HomeMy WebLinkAboutBlower Door TestDuct Leakage Test Report
Prescriptive or Performance Method
Permit #
1lob information
Builder: DR HORTON
Community: CREEKSIDE Lot: 36
Address; 3350 TRINITY CIRCLE Unit:
City, FORT PIERCE
State: FL Z712- 3494fi
Duct Leakage Test Results
Presciptive, Method 0 Performance Method
System 1
system 2
System 3
Sum of any additional
�Total of all systems
52 1828 0.02 Qn
Total of all systems
PASS
Testing Company
Total Conditioned
Square Footage
I
I I
L - I FAIL
D Prescriptive Method cfm25 (total)
ro qualify as "substantially leak free" Qn must be less than or equal to 0.04
if air handier unit is installed. If air handier unit is not installed, Qn Total
must be less than or equal to 0.03. This testing method meets the
requirements in accordance with Section R403.2-2
:) Performance Method dm25 (Out or Total)
ro qualify as "substantially leak free" Qn must not be greater than the
proposed duct leakage Qn specified on Form R405-2014
Leakage Type satected Qn specified an Form
on Form R4052014 R405-2014 (Energy Ca1c)
(Shergy 071c)
Company Name: SUN SEAL LLQ Phone: 321-412-0035 --
I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected
compliance path as stated above, either the Prescriptive Method or Performance Method.
Date of Test, 10119/2021
Signature of Tester.
Printed Name of Tester: DANIEL MURPHY
License/Certification # 5066440 Issuing Authority.
Envelope
'BlowerDoor Test)
R402.4.1.2 Compliance
Permit #
,lob Information
Builder: DR HORTON Community:
CREEKSIDE Lot: 36
Address: 3350 TRINITY CIRCLE
Unit:
City: FORT PIERCE
State: FL Zip:
Air Leakage Test Results Passing results must be 7 ACH(SO)
or less
1265 X 60 15720 ^ 4
Method for calculating, building volume:
CFM(50) Building Volume ACH(50)
Q Retrieved from architectural plans
.....___. LE
(VCode software calculated
PASS �_� _. ? FAIL
Q Field measured and calculated
When ACH(50) is less than 3, Mechanical
Ventilation installation must be verified by building department.
Certification of Test Results
R402.4.1.2 Testing, The building or dwelling unit shall be tested and verified as having an air ieaKage We Ur HUC exLE.Mlig , all U1VJ 1r,—
per hour in Climate Zones 1 and 2., 3 air changes per hour in Climate Zones 3 through 8, Testing shall be conducted with a blower door at a
pressure of 0.2 inches mg. (50 Pascals). Testing shall be conducted by wither individuals as defined in Section 553.993(5) or (7), F.S. or
individuals licensed as set forth in Section 489.105(3)(t), (g), or ji) or an approved third party. A written report of the results of the test
shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of
build
Testing Company
Company Name: SUN SEAL LLC Phone, 321-412-0035
:1 hereby verify that the above duet leakage testing results are in accordance with the Florida Building code requirements with the selected
compliance path as stated above, either the Prescriptive Method or Performance Method.
Date of Test: 10/19/2021
Signature of Tester: .1ry
Printed Name of Tester: DA 1'EL MURPHY
Licensexertificatlon 4 5060440 Issuing Authority BPI