1"
5'-1"5'-1"
5'-1"5'-1"
5'-1"
5'-1"
5'-1"
5'-1"
R1
J-BOX GUTTERRIDGEGUTTERGROUND ACCESS
(TYP)
FIRE SETBACK
(36" VENTILATION,
36" ROOF ACCESS)
3'-0"
3'-0"
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
2 / 15
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
PANEL SPECIFICATION
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
3 / 15
PANEL LOAD TESTING
RESULTS
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.1
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
4 / 15
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.2
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
INVERTER SPECIFICATION
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
5 / 15
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.3
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
COMBINER BOX SPECIFICATION
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
6 / 15
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.4
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
JUNCTION BOX SPECIFICATION
JUNCTION BOX SPECIFICATION FOR SHINGLE ROOFS
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
7 / 15
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.5
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
ATTACHMENT DETAIL
ATTACHMENT DETAIL FOR SHINGLE ROOF
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
8 / 15
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.6
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
STRUCTURAL CALCULATION
2-RAIL RACKING PLUS SOLAR SYSTEM DEAD LOAD
COMPONENT WEIGHT/UNIT (LB)#
MODULES 0 24
INVERTERS 4.0 24
RAILS (2-RAIL) @ 1.8LB/LF.1.8 12.0
ATTACHMENT/FLASHING 0.98 35
ARRAY TOTAL AREA (SQFT)462
ARRAY TOTAL WEIGHT (LB)152
TOTAL DEAD LOAD PER SF (LB/SQFT)2.60
10 % OF LEAST HORIZONTAL DIMENSION OR 40% OF THE BUILDING HEIGHT WHICHEVER IS
SMALLER BUT NOT LESS THAN EITHER 4% OF THE LEAST HORIZONTAL DIMENSION OR 3'-0"
WIND PRESSURE ZONE CALCULATION (ASCE FIGURE 30.4-2A, 2B)
HORIZONTAL DIMENSION A 51.5'X 10% = 5.15'
HORIZONTAL DIMENSION B 58.099998474121'X 10% = 5.80999984741211'
BUILDING HEIGHT 15'X 40% = 6'
PRESSURE ZONE WIDTH 5' 1.8 "
CERTIFICATION OF WIND LOAD PRESSURE CALCULATION THIS IS A 2-RAIL DESIGN
DESIGN LOAD CRITERIA. AS PER ASCE 7-16 (2.4.1)
FOR THIS PARTICULAR CASE, THE "DOWNFORCE" CASE 2 AND
UPLIFT HAVE BEEN TAKEN INTO CONSIDERATION.
P (PSF) = 1xD + 1x PNET (DOWNFORCE)
P (PSF) = 0.6xD + 0.6x PNET (UPLIFT)
(P = TOTAL DESIGN LOAD)
(PNET = WIND LOAD)
(D = DEAD LOAD)
PNET HAVE BEEN CALCULATED FOLLOWING THE ALLOWABLE STRESS DESIGN METHOD.
THE MAXIMUM ABSOLUTE VALUE OF THE 2 CASES IS THE UPLIFT LOAD.
THIS 2-RAIL DESIGN IS WELL UNDER THE CAPACITY OF THE INDIVIDUAL ATTACHMENT
CAPACITIES FOR THE DESIGN. THE PHOTOVOLTAIC MODULES USED IN CONJUNCTION WITH
2-RAIL ATTACHMENT SYSTEM ADDED HAVE A DESIGN CAPACITY OF -4,000 PA., 84 PSF. THIS
DESIGN IS WITHIN THE LOADING CAPACITIES OF THE PHOTOVOLTAIC MODULE 2-RAIL DESIGN
TESTING CAPACITIES THAT HAVE BEEN PERFORMED BY INDEPENDENT TESTING BY THE PANEL
MANUFACTURERS ENGINEERS. SEE ATTACHED MANUFACTURERS TEST DATA.
WIND LOAD CALCULATIONS (ASCE 7-16 EQ. 29.4-7)
VELOCITY PRESSURE Qh = 0.00256 Kz*Kzt*Kd*Ke*V^2(LB/SQFT) (EQ. 26.10-1)
EXPOSURE B
Kz (VELOCITY PRESSURE EXPOSURE)0.57
Kzt (TOPOGRAPHIC FACTOR)1
Kd (WIND DIRECTIONALITY)0.85
Ke (GROUND ELEVATION FACTOR)1
V (WIND SPEED)160
MEAN HEIGHT 15.00
TOTAL PRESSURE AND ATTACHMENT SPACING FOR GABLE ROOF WITH 7 to 20 DEGREE TILT
GCp p- (LB/SQFT)p+
(LB/SQFT)
pnet- (LB/SQFT)pnet+
(LB/SQFT)
ATTACHMENT SPACING (INCH)UPLIFT PRESSURE FOR EACH
ATTACHMENT (LB)
ZONE UPLIFT DOWNWARD ARRAY INTERIOR ARRAY EDGE ARRAY INTERIOR ARRAY EDGE ARRAY INTERIOR ARRAY EDGE ARRAY INTERIOR ARRAY EDGE
1 -2.00 0.30 -50.80 -76.21 7.62 -28.92 -44.16 10.22 48.00 24.00 -330.19 -252.10
2e -2.00 0.30 -50.80 -76.21 7.62 -28.92 -44.16 10.22 24.00 24.00 -165.10 -252.10
2n -3.00 0.30 -76.21 -114.31 7.62 -44.16 -67.02 10.22 24.00 24.00 -252.10 -382.60
2r -3.00 0.30 -76.21 -114.31 7.62 -44.16 -67.02 10.22 24.00 24.00 -252.10 -382.60
3e -3.00 0.30 -76.21 -114.31 7.62 -44.16 -67.02 10.22 24.00 24.00 -252.10 -382.60
3r -3.60 0.30 -91.45 -137.17 7.62 -53.31 -80.74 10.22 24.00 16.00 -304.30 -307.27
WIND PRESSURE PNET IS CALCULATED BY ASCE 7-16 EQ. 29.4.7, WHERE Qh IS CALCULATED BY
EQ. 29.4-7 (PARAMETERS SHOWN IN THE TABLE).
GCp ARE CHOSEN FROM FIGURE 30.3-A-I FOR SPECIFIC ROOF TYPE AND ROOF TILT WITH
EFFECTIVE WIND AREA EQUALS TO 10 SQFT (INTERPOLATION MAY REQUIRED).
ARRAY EDGE FACTOR rE = 1.5 FOR ARRAY EDGES UPLIFT PRESSURE IF ARRAY EDGE IS MORE
THAN 10 FEET (0.5h) TO ROOF EDGES AND MORE THAN 4 FEET TO ADJACENT ARRAY OR NEXT
ADJACENT PANEL. rE = 1.0 FOR ARRAY INTERIOR UPLIFT PRESSURE AND ALL DOWNWARD
PRESSURE AS DEFINED IN ASCE 7-16 29.4.4.
SOLAR PANEL PRESSURE EQUALIZATION FACTOR ra = 0.8 AS PER ASCE 7-16 FIGURE 29.4-8.
NO PANEL ARE LOCATED IN ARRAY EDGE AREA AS DEFINED BY ASCE 7-16 29.4.4. FOR
THIS PROJECT.
ALLOWABLE LOAD / ATTACHMENT 5/16” LAG SCREW W/ 3.00” EMBEDMENT INTO RAFTER
BELOW ACCORDING TO THE NATIONAL DESIGN SPECIFICIFICATION FOR WOOD
CONSTRUCTION 2015 EDITION. = W' = W X CD X CT. - PER TABLE 11.3.1 NDS
5/16” DIA. 4" LONG LAG W/ 3.00” EMBEDMENT INTO 2X ROOF RAFTER
W' = 266LB/IN EMBEDMENT (NDS11.3.1 TABLE 12.2A) FOR DF. LARCH, S.Y.P., AND S.P.F.
SPECIES
CD = 1.6 (TABLE 2.3.2 2015 NDS)
CT = 1.0 (TABLE 10.3.4 2015 NDS)
W' = 266LB/IN X 3.00” X 1.6 X 1.0 = 1,276.8LBS = ULTIMATE
MAX ALLOWABLE UPLIFT PRESSURE WITH 60% OF ULTIMATE CAPACITY
1,276.8LBS X 0.6 = 766.08LBS
-THREAD MUST BE EMBEDDED IN THE SIDE GRAIN OF A TRUSSES OR OTHER
STRUCTURAL MEMBER INTEGRAL WITH THE BUILDING STRUCTURE.
-LAG BOLTS MUST BE LOCATED IN THE MIDDLE THIRD OF THE STRUCTURAL MEMBER.
-THESE VALUES ARE NOT VALID FOR WET SERVICE.
-INSTALL LAG BOLTS WITH HEAD AND WASHER FLUSH TO SURFACE (NO GAP). TORQUE
AS PER MANUFACTURERS SPECIFICATIONS. DO NOT OVER-TORQUE.
-WITHDRAWAL DESIGN VALUES FOR LAG SCREW CONNECTIONS SHALL BE MULTIPLIED
BY APPLICABLE ADJUSTMENT FACTORS IF NECESSARY. SEE TABLE 10.3.1 IN THE
AMERICAN WOOD COUNCIL NDS FOR WOOD CONSTRUCTION.
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
9 / 15
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.7
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
SEALANT SPECIFICATION
SEALANT SPECIFICATION FOR SHINGLE ROOFS
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
10 / 15
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.8
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
SEALANT SPECIFICATION CONT.
Roofing Read Safety Data Sheets before using this product.
19 Flashing Cement
DESCRIPTION:
KARNAK 19 Flashing Cement is a scientifically compounded composition of
selected asphalts, mineral fibers, and refined solvents that are manufactured to a
heavy consistency for application by trowel to provide a durable, elastic
coating of excellent adhesion and high resistance to water and weathering. This
product dries to a tough, flexible, waterproof and corrosion proof coating which
gives excellent performance over wide ranges of temperature and weather
conditions. KARNAK 19 Flashing Cement is available in 3 consistencies: Summer,
Semi and Winter.
USES:
KARNAK 19 Flashing Cement is a general purpose cement for repairing leaks in
shingles, concrete, metal or asphalt roofs, flashings on walls, chimneys, flues,
downspouts and cornices. It is excellent for sealing cracks in concrete and brick, as
a joint filler for precast roof slabs and for general purpose use in maintenance of
exposed buildings and structures.
SURFACE PREPARATION:
All surfaces should be clean, dry and free from oil or grease, dust, dirt, loose paint
or other foreign matter. Recommended application temperature is 40°F to 120°F.
If applying at temperatures lower than 40°F, the substrate must be free of
moisture and/or ice crystals.
APPLICATION:
Spread KARNAK 19 Flashing Cement to an average thickness of 1/8”
(approximately 8 gallons per square) and press tightly into joints, seams or cracks.
To repair large cracks, breaks and blisters:
1. Spread KARNAK 19 Flashing Cement over the damaged area.
2. Embed KARNAK Cotton, Fiberglass or Poly-Mat Membrane reinforcement.
3. Apply another coat of KARNAK 19 Flashing Cement over the entire patch.
SPECIFICATIONS:
Federal Specification SS-C-153 Type I (Except Non-Asbestos)
ASTM D-4586 Type I Class I
Revised 12.14.18
330 CENTRAL AVENUE, CLARK, NJ 07066
732-388-0300 • 800-526-4236 • FAX: 732-388-9422
WEB: http://www.karnakcorp.com
Roofing Read Safety Data Sheets before using this product.
19 Flashing Cement
PHYSICAL PROPERTIES:
1. Consistency: A smooth, heavy trowel consistency which will readily spread on
and adhere to vertical and horizontal surfaces without sagging.
2. Character of Dried Film: Uniform, excellent adhesion to masonry, steel, cured
concrete, shingles, asphalt roofing and a variety of other surfaces.
3. The dried film retains its flexibility and ductility so that the coating will resist
extreme variations in temperature and weather.
4. Has excellent resistance to flow at high temperatures when used on a
vertical surface.
CAUTION:
Do not use near open flame. Material is for building exterior applications only.
Avoid breathing solvent fumes and prolonged contact with skin. Do not take
internally. If swallowed, do not induce vomiting. Call a physician immediately.
Keep out of reach of children. Keep container covered when not in use. Do not thin.
Dispose of in an environmentally safe manner. Cover air intakes during application
and while drying.
PACKAGING:
Available in 5 gallon, 3 gallon, 1 gallon cans and 10.1 oz. caulk tubes.
If further information is needed, contact Karnak Technical Services at
1-800-526-4236.
Revised 12.14.18
330 CENTRAL AVENUE, CLARK, NJ 07066
732-388-0300 • 800-526-4236 • FAX: 732-388-9422
WEB: http://www.karnakcorp.com
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
11 / 15
ENPHASE 80A
AC COMBINER
BOX
10A/15A BREAKER
(MANUFACTURER
SUPPLIED FOR
ENVOY)
20A BREAKER (A)
20A BREAKER (B)
2A
2B
3
GND
NEU
TERMINATION CAP
INSTALLED ON
END OF CABLE
INVERTERS
INSTALLED ON
RAIL SYSTEM
=...==
=...==
1A TO 1B
ROOF
JUNCTION
BOX
BRANCH CIRCUIT A
12 MICRO-INVERTERS
BRANCH CIRCUIT B
12 MICRO-INVERTERS
24 HANWHA Q.PEAK DUO BLK-G6+/AC 340 340W MODULES PAIRED WITH
24 ENPHASE IQ7PLUS-72-2-US MICRO-INVERTERS
GND BUS
NEU BUS
POWER
GROUND
EXISTING SQUARE D 200A
MAIN SERVICE PANEL 240 V
MAIN BREAKER: 200A
200A
UTILITY
METER
GRID
GND BUS
NEU BUS
POWER
GROUND
EXISTING SQUARE D 200A
MAIN SERVICE PANEL 240 V
MAIN BREAKER: 200A
200A
UTILITY
METER
GRID
GND
NEU
4
EATON 60A FUSIBLE
SOLAR AC DISCONNECT
40A
40A FUSES
SOLAR CIRCUIT
DISCONNECTING MEANS
GND BUS
NEU BUS
POWER
GROUND
EXISTING SQUARE D 200A
MAIN SERVICE PANEL 240 V
MAIN BREAKER: 200A
200A
UTILITY
METER
GRID
PV SYSTEM CURRENT 36.3 A
SOLAR
AC
DISCONNECT
EMPHASE
COMBINER
BOX
EXISTING
METER
MSP LOCATED INSIDE
OF STRUCTURE
MSP
METER
RISER
#2/0 AWG SERVICE
CONDUCTOR FROM
OVERHEAD FOR
200AMP SERVICE
HOT LINE TAPS
MINUMUM BEND
RADIUS 4"
ENCLOSURE DIMENSIONS
LENGTH: 21.31"
WIDTH:10.3"
DEPTH:9.06"
#2/0 AWG SERVICE
CONDUCTOR FROM
UTILITY METER FOR
200AMP SERVICE
Wire Tag Conduit Wire Qty Wire
Gauge Wire Type Temp.
Rating
Wire
Ampacity (A)
Temp.
Derate
Conduit
Fill Derate
Derated
Ampacity (A)
Inverter
Qty NOC (A)NEC
Correction
Design
Current (A)
Ground
Size
Ground Wire
Type
1A TO 1B OPEN AIR 2 12 AWG Trunk Cable 90°C 30 0.96 1 28.80 12 1.21 1.25 18.15 06 AWG BARE CU
2A 1” PVC 2 10 AWG THWN-2 75°C 35 0.96 0.8 26.88 12 1.21 1.25 18.15 08 AWG THWN-2
2B 1” PVC 2 10 AWG THWN-2 75°C 35 0.96 0.8 26.88 12 1.21 1.25 18.15 08 AWG THWN-2
3 1” PVC 3 + G 08 AWG THWN-2 75°C 50 0.96 1 48.00 24 1.21 1.25 36.30 08 AWG THWN-2
4 1” PVC 3 + G 06 AWG THWN-2 75°C 65 0.96 1 62.40 24 1.21 1.25 36.30 THWN-2
THREE LINE DIAGRAM
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-4
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
ELECTRICAL SERVICE ELEVATION INTERCONNECTION DETAIL
NOTE: LETTER "G" IN WIRE QTY TAB STANDS FOR GROUNDING CONDUCTOR.
FSEC CERTIFICATION STATEMENT:
PER FL. STATUE 377.705 , I, MINA A. MAKAR PE# 86753,
CERTIFICATE OF AUTHORIZATION #33404, AN ENGINEER
LICENSED PURSUANT TO CHAPTER 471,CERTIFY THAT THE PV
ELECTRICAL SYSTEM AND ELECTRICAL COMPONENTS ARE
DESIGNED AND APPROVED USING THE STANDARDS
CONTAINED IN THE MOST RECENT VERSION OF THE FLORIDA
BUILDING CODE. FBC 2020
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
12 / 15
ELECTRICAL NOTES
SUB PANEL
BREAKER SIZE
# OF MODULES PV BREAKER
PER BRANCH
UP TO 16 20A
PV ADODULE RATINGS
MODULE MAKE HANWHA
MODEL Q.PEAK DUO
BLK-G6+/AC 340
MAX POWER 340W
OPEN CIRCUIT VOLTAGE 40.66V
MPP VOLTAGE 33.94V
SHORT CIRCUIT CURRENT 10.52A
MPP CURRENT 10.02A
NUMBER OF MODULES 24
UL1703 COMPLIANT YES
INVERTER RATINGS
INVERTER MAKE ENPHASE
MODEL IQ7PLUS-72-2-
US
MAX OUTPUT POWER 290W
OPEN DC VOLTAGE 60V
NOMINAL AC VOLTAGE 240V
MAX AC CURRENT 1.21A
CEC INVERTER EFFICIENCY 97%
NUMBER OF INVERTERS 24
UL1703 COMPLIANT YES
VOLTAGE DROP CALCULATIONS
FORMULA USED PER NEC 2014 HANDBOOK 215.2(A)(4) WHERE APPLICABLE
WIRE RUN Vmp Imp R L (FT)Vo % Vo WIRE SIZE
BRANCH TO J-BOX 240.00
J-BOX TO LOAD
CENTER 240.00
LOAD CENTER TO AC
DISCONNECT 240.00
AC DISCONNECT TO
INTERCONNECTION 240.00
#NUM!1.98 #NUM!#NUM!#NUM!12 AWG
0 1.24 50.00 0.000 0.00%10 AWG
0 1.24 3.00 0.000 0.00%10 AWG
0 1.24 10.00 0.000 0.00%10 AWG
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-4.1
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
MAKE MODEL VOLTAGE
RATING
CONDUCTOR
RANGE MAIN
CONDUCTOR
RANGE TAP
ILSCO IPC 4020 600 V 4/0-4 AWG 6-14 AWG
ILSCO IPC 4006 600 V 4/0-2 AWG 2/0-6 AWG
INSTRUCTIONS FOR LINE TAPS
FIGURE 1:
1.ADJUST THE CONNECTOR NUT TO SUITABLE
LOCATION
2.PUT THE BRANCH WIRE INTO THE CAP SHEATH FULLY
3.INSERT THE MAIN WIRE, IF THERE ARE TWO LAYS OF
INSULATED LAY IN THE MAIN CABLE, SHOULD STRIP A
CERTAIN LENGTH OF THE FIRST INSULATED LAY
FROM INSERTED END
4.TURN THE NUT BY HAND, AND FIX THE CONNECTOR IN
SUITABLE LOCATION.
5.SCREW THE NUT WITH THE SLEEVE SPANNER.
6.SCREW THE NUT CONTINUALLY UNTIL THE TOP PART
IS CRACKED AND DROPPED DOWN
THIS SOLAR PHOTOVOLTAIC SYSTEM COMPLIES WITH THE 2020
FLORIDA BUILDING CODE AND THE 2017 NATIONAL ELECTRICAL CODE
1.ALL CALCULATIONS FOR VOC, VMAX, IMP AND ISC HAVE BEEN
CALCULATED USING THE MANUFACTURED STRING CALCULATOR BASED
ON ASHRAE 2% HIGH AND EXTREME MINIMUM TEMPERATURE
COEFFICIENTS.
2.THE ENTIRE ARRAY IS BONDED ACCORDING TO (NEC 690.46 - 250.120
PARAGRAPH C). THE GROUND IS CARRIED AWAY FROM THE GROUNDING
LUG USING #6 BARE COPPER WIRE OR #8 THWN-2 COPPER WIRE.
3.THIS SYSTEM COMPLIES WITH NEC 2017
4.BRANCH CIRCUIT CALCULATION FOR WIRE TAG 1 DISPLAYS THE
LARGEST BRANCH CIRCUIT IN SYSTEM. OTHER BRANCH CIRCUITS
SHALL HAVE LOWER DESIGN CURRENT THAN THE ONE SHOWN. IN
ADDITION, VOLTAGE DROP CALCULATIONS FROM PANELS TO THE
COMBINER BOX SHALL BE SHOWN IN A SIMILAR FASHION
5.ALL CONDUCTORS ARE SIZED BASED ON NEC 2017 ARTICLE 310
6.ALL EQUIPMENT INSTALLED IS RATED AT 75°C
7.INVERTER NOC (NOMINAL OPEN CURRENT) OBTAINED FROM
EQUIPMENT DATASHEET
8.CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ALL
LOCAL AND NATIONAL CODE REQUIREMENTS.
9.EACH MODULE MUST BE GROUNDED ACCORDING TO USER
INSTRUCTIONS
10.ALL EQUIPMENT SHALL BE LISTED PER NEC 690.4(B)
11.PER NEC 690.13, 690.15, PROVIDE A WARNING SIGN AT ALL LOCATIONS
WHERE TERMINALS OF THE DISCONNECTING MEANS MAY BE
ENERGIZED IN THE OPEN POSITION> SIGN SHALL READ *WARNING -
ELECTRIC SHOCK HAZARD - DO NOT TOUCH TERMINALS - OR
EQUIVALENT.
12.PER NEC 705.10, PROVIDE A PERMANENT PLAQUE OR DIRECTORY
SHOWING ALL ELECTRIC POWER SOURCES ON THE PREMISES AT
SERVICE ENTRANCE.
13.INTERCONNECTION METHOD SHALL COMPLY WITH NEC705.12
14.AND OPTION FOR A SINGLE CIRCUIT BRANCH TO BE SPLIT INTO TWO
SUB-CIRCUIT BRANCHES IS ACCEPTABLE.
ELECTRICAL NOTES:
15.ALL CONDUCTORS MUST BE COPPER.
16.NEUTRAL AND EQUIPMENT GROUNDING CONDUCTOR BONDED AS PER
NEC 250.24(C).
17.EQUIPMENT GROUNDING CONDUCTOR IS CONNECTED TO A
GROUNDING ELECTRODE SYSTEM PER 250.54(D).
18.FUSES FOR PV DISCONNECT HAVE AIC RATINGS OF 200KA AC AND 20KA
DC.
19.SUPPLY SIDE CONNECTION SHALL BE MADE USING ILSCO INSULATION
PIERCING CONNECTORS (IPC). MAKE, MODEL, AND RATING OF
INTERCONNECTION CAN BE SEEN ON TABLE 1 BELOW.
20.METHOD OF INTERCONNECTION CAN BE SEEN IN FIGURE 1.
21.UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL PHOTOVOLTAIC
SYSTEM COMPONENTS LOCATED AT THE SERVICE ENTRANCE.
22.WORKING CLEARANCES AROUND THE EXISTING AND NEW ELECTRICAL
EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH NEC ARTICLE
110.26.
23.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT
RESISTANT PER NEC ARTICLE 300.6 (C)(1) AND ARTICLE 310.8 (D).
24.CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR
USE IN WET LOCATIONS PER NEC ARTICLE 310.10 (C).
25.TOTAL AREA OF ALL CONDUCTORS, SPLICES, AND TAPS INSTALLED AT
ANY CROSS SECTION OF THE WIRING DOES NOT EXCEED 75% OF THE
CROSS SECTIONAL AREA OF THE SPACE. NEC 312.8(A)(2).
26.SYSTEM IS CONSIDERED AN AC MODULE SYSTEM. NO DC
CONDUCTORS ARE PRESENT IN CONDUIT, COMBINER, JUNCTION BOX,
DISCONNECT. AND COMPLIES WITH 690.6 - NO DC DISCONNECT AND
ASSOCIATED DC LABELING ARE REQUIRED.
27.SYSTEM COMPLIES WITH 690.12 RAPID SHUTDOWN AND ASSOCIATED
LABELING AS PER 690.56(C). AC VOLTAGE AND SYSTEM OPERATING
CURRENT SHALL BE PROVIDED 690.52.
28.CONDUCTORS IN CONDUIT ARE AC CONDUCTORS BRANCH CIRCUITS
AND NOT PV SOURCE CIRCUITS. 690.6.
29.ALL GROUNDING SHALL COMPLY WITH 690.47(A) IN THAT THE
AC MODULES WILL COMPLY WITH 250.64.
30.NO TERMINALS SHALL BE ENERGIZED IN THE OPEN POSITION
IN THIS AC MODULE SYSTEM 690.13, 690.15, 690.6.
31. WHERE APPLICABLE: INTERCONNECTION SHALL COMPLY
WITH 705.12(A) OR 705.12(B)
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
13 / 15
29.04
ELECTRICAL SHOCK HAZARD
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
QUANTITY LOCATION
A
LABELTAG
B
C
1 JUNCTION BOX
1 COMBINER BOX 1 AT ANY COMBINER BOX
1 AT ANY JUNCTION BOX
NOTE EXAMPLES
A B
DC
RATED AC
OUTPUT CURRENT
NOMINAL OPERATING
AC VOLTAGE
A
240 V
PHOTOVOLTAIC SYSTEM
AC DISCONNECT
WARNING: PHOTOVOLTAIC
POWER SOURCE
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
AC SOLAR VOLTAGE
12 AC CONDUITS
1 AT EVERY SEPARATION BY
ENCLOSURES / WALLS /
PARTITIONS / CEILINGS / FLOORS
OR NO MORE THAN 10'
F G BACKFEED
ELECTRICAL SHOCK HAZARD
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
CAUTION
29.04
D
POWER TO THIS SERVICE IS
ALSO SUPPLIED FROM ON-SITE
SOLAR GENERATION
AC SYSTEM DISCONNECT
CAUTION
E
F
1 INTERCONNECTION
POINT
1 UTILITY METER
1
AC DISCONNECT
(RAPID SHUTDOWN
SWITCH, MAX 3FT
FROM SERVICE
DISCONNECT)
1 OF EACH AT FUSED AC
DISCONNECT
COMPLETE VOLTAGE AND
CURRENT VALUES ON
DISCONNECT LABEL
1 OF EACH AT BUILDING
INTERCONNECTION POINT AND
ONE DIRECTORY PLACARD
1 AT UTILITY METER AND ONE
DIRECTORY PLACARDREVENUE METER
DUAL POWER SUPPLY
SECOND SOURCE IS
PHOTOVOLTAIC SYSTEM
WARNING
RAPID SHUTDOWN SWITCH FOR
SOLAR PV SYSTEM
1
G
DUAL POWER SUPPLY
SECOND SOURCE IS
PHOTOVOLTAIC SYSTEM
WARNING
BACKFEED PANEL
1 PV METER
SOCKET
1 AT PV METER SOCKET AND
ONE DIRECTORY PLACARD
PV METER
WARNING
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
ENTIRE PV SYSTEM
SOLAR ELECTRIC
PV PANELS
SECTIONS OF THE PV SYSTEM THAT
ARE SHUT DOWN WHEN THE RAPID
SHUTDOWN SWITCH IS OPERATED
SECTIONS OF THE PV SYSTEM THAT
ARE NOT SHUT DOWN WHEN THE RAPID
SHUTDOWN SWITCH IS OPERATED
EMERGENCY RESPONDER
THIS SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
PHOTOVOLTAIC SYSTEM
INSTALLED BY
MOMENTUM SOLAR
3096B HAMILTON BLVD
S. PLAINFIELD, NJ 07080
PHONE NUMBER:732-902-6224
EQUIPMENT LABELS
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-4.2
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
14 / 15
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-5
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
ROBERT MCCLELLAN - MS86155
2809 PLACID AVE
FORT PIERCE, FL 34982
7723327842
SN
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
9/17/2021
SYSTEM SIZE (DC ): 8.16 KW
24 MODULES: HANWHA Q.PEAK DUO
BLK-G6+/AC 340
24 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
STRUCTURAL CERTIFICATION
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2021.09.17 05:09:10 -05:00
Powered by TCPDF (www.tcpdf.org)
15 / 15