HomeMy WebLinkAboutLetter; Construction Plan AdjustmentsM SEASIDE -- ENGINEERS — Civil and Structural Engineering September 23, 2019 Angela Staples White Aluminum — Palm City 519 NW Enterprise Drive #1607 Port St. Lucie, FL 34986 RE: Colaner Residence —10725 S. Ocean Drive, Jensen Beach Ms. Staples, You have requested that I prepare a construction plan for the above referenced property to enclose a portion of the residence with a Type III sunroon and also enclose existing openings in the host structure. The adjacent room is a sleeping room; however, gress °ui cl ange,�,,_, fh proposed-constru as t�hrsr'"`e�is aq�al q_ te—gr�ess path. Additionally, the proposed construction is compliant with Housing and Urban Develo regulations. Please direct the building official to contact me if there are any questio c6rrr Osi��/* Sincte�®.•��GE Sic• • e� / v ® e P` Cr� •• o , V. SAP i Principal Engineer01 -1 - SeaSg. �•�� 202-8008 edward SeasideEn ineers.wo www.. m ( www.facebook.com/seasideengineers ,����st►a e t � eeee�� "I Pil Sir. t . {m COUNTY } BOCC 4265 60th Court * Vero Beach, Florida 32967 * (772) 202-8008 *info@seasideengineers.com www.seasideengineers.com LEGAL DESCRIPTION LOT 18, BLOCK A, HOLIDAY OUT OF AMERICA AT ST. LUCIE, INC., ACCORDING TO THE PLAT THEREOF, AS RECORDED IN PLAT BOOK 14, PAGE 28, OF THE PUBLIC RECORDS OF ST. LUCIE COUNTY, FLORIDA; LESS AND EXCEPT A PORTION OF SAID LOT 18, BLOCK A, WHICH LIES NORTHWESTERLY OF THAT "PROPOSED OWNERSHIP LINE" AS SHOWN ON EXHIBIT "A"ATTACHED HERETO, WHICH PORTION OF LOT 18, BLOCKA BEING LESSED OUT IS DESCRIBED AS FOLLOWS. BEGINNING AT THE WESTERLY PLATTED COMMON CORNER OF LOT 17 AND LOT 18, BLOCK A OF SAID PLAT BOOK 14, PAGE 28, THENCE RUN N31 °41'46"E (PLAT BEARING) ALONG THE PLATTED COMMON LINE FOR SAID LOT 17 AND LOT 18, BLOCK A, A DISTANCE OF 85.36 FEET TO THE EASTERLY PLATTED COMMON CORNER OF SAID LOT 17 AND LOT 18, BLOCK A,; THENCE RUN S23°49'31 "E ALONG THE PLATTED EASTERLY LINE OF SAID LOT 18, BLOCK A, A DISTANCE OF 12.00 FEET TO A POINT; THENCE RUN ALONG A "CLOSING LINE" S38°51'16"W A DISTANCE OF 79.18 FEET TO THE POINT OF BEGINNING. Flood Zone: AE Community Number:120285 Panel:12111 C0314 Suffix: J Base Flood Elevation: 8 (NAVD88) FIRM Date: 2-16-2012 FIRM Effect./Rev Date: 2-16-2012 Iirt67l0W 1. LEGAL DESCRIPTION PROVIDE BY CLIENT 2. NO SEARCH OF THE PUBLIC RECORD FOR THE PURPOSE OF ABSTRACTING TITLE WAS PERFORMED BY THIS OFFICE 3. NO SUBSURFACE IMPROVEMENTS WERE LOCATED AS PART OF THIS SURVEY 4. ALL ANGLES AND DISTANCES SHOWN HEREON ARE BOTH RECORD AND MEASURED UNLESS OTHERWISE NOTED FOUND 1/2. IRON ROD FOUND 1/211 o�, IRON ROD 0�,�4, o NO I.D. ti /tiG''�'c Cu�O Cb k LOT 17 BLOCK A 4:��/ %N; OZv % �. pRoApJ* Qv� / S>- Q' :d NO I.D. }=20.00' .(2.0'OFFSET)=19.74'�N►i / / �''�� • - L-- SET 1%2"�. • IRON ROD LB# 7463 `<0 -- = R` 02 n,. �� � 4�0 Sp �'• 28 4d f 0 U oC 4 ,, IV 151RSTTI� VDyTOF' 6�k (Ij. . CoMM q y (IMPS <pj ) 4� N �SE(PJ Ro�F�) �N- 2 Lpo G GJ 3 0 oQ° RESIDENCE >::��p61���l��• O•� F.F. EL.-8.9T CV 0Nlo 281 Off% ` • o S66 �3 �G� %FOUND 1/2" IRON ROD \\. NO I.D. (2.01 OFFSET). V. FOUND 1/2" IRON ROD NO I.D. LOT 19 BLOCK A MIN. Sri BA},K FRONT SIDES Ilk S!J 0 LOCATION MAP NOT TO SCALE LEGEND A/C AIR CONDITIONER B.F.P. BACKFLOW PREVENTER C.B.S. CONCRETE BLOCK STRUCTURE EL. ELEVATION F.F. FINISHED FLOOR I.D. IDENTIFICATION L LENGTH L.B. LICENSED BUSINESS M MEASURED N.T.S. NOT TO SCALE N&D NAIL & DISC N.A.V.D.NORTH AMERICAN VERTICAL DATUM N.G.V.D.NATIONAL GEODETIC VERTICAL DATUM O.R.B. OFFICIAL RECORDS BOOK PSM PROFESSIONAL SURVEYOR AND MAPPER P.R.M. PERMANENT REFERENCE MONUMENT PG. PAGE P.B. PLAT BOOK PK PARKER KYLON NAIL R RADIUS TAN TANGENT T.B.M. TEMPORARY BENCH MARK q CENTERLINE AND # NUMBER 0 DELTA OR CENTRAL ANGLE • *• - CONCRETE ORIGINATION BENCHMARK ST. LUCIE COUNTY BRASS DISK "G-308 " N.A.V.D. ELEVATION = 4.41' REVISIONS: 1. ADDED SITEPLAN: 11-05-2019 2. REVISED SITE PLAN: 11-19-2019 3. ADDRESS COMMENTS:12-05-2019 SURVEYORS CERTIFICATE: EREBY CERTIFY THAT THIS BOUNDARY � �URVEY IS A TRUE AND CORRECT REPRESENTATION OF A SURVEY PREPARED UNDER MY DIRECTION. NOT VALID WITHOUT A RAISED EMBOSSED E/A�A�NDiSIGNATURE. KENNETH J. OSBORNE PROFESSIONAL SURVEYOR AND MAPPER #6415 U- O w Of W co00r� w q, wWm ��A Q L W o oUw "j U x � g SOW w W�� a a U U w M C0 ... C-18237 1 OF1 10-16-2019 �. 1 "=10' 0 0 � wM a •5�, F Un o ° z 0 W o 01) 6 �� tn tn C a 4 NOTE: THIS DRAWING IS FOR ILLUSTRATIVE PURPOSES. DRAWING NOT TO Design Parameters SCALE. USE DIMENSIONS GIVEN. CABLE BRACING MAY TERMINATE AT SLAB 1. Building Occupancy Category, Paragraph 1604.5 and Table 1604.5: Risk IN DIFFERENT LOCATION. MAINTAIN ANGLE PER DETAIL. Category 1. 2. Basic Wind Speed, Table 1609C, State of Florida Debris Region 8L Basic Wind Speed, Paragraph 1609.3.1 and Table 1609.3.1 Equivalent Basic Wind Speed, VuLT=160 MPH 3. Exposure Category, Paragraph 1609.4.3 : D Applicable Codes, Regulation and Standards 1. The 6th Edition (2017) Florida Building Code, specifically Chapter 16 Structural Design, Chapter 20 Aluminum, and Chapter 23 Wood. ,_9A 2. AA ASM 35 and Specifications for Aluminum Structure, Part 1-A of the Aluminum Design Manual prepared by The Aluminum Association, Inc. Washington, D.C., 2010 Edition Mil 3. ASCE 7-10 36 General Notes r 1. The contractor shall verify all dimensions prior to construction 2. All work shall comply with all local and regional ordinances. 3. Any deviation from this plan shall be reviewed by the engineer of record and is y subject to approval. 9 Specifications The following specifications are applicable to this projects 1. Where concrete specification are required, whether in the screen enclosure scope or not, by one or more regulatory agency, the following specifications are applicable. 1.1. Concrete shall conform to ASTM C94 for following components: 1.1.1. Portland Cement Type 1, -ASTM C 150 1.1.2. Aggregate - Large Aggregate 314" max - ASTM C 33 1.1.3. Air entraining +/-1 % - ASTM C 260 1.1.4. Water reducing agent - ASTM C 494 1.1.5. Clean Potable water 1.1.6. Other admixture not permitted 1.2. Metal accessories shall conform to: 1.2.1. Reinforcing Bars - ASTM A615, grade 60 4 1.2.2. Welded wire fabric - ASTM A185 1.3. Concrete slump at discharge per chute not less then 3" or more than 5'. Water added after batching is not permitted. 1.4. Prepare and place concrete per American Concrete Institute Manual of Standard Practice, Parts 1, 2 and 3 including hot weather recommendation: 1.5. Moist cure or polyethylene curing required. 1.6. Prior to placing concrete, treat the entire subsurface area for termites in compliance with the FBC. 1.7. All aluminum components embedded within concrete shall be coated with e bituminous paint or epoxy. 1.8. Fiber reinforced concrete per ASTSM C1116 is an acceptable alternative to 6X6 W1.4/W1.4 WWF. 2. Aluminum extrusions shall be 6005 T5 Alloy. 3. Fasteners are required to be corrosion resistant, minimum SAE Grade 2 or better zinc plate to ASTM B633, or stainless steel series "300". 4. All Self Mating Beam Sections are to be stitched with either #14 screws 6" from end 24" on center or #12 screws 6" from end 12" on center. 5. Screened enclosures containing swimming pools shall comply with the applicable requirements of FBC R4501.17 Residential Swimming Barrier requirements. 6. Door location shall be determined by contractor in the field. 7. When installing pavers over concrete slab or footing which are supporting aluminum members, such as continuous screen tracks or upright, the anchors must extend past the pavers and reach proper embedment into the underlying foundation. 8. All flashing and waterproofing shall be provided by the contractor. `• 9. Use of these plans acknowledges and accepts a limit of liability not to exceed design and engineering fee. 10. Vinyl and acrylic panels shall be removed when wind speeds exceed 75mph Foundation Design: New 12"x12" (2 #5 bar Cont.) thickened edge, 4" monolithic slab Concrete shall be a minimum 2,500 psi FIBERCRETE. Reber 31" lap splice. Use 3" chairs. Per current edition of the Florida Building Code, Residential, Section 401.4.1, soils testing is not required for design using the presumptive bearing pressure of 1,500 psf. Roof Type Screen Size Composite NONE - SUN ROOM ALUMINUM MEMBER DIMENSIONS HOLLOW SECTIONS SELF MATING BEAM ISMS) 2x2: 20x 2"x 0.046" 2x4SMB: 2x4"x0.044"x0.100' 2 x 3: 2' x 3' a 0.05(" 2 x 5 SMB: 2x5'x O.050'x0.10G' 2x4: 2"x4"x0.05W 2x6SMB: rx6"x0.0S0'x0.120' COLUMNS 2x5: 2"x 5'x 0.050' 2x7SMS: rx7"x 0.057"x0.120. 2xSSMB: r x 8'x 0.072 x 0.124' 2x9'xO.072"x0.124' 3x3: 31x31x0.125" 4x4: 4'x41x0.125" OPEN BACK SECTIONS 1 x2: 1'x2'xO.040' 2x9SMB: 2x 10 SMB: rx10'x0.092'x0,998, 6 x 6: 6' x 6' x 0.125, 1 3: 1' x 3' x 0.045 MINIMUM FASTENER EDGE DISTANCE :112' BRACE MINIMUM FASTENER SPACING: 314" RC: RECECHANNEL AP SECTIONS �2x2SIi.p: 2'x2"x0.045' CONCRETE SCREW ANCHOR: SHEETMATEL SCREWS ISMS): 3 Snap: 2" x 3x 0.050, 4 Snao: 2'x4"x 0.045" SIMPSON TITEN HD OR EQUNALENT ITW BUILDER OR EQUIVALENT REMOVE AND REPLACE WOOD DECK DOUBLE ZX10 PT BEAM (TYP) 2X8 PT RUA JOIST (TYP) 2X8 PT JOISTS ® i6" O.C. 2X8 PT BLOCKING. (TYP) axe PT POSTS OW) 1X6 PT DECK BOARDS STAIRS WITH CONCRETE SLAB LANDING (MIN. T x 3• x 4"). EXTEND AS REQUIRED FOR STRINGER DEPTH AND ATTACHMENT (TYP) STAIRS WITH CONCRETE -/ SLAB LANDING (MIN. Tx 3' x 41. EXTEND AS MIN. REQUIRED FOR STRINGERDEPTHAND ATTACHMENT(rYP) 4 a • I'd a.. f 4 ° a. d y #4 d:. . • ° e: W • ,'' / o d. 4 a '• ed, a'Q ' e Z e d, w 4 a.4 WL� anwa • .'a F :a 4 , ; / W - 5 WA N 80TT01 FI3I Ili M W WAN S OFAR CO CKM 00%9L CONCRETE SLAB SHALL BE PWALIID ONLY ON CDMPACIED. WELL GRADED CLEW SAND FILL 2. PER DIAAti MIXIN OF THE F1.OWDA BUI DIN0 CODE. RESIDENTIAL SECTION 401.4.1. SOLS 7ESIM IS NOr REMIRFA FOR OEM USING THE PRESIJMPIIVE BEARNO PRESSURE OF 1.5W PSF. 3. CONCRETE SHALL BE PROPERLY AIM AOEOUATELY CONSOl1GATED TO REMOVE ALL VOIDS IN MOCK CE11S AND AROWID REI FORCEMEMr 4. REPAR SHALL HAVE A 31" LAP SPUCE USE 3' C10aRi 70 W01rAN 3' CLEARANCE FROM THE SOIL THICKENED EDGE SLAB ON GRADE 3' 0.024' ALUM. SKIN 14-B EPS FOAM CORE PANELS. (FL#12225.1) Kaycan LTD, Contessa Mnyl siding (FL12192s) Entailed per product approval requi-ras iztr 00988#pq w OOOOVC�" ��'W ODDD i �00 � a� DDO o�® i�1ro diA 0. % 0 o 0 0 ODDOOOOas �00000 TRANSOM WALL. FILL IN WITH KICKPIATE m mm _I 3X3 O i 3X3 N A--0 9 m z LU U) m 2 I 3X3 TRANSOM WALL. FILL IN WITH KICKPLATE IEv�- d P�F WED FOR COMPLIANCE it i gIliiC tlPl ^i 1AITV WINDOW/DOOR C EDULE MARK Q TYPE HEIGHT (INCH) FACTURER MODEL LNG PRESSOR--- PRODUCT PRESSURE(PSF) A HORIZ ROLLER WINDOW EONCH) VARIES POT HR-210 FPA1t1A2.1 - B SWING DOOR 80 PGT CO.290 FPA#331.1 40.8 -44A- - ACCORDIANSHUTTERS VARIES TOWNANDCOUNTRY STREAMLINE FPA#137572 40.8 •44.4 300.0 -100.0 ALL DOORS AND WINDOWS SHALL BE INSTALLED PER MANUFACATURERS SPECIFICATIONS AND WATERPROOFED PER FBC, LOCAL JURISDICTIONAL REQUIREMENTS, AND F.S.553R42. e w N s hT•yh °•C"'� N ° eV o0 W e� �e N � ' 0 o E W 9 SHEET - NOT ALL DETAILS ARE USED FC "LAGS, 4" FROM ENDS & 18" O.C. MAX. 1" MIN LONGER THAN THE PANEL THICKENESS. W/ NEOPRENE WASHER ON EACH LAG SEE FLASHING - INSTALL UNDER EXISTING DRIP EDGE 914 X 3/4" SMS @ 6" O.C. TOP AND BOTTOM • ' W/ 1-1/2" DIA, NEOPRENE WASHER @ TOP SCREW ONLY 3" X 0.082 ALUM RECEIVING CHANNEL WI #12 X 3/4" TOP AND BOTTOM AS END CAP (2) 3/8" DIA THRU BOLTS - IF SCREEN WALL BENEATH - COMPOSITE ROOF, 1" x 2" W/ (2) #10 x 2" SMS INTO SCREW BOSSES INTO UPRIGHT & (1) #14 X 2" SMS 6" FROM EACH SIDE OF UPRIGHT & @ 24° O.C. NOTCH UPRIGHT OR POST - TO ACCEPT BEAM. SEE PLAN SHEET FOR MEMBER 1 INFORMATION CR-0 COMPOSITE ROOF TO BEAM 2 SCALE:NTS I I" MIN. TREAD DEPTH !"NOSING ti ri 7 %" MAX. RISER HEIGHT 17 DECK FRAMING (MAY OOK DIFFERENT THAN ILLUSTRATED) SIMPSON WC28Z ON ROOF PANEL .1" X 1" X 1/8" ALUM ANGLE (2) 1/4" DIA. X 3" LAG SCREWS @ 6" W/ (3) #12 X 3/4" SMS IN COMPOSITE Pi FLANGE INTO UPRIGHT. RECEIVING CHAP (BOTH SIDES OF UPRIGHT) SHIM AS NECESSARY IF OTHER THAN A PLUMB CUT FASCIA BEAM. SEE PLAN SHEET FOR MEMBER . • WOOD: INFORMATION (2) 1I4" x 3" LAG SCREWS, 6" _ FROM END & @ 16° O.C. CONC. • • (2) 1/4" DIA. x 2 1/4" CONCRETE SCREW ANCHOR, 6" FROM END & @ 16" O.C. 1x TRIM BOARD AS DESIRED lx WOOD RISER AS DESIRED 2x PT WOOD OR COMPOSITE V, TREAD Q 94 2x4 PT NAILER ANCHORED TO y CONCRETE SLAB OR WOOD DECK H ca 2X12 PT STRINGERS O 16" C. MAX SPACING (12- O.C. FOR COMPOSITE DECKING) CI- DECK STAIRS 2 SCALE:NTS CR-1 COMPOSITE ROOF TO HOST 2 SCALE:NTS ATTACH INSIDE USING 2"x2"xi WITH (8) #14 x 112" DIA THRU SO NUT WITH TH LIEU) INTO TIGHTEN. I COLU `--1"x 2" O.D. ATTACH TO UPRIGHT WITH (2) #10 x 2 1/2" SMS THRU UPRIGHT INTO SCREW BOSSES 1" x 2" O.B. ATTACHE PLUS #10 x 1 112" SMS 6" FROM EACH SIDE OF POST EACH SIDE OF UPRIGHT AND WITH #12 x 1-1/2" SMS TYPICAL AT 24" O.C. MAX @ 6" FROM BOTTOM AND 24" O.C. NOTE: IGNORE 1" X 2" 0.13, AND CONNECTION IF SCREEN ISN'T BEING INSTALLED C-4 CARRIER BEAM TO COLUMN CONNECTION 2 SCALE:NTS o Id e OPTION 1: (4) #10 x 1-1/2" SMS INTO SCREW BOSSES (TYP) SNAP OR — SELF -MATING BEAM ONLY #10 x 3" WOOD SCREWS @ ENDS & 12" O.C. CONC. 1/4" DIA. x 3" CONCRETE SCREW' ANCHOR @ 6-FROM ENDS & 24" O.C. OPTION 2: 2" x 2" x 1/8" ANGLE WITH (2) #10 x 3/4" SMS IN EACH FLANGE, EACH SIDE (TYP) / I PURLIN / GIRT! CHAIR RAIL M-1 PURLIN / GIRT / 0.13 TO HOST CONNECTION 2 SCALE:NTS; 2" x 2" x 1/8" (x WIDTH OF INTERIOR REC CHANNEL) ANGLE EACH SIDE OF POST (4) #14 x 314" SMS INTO POST, EACH SIDE. O O O ECKBOARDS ECK FRAMING SIDE VIEW 1/4" DIA x 4" LAG BOLTS @ 12" O.0 (1) 3M' DIA LAG SCREW ANCHOR EACH SIDE (4" EMBEDMENT INTO WOOD z FRAMING - NOT INCLUDING REC DECKBOARDS) REC CHANNEL CHANNE EccHANNELNOT REQUIRED ON DOOR INSTALLATIONS FRONT SECTION VIEW SRJ' COLUMN TO WOOD DECK FRAMING CONNECTION 2 SCALE:NTS 5%00099801oo Opp 00 {� 61bT o 01�J "o W. c e SHEET 2 co O r DTE - NOT ALL DETAILS ARE JOISTS PER PLAN ATTACH JOIST TO BEAM WITH SIMPSON H1Z (H2.5Z ON BEAM EDGE) BEAM PER PLAN. W MAX CANTILEVER ATTACH POST TO BEAM WITH SIMPSON BC46 (BC4 FOR 4X4 POST). ADD FILLER AS REQUIRED. PT POST PER ATTACH POST TO FOUNDATION SIMPSONS ABA66Z FOR 6X6 1 (ABA44Z FOR 4X4 F PROJECT �- COLUMN/BEAM/JOIST ATTACHMENT 3 SCALE:NTS (4) #10 x 3/4' SMS INTO POST, - r� „ Z J O U FRONT SECTION VIEW 318" DIA. ANCHOR THRU 4M INTO HOST. EACH SIDE. CONC: 2-1/4" EMBEDMENT WOOD: 3-112" EMBEDMENT SIDE. BLOCK AT MIDSPAN. STAGGER BETWEEN JOISTS. SCREW ENDS WITH (2) #10 x 2-1/2" EXTERIOR WOOD SCREWS CONNECT DOUBLE BEAM WITH #10 x 2-1/2" EXTERIOR WOOD SCREWS @ 6" FROM ENDS AND 12' O.C. STAGGERED 910 x 3/4" SMS @ 6" FROM END AND 24" O.C. BEAM O a O O O O SIDE VIEW r2"x2l".lA81"(xWlDTHOF COLUMN) ANGLE. EACH SIDE —WOOD: #10 x 3' WOOD SCREWS @ 6- FROM ENDS & 12" O.C. CONC. 1/4" DLA. x 3' CONCRETE SCREW ANCHOR @ 6"FROM ENDS & 24" O.C. SR-2 COLUMN TO HOST CONNECTION 3 SCALE: NTS ---ANGLED JOISTS: SIMPSON LS70Z (LS50Z FOR 2X6 JOISTS) -----JOISTS AT EDGE: SIMPSON LUC28Z (LUC26Z FOR 2X6 JOISTS) TYPICAL JOIST: SIMPSON LUS28Z (LUS26Z FOR 2X6 JOISTS) D-3 JOIST ATTACHMENT TO RIM JOIST OR LEDGER 3 SCALE:NTS 2" x 2" x 1/8" ANGLE WITH (2) #10 x 3/4" SMS IN EACH FLANGE, EACH SIDE (TYP), 2" x 2" x 1/8" ANGLE WITH (2) #10 x 314" SMS IN EACH FLANGE INTO MEMBER. (1) 318" DIA ANCHOR THRU BEAM INTO HOST. 2-1/4" PURLIN / GIRT / EMBEDMENT FOR CONCRETE, CHAIR RAIL 3-1/2" EMBEDMENT FOR WOOD BEAM INSIDE OF REC. 910 x 3" WOOD SCREWS L ENDS & 12° O.C. CONC. 1/4" DL4, x 3" CONCRETE SCREW ANCHOR @ 6-FROM ENDS & 24" O.C. • TOP VIEW SR-3 PURLIN / GIRT / CHAIR RAIL ATTACHMENT 3 SCALE:NTS DECK BOARDS PER PLAN. SPACE FOR 118" FINAL GAP. ADJUST FOR PT DRYING AND SHRINKAGE. #10 x 2-1/2" 305SS DECK SCREWS FLAT HEAD JOIST �- DECK ATTACHMENT 3 SCALE:NTS o N pppo°° uuuaunaaa°00oo n 0000�0.0 ��®� 0000 ®8y� ; cco�o 0 QQ ®q(' p ® o O�� ✓ V c O o °40nnnooanaau°°° d Ed � r •E R m O mLL V TRANSOM WALL 0 UPRIGHTPER PLAN ` ccm m 2"x2"x1/8"x BEAM DEPTH ^ v = INTERNALALUM y RECEIVING O O •� CHANNEL W/ (4) O O Q #14 x 3/4° EACH IL FLANGE CARRIER SEA PER PLAN ECEIVING CHANNEL WITH MIN. (2)#12XJ" ' SMS TO COVER OPEN END SHEET W TRANSOM WALL ON BEAM 3 SCALE:NTS 3 J IA � "•NOTE - NOT ALL DETAILS ARE USED FOR THIS PROJECT. SEE PLAN FOR DETAIL CALL OUTS-* 4 F LL C LL (C a z M4AX T J � Q U� �Q W m J �0 Op U a v °D 4" MAX. (2" POOL BARRIER) k-MAX SPACING BETWEEN POSTS = 8FT--- TYPICAL RAILING PROFILE t( SCALE: NTS TOP RAIL PER PLAN �—PICKETS PER PLAN _-------POSTS PER PLAN —90TTOM RAIL PER PLAN o� e OUOOppp Opo� 0 LL6gz�o 0 c �o Q0 00 o V � � ' QQOOOO�Do 0 0�1la0 � N o o ti O 9 oU,o w �orT � u w ow Acce MCI w ` r �� U 9 SHEET 4