HomeMy WebLinkAboutProject InformationManual S Compliance Report Job: 4906 Matanle zas A �+ wrightsoft® Date: April 26, 2021 MAIN By. Eneropalcs.net CJS Contracting Erergyca1cs.rst267 deleon road, Debary, FL 32713 For. Ws Contracting 4906 MatanzasAvenue, Fort Pierce, FL 34949 Design Conditions Outdoor design DB: 91.0°F Sensible gain: 23725 Btuh Entering coil DB: 77.1 °F Outdoor design WB: 78.0°F Latent gain: 4788 Btuh Entering coil WB: 63.6°F Indoor design DB: 75.0°F Total gain: 28513 Btuh Indoor RH: 50% Estmiated airflow: 1000 crm Manufacturer's Performance Data at Actual Design Conditions Equipment type: SplitASHP Manufacturer. GENERIC 2.5 TON Model: GENERIC+GENERIC Actual airflow: 1000 dm Sensible capacity. 25000 Btuh 105% of load Latent capacity. 5000 Btuh 104% of load Total capacity: 30000 Btuh 105% of load SHR 83% Design Conditions Outdoor design DB: 43.0°F Heat loss: 18696 Btuh Entering coil DB: 70.0°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpfitASHP Manufacturer. GENERIC 2.5 TON Model: GENERIC+GENERIC Actual airflow: 0 cI n Output capacity: 30000 Btuh 160% of bad Capacity balance: 0 °F Supplemental heat required: 0 Btuh Economic balance: 0 °F Meets all requirements ofACCA Manual S. -*- wrightsoft, 2021.1ur2915:12:50 m� aMR.,•,� ��..� c.,,, RigttSute®Uriwrsal202121.0.07RSU19927 Page CJS C ...ortractirg MatarraasAve RVD 062921 MJS.rtp Calc= MA Frort Door faces: S Building Analysis Job: 4906MataraasAm -�+ wrightsofte y Data: April 28, 2021 MAIN By. Energycalcs.net CJS Contracting Energycalcs.net267 delean road, Debary, FL 32713 Project Information For. Ws Contracting 4906 MatanzasAvenue, Fort Pierce, FL 34949 Location: Vero Beach Municipal AP, FL, US Elevation: 30 ft Latitude: 28°N Outdoor. Heating Dry bulb (°F) 43 Daily range (°F) - Wet bulb (°F) - Wnd speed (mph) 15.0 Indoor Indoor temperature (°F) Design TD (°F Relative hu ily (% Cooling Moisture drfference grAb) 91 Infiltration: 20 (M) Method 78 Construction quality 7.5 Fireplaces Component BtuhAi? Btuh % of bad Walls 3.6 5878 31.4 Glazing 8.1 1189 6.4 Doors 10.5 417 2.2 Ceilings 0.7 1085 5.8 Floors 3.1 4807 25.7 Infiltration 1.9 2903 15.5 Ducts 2417 12.9 Piping 0 0 Humidification 0 0 Ventilation 0 0 Adjustments 0 Total 18696 100.0 Cooling Component Bhjh/ftz Btuh % of load Walls 2.1 3464 14.6 Glazing 11.3 1665 7.0 Doors 10.7 425 1.8 Ceilings 1.3 2049 8.6 Floors 0 0 0 Infiltration 0.6 905 3.8 Ducts 6592 27.8 Ventilation 0 0 Internal gains 8625 36.4 . Blower 0 0 Adjustments 0 Total 23725 100.0 Latent Cooling Load = 4788 Btuh Overall U-value = 0.101 Btuh/ft2--°F Data entries checked. G Heating 27 50 22.0 Simplified Average 0 Ceilings rluulb Ducts Gains Cooling 16 50 59.9 -OfA- wr1ghtsoft- 2021-Jm-2915:12:50 -^+-­ Rigt tSUte® Universal 2021 21.0.07 RSU19927 Page 1 ..CJSCortracdngMatanzas Aye RVD062921MJS.np CaIc=MJ8 FrortDoorfacesS , Component Constructions Job: 4906 Matanzas Abe �+ wrightsoft® p Date: April 28, 2021 MAIN By. Energyr alcs.net CJS Contracting Erergycalcs.net267 delean road, Debary, FL 32713 For. CJ's Contracting 4906 MatanzasAvenue, Fort Pierce, FL 34949 Location: Vero Beach Municipal AP, FL, US Elevation: 30 ft Latitude: 28 °N Outdoor. Heating Dry bulb (°F) 43 Daily range (T) - Wet bulb (°F) - Wnd speed (mph) 15.0 Indoor Indoor temperature ("F) Design TD (T) Relative humidity (%) Cooling Moisture difference (grAb) 91 Infiltration: 20 (M) Method 78 Construction quality 7.5 Fireplaces Heating 70 27 50 22.0 SQnpfified Average 0 Cooling 75 16 50 59.9 Construction descriptions or Area U-value lnstd R Htg HTM Loss Clg HTM Gain it Bkt ft 'F ffv Bfuh BUM Bbb BUM BWh Walls 13A-4ots: Blkvial], stucco wit, r-4 erd bd ins, 8"thk, 3/8"wood shth, 1/2" n 368 0.143 4.0 3.86 1420 2.33 857 gypsum board int fish a 357 0.143 4.0 3.86 1379 2.33 832 s 201 0.143 4.0 3.86 777 2.33 469 w 437 0.143 4.0 3.86 1687 2.33 1019 all 1363 0.143 4.0 3.86 5263 2.33 3177 Partitions 12C-0sw: Fnn wall, stucco ext, r-13 cav ins, 2"W wood frm, 16" o.c. stud Windows 1013�: 2 glazing, dr lowe out;, air gas, vni frm mat, dr innr, 1/4" gap, 1/8" n thk; NFRC rated (SHGC=0.25); 1.3 ft overhang (6.7 it window ht, 1.3 ft sep.); 6.67 ft head ht 4A5-2ov: 2 glazing, dr lowe out;, air gas, vni fan mat, dr innr, 1/4" gap, n 1/8" thk; NFRC rated (SHGC=0.25); 12.3 ft overhang (5.3 ft window ht, 1.3 ft sep.); 6.67 ft head ht 4A5-2ovd: 2 glazing, dr lowe out;, air gas, vni frm mat, dr innr, 1/4" gap, n 1/8" thk NFRC rated (SHGC=0.25); 12.3 ft overhang (6.7 ft window ht, 1.3 It sep.); 6.67 ft head ht 4A5-2ov. 2 glazing, dr lowe outr, air gas, vni frm mat, cir innr, 1/4" gap, e 1/8" thk; NFRC rated (SHGC=0.25); 1.3 ft overhang (1 It window ht, 1.3 ft w sep.); 6.67 ft head ht all 4A5-2ov 2 glazing, dr lowe outr, air gas, vnl frm mat, dr innr, 1/4" gap, e 1 /8" thk; NFRC rated (SHGC=0.25); 1.3 ft overhang (3.2 it window ht, 1.3 ft sep.); 6.67 ft head ht 4A5-2ov. 2 glazing, dr lowe outr, air gas, vni frm mat, dr innr, 1/4" gap, s 1/8" thk NFRC rated (SHGC=0.25); 6.3 ft overhang (2 It window ht, 1.3 ft sep.); 6.67 ft head ht 4A5-2ov 2 glazing, cir lowe out;, air gas, vni frm mat, cir innr, 1/4" gap, s 1/8" thk; NFRC rated (SHGC=0.25); 1.3 ft overhang (5.3 ft window ht, 1.3 ft sep.); 6.67 It head ht 250 0.091 13.0 2.46 615 1.15 287 36 0.300 0 8.10 289 7.03 251 16 0.300 0 8.10 132 10.0 164 40 0.300 0 8.10 326 10.0 404 3 0.300 0 8.10 24 28.8 86 3 0.300 0 8.10 24 28.8 86 6 0.300 0 8.10 49 28.8 173 10 0.300 0 8.10 80 28.8 284 6 0.300 0 8.10 49 10.0 60 33 0.300 0 8.10 265 10.0 328 ti Ark- wrightsoft® 2021-1th2915:12:50 •"*•t• ", �m�m Rigtt-SUta@ universal 2021 21.0.07 RSU19927 Page 1 ACCA cis cortracfing Matanzas Ave RVD 062921 MJS.rnp Calc=MJB Fmrt Door faces: S r I , } Doors 11 DO: Door, and sc type Ceilings 161338ad: Attic ceiling, asphalt shingles roof mat, r38 cell ins, 1/2" gypsum board int fish Floors 22A-cpl: Bg floor, light dry soil, on grade depth, carpet fir fnsh s 20 0.390 n 20 0.390 all 40 0.390 1545 0.026 180 0.989 0 10.5 212 10.7 216 0 10.5 206 10.7 210 0 10.5 417 10.7 425 38.0 0.70 1085 1.33 2049 0. 26.7 4807 0 0 t -141d- wrlghtsoft® 2021-Jm-2915:12:50 .• .•w� P� RigttSufe®Uriversal202121.0.07RSU19927 Page CJS Cortradirg Matanzas Ave RVD 062921 MJS.nrp Calc= MA Front Door faces: S 1 I r Project Summary Job: 4906 Matarmas Am wrightsoft® rY Date: April 2e, 2021 MAIN By. Energycares.net CJS Contracting Energyralcs.net267 deleon road, Debary, FL 32713 For. Ws Contracling 4906 MatanzasAvenue, Fort Pierce, FL 34949 Notes: Design Information Weather. Mero Beach Municipal AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 43 OF Outside db 91 OF Inside db 70 OF Inside db 75 OF Design TD 27 OF Design TD 16 OF Daily range M Relative humidity 50 % Moisture difference 60 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 16279 Btuh Structure 17133 Btuh Duds 2417 Btuh Duds 6592 Btuh Central vent (0 ctm) 0 Btuh Central vent (0 ctm) 0 Btuh (none) (none) Humidfication 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 18696 Btuh Use manufacturer's data y Rate/swing multi lier Equipment bad 1.00 23725 Btuh Infiltration sensible Method Simplified Latent Cooling Equipment Load Sizing Const uclion quality Average Fireplaces 0 Structure 3094 Btuh Duds 1694 Btuh Central vent (0 ctm) 0 Btuh Heating Coolingg (none) Area (f�) 1545 1545 Equipment latent bad 4788 Btuh Volume (ft3) 15450 15450 Air changes/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 28513 Btuh Equiv. AVF (ctm) 98 52 Req. total capacity at 0.83 SHR 2.4 ton Heating Equipment Summary Cooling Equipment Summary Make GENERIC 2.5 TON Make GENERIC 2.5 TON Trade Trade Model GENERIC Cond GENERIC AHRI ref coo GENERIC AHRI ref Efficiency 8.5 HSPF Efficiency 15 SEER Heating nput Sensible cooling 24900 Btuh Heating output 30000 Bbuh @ 47°F Latent cooling 5100 Btuh Temperature rise 0 OF Total cooling 30000 Btuh Actual airflow 0 din Actual airflow 1000 din Air flow factor 0 ckrffiWh Air flow factor 0.042 cfrrdBtuh Static pressure 0.40 in H2O Static pressure 0.40 in H2O Space thermostat Load sensible heat ratio 0.83 apacalancepont = 0 °F Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft® 2021-JuF2915:12:50 MgttSdte® Uriversal 2021 21.0.07 RSU19927 Page 1 CJS Cartrac5ng MalarvasAye RVD 062921 MJSxW Calc= MJ8 Frort Docrfaoes: S t 4 o 0 0 V 1/ Job #: 4906 Matanzas Ave Performed by Energycalcs.net for: W.- Contracting 4906 Matar¢asAvenue Fort Pierce, FL 34949 Level 1 CJS Contracting Energycalcsnet267 deleon mad Debarx FL 32713 12 Scale: 1 : 86 Page 1 Right Suihe®Universal2021 21.0.07 RSU19927 2021-Jun-2915:13:22 Matanzas Ave RVD 062921 MJS.rup t • . s Duct System Summary Job: 4906 Matarvas Awe -- wrightsoft® y Date: April 28, 2021 MAIN By. Energycalcs.net CJS Contracting Erergycalcs.net 267 deleon road, Debary, FL 32713 For. CJ's Contracting 4906 Matanzas Avenue, Fort Pierce, FL 34949 External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual airtlow Total effective length (TEL) Heating OAO in H2O 0 in H2O 0.40 in H2O 0.300 / 0.100 in H2O 0.142 in/100ft 0 clfn 281 ft Supply Branch Detail Table Cooling OAO in H2O 0 in H2O OAO in H2O 0.300 / 0.100 in H2O 0.142 in/100ft 1000 CfM Name Design (Btuh) Htg (drn) Clg Orn) Design FIR Dram (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BDRM 2 c 3057 0 129 0.142 7.0 Ox 0 VIFx 51.1 160.0 st3 BDRM 3 c 2762 0 116 0.143 7.0 Ox 0 VIFx 49.1 160.0 st3 BTH c 535 0 23 0.145 4.0 NO VIFx 46.3 160.0 st3 GREATRM/DINING c 3226 0 136 0.180 7.0 Ox0 VIFx 31.3 135.0 st2 GREAT RM /DINING -A c 3226 0 136 0.178 7.0 OX0 VIFx 33.3 135.0 st2 KITCHEN c 4977 0 210 0.213 8.0 OX 0 VIFx 25.6 115.0 st1 MBDRM c 3850 0 162 0.215 7.0 Ox 0 VIFx 24.7 115.0 st1 M.BTH c 913 0 38 0.227 4.0 Ox 0 VIFx 17.1 115.0 SO M.WIc c 778 0 33 0.204 4.0 Ox0 MR 32.2 115.0 st1 PWDR c 403 0 17 0.290 4.0 Ox 0 MFx 8.5 95.0 Supply Trunk Detail Table Trunk Htg clg Design Veloc Diam H x W Duct Name Type (cfm) (dm) FIR (fpm) (in) (in) Material Trunk st3 PeakAVF 0 268 0.142 491 10.0 0 x 0 VinlFbc st2 st2 PeakAVF 0 540 0.142 687 12.0 0 x 0 VlnlFbc st1 st1 PeakAVF 0 983 0.142 704 16.0 0 x 0 VnlFbc wrightsoft® 2021.1uf2915:12:50 �M ....... cno.H.m mmpm Mglt &&OUriversal 2021 21.0.07 RSU19927 Page 1 +�...CJSCortractirgMatanzas Ave RVD062921 MJS." Calc=MJ8 Frort Door Was: S t. '36 r -, Name Grille Size (in) Htg (Cfm) Gg (Cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox 0 0 1000 70.3 0.142 566 18.0 Ox 0 VIFx rst3 Name Trunk Type Htg (Cfm) Gg (Cfm) Design FIR Veloc Qpm) Diam (in) H x W (in) Duct Material Trunk rst3 PeakAVF 0 1000 0.142 566 18.0 0 x 0 UnlFbc Act -*- wrightsoft® 2021-Jui-2915:12:50 AM,•t• Riglt-SUte®UAversal202121.0.07RSU19927 Page 2 cJSCortracdrgMatarresAve RVD062921MJS.nip Calc=MA FrortDoorraoes:S