HomeMy WebLinkAboutFire Alarm System PlansAt IL fil 0 0 1 JIM] i__imm 14 FIRE ALARM SYSTEM GENERAL NOTES 1. ALL WALL -MOUNTED VISUAL SIGNALING APPLIANCES SHALL BE MOUNTED SUCH THAT THE ENTIRE LENS IS NOT LESS THAN 80 IN. (2.03m) AND NOT GREATER THAN 96 IN. ABOVE THE FINISHED FLOOR (A.F.F.) PER NFPA 72 2016 CH. 18.5.5 ALL WALL MOUNTED AUDIBLE DEVICES SHALL BE A MINIMUM OF 90" A.F.F. TO THE TOP OF DEVICE PER NFPA 72 2016 (SECTION 18.4.8.1). AREAS HAVING MORE THAN 2 STROBES IN THE FIELD OF VIEW SHALL BE SYNCHRONIZED PER NFPA 72, SECTION 18.5.5.4.2. 2. SMOKE DETECTORS AND HEAT DETECTOR LOCATIONS ARE BASED ON SMOOTH CEILING WITH MAXIMUM HEIGHT OF 10 FEET UNLESS OTHERWISE NOTED. 3. STROBE LOCATION IS BASED ON 10 FOOT CEILING HEIGHT AND ARE INSTALLED ACCORDING TO NFPA 72 REQUIREMENTS UNLESS OTHERWISE NOTED. ANY DEVICES ON CEILINGS OVER 10 FT. WILL BE DERATED PER NFPA 72. 4. CENTER OF MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" ABOVE FLOOR LEVEL. 5. ALL EQUIPMENT SHALL BE U.L. LISTED. 6. ALL WIRING SHALL BE IN ACCORDANCE WITH N.E.C. AND AUTHORITIES HAVING JURISDICTION. 7. ALL JUNCTION BOXES SHALL BE SIZED IN ACCORDANCE WITH THE N.E.C. 8. ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT REQUIRE SERVICING, TROUBLE SHOOTING, ETC. 9. DO NOT DEVIATE FROM CONDUIT RUNS AS SHOWN ON FLOOR PLANS WITHOUT PRIOR APPROVAL FROM SYSTEM SUPPLIER. FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITIONAL PARTS, ENGINEERING, ETC, THAT ARE A RESULT OF CONDUIT RUN DEVIATIONS SHALL BE THE SOLE RESPONSIBILITY OF ELECTRICAL CONTRACTOR. 10. DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR -FLOW, NOR CLOSER THAN 3 FEET (900mm) FROM AN AIR SUPPLY DIFFUSER. 11. ALL DUCT SMOKE DETECTORS SHALL BE MOUNTED BY THE MECHANICAL OR ELECTRICAL CONTRACTOR. DUCT DETECTORS EXPOSED TO THE WEATHER SHALL BE WEATHER PROTECTED IiY THE MECHANICAL CONTRACTOR. ALL AIR VELOCITY TESTING SHALL BE PERFORMED BY THE MECHANICAL CONTRA( TOR. 12. ALL 120 VAC POWER REQUIREMENTS FOR THE FIRE ALARM SYSTEM SHAI-L BE FURNISHED BY THE ELECTRICAL CONTRACTOR AND SHALL MEET ALL REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. 13. ALL FIRE ALARM DEVICE BACK BOXES, FIRE ALARM TERMINAL CABINETS, GUTTERS, JUNCTION BOXES AND ASSOCIATED SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. REFER TO FIRE ALARM SYMBOL LIST AND/OR MOUNTING DETAILS FOR ADDITIONAL INFORMATION. SYSTEM SUPPLIER PROVIDED BACK BOXES SHALL BE INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. 14. SMOKE DETECTOR TESTING SHALL BE ACCOMPLISHED WITH SMOKE OR LISTED AEROSOL APPROVED BY THE MANUFACTURER PER NAFP 72, AS ACCEPTABLE BY THE A.H.J. 15, ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION. THE FIRE ALARM CONTROL PANEL TO SUPERVISE THE ANNUNCIATOR PANEL, ALL INITIATING AND INDICATING DEVICE CIRCUITS. 16. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE LOOPED THROUGH DEVICES. 17. POINT AND COMMON ANNUNCIATION AND T-TAPPING ARE PROHIBITED T--APPIN IS P;LL0',1jABLE ON ADDRESSABLE STYLE 4 SLC LOOPS). 18. THE ALARM SYSTEM SHALL HAVE AN AUDIBILITY OF NOT LESS THAN 15dB ABOVE: AMBIENT NOISE LEVELS, BUT NOT LESS THAN 75dB THROUGHOUT AREA OF ALARM. TESTING SHALL BE ACCOMPLISHED WITH A dB METER. WHERE APPLICABLE, AUDIBLE TONE WILL BE TEMPORAL PATTERN. 19. FIRE ALARM SIGNAL SHALL MEET ANSI S3.41. AUDIBILITY EMERGENCY EVACUATION SIGNAL (TEMPORAL PATTERN) 20. ALL CONDUITS ARE 3/4" UNLESS OTHERWISE NOTED. 21. ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED PER MANUFACTURERS SPECIFICATIONS. 22. SYSTEM SHALL BE FURNISHED AND INSTALLED BY AN AUTHORIZED DISTRIBUTOR. 23. TAMPER PROOF SCREWS OR OTHER APPROVED MECHANICAL MEANS SHALL BE USED ON ALL COVERS OF EXTERIOR ELECTRICAL JUNCTION BOXES IN LIEU OF ELECTRICAL SUPERVISION OF TI IE COVERS. PER THE 2016 NFPA 72 23.8.5.11.1. 24. ELECTRICAL POWER SERVICE SHALL BE ON A DEDICATED BRANCH CIRCUI I (S) AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED (CIRCUIT BREAKERS SHALL BE LOCKED IN THi ON POSITION WITH AN APPROVED MECHANICAL CLIP). CIRCUIT DISCONNECTING MEANS SHALL HAVE A RE[) MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT." THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIDE ALARM CONTROL UNIT. 25. UPON COMPLETION OF ALL INSTALLATION AND TESTING, THE CONTRAC I OR SHALL PROVIDE TO THE AUTHORITY HAVING JURISDICTION AND THE BUILDING OWNER A COMPLETED AND SIGNED NFPA 72 CERTIFICATE OF COMPLETION. 26. SECTION 17.7.1.11.3 OF THE 2016 EDITION OF NFPA 72 STATES THAT "WHERE DETECTION IS NOT REQUIRED DURING CONSTRUCTION, DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER ALL OTHER CONSTRUCTION TRADES HAVE COMPLETED CLEANUP." 27. IN -BUILDING PUBLIC SAFETY RADIO SYSTEM ENHANCEMENT, IF REQUIRED, SHALL. BE FURNISHED AND INSTALLED BY OTHERS. PROJECT SCOPE OF WORK 1. INSTALLATION OF NEW FIRE ALARM CONTROL PANEL & BOOSTER PANEL 2. INSTALLATION OF NEW FIRE ALARM SYSTEM INITIATION DEVICES, (SMOKE: DET., HEAT DET., PULL STATIONS, INTERFACE MODULES) 3. INSTALLATION OF NEW FIRE ALARM SYSTEM AUDIBLE/VISUALS, & VISUAL DEVICES. 4_ MONITOR MODULES FOR CONNECTIONS TO WATERFLOW SW., TAMPER SW., TO IBE PROVIDED. CONNECTIONS BY OTHER. 5. 120VAC POWER CONNECTION TO BE PROVIDED BY DEDICATED CIRCUIT. 6. CELLULAR COMMUNICATOR TO BE PROVIDED FOR CENTRAL STATION MONITORING. 7. PROGRAMMING OF FIRE ALARM SYSTEM TO OPERATE AS SHOWN IN SEQUENCE OF OPERATIONS. APPLICABLE CODES / STANDARDS PARTIAL LIST OF APPLICABLE NFPA STAIJDARDS NFPA 72-National Fire Alarm Codes (2016 Edit Cr NFPA 101-Life Safety Code (2018 Edition) 2020 Florida Fire Prevention Code 7th Edition H:11 A111111111111111I 19 man _;Lej Rai 2 U I N _" ;N2 W� a m I Avg-MEC ��1L�11'1 PROJECT CRISTELLE CAY CONDOMINIUM - MAHI MAHI BLDG. 1i � 1,l Fire & Life Salett� Powered BY 5erl�ice ADDRESS 4802 OCEAN PALMS DR. C7Y,ST,ZIP FORT PIERCE, FL 34949 TOTAL STANDBY ALAR[VI TOTAL ALARM ST )I IDBY CURRENT PER CURRENT PER CURRENT PER PER UNIT LINT(AMPS) ITEM PART QUANTITY UNIT(AMPS) UNIT(AMPS) (AMPS) FACP 1010 EST IO1 C 1 0.172000 0.172000 0.267000 0.267000 SIGNATURE OPTICA SMOKE DET SIGA OSD 5 0.000032 0.000160 0.000045 0.000225 HEAT DETECTOR SIGA-FiRD 4 0.000051 0.000204 0.000068 0.000272 INTELLIGENT CO DETECTOR SIGA-COD 2 0.000051 0,000102 0.000068 0.000136 PULLSTATION DOUBLE ACTION SIGA-278 0.000250 0.0007`70 0.00040C 0.001200 INPUT MODULE SINGLE SIGA-CT1 i5 0.000250 0.003750 0.00040 0.006000 DUAL INPUT MODULE SIGA-CT2 5 0.000396 0.0019so 0.00068 0.003400 CONTROL RELAY SIGA-CR 6 0.000075 0.000450 0.000075 0.000450 HIGH CURRENT CONTROL RELAY SIGA-CRH 1 2 O.000075 0.000150 0.000075 0.000130 TOTAL ALARM TOTAL STANDBYCURRENT CURRENT 4�.171 (AMPS) 0.278833 REQUIRED TOTAL SYSTEM STANDBY TOTALSYSTEM REQUIRES ALARM TIME REQUIRED ALARM CAPACITY (AMP REQUIRED STANDBY TIME (HOURS) STANDBY CURRENT CAPACITY ALARM CURRENT (MINUTES) HOURS) (AMPS) (AMP (AMPS) HOURS; 24. 00 1 0179546 4.31 115.00 0.278833 0,07 REQUIRED ALARM OT».L REQUIRED 2 . 12 V D.T lER ES.� ST'l D REQUIRED STANDBY CAPACITY (AMP HOURS) CAPACITY (AMP REQUIRED SAFETY FACTOR BATTERY 1-IrJURt aPACITY CAPACITY (AMP AMP/HR RATING PAR] # Lip � 7.00 12V7A 3 t:.vt311 S 4 5. - FACP BATTERY- CALCULATIONS PROJECT CRISTELLE CAY CONDOMINIUM - MAHI MAHI BLDG. Ist Fire & Secu:. Life Safety Powered 11v Sertice ADDRESS 4802 OCEAN PALMS DR. CITY,ST,ZIP FORT PIERCE, FL 34949 r a ;,. ALARM ALARM CURRENT PER CURRENTPER 1��UuNrlT1f CURRENTIPER PER UNIT QUANTI UNIT (AMPS) U N I T (A M P S) POWER SUPPLY 'GENESIS LED G4 HORN STROBE, WALL, 75, 110cd HORN/STROBE'REMOTE ' OUTDOOR 35cd Ms TOTAL . D • , LLA I A CURRENT CURRENT # f !•!fi • REQUIRED TOTALSYSIF"M" STANDBY REQUIRES TOTALSYSTEM REQUIREDALARM CAPACITY (AMP REQUIRED STANDBY TIME (HOURS) SIANDBYCURRENT CAPACITY ALARMTIME ALARM CURRENT HOURS) (AroviPS) (AMP (MINUTES) (AMPS) HOURS} 24.00 0.070000 6, s 15,00 6,230000 1.56 TOTAL REQUIRED 2 X 12 VOLT BATTE RI ES INST ALLED REQUIRED ALARM REQUIRED REQUIRED STANDBY CAPACITY (AMP HOURS) CAPACITY (AMP SAFETY FACTORBATTERY CAPACITY CAPACITY (AMP AMP/HR RATING PART# HOUR) (AMP HOURS 7.00 12V 7A BPS BATTERY CALCULATIONS 333 l iew Avenue Amityville, New York 11701 For SaleS r Repairs, 45-9440or 45 Starl-ink SLE-LTEV-CFB-PS Fire Alarm For T For o l Service, (B00},1100) 40 or visit us at htlp: fftech.naucosocurity.coml a (Note: Technical Service Is for security professionatsonly) Communicator Standby Battery Calculations NAPCO Publicly traded on Is Symbol: NSSC NAPCO 2019 WI2335L): 4/19 Standby Current Calculations for the model SLE-LTEV-CFB-PS Fire Alarm Communicator: Standby• .•. • Standby Current Draw of • s • • )- • • 8t Standby Time (Hours) = Battery Capacity . 0.80 = 65.9 Hours Communicator CurrentDraw Examples: 4 AH battery = (4AH / 0.085A) x 0.80 = 37.6 Hours 7 AH battery = (7AH / 0.085A) x 0.80 = 65.9 Hours CELLULAR COMMUNICATOR BATTERY CALCULATIONS RECEIVED SEE ATT I):tT;: AM, Air - = fist Fire & SecurltyNC. Life Safety Powered By Service VOLTAGE DROP CALCULATIONS PROJECT NAME CRISTELLE CAY CONDOMINIUM MAHI MAHI BLDG. � J PANEL BPS10A i � u NAC Wire AWG & Type Ohms Per 1000 Ft. * Length(ft) One -Way Starting Voltage Actual Ohms** Volts @ EOL %Drop Total current (A 4 ^ , r ` .: �.,�; ,` 14ga Solid 200 24.0 1.28 23.74 1.06 2 14ga Solid 3.19 510 24.0 3.25 17.75 26.03 1.92 3 14ga Solid 3.19 530 1 24.0 3.38 1 17.51 27.05 1.92 4 14aa Solid 3.19 1 550 124.0 3.51 17.26 1 2&07 1:92 taken from NEC Chapter 9 fable 8 - calculated for resistance over 2 conductors Maximum Current per NAC Circuit = 2.500 A nips BPS MODEL 110/A I AVAIL AMP 1 101 PERCENT USED I NAC- G4AVRF-75-110 GENESIS LED G4 HORN STROBE1751110 CD 41 Alarm: mA mA 250-3, � .., .. :.... �: ,. , 1„ ;,1 . r � q � CMS?' G4AVWF-75-110 GENESIS LED G4 HORN STROBE/751110 CD WG4WF-HVMC-35 GENESIS HORN-STROBEIWP OUTDOOMRED135cd777, G4LFWN H GENESIS LOW FREQUENCY HORN 50 238 112 Current Subtotals: mA �2' 0 mA l " , ' mA ,i�a ,...{3..." b { r y � �; mA r, z5 /344 uw,.Current Subtotals: mA €34AVWF_75-110 GENESIS I-ED G4 HORN STROBE1751110 CD GENESIS HORN-STROBEtWPOUTDOOMRED135cd GENESIS LOW FREQUENCY HORN 2 2 �12 Alarm: Alarm: mA mA 50 238 � ` r $" )" t N k mA mA 100 476 WG4WF-HVMC-35 G4LFWN-H Alarm: mA 112 , . _ 1 r" ,. „mA 1344 Current Subtotals: mA 1,i20 NAC-4 G4AVWF-75-110 GENESIS; LED 04 ,MORN ST€POSE 75 110 CD 7 mA WG4WF-HVMC-35 GENESIS HORN-STROBEF.>ir P OUTDOOR''.RE;:�`,35cd 2 Alarm: mA238 Y ll, x}' r ,,,., mA ^' ; G4LFWN H GENESIS LOW FREQUENCY HORN 1 121 Alarm mA 1 112 .,, , x ; ° = ' 1rA ,344 I 1,. Current Subtotals: mA 1 i2C BPS VOLTAGE DROP CALCULATIONS O w z o w 0O Uj z � CV/> l,- _, w a o v CD W z I,o W U00 z z Z! W CM w. _ > FLL a rn U U (n W = N m t w U J O Z U O J W 1- W Cu W Lu I- Z J J � Lu a a J U ag 0't� c CF) G U) a W W:" z 0 z w I EEF SS_ T - SL LUCIE COUNTY PLAN REVIEW BLDG: DATE: ELEC DATE: PLUMB: DATE: MECH: DATE: ' LLI I-- z +�S c/) T Z) Uj I` LU 2 0 LLI LLJ z Lu LIU w ~ 0 Q t� z n. c'`I w > 0 _ -Q- L Drawing Number mu] I OF 5 NOTES: 120V SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX QTY HEIGHT FACP FIRE ALARM CONTROL PANEL i01000 1 PROVIDED 66" A.F.F. BPS REMOTE BOOSTER POWER SUPPLY BPS1OA 1 4" SQUARE 1-1/2" DEEP 66" A.F.F. SD PITCAL SMOKE DETECTOR W/BASE SIGA-OSD/ SIGA-SB4 5 4" SQUARE 1-1/2" DEEP CEILING OHD HEAT DETECTOR SIGA-HRD 4 4" SQUARE 1-1/2" DEEP VERIFY IN FIELD CO INTELLIGENT CO DETECTOR SIGA-COD/ SIGA-SB4 2 4" SQUARE 1-1/2" DEEP CEILING �p DOUBLE ACTION PULLSTATION SIGA-278 3 1 GANG 1-1/2" DEEP 48" A.F.F. CT1 SINGLE INPUT MODULE SIGA-CT1 15 1 GANG STANDARD VERIFY IN FIELD CT2 DUAL INPUT MODULE SIGA-CT2 5 1 GANG VERIFY IN FIELD STANDARD rCRI CONTROL RELAY MODULE SIGA-CR 6 1 GANG VERIFY IN FIELD STANDARD HIGH POWER CONTROL RELAY MODULE SIGA-CRH 2 4" SQUARE 2-1/8" DEEP VERIFY IN FIELD ❑P wP WEATHERPROOF, DOUBLE ACTION PULLSTATION MPSR2-S45W-GE 6 PROVIDED 48" A.F.F. WEATHERPROOF, HEAT DETECTOR/BASE 302-AW-135/ AP-P 6 PROVIDED CEILING HS HORN STROBE G4AVWF 10 STANDARD 1 GANG 80" A.F.F. 4 WEATHERPROOF HORN STROBE WG4WF-HVMC 6 DOOR RATED OUTDOOR 80" A.F.F. HS H] ��JJ LOW FREQUENCY HORN G4LFWN-H 36 241 / S8 UADEEEP 80" A.F.F. O TAMPER SWITCH F.B.O 5 ----- ----- OWATERFLOW SWITCH F.B.O 4 ----- ----- OOC SYSTEM RECORD DOCUMENTS SS000689 1 ----- ----- ue VOLTAGE SURGE PROTECTOR ASCO 237 3 ----- ----- ` CELL DIALER SLE-LTEV-CFB-PS 1 PROVIDED VERIFY IN FIELD DEVICE QUANTITIES REFLECT OVERALL PROJECT FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F CKT # DEVICE # IHSI B-i-1 1 75 CD s3—CANDELLA RATING DEVICE SYMBOL SD �—DEVICE o0t ADDRESS FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL OR EQUIVALENT B (SLC DATA LOOP) 16-2 FPL OR EQUIVALENT ALL CONDUITS 3/4" EMT. MINIMUM UNLESS OTHER WISE NOTED. 40% FILLED MAX. rui..N r 1,- LIVING RM. BEDROOM I; IIi d t BATH , [� 2 -d4�� ---- BEDROOM F3A TM TANR;1 \ i B 1J SL 2 SL 3 a SL 4 - ; .I.0 " a W.LC ( KITCHEN __: �s KITCHEN it �� �� _.- -- C� sKITCHEN ILr `',I C W.LC i CL.,, -it h EUDL T1 I - L_?-J - -- t CL CL BATH I , - - - p BATH , i I - -- - - _El-iH - 'IF__'� .t •. _ ! �28 Tom:' ----____ -------- -- BEDROOM __ BEDROOM f"EN TIY - 11 d/Kit j o1 I1 4 Si SL 10 LSD 41 -HD [ 07 -- ELEV i fI SL 1 1 r TO ASH.,RM i q HALLWAY E 2ND FLOOR - DEVICE LAYOUT N-ALS SCALE: 118" = 1'-0" 7r w STOR STOR ELEV 2 BATH -.1 , i -tom i* h. � f_ ...... �' ± - -- -- -- -- -- BEDROOM _ Ia STAR g 47KO 1 .N- = - 215 EXACT LOCATION T.B.D r ALARt,� r � 4 iY(! SUPRV q 7Kr ys I — I 12_aI t ,4 r, E : �._EPS AC2 FROM' GARAGE F1,0 m LC DA3 LOOP TO 3RD 0 z W' I- i cam„ 0 0 ' � 'S W ® 0 Cn O 1 7 q W a 0 0 0 0 U) z O w of �1! U d co Z Z v O) W — M �✓ U � U) W z ry � W U U J O Z d U O -1W >? U J W W� Z J J w Q Q U 0- LL Q I' W am w 0- 2 - OCL w w z CD z w �a - I -;I 0 - Hl -1 EXACT LOCATION EXACT LOCATION LLB T.B.D _ T.B.D — — r - - q Lu �y i....t - 14T'ry47k;,1r,1 I r� ?A E; �7 { —, — — 1--- t I % —1 (, T FA RISER i. SL 12Ir WE 1- L- J L .- J BACK FLOW Lu®a BPS NAC4 TO 4TH FLOOR (PENTHOUSE) PREVENTER CL �L '(BPS NAC93 TO 3RD �"`FL'j#Off))OR w g0g PS NAC2 T O ��:ND F �.it 0R Q p c a uj Li— z m LD O w E GARAGE FLOOR - DEVICE LAYOUT N S SCALE: 118" = 1'-0" w NOTES: 120V SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX OTY HEIGHT FACP FIRE ALARM CONTROL PANEL i01000 1 PROVIDED 66" A.F.F. BPS I REMOTE BOOSTER POWER SUPPLY BPS10A 1 4" SQUARE 1-1/2" DEEP 66" A.F.F. SD PITCAL SMOKE DETECTOR W/BASE SIGA-OSD/ SIGA-SB4 5 4" SQUARE 1-1/2" DEEP CEILING OHD HEAT DETECTOR SIGA-HRD 4 4" SQUARE 1-1/2" DEEP VERIFY IN FIELD CO INTELLIGENT CO DETECTOR SIGA-COD/ SIGA-SB4 2 4" SQUARE 1-1/2" DEEP CEILING p DOUBLE ACTION PULLSTATION SIGA-278 3 1 GANG 1-1/2" DEEP 48" A.F.F. CT1 SINGLE INPUT MODULE SIGA-CT1 15 1 GANG STANDARD VERIFY IN FIELD CT2 DUAL INPUT MODULE SIGA-CT2 5 1 GANG VERIFY IN FIELD STANDARD CONTROL RELAY MODULE SIGA-CR 6 1 GANG STANDARD VERIFY IN FIELD CRH HIGH POWER CONTROL RELAY MODULE - SIGA CRH 2 4 SQUARE 2-1/8" PEEP VERIFY IN FIELD ❑P WEATHERPROOF. DOUBLE ACTION PULLSTATION MPSR2-S45W-GE 6 PROVIDED 48" A.F.F. HD O WEATHERPROOF, HEAT DETECTOR/BASE AP-P 302-AW-135/ 6 PROVIDED CEILING HS HORN STROBE G4AVWF 10 1 GANG STANDARD 80" A.F.F. IHS1 WEATHERPROOF HORN STROBE WG4WF-HVMC 6 OUTDOOR RATED 80" A.F.F. PROVIDED MIF LOW FREQUENCY HORN G4LFWN-H 36 2-1 SQUARE DEEP / 80" A.F.F. O TAMPER SWITCH F.B.O 5 - -- ----- OWATERFLOW SWITCH F.B.O 4 ----- ----- rD__0Cj SYSTEM RECORD DOCUMENTS SS000689 1 ----- ----- un VOLTAGE SURGE PROTECTOR ASCO 237 3 ----- ----- CELL DIALER SLE-LTEV-CFB-PS 1 PROVIDED VERIFY IN FIELD DEVICE QUANTITIES REFLECT OVERALL PROJECT FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B,FACP=F CKT# DEVICE # Ei-t-t HS 75 CD —CANDELLA RATING DEVICE SYMBOL SD .-- 001 DEVICE ADDRESS FIRE ALARM WIRE L EGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL OR EQUIVALENT B (SLC DATA LOOP) 18-2 FPL OR EQUIVALENT ALL CONDUITS 3/4" EAT. MINIMUM UNLESS OTHER WISE NOTED. 40% RLLED MAX t ICI II 4 ,a % LIVING RM. i BEDROOM P H B-4-13 ! B-4-12 LF j q IF _ - H H C L. KITCHEN r i � t i _J L. � r � rl i ..-. ram\ �-„✓-,_,_ tell i;,4 If LIVING RM. LIVING RM. �I �i LIVING RM. BEDROOM _ I BEDROOM BEDROOM , 8-4-10 P H P I -"-I �" B-4-7 B-4-6 _v _ ^? F�Ly , B-4-4 u 8-4-11 � `� PG 1 G j, tf — Lti '' i LF t H H Y - -- K:H: H H H -- j TE CLJ I - - , TCHENKI-KITCHEN KITCHEN- jW.1.0 W.I.CW.LC W LC' l 1 i -- -- )' I BATH - ' j LF H it \� if BEDROOM �ATIi A NTR STAIR i `- B-4-16 _.L'. L 75CDmmFB-4-1 35CD l 1 I , _ I Z I r� �3 I I' �1 t ,�-, CL. L. C I BATH _ j BATH lii I i , � i 1 I \ i ELEV 1 (; LF BArmk I H `. BEDROOM LF t H BEDROOM 13-4 $ HALLWAY TR \ ELEV 2 f Ell y`Ti f� Vx.i E I , BATH _ �. H ' B-4-3 NTR AT,H BEDROOM _ B 4-1� �s 75CD A STAIR 2 H S — B-4-2 35CD FA RISER - -- - -- ( s EXACT LOCATION T.B D BPS NAC4 FROM GARAGE FLOOR 's + ( 47 `4i L t ai,3 ;e.i LOOP TO �i°.00 j PA�'' EllI z_ t L_ J L--J E 4TH FLOOR PENTHOUSE, - DEVICE LAYOUT N S SCALE: 1 f 8" = 1'-0" 7PIC w LIVING RM. BEDROOM 8-3-5 KITCHEN -._.. ;: �� --kITCHEN �' 11i� - I !! i W.I.0 ! W.LC_ y, KITCHEN T WIC W LC': - r ` STAIR 1 75oa, s _ H 5 r y � ; CL.iV CL. - - BATH _ - - - ilk BATH LF U H HtJ -- 8-3-9 BEDROOM ELEV 1 F't; BEDROOM DWP �_ T B-3-15 35CD't HALLWAY- E 3RD FLOOR - DEVICE LAYOUT N S SCALE: 1/8" = 1'-0" w BATH _— % H p ,�i y NTR EATIf BEDROOM ELEV 2 l BATt T _ , TaIR 2 1 - P7 R - B-3 1 HS 75CD 8-3-2 1A FA RISER a EXACT LOCATION _ T.B.D j �t litg t ,t 7t 'r� iOL. �a , \—BPS NAC3 FROM GARAGE FLOOR S 1 ETA LOOP FROXII '_':NO FLOOF" t _ �'A LOOP TO4TP 1�LOOR (P�;1v I"LICItj�aLs) 0 w _j z E- U 00 CD Z w U)O a H o w N Z W ev o � W 't N Z v C _ W — M J U J W � > 1- LI_ n rn C'? U U) w_ U U d J W U J O Z U O J w 0J W Z J w J \~� Q w rn 0 Q n n- (L. u z ( Z w i CD r C") < ILL- CL � a�3 U1 Lu w S.S.. 05 0 41- LL_ `s�Ia 1 ._ LJ ce% 1 ^ t ELEVATOR 1 CONTROL L - -" - - - - - - - - - - - J ELEVATOR 2 CONTROL E ROOF - DEVICE LAYOUT NAL-, SCALE: 1Z8" = 1'-0" 7�� FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SyMBq_L_F DESCRIPTION MODEL # p.T.Y BACKBOX HEIGHT FACP FIRE ALARM CONTROL PANEL i01000 1 PROVIDED 66' A.F.F. BPS REMOTE BOOSTER POWER SUPPLY BPS10A 1 1-1/2" 4" SQUARE DEEP 66" A.F.F. SIGA-OSD/ 5 4" SQUARE CEILING SD PITCAL SMOKE DETECTOR W/BASE SIGA-SB4 1-1/2" DEEP HD HEAT DETECTOR SIGA-HRD 4 4" SQUARE 1-1/2" DEEP VER'FY IN FIELD SIGA-COD/ 2 4" SQUARE CEILING CO INTELLIGENT CO DETECTOR SIGA-SB4 1-1/2" DEEP ❑p DOUBLE ACTION PULLSTATION SIGA-278 3 1 GANG 1-1/2' JEEP 48" A.F.F. CT1 SINGLE INPUT MODULE SIGA-CT1 15 1 GANG STANDARD VERIFY IN FIELD CT2 DUAL INPUT MODULE SIGA-CT2 5 1 GANG STANDARD VERIFY IN FIELD CR CONTROL RELAY MODULE SIGA-CR g 1 GANG STANDARD VERIFY IN FIELD 4' SQUAREq,IFY IN FIELD CRN HIGH POWER CONTROL RELAY MODULE SIGA-CRH 2 2-1/8' DEEP ❑P en WEATHERPROOF, DOUBLE ACTION PULLS TATION MPSR2-S45W-GE 6 PROVIDED 48" A.F.F. xv HD WEATHERPROOF, HEAT DETECTOR/BASE 302-AW-135/ AP-p 6 PROVIDED CEILING HS HORN STROBE G4AVWF 1 GANG STANDARD 8C" A.F.F. _ HS WEATHERPROOF HORN STROBE WG4WF-HVMC 6 OUTDOOR RATED PROVIDED SC" A.F.F. 4" SQUARE 2-1/8" DEEP 8C' A.F.F. L, H NI LOW FREQUENCY HORN G4LFWN-H 36 OTAMPER SWITCH F.B.O g ----- ----- OWATERFLOW SWITCH F.B.O 4 ----- ----- DOC 1 SYSTEM RECORD DOCUMENTS SS000689 1 - --- ----- VOLTAGE SURGE PROTECTOR ASCO 237 3 ----- CELL DIALER SLE-LTEV-CFB-PS PROVIDED VERIFY IN FIEUI DEVICE QUANTITIES REFLECT OVERALL PPCJEC- FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F CKT # DEVICE # B-1-1 HS 1 75 CD -e---CANDELLARATING DEVICE SYMBOL •--DEVICE ADDRESS SD 001 FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NArl 14-2 FPL OR EQUIVALENT B (SLC DATA LOOP) 18-2 FPL OR EQUIVALENT ALL CONDUITS 3/4 ENT. NINIMIM UNLESS OTHER VASE NOTED. 46Z HIED MAX. SYSTEM OUTPUTS % co cj Z z SYSTEM INPUTS '*r A c- B CQ- Q D 'r E ' F c G v H I J I K -< L M r. N 0 1. MANUAL FIRE ALARM BOXES • • 1 1 1• • • 2. SMOKE DETECTOR 0101 • • • 3. SMOKE DETECTOR - 1ST FL ELEV. LOBBY. 0191 • • • • 4. HEAT DETECTOR - ELEV. LOBBY. • • • • • • 5. CO DETECTOR • • • • 6. 1HEAT DETECTOR • • • • • 7. WATERFLOW • • • • • 8. SPRINKLER CONTROL VALVE TAMPER SWITCH • • • • 9. FIRE ALARM AC POWER FAILURE • • • 10. FIRE ALARM SYSTEM LOW BATTERY • • • 11. OPEN CIRCUIT • • • 12. GROUND FAULT • • • .1 NOTIFICATION APPLIANCE CIRCUIT SHORT • • • SEQUENCE OF OPERATION ROOF NOTES: 1. FIRE ALARM CONTROL PANEL SHALL BE ANALOG ADDRESSABLE TYPE. 2. INITIATING DEVICE CIRCUIT SHALL BE CLASS "B". 3. NOTIFICATION APPLIANCE CIRCUIT SHALL BE CLASS "B". I 'I 4TH FLOOR 1B,1A-j J. BOX J. BOX J. BOX F------------------SHUNT --1 I PRIMARY ALTERNATE FIREHAT SHUNT TRIP STATUS I 1 B 1 t ! CR ------ CR bCp, L----------------------� ELEVATOR 2 CONTROL I ----------------------� SHUNTTRIP 1 SHUNT TRIP FIREHAT ALTERNATE PRIMARY I 1 L----------------------J ELEVATOR 1 CONTROL ROOF 1 A _&N- 45-Y., v� �r =1I =F S SZIF 15KI1Aa LF� 1 EOL nc is u u i i n a �sra n n n n n 75CD I 35C EXACT LOCATION T.B.D r — — 1 WP r Q 1 ' 1 ra A � y 7" L--- ----� EN s NO 4.KCC` 1_OL. 4TH FLOOR 1A -tic►-..� 15 L. LF�L. �� F EOL H S �xa n S asco H H H H 75CU I 35CD EXACT LOCATION T.B.D r — supp— — — WP h7K0 '} 47K.0 P EOL. 47K4 c� 4' 1, 1f EQL. 1 EOL. Wr 1 B �T 1 Tr, 1 l ---- --- = I 13$ 1 1 �' 4 i_I 142 f, i 43j -- H H 47KQ 3RD FLOOR 3RD FLOOR A 4 '"✓' - 1B 2A d L� ',C 35ro % I C I I EOL Yg r ,r`r Lr Ld EXACT LOCATION I .s T.B.D � r - -� V{P SSp YAP H G,z 4, Kc 47KSi Foil_ EOL. ri ----_- EOL L—_ 1. CT1 I ----- C � 1 c 2ND FLOOR 1 B,3A L-- +r---J O J a U co cv �. o Z W N r O F- W a . o CD o cn z O >— W of G'V O U 00 � o Z W �M P—+ J Tt _j LL > F- W CL U U cn — - w N J W U J O z LU 0o� W W 5 I- w � Q J IjI-z JD .J D < WW =mom Nr F- Q LL Q Q W rn 0 I- d L✓ W W z c.D Z W Q CL' LLI C/) Clr W F— Z) 0 LLI LU LU 2 s Q Z LL W c) LU 0 U P(j'j"'L' 1) # 12THHN Drawing Number GARAGE FLOOR GARAGE FLOORF 0 ---________�_..__ (GREEN) -___________�______ ____�._ .�___ RISER DIAGRAM 4 OF __—.._... --- .___—_—__._ I 1 1B i I -1I BPS-10A IRELESS CELL SIGNAL TO CENTRAL STATION. SUR FAQ --. ( CELLULAR GROUND L.__ "�T !N .FAUL?____ 1COMMUNICATOR SUR 120VAC DEDICATED _ ]STARLINK FIRE (1) # 12THHN _,._ ______ _�TEv-c�-Psi (GREEN) Ll DEDICATED iOl OOOGD 120VAC�-- SUR FAr+P 2ND FLOOR 1B - J. BOX — --- 1 _ _..._.— I? - — - --- �, L ---- _.. _ .�. _ — - - C U --- ( - ; rM� T" EXACT LOCATION EXACT LOCATION i T.B.D T.B.D 1 _ r '-7RV. NLfit4 Ni QS %P w KQ 1 n{ I1 U 1L_�J i� ILMO � BACK FLOW 133� I- - J L - - PREVENTER I ME t�3 UJI 0 UJ LU Q O d�"-$ CD LL. EST 10- 1 MOUNT EST SIGA SERIES MODULES SIGA-CT1/CT2, SIGA-CR, SIGA-MM1 SIGA-WTM. TO STANDARD SINGLE GANG DEEP ELECTRICAL BOX. THE TERMINALS WILL ACCEPT #14AWG WIRE. \ COMPATIBLE ELECTRICAL BOX EOL OHM MOUNT EST SIGA SERIES MODULES SIGA-CT1/CT2, SIGA-CR, SIGA-MM1 SIGA-WTM. TO STANDARD SINGLE GANG 1/1-2' DEEP ELECTRICAL BOX. THE TERMINALS WILL ACCEPT /14AWG WIRE COMPATIBLE ELECTRICAL BOX EOL OHM TIP. N.O. TYP. N.O. NfINTIC DEVICE NTDATNG DEVICE 1 INPUT t INPUT 2 Ea. 47K OHM MOUNT EST SIGH SERIES MODULES SIGA-CT1/CT2. SIGA-CR, SIGA-MM1 SIGA-WTM. TO STANDARD SINGLE GANG 1/1-Y DEEP ELECTRICAL BOX. THE TERMINALS MILL ACCEPT /14AWG WIRE. \ COMPATIBLE ELECTRICAL. BOX 0 w (n z F- L)Lu O a F- o c_� s� C4 0 o w v D TB2 0 0 8 7 T82 e 7 a a erw r a. e. 0 SIGA-CT1 ® SIGA-CT2 v. is th � � IFD u°mD OPTIONAL SELF-ADHESIVE N n oPTKNyAL ° SELF-ADHESIVE NO�aAL 1 10 VAC N 0 N -LIMITED [POWER LIMITED ONLY ( > ° ° FRENCH°�`��` �1 m t ° ° ,,�►f�Ae FRENCH `�� �1 0 ' 0 I / WALL PLATE. WHITE / WALL LPPLATE, WHITE /1 rs 0 w as s w FROM FACP OUT(*) ....__�_�...__ ...__.-_____._.._......- °ArA sw FROM FACP .--..e+) /�/v�(�,�. , 0 OR TO NEXT PREVIOUS DATA X-) Dar art(-) DEVICE I pUEV�IOR OUISDAu INC-)0 u - - I DEVICE CEILING MOUNTED SMOKE/HEAT- DETECTOR 24' MIN HANDICAP BEDROOM STROBE MORE THAN TWO APPLIANCES IN THE SAME ROOM OR ADJACENT SPACE WITHIN THE FIELD OF VIEW SHALL FLASH IN SYNCHRONIZATION. FINISHED FLOOR o 0 T r' rr ur DO NOT USE HOLES FIRE ALARM DEVICE MOUNTING GUIDE A/C SUPPLY DIFFUSER f ACCEPTABLE HERE 4" AUDIOVISUAL / DO NOT INSTALL I (MAX) & VISUAL -ONLY IN THIS AREA DEVICES CEILING MOUNTED NOTIFICATION DEVICE. WALL MOUNTED l SEE PLAN FOR LOCATION. SMOEK/HEAT DETECTOR 96" MAX (NFPA, ADA) TO THE BOTTOM. ABOVE FINISHED FLOOR TO TOP OF LENS 5'-0 80" MIN (NFPA, ADA) ABOVE FINISHED FLOG TO BOTTOM OF LENS MAX FROM EXIT DOOR 3 MANUAL PULL MAGNETIC FIRE STATION DOO REMOTE PHONE HOLDER 0° ANNUNCIATOR JACK 5" DUCT DOOR DETECTOR WIDTH REMOTE TEST LESS 3" s 0 } 0 ® w Q �o 52 48' MAX (NFPA, ADA) 0 42" MIN (NFPA) MEASUREMENTS SHOWN ARE ¢.N TO THE TOP OF PULL HANDLE IMPORTANT NOTE NOTE NOT A DEVICES SHOWN ON THIS DETAIL APPLY TO THIS FIRE DEVICE MOUNTING DETAIL CHECK WITH MANUFACTURE'S INSTALLATION SHEET PROJECT. SEE THE PLAN VIEW LAYOUT OF THE FIRE ALARM FOR THE EXACT ROUGH -IN HEIGHTS, LOCATION OF SYSTEM TO VERIFY WHICH DEVICES APPLY. AND WHICH DO NOT. N.T.S. BACK BOXES, AND WIRING REQUIREMENTS. STROBE OR sPEAKER/STRO tF O O 80. A.F.F. OR E O 6' BELOW CELNIG (WHICHEVER IS LOWER) PULL STATION O 48" A.F.F. LT p ADA HEIGHT REQUIREMENTS NO SCALE WIRE STRIPPING GUIDE STRIP 1 /4" FROM THE ENDS OF ALL WIRES THAT CONNECT TO THE TERMINAL BLOCKS OF THE MODULE. 1 /4" DO NOT EXPOSE MORE THAN 1 /4" SIGA—CT1 MOUNTING DETAIL N.T.S. TYPICAL SPEAKER OCT. T84 T81 TO — NEXT DEVICE OR RBEB our(-) EOL RESISTOR FROM FAC- P p FROM FACP-�----. OR TO NEXT PREVIOUS DEVICE Dm _ DAyI _ DEVICE SINGLE INPUT MODULE WIRING DIAGRAM N.T.S. SINGLE INPUT RISER MODULE WIRING DIAGRAM N.T.S. COVER RELEASE SCREW COMPATIBLE ELECTRICAL BOX TB2 B SIGA-278 d BACK Ilm ° PLATE O O NORMAL T01 4 3 2 / ° 0 un°V` 0 ' 010 ° TOGGLE f SWITCH (III ° FROM FACP OR I TO NEXT PREVIOUS DATA - l DATA art(-) DEVICE ~_ EEASASS ROD O EVER MANUAL PULL STATION SINGLE MODEL — SIGA-278 STAGE WIRING DIAGRAM N.T.S. INSTALL EST SIGA SERIES 270/278 MANUAL PULL STATION USING STANDARD 1-1/2"(38mm) DEEP CONCRETE SLAB BACK BOX 3 4" EMT CONDUIT / DETECTOR TYPICAL HEAT DETECTOR/SMOKE DETECTOR MOUNTED ON CONCRETE OR GYPSUM CEILING NOT TO SCALE - 3/4" EMT CONDUIT BACK BOX SIGA—CT2 MOUNTING DETAIL N.T.S. CKT. TB4 SIGA-CC 1 � o /COTE NOOK 8 7 6151 4 3 2 1 T81 0 0 011 TB1 TO NEXT DEVICE OR _ RLSER Glm-1 EOL RESISTOR FROM FACP - l I FROM FRCP —CAR OR TO NEXT PREVIOUS DAu _ pW _ VICE DEVICE SINGLE INPUT RISER MODULE WIRING DIAGRAM N.T.S. AM-07-06-052197-00 DATA OUT(,) TO NEXT DATA OUT(-) DEVICE DUAL INPUT MODULE WIRING DIAGRAM N.T.S. SIGA—CR MOUNTING DETAIL N.T.S. ANIM ---NWC DUDr oErECIOB \ \ \ \\ Swung N r'DaE E*MW TIME D i ®ROCKET \ TUBE \ DOWIbi TUBE /\:,/ ! THIN ; I 1 /10 BNEET 1&TN, sclan (%'Y) IiWOC W91�T DUCT DETECTOR HOUSING DIAGRAM N.T.S. LOCATION REMOTE POWER SUPPLY ..........___O NOTIFICATION APPLIANCE CIRCUIT I NAC1 ± NAC2± - __....!.�_ .._..__.. NOTIFICATION APPLIANCE CIRCUIT 2 NAC3 +_ M- NOTIFICATION APPLIANCE CIRCUIT 3 NAC4± NOTIFICATION APPLIANCE CIRCUIT 4 24VDC NAIN NA SENSE 1 COM - OUT SENSE 2 COMOUT NO TROUBLE COM NC r FROM FACP OR AN DATA N(-) PREVIOUS DEVICE sKu-On rm wmu ,maE 0.ATA OUT'(1, TO NEXT DATA OUT(-) DEVICE REMOTE BOOSTER POWER SUPPLIES MOUNTING DETAIL (BPS 10A) N.T.S. NEW VISUAL ALARM DEVICE DRYWALL TYPICAL VISUAL DEVICE INSTALLATION ON GYPSUM WALL NOT TO SCALE - SIGA-AB4GT, O O ® SIGA-AB4G-LF: SIGA-AB4G, SIGA-AB4G-LF: JUMPER CUTS OUTPUT MODE DEFAULT = FIRE VOLUME SETTING CUT/REMOVE JUMPER FOR DEFAULT = HIGH FIRE PLUS CO CUT/REMOVE JUMPER FOR SIGA-AB4G: LOW dB ® ® TONE SETTING DEFAULT = TEMPORAL DATA- DATA- OAT ­ SIG+ sic -OUT ININ/OUT CUT/REMOVE JUMPER FOR STEADY O SIGA-AB4GT: NOT USED 24 VDC IN FROM POWER SUPPLY 24 VDC OUT OR PREVIOUS BASE* + TO NEXT BASE OR EOL RELAY DATA IN DATA OUT FROM SIGNATURE CONTROLLER TO NEXT SIGNATURE DEVICE OR PREVIOUS DEVICE AUDIBLE SOUNDER BASES FIRE MODE AB4GT A84G AB4G-LF SOUNDER BASES - NOT TO SCALE - T82 8 7 8 SIGA-CR E 0 OPTIONAL NOIBBIt SELF-ADHESIVE TBI 0 (SUPPLIED) WA PLATE, WHITE / (1 GANG) '. DATA N(+) p4ah (7f+) FROM FACP \ OR O NEXT TDEVICEE PREVIOUS DATA -) DATA O -) DEVICE CONTROL RELAY MODULE WIRING DIAGRAM N.T.S. DETECTOR MOUNT BASE TO 4' SQUARE STANDARD ELECTRICAL BOX 1-1/2- DEEP. TAMPER -RESIST LEVER ARM -BREAK OFF TO DISABLE - (LOCATED ON BASE) ACCESS SLOT FOR TAMPER -RESIST MECHANISM SD / HD SIGA—OSD PS/HRS MOUNTING DETAIL N.T.S. CONTACTS SHOWN WHEN RELAY IS DE -ENERGIZED H—FSDN E.S.T. SIGA-CR I POWER TB2 e 7 B NOTE ALSO USED FOR ELEVATOR N.: C N.Q• • SHUNT TRIP. RECALL AND FAN SHUTDOWN �� o 0 NpM4 zw T81 rwn,n,n' B B DATA 129�) FROM FACP OR TO NEXT PREVIOUS DATA N(-) DATA OUT(-) DEVICE DEVICE CONTROL RELAY MODULE WIRING DIAGRAM DETAIL #5 co z O U) w c"i v U d - :. Z Z v W - M x--i 2 J >F-UL d d' U _W 5 (n=N �, Q J ' W V o 0 Z U O J W W LU at; Lu J Q = 00 � a a UHF- LI- Q Q CL W m O < a w w CD w Qj ca o CD ui tE en __j_j C�ui u 0 of d co (D