HomeMy WebLinkAboutPROJECT INFORMATIONwrightsofto Manual S Compliance Report Job: Lot52 Block, WaterStone...
&ntfre House Bate: Dec 01, 2011
By: RH
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W WW.DELAIR.COM Licerse: CMC 1249777
For: ADAMS HOMES
5375 Lugo Street, Fort Pierce, FL 34951
Design Conditions
Outdoor design DB: 90.4°F
Outdoor design WB: 77.4 cF
Sensible gain: 22409
Latent 4041
Btuh Entering coil DB: 76.3OF
Btuh
Indoor design DB: 75.0 OF
gain:
Total gain: 26451
Entering coil WB: 63.2°F
Btuh
Indoor RH: 50%
Estimated airflow: 947
cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype: SpIitASHP
Manufacturer: Carrier
Model: 25HBC530AP03+FX4DNF031 L00
Actual airflow: 947 cfm
Sensible capacity: 22609 Btuh
101%of load
Latent capacity: 4739 Btuh
117% of load
Total capacity: 27348 Btuh
103% of load SHR: 83%
Design Conditions
Outdoor design DB: 38.0 cF Heat loss: 26293 Btuh Entering coil DB: 69.5OF
Indoor design DB: 70.0 OF
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype: SpIitASHP
Manufacturer: Carrier Model: 25HBC530AP03+FX4DNF031 L00
Actual airflow: 947 cfm
Output capacity: 25322 Btuh 96% of load Capacity balance: 36 cF
Supplemental heat required: 971 Btuh Economic balance: -99 cF
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 947 cfm
lk Output capacity: 8.3 kW 1071/o of load Temp. rise: 27 OF
Meets all requirements ofACCA Manual S.
- wrightsoft® 2021-Sep-01 165401
Right-Sute®Uriversa12021 21.0.07 RSU23828
...aterstore203OBGR\Lot52BIklWaterstone2O3OBGR.rLp Calc=MJ8 Horsefaces: W Page
wri htsoft® Component Constructions Job: Lot 52 Block 1 Waterstone...
9 Entire House Date: Dec 01, 20„
By: RH
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Ptnre:407-333-2665 Fax:407-333-3853 Web: W WW.DELAIR.COM Lioerse: CMC 1249777
•,ject Information
For: ADAMS HOMES
5375 Lugo Street, Fort Pierce, FL 34951
Design
• • •
Location:
St Lude Co Intl, FL, US
Indoor:
Indoor temperature (OF)
Heating
70
Cooling
75
Elevation: 26 ft
'
Design TD (OF)
32
15
Latitude: 28 ON
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (gr/lb)
5.7
56.9
Dry bulb (OF) 38
90
Infiltration:
Daily range (OF) -
Wet bulb (OF) -
15 (L
77
) Method
Simplified
Wind speed (mph) 15.0
7.5
Construction quality
Fireplaces
Average
0
Construction descriptions or Area u-value Insul R Htg HTM Loss CIg HTM Gain
ft' BtUMtz"F ftz*FBtuh Btuh/TV Btuh Btuh/W Rh ih
Walls
168-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum
board int fnsh
DftWall: Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int
fnsh
Partitions
12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int
fnsh, 2'5(4" wood frm, 16" o.c. stud
Windows
10C-v: 2 glazing, clr low-e outr, air gas, vnl fan mat, dr innr, 1/4" gap, 1/8"
thk; NFRC rated (SHGC=0.70); 50% drapes, medium; 17 ft overhang (6.7
ft window ht, 0.17 ft sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr lower outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 2 ft overhang (5.25
ft window ht, 1 ft sep.); 6.67 ft head ht
1 OC-v: 2 glazing, clr low•e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8"
thk; NFRC rated (SHGC=0.70); 50% drapes, medium; 10.3 ft overhang
(6.7 ft window ht, 0.17 ft sep.); 6.67 ft head ht
n
20
0.049
19.0
1.57
31
2.59
52
e
20
0.049
19.0
1.57
31
2.59
52
s
20
0.049
19.0
1.57
31
2.59
52
w
20
0.049
19.0
1.57
31
2.59
52
all
80
0.049
19.0
1.57
125
2.59
207
n
406
0.201
4.1
6.43
2611
4.98
2023
e
256
0.201
4.1
6.43
1644
4.98
1274
s
359
0.201
4.1
6.43
2312
4.98
1791
sw
27
0.201
4.1
6.43
175
4.98
136
w
54
0.201
4.1
6.43
348
4.98
270
nw
27
0.201
4.1
6.43
175
4.98
136
all
1130
0.201
4.1
6.43
7265
4.98
5629
190
0.091
13.0
2.91
554
1.62
308
n
18
0.550
0
17.6
314
12.6
226
n
16
0.330
0
10.6
171
8.52
138
e
18
0.550
0
17.6
314
12.6
226
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" a
10
0.330
0 10.6
103
18.6
182
• thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 2 ft overhang (3.17
ft window ht, 0.67 ft sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" a
32
0.330
0 10.6
342
20.4
661
• thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 2 ft overhang (5.25 s
49
0.330
0 10.6
513
8.52
ft window ht, 0.67 ft sep.); 6.67 ft head ht
414
all
81
0.330
0 10.6
855
13.3
1075
wrlghtsc ft °
..-....,.� ,....,.,,.,..• Right-Sute®Uriversal 2021 21.0.07 RSU23828
2021-Sep-01 1654 01
1
aterstore2030BGRIot52BIkiWaterstore2030BGR.nQ Calc=MJB Housefaces: W
Page
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
a 32 0.330
thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 10.3 ft overhang
(5.25 ft window ht, 0.17 ft sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
sw 15 0.330
thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 2 ft overhang (5.25
w 23 0.330
ft window ht, 0.67 ft sep.); 6.67 ft head ht
nw 15 0.330
all 54 0.330
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
w 7 0.350
thk; NFRC rated (SHGC=0.26); 50% drapes, medium; 2 ft overhang (6.7
ft window ht, 2.7 ft sep.); 6.67 ft head ht
26-2fv: 2 glazing, dr low-e outr, air gas, vni frm mat, dr innr, 1/4" gap, 1/8"
w 5 0.330
thk; NFRC rated (SHGC=0.31); 50% drapes, medium; 2 ft overhang (1.3
ft window ht, 0.58 ft sep.); 6.67 ft head ht
2B-2fv: 2 glazing, dr low-e outr, air gas, vni frm mat, dr innr, 1/4" gap, 1/8"
w 7 0.330
thk; NFRC rated (SHGC=0.31); 50%drapes, medium; 2 ft overhang (6.67
- ft window ht, 0.58 ft sep.); 6.67 ft head ht
Doors
11 JO: Door, mtl fbrgl type
w 20 0.600
11 DO: Door, wd sc type
n 18 0.390
Ceilings
16B-30ad:Attic ceiling, asphalt shingles roof mat, r-30 cell ins, 1/2"
2440 0.032
gypsum board int fnsh
Floors
22A-tpl: Bg floor, light dry soil, on grade depth
201 0.989
0 10.6
342
8.52
276
0 10.6
162
12.6
193
0 10.6
245
19.1
443
0 10.6
162
16.6
254
0 10.6
568
16.5
890
0 11.2
75
25.9
173
0 10.6
55
13.1
68
0 10.6
70
26.3
175
6.3 19.2 386 17.6 353
0 12.5 223 11.4 204
30.0 1.02 2499 1.69 4123
0 31.6 6348 0 0
Wrlghtsc3 t" 2021-Sep-011654,01
e• •• _ - �m� •, FUgtt-Sute®UIversa12021 21.0.07 RSU23828 Page t
aterstone203OBGR\Lot52BIkIWaterstom2O3OBGR.rLp Calc=MJ8 Housefaces: W
- wrightsoft® Project Summary
Entire House
DEL AIR HTG, A/C & REFRIG. INC
Job: Lot 52 Block 1 Waterston...
Date: Dec 01, 2011
By: RH
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax:407-333-3853 Web: W W W,DELAIR.COM License: CMC 1249777
MENNEN
For: ADAMS HOMES
5375 Lugo Street, Fort Pierce, FL 34951
Notes: REVISED 3-23-12 SGT
RVSD 6/15/12 DCS
JA 8-19-15
L. S. 9-1-21 VWK
Design Information
Weather: St Lude Co Inti, FL, US
Winter Design Conditions
Summer Design Conditions
Outside db 38 OF
Inside db 70 OF
Outside db
Inside db
90 OF
OF
Design TD 32 °F
Design TD
75
15 OF
Daily range
L
Relative humidity
50 %
Moisture difference
57 gr/lb
Heating Summary
Sensible Cooling Equipment
Load Sizing
Structure 23476 Btuh
Ducts 2810
Structure
18101 Btuh
Central vent (0 cfm) Btuh
(none)
Central vent (0 cfm)
Btuh
Hu nidification 0 Btuh
(none)
Blower
0 Btuh
Equipment load 26293 Btuh
Use manufacturer's data
Infiltration
Rate/swing multiplier
Equipment load
y
1.00
sensible
22409 Btuh
Method Simplified
Construction quality Average
Latent CoolingEquipment Load Sizing
Fireplaces 0
Structure
2762 Btuh
Ducts
Central vent (0 cfm)
1279 Btuh
0 Btuh
Area ft2 Heatingg Coolingg
( ) 2038 2038
(ft)3
Volume 17103
(none)
Equipment latent load
4041 Btuh
17103
Air changes/hour 0.32 0.16
Equiv. AVF (cfm) 91
Equipment Total Load (Sen+Lat)
26451 Btuh
46
Req, total capacity at 0.75 SHR
2.5 ton
Heating Equipment Summary
Cooling Equipment Summary
Make Carrier
Trade
Make Carrier
Model 25HBC530AP03
AHRlref 204840289
Trade
Cond 25HBC530AP03
Coil FX4DNF031L00
Efficiency 8.5 HSPF
Heating Input
AHRI ref 204840289
Efficiency 12.5 EER,15
SEER
Heating output 28200 Btuh @ 47OF
Temperature rise °F
Sensible cooling
Latent cooling
300 Btuh
211 00 Btuh
27
Actual airflow 947 cfm
Total cooling
Actual airflow
28400 Btuh
Airflow factor 0.036 cfm/Btuh
Static pressure 0.40 in H2O
Airflowfactor
Static pressure
947 cfm
0.042 cfm/Btuh
Space thermostat
Capacity balance point = 36 OF
Load sensible heat ratio
0.0.40 40 in H2O
Backup:
Input = 8 kW, Output = 28192 Btuh,100 AFUE
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
C -wrightsoft ° �� " Right-Sute®Uriversa1202121.0.07RSU23828 2021-Sep-01 16S4:01
aterstone2030BGR1Lot52Blk1 Waterstone203oBGR.nQ Calc= W8 House faces: W Page 1
- wrightsoft° Right-JO Worksheet
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Licerse: CIVIC 1249777
Job: Lot 52 Block 1 Waterston 20...
Date: Dec 01, 2011
By: RH
1
Room name
Entire House
M.BTH
2
3
ENposed wall
Room height
200.6 ft
125 ft
4
Room dimensions
8A It d
85 ft heaV000l
5
Room area
2043.5 ftz
1.0 x 101.3 ft
101.3 ft'
Ty
Construdion
U-value
Or
HTM
Area
(ft2)
Load
Area
(ftz)
Load
number
(Btuh/ftz h�
(Btuh/ft2)
or perimeter
(ft)
(Btuh)
or perimeter
(ft)
(Btuh)
Heat
Cool
Gross
N/M
Heat
Cool
Gross
N/P/S
Heat
Cool
6
�W .�..:
V)/
...52_..�:�
�
0
0`
166-19ad�..__.m_�
DftWall -
0049.7:5�n^_20.®.:�....�,_31
)L----G
10C-v
0201
0550
n
n
6.43
17.60
498
12.64
440
18
406
0
2611
314
2023
226
0
0 �0
0
_
2A-2ov __V
n
10.56_
852
-_ 16
0
171
138
0
0
0 0
0
0
0
d
_--0330
-' -O�O
_'°6.43
�. a3
__,
'_
_
Zf
_
_ __0
--50
_
_
Mall
e
4.98
8
26a
134
1274
y� 6�
320
250
j2640
0
0
3
103
182
10
3
103
182
2A-2ov
0230
a
1056
20A2
32
6
342
661
0
0
0
0
2A-2ov _ _
0.330
a
1056
852
32
32
342
276
0
0
0
0
VN
0049
0201
ri's_.
s
157.
6.43
259
4.98
^Y �__20
408
,__ 20
359
.; 31Df[Wall:
2312
_
52
1791
0
2A-2ov
2A-2ov
0.330
s
1056
852
49
49
513
414
40
40
257
199
0201
s, sw
6.43
4.98
43
27
, •.77ft
0
0
0
' `. 0
0
0
0
- 0
r----('
16B 19ad
1056
1262
,.: ._ .._15
_ :. $
162
_.-__193
w. 0
_ 0
_ . w
_ _ 0
.---,--0
DBWaII•
2A2ov
2A-2ov
0049,_
0201
0330
w
w
•w
_ 1.57
_ 6.43
1056
__q 259
, . 4.98
19.09
_,. �20
• � j%
,, ... 23
20
— 54
,` 4
31
,. 348
., 245,
52
276
0
_ 0
0
.�»• _ 0
0
. .'° 0
�.Y 0
0
0
_;0
0
0.350
w
1120
25B7
7,
, < ,0
„75
173
, 0
;, . 0
0
` 0
2B-2fv
0.330
w
1056
' -13.12
5
4
55
.
68
0
' 0
2B 2fv " •
0.330
w
1056
26.31
`.. 7
1
.70
. 175
. • .
, ' 0
0
: 0:
0
0
,0
VI/
MII_
2A-2ov
Q,600
0201
w .
nw
v 1920
6.43
n1758
4.98
: 2Q
43
. , r . 20
27
_' ' 386
175
M ,,
138
Q
. , , �Q
-- 0..�
Q
0
0
I�
P _ _
2A 2ov
-12C '
_ 0.330
nw
10.56
16.61
15
0
162
254
0
0
0
0
0
0
I _
r—D
Osw
0 091
0890
=
2 91
1:62
208
190
__._ 554
3b8
0
0
0
_ ,.
r0
C
-11D0 -___ _
166 30ad
,r
n_
-1 2-48
11 43
_18
e_ 18
_ 223
_ _ 204
r0
2440
r-
�2499
_ 4123
, .� ,13
21__396
0
101.
..�._,......_"-
._._..cam
.._._....�...
......._i
......._.__..
._.._
- ..
�,.....
_......._..,....._..._,..._a.-_..,
_.,_,.......�,.
..
.........._,_
... ..
__.......-....
6
excursion
..a
c) AED
-1126
-
-1~9
Envelopeloss/gain
20268
14379
1229
859
12
a) Infiltration
b) Roomventilation
3208
772
217
52
0
0
0
0
13
Internal gains: Occupants@ 230
5
1150
0
Appliances/other
1800
0
0
Subtotal (lines6 to 13)
23476
18101
1446
911
Less external load
0
0
Lea transfer
0
0
0
0
Redistribution
0
0
0
0
14
15
Subtotal
Dud loads
23476
18101
0
1446
0
911
12 %
24 %
2817
4308
12 %
24 %
173
217
Total room load
Air required (cfm)
26293
22409
1619
-[
1128
947
947158
48
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
�P. f'I.F wrigF�tsoTt^ 2021-Sep-011654,01
Right-Sute®Uriversal 2021 21.0.07 RSU23828
aterstore2030BGR1Lot528Ik1Waterstore2030BGR.nQ Calc=MJ8 Housefaces: W Page 1
-�- wrightsoftm Right-M Worksheet
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Lir -m - rMn 19AQ777
Job: Lot 52 Block 1 Waterstone 20...
Date: Dec 01, 2011
By: RH
Calculations approved byACCAto meet all requirements of Manual J 8th Ed
��- wr_ ➢gF�tsoTt
/R-. K "-' ` Rig11-Sate®Uriversa12021 21.0.07 RSU23828 2021-Sep-01 1654:01
aterstone2030BGRIot5261k1Waterstore20308GR.np Calc=W8 Hoisefaces: W Page
wrightsoft- Right-M Worksheet Job: Lot 52 Block 1 Waterston 20...
Entire House Date: Dec 01, 2011
DEL AIR FITG, A/C & REFRIG. INC By: RH
531 CODISCO WAY, SANFORD, FL32771 Phone:407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COMUoerE;e:CM0124Q777
1
2
3
4
5
Room name
Exposed wallKITCHEN
Room height
Room dimensions
Room area
ft
8.5 It 12.5 heaV000l
180.9 ft 2 1.0 x 180.9 ft
MWIC
8.0 ft 0 ft heatbool
76.0 ft 95 x 8D ft
Ty
Construction
number
U-value
(Btuh/ftzcq
Or
HTM
(Btuh/ft2)
Area (ft2)
or perimeter (it)
Load
(Btuh)
Area (112) -
or perimeter (ft)
-
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P)S
Heat
Cool
6
66 g7ad
DftWall
I OC-v
2A-2ov
DfIWaII
1 OC-v
2A-20v
2A-2ov
2A-2ov
16 &_1 9ad
Mall
2A-2ov
bifVValF- 7"
A-2QY-- ' -
1613-19ad
2A-2ov
2A-26v
2B-2fv
213 -2fv
DftWall
2A-2ov
.
16B-30ad - --- ------
oTb
0201
0550
0.330
0201
0.550
0.330
0330
0230
0201
0,330
:7n_
n
n
n
e
e
e
e
e
s
s
-s-w
--Sk.
w
w
w
VV
, •w
w
,-'AL-
nw
rLW
6.43
17.60
1056
6.43
17.60
10.56
1056
10.56
6.43
10.56
3
1.57
1056
11-20
1056
-1056
-I.RZ Q
6.43
10.56
291
S
12,48
1.92
__31.65
4.98
12.64
8,52
100
0
0
0
0
0
0
0
0
0
0
0
7 - 6
0
9
-0
�0
0
0
184
100
0
0
0
0
0
0
0
0
0
�O
_-_0
.
0
Q
0
'0
0
0
, , '0-
184
643
0
0
- 0
6
0
0
0
0
0
--- 6
498
0 0
0 0
0
0
0
0
0
0
==
0
d
0 0
0 0
0
-YV-.-
-�G
-�-G
--G
G
Vr--G
,'L-D
C__
4.98
12.64
18.60
20.42
^ 852
4.98--
8.52
4,S8
--1
259
-4.98
19.09
25.K
18.12
2631
4.98
16.61
-'-Jl .43
1.69
Q-60
0 0
0 0
0 0
0 0
0 0
'-76
d
0
0-
0
, 0
0
"0
0
--
0
0
0
0
0
0
- -0
0
0
6
------- -f-10
0
0
0
0
0
0
0
76
0
0
0
0
0
0,---
0
'0
------0
0
0
0
0
'0
'0
0
0
0
76
0
0
0
0
0
:07
0
0
0
0
0
_6
0
0
0
-
0
'0
0
�,--a
0
0
0
0
0
0
0
. 0
78
0.049
0201
0.330
6��50
0.330
0.330
AM0
0201
0230
0.032
A9R9,-_:
0
6
0
0
'0
0
0
0
128
--7
7
--777'-
7-
7
7
%
r16
c) Arn excursion
-95
.6 I
-
Envelope loss/gain
1227
715
78
122
12
a) Infiltration
b) Roorriventilation
217
0
52
0
-
0
0
0
0
13
internal gains: Occupants@ 230
Applianoeslother
0
01
1200
0
0
0
Subtotal (lines 6 to 13)
-
1445
1967
78
-
122
14
15
Less external load
Less transfer
Redistribution
Subtotal
Ductloads
120/,
----
0
0
0
1445
173
0
0
0
1967
468
12%
249/6
0
0
0
78
91
0
0
0
122
29
Total room load.
Air required (cfm)
1618
58
��
2435
103
:A
T
1
87
31
152
61
-ii- Calculations proved bVACCA to meet all requirements of Manual J 8th Ed.
Right-Suite@Universal 2021 21.0.07 RSU23828 2021-Sep-01 16:54D1
aterstore203OBGRLot52BIkIWaL-rstom2O3OBGR.rLp Calc=MJS Housefaces: W Page 3
- - wrightsoft° Right-M Worksheet
Entirle House
DEL AIR KrG, A/C & REFRIG. INC
531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Ucerse: CMC 1249777
Job: Lot 52 Block 1 Waterstone 20...
Date: Dec 01, 2011
By: RH
i
2
Room name
Exposedvdl
MWC
BD
BDRM2
3
4
Room height
Room dimensions
105 ft.
8.4 ft heat/cool
ft
85 ft heaUcool
5
Room area
6.0 x 4.5 ft
27.0
135 x 12.0 ft
ftz
162.0 ftz
Ty
Construction
number
U-value
(BtuM-9
Or
HTM
(BtuhRtz)
Area (ft2)
or
Load
Area (ft2)
Load
perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
NOS
Heat
Cool
6
!W
16B 19ad_� _.._ ___.
___OA49-n
___._ 157
�6.43
. 259
_
;
0 ..__._ .Q
�'
0 0
_ o
_d
_
F----GG
OCalI_
0201
0.550
ri
n
17.60
498
12.64
0 0
0 0
0 0
0
0
0 0
0
11
_
W =
2A-2ov
16& 19ad. =
0,330
.�__ 0 049
n
.fie
10.56
Ji S7=259
_ 8.52
T :� `
00
p . _ _ _ 0
, _ 0
0
0 0
-.-.._ _
0
- - - r0
0
0 ____�__
0 0
0 0
`-v: p
0
_ 0
DftWall
10C-v
2A-2ov
OP01
0550
0.330
a
a
a
4.98
12.64
18.60
48
48
0 0
^- �309
_
239
0 0
_
._.�. �:
0
0
0 _`
0 0
0 0
Q
_0
0
8.43
17.60
10.56
2A-2ov
0230
a
1056
20.42
0
0 0
0
0
0 0
0
0
0
0
0
0
0
0
2A-2ov
0.330
a
1056
852
0
0
0
__ 0
":p___0
0
0
0
0
0
V�1
DftWall
�0049.-s_.
0201
s
157
6.45
259._
498
0
36
p,
f' 36
:0
232
179
_
u� _.;;p
T 0
398
L -(
2A-2ov
0.330
s
1056
852
0
_ 0
. 0
96
80
513
VN'"
DftN/all _
sv
4.98
_
0
0
. _ _ o
16
__ o
16
._ __ 0
171
_ _._.0
. 138
,0
_ __ __ 0
W _
166 19ad
DflWall ._.-.._ .___._._,.
2A-26v
0.049
� , 0201
0.330
__ w
w.
_. 1056
157
6.43
'i056
_12_62
___ _ 259
� 4.98
"
' 0
__ 0
•r 0
0
0
.„ `" .p
0
0
0
--- 0
0
__ _ aN �O
0
,_ _....___�
0
0
- _.V O
w.-__
0
,�__� ___.0
0
-..-....__...;0
.:'_'__ 0.
6
,2A-2ov
, w_,
19.09
0
0
,- 0:
u A
0
,. 0
0
0
0.350
w
1120
. 25B7
0
0
0
0
0
0
0
2B-2fv
2B 2(v
'0.330
.w ,
1056
0
: p
., 0
'0
0
` 0,
0
0
0
11J0l.-- --- T
0330
-0.600
w
__�!
_._1920
2621
J75.8
0
0
0
w_ 0
0
? .. 0
•. 0
1.
0
..: 0
Q
0
p
°' 0
W-
L-
DftWall
0201
nw
6.43
4.98
.__..�
0
rv' 0
0
____
0
0
� w 0
0
�0
0
0
0
G
P
2A-2ov
12C Osw
0 330
nw
10.56
16.61
0
0
0
0
0
0
0
0
-11D0 _
0091
0390
__n_
291
_-._12.48
1.62
JL43
p
0
0
�_ 0
0
0
- 0.
_ _0
0
_ _0
_p
_ .ro
C
161330ad _
0.032
„_
_. 1.02
1.69
38
. 38
_ 39
64
0
236
242
399
_ 236
_31.65--
_
0.
6
c) AED
excursion
24
45
Envelope loss/gain
912
459
1306
890
12
a) Infiltration
b) Room ventilation
182
44
208
50
0
0
0
0
13
Internal gains Occupants@ 230
0
0
0
Appliances/other
0
0
0
Subtotal (lines 6 to 13)
1094
502
1515
940
Less external load
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
0
0
0
0
15
Duct loads
12 %
24%
1094
131
502
120
12 %
24%1
1515
182
940
224
Total room load
Air required (cfm)
122255
626F
1
1
16996
1163
611
-
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed
Rigk-Su2021-Sep-0116:54:01
te®Uriversal 2021 21.0.07 RSU23828 aterstore203OBGR\Lot52BIklWatLrstore2030BGR.rLp Calc=MJS Horsefaces: W Page 4
- wrightsoft® Right-JO Worksheet Job: Lot52 Block 1 Waterstone 20...
Entire House Date: Dec 01, 2011
DEL AIR HTG, A/C & REFRIG. INC By: RH
531CODISCOWAY. SANFORD,FL32771Phore:407-333-2665Fax: 407-333-3853 Web: WWW.DELAIR.COMUcerse:CMC1249777
1 Room name BDRM3 STUDYBDRM4
2 Exposed wall 125 It 245 ft
3 Room height 8.5 ft heat/cool 85 ft heatl000l
4 -Room 5 Room dimareensions 1688 ft2 13.5 x 125 It 135 x 11.0 ft
148.5 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (BtuhAt -9 (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/PS Heat Cool Gross N/PS Heat Cool
6 W 166 19adm 0.049 _n 1T7, 0 0.
V)/ DftWall - 0201 n 6.43 428 0' 0 0 0 0 0 0 0
10C-v 0550 n 17.60 12.64 0 0 0 0 0 0 0 0
2A 2ov 0.330 n 1056 _ 852 _a 0 0 _ 0 0 �_ _.0 _ 0 0 0
259 , 0 T,.. 0 0 _w 0 0 ,. _v.,_.,
-0� 0_0
DflWall 0201 a 6.43 w T428 0_ 0 0 :��0 0 _� 0 0 0
10C-v 0550 a 17.60 12.64 0 0 0 0 0 0 0 0
2A-2ov 0230 a 1056 18.60 0 0 0 0 0 0 0 0
2A-20v 0.330 a 1056 20.42 0 0 0 0 0 0 0 0
2A-20v 0.330 a 10.56 852 0 0 0 0 0 0 0 _0
W 166 19ad_� =_� - 0049 _ s�__�__ 157 ._�.259 D
V?/ DftWall 0201 s 6.43 428 100 84 ' 539 418 88 ' - 72 462 358
2A-2ov 0.330 s w10.56 852 16 ry M 16 _ 171 138 16 16 171 138
DftWall 0201 `sw, 6:43 . 496 0 0 . µ� 0 p ` - 0 -- U_
2A 2oy._
W_ r 161319ad 0.049 _ w 157 259 0 0 0 0 rv0 0 �0 0
DftNlall . - �. _ 0201 w 6.43 0 - 0 0 . _._. 0 0 O _ 0, _ .
2A-2ov 0330 w 1056 19.09 , 0 0, 0 0 0 `0 0 0
2A-2ov ' . 0.350 w 1120 25B7 0 0 0 .
, 0 p p' 0 p
26 2N 0,390 - w 10.56 13.12 0, . 0 0 0 0 0. 0 p
26-2N 0330 = w., 1056 2631 0 .. t 0 0 . 0 , , 0 '0 . 0 0
_w._0.500_ w_ �1920,_ 17.58,. 0d__ �0 _0. _0 �.. RQ -0 - -0, 0
V+1 DftWall 0201 nw 6.43 428 0 0 0 0 0 0 0 0
_ L_-_G_ _2A 2oy_._ _ 0.330 nw _ 1056 16.61 _ 0 0 0 0 0 ___ 0 0 0
,T __ _
P 12C Osw . 0 091 2 91 1.62 0 0 0 -W~ 0 "" 108 ' 108 314 - 175
L-D :11 DO -, - -0.990_,n_ 12.48 1143 0 0 0 0 0 0 0 �0
.16B 30ad _ 0.032 _ _ _ ,_ 1.02 _ 1.69 _w_246 _ . _ __ 246 __ 252 _ __.� 416 217 __�217 __ _222 . _366
F.�_ 72A-W1 ~ - _0989 31.65 - "- 0.00 .._ w69 396
6 c) AED excursion -47 -50
Envelope loss/gain 1358 924 1945 987
12 a) Infiltration 217 52 191 46
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants@ 230 0 0 0 0
Appliances/other 0
0
Subtotal (lines 6 to 13) 1575 977 21361 1033
Less extemalload 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 1575 977 2136 1033
15 Dudloads 12% 24% 189 232 12% 24% 256 246
Total room load 1764 1209 2392 1279
Air required(cim) 64 51 86 54
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed
AeuA wrigFrttsoft^ 2021-Sep-0116:54,01
Right-Sute®Uriversal 2021 21.0.07 RSU23828 Page 5
aterstore2030BGR\Lot52Blk1 Waterstore2030BGR.np Calc= MJ8 House faces: W
-�- wrightsoft° Right-JO Worksheet Job:
Entire House Date:
DEL AIR HTG, A/C & REFRIG. INC By:
531 CODISCO WAY, SANFORD, FL32771 PhDre:407-333-2665 Fax:407-333-3853 Web:WWW nFi niprunei
Lot 52 Block 1 Waterston 20...
Dec 01, 2011
RH
Calculations approved b ACCAto meet all requirements of Manual J 8th Ed.
Right-Sdte®Uriversa12021 21.0.07 RSU23828 2021-Sep-01 1654.01
aterstone2030BGR\Lot5281k1 Waterstore2030BGR.rLp Calc= MJ8 House faces: W Page 6
- wrightsoftm Right-M Worksheet
Entire House
DEL AIR WIG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM License: CMC 1249777
Job: Lot 52 Block 1 Waterstone 20...
Date: Dec 01, 2011
By: RH
1
2
3
4
5
Room name
EVosed wall
Room height
Room dimensions
Room area
DIMING
46.6 ft
8.4 It heaV000l
1.0 x 291.3 ft
291.3 112
Ty Construction U-value Or HTM
number (Btuh/f?-`q (Btuh/ft2)
Area (it) Load
or perimeterO (Btuh)
Area Load
or perimeter
Heat Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
W • 4
W---
i6&19ad..�_..__••.
DftWall
10C v
2A 2ov _
19a_d _ - =_
DftWall
10C-v
2A-2ov
2A-2ov
2A-2ov
16B-19ad-- --
DBWaII
2A-2ov _--p-- _
Dft Wall _ -
1613-19ad .._--w_.. ,
DftVllall ' .
2A-2ov
2A-2ov
2&2fv
26 2W
DfIWall
2A_2ov _
,11D0 ___,____
166 30ad
'22A->pL_�_.-_._.._
_._._ 0049
0201
0550
0 330
--nw
n
n
n
e_
a
a
a
a
a
�s._
s
s
-sw ,.
_sw
, w_
w::
w
,w
• w .
bin
_ w
_157
6.43
17.60
16
05157
6.43
17.60
1056
10.56
1056
r�157
6.43
10.56
, �._643
__ iQ56.
__ -157
6,43
1056
1120
1056
1056
1920
6.43
1056
2.91
1248
.__31;65
-._._259
4.28
12.64
852
..._.__. 0
88
0
_ 0
0
0
0
0
0
-1-1 0
48
0
.43
15
0
°- 116
23
7
,5
°" 7
20
43
15
36
0
295
_____�291
__-_..__.._0
88
0
_ 0
0
0
0
0
0
__.. 0
rt`-_�._0
566
0
_ 0
0
0
0
0
0
- �0
__._.._: 0
� 439
0
0
0
0
0
0
0
239
�- 0
_... 0
270
443
173
e,,, ' 68
175
136
254
58
_:--- 0
__._,..
0 049
_ 0201
0550
0330
0330
0230
__ 0.049
0201
0230
0201
_ 0 049
0201
0.330
0350
0,330
0.330
--0.600
_
4.98
12.64
18.60
20.42
8.52
._-- 259
428
852
498
12.62.,�
2.59
-.. - _
4.98
19.09
2527
13.12
26.31
---1758
4.98
16.61
1.62
11;43
1.69
__0.00
_____.
48
0
3
27,
----0
0
54
; 4
0,
{ 4
1
27
0
'w3fi
309
0
; 175,
-:_ 162._�
_ 0
�' ry 348
." ` ..245,
„ 75
.;: 55
70
175
162
105
303
__�,„1474
-
`;
-
yJ.
W --_
V)/
_ I�-G
P
�D
C _
F__ .__-
0201
0330
0.091
0390
0.032
-_-___0.989
nw
_ nw
n-.
____,
295
,_�•47
.
6
c) AED excursion
749
Envelope loss/gain
4609
4185
12
a) Infiltration
b) Room ventilation
732
0
176
0
13
Internal gains: Occupants@ 230
Appliancesrother
1
230
0
Subtotal (lines 6 to 13)
5341
4591
14
15
Less external load
Less transfer
Redistribution
Subtotal
Duct loads
12 %
24 %
0
0
0
5341
641
0
0
0
4591
1093
Total room load
Air required (cfm)
5982
215
5684
240
Calculations approved byACCAto meet all requirements of Manual J 8th Ed. P. -1-wri_gF�tsoft^ 2021-Sep-01 16:5401
Right-Sute®Uriversal 2021 21.0.07 RSU23828 Page 7
atersto-2030BGRIot52BIk1Waterstore2030BGR.np Calc=MJ8 Horsefaces: W
- wrightsoft® Duct System Summary Job: Lot 52 Block 1 Waterston...
Entire House Date: Dec 01, 2011
By: RH
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM License: CMC 1249777
For: ADAMS HOMES
5375 Lugo Street, Fort Pierce, FL 34951
External static pressure
Heating
0.40 in H2O
Cooling
0.40 in H2O
Pressure losses
Available static pressure
0.06 in H2O
0.06 in H2O
Supply/retumavailable pressure
0.34 in H2O
0.170/0.170 in H2O
0.34 in H2O
0.170/0.170 in H2O
Lowest friction rate
0.247 in/100ft
0.247 in/100ft
Actual air flow
947 cfm
947 cfm
Total effective length (TEL)
138 ft
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FR
Diam
(in)
H x W
(in)
Duct
Mat
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
BDRM2
BDRM 3
h 1696
61
49
0.266
6.0
Ox0
VIFx
27.9
100.0
BTH2
h 1764
64
51
0.384
6.0
Ox 0
MFx
18.6
70.0
DIMING
c 104
2
4
0.469
4.0
Ox 0
MR
2.5
70.0
DINIING-A
c 2842
108
120
0.321
6.0
Ox 0
VIFx
21.0
85.0
GREATROOM
c 2842
h 2815
108
101
120
0.322
6.0
Ox 0
VIFx
20.7
85.0
GREATROOM-A
h 2815
101
95
95
0.340
0.333
7.0
7.0
Ox0
Ox 0
MR
VIFx
14.9
85.0
KrrCHEN
c 2435
58
103
0.420
6.0
Ox 0
MFx
17.2
11.0
85.0
70.0
LAUNDRY
c 1150
27
49
0.409
5.0
Ox 0
VIFx
13.0
70.0
M.BTH
M.Wc
h 1619
58
48
0.261
5.0
Ox 0
VIFx
30.1
100.0
M.Wic
h 1225
44
26
0.247
5.0
Ox 0
VIFx
37.7
100.0
MASTERBDRM
c 152
c 2968
3
125
6
125
0.272
0.269
4.0
7.0
090
Ox0
MR
MR
25.0
100.0
STUDYBDRM4
h 2392
86
54
0.374
6.0
Ox0
VIFx
26.5
21.0
100.0
70.0
Trunk
SO
St2
st2
sti
st1
SO
SO
SO
st3
Name
Trunk
Type
Htg
(cfm)
Clg
(cfm)
Design
FR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Duct
Material
Trunk
sti
st3
S2
PeakAVF
PeakAVF
PeakAVF
494
292
215
446
255
240
0.247
0.247
0.321
463
535
544
14.0
10.0
9.0
0 x 0
0 x 0
0 x 0
VinlFlx
VinlFlx
VinlFlx
st1
wrightsofta �2021-Sep-01 16:54:02 � a /Oa.6Mmxeq.wa,tomro�Y Right-Sute®Uriversa12021 21.0.07 RSU23828
Page1
aterstone2D30BGRLot52BIk1Waterstone2030BGR.nQ Calc=MJ8 Housefaces: W
Return Branch Detail Table
Name
Grille
Size (in)
Htg
(Cfm)
Clg
(cfm)
TEL
M
Design
FR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Matl
Trunk
rbi
Ox 0
947
947
0
0
0
0
Ox 0
VIFx
.- -rk wrightsoft, 2021-Sep-01 16:54:02
Right-Sute®Uriversal 2021 21.0.07 RSU23828 Page t
ICCK aterstone2030BGR1Lot52BIkiWaterstore2030BGR.nQ Calc=W8 Housefaces: W
2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA a
Project Name: Lot 52 Block 1 Waterstone 2030 BGR
Street: 5375 Lugo Street
City, State, Zip: Fort Pierce , FL , 34951
Owner:
Design Location: FL, ST_LUCIE_CO_INTL
COMPONENT
AIR RARRIFR rlQ1T1=P1A
Builder Name: ADAMS HOMES
Permit Office:
Permit Number: Y
Jurisdiction: 661000 U
w
2
U
IKIB111 AT1A%I
General
-- -- -
A continuous air barrier shall be installed in the building envelope.
..--- - - . .- I �V1-M I lwm VICI 1 Cr[IH
Air -permeable insulation shall
requirements
The exterior thermal envelope contains a continuous air barrier.
Breaks or joints in the air barrier shall be sealed.
not be used as a sealing material.
Ceiling/attic
The air barrier in any dropped ceiling/soffit shall be aligned with
the insulation and an y gaps in the air barrier shall be sealed.
The insulation in an dropped
Y aped ceiling/soffit
Access openings, drop down stairs or knee wall doors to
shall be aligned with the air barrier.
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
Knee walls shall be sealed.
with a material having a thermal resistance of R-3
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/doorjambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
(including
The air barrier shall be installed at any exposed edge of
insulation.
Floor framing cavity insulation shall be installed to
above -garage
maintain permanent contact with the underside of
and cantilevered
subfloor decking, or floor framing cavity insulation
floors)
shall be permitted to be in contact with the top side
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace wall
.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned s ace shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
as.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the finished surface.
thermal envelope shall be airtight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
behind
Shower/tub
on exterior wall
-extend
The air barrier installed at exterior walls adjacent to showers and
popina and wiring
Exterior walls adjacent to showers and tubs shall
tubs
shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exteriorwalls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal
envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be'sealed, concealed fire sprinklers shall only be
sprinklers sealed
in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
a. In addition, Inspection Of
IOa Walls shall ha in accnrrlano IAIifh fho nffi i..... .. Inr Ann
9/1/2021 4:58 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
FORM R405-2020
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the
Residential Simulated Performance Alternative shall include:
❑ This checklist
❑ Form R405-2020 report
❑ Input summary checklist that can be used for field verification (usually four pages/may be greater)
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page)
❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4
allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to
comply with Section C402.5
❑ If Form R405 duct leakage type indicates anything other than "default leakage" then a completed
2020Duct Leakage Test Report - Performance Method (usually one page)
9/1/2021 4:57:24 PM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Duct Leakage Test Report
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
System 1
cfm25
System 2
cfm25
System 3
cfm25
Sum of others
cfm25
Total of all
cfm25
2038 On
Total of all Total Conditioned
systems Square Footage
❑PASS ❑FAIL
sQ Prescriptive Meth ,& cfm25 (Total)
To qualify,eas "substantially leak free" QnTotal must be: less than or
equal to 0:04 if:,air:handler unif i5 installed. If:air'handle`r unit is not -
Installed, Qn Total -must l3e.less than or equal.to 0 03. Tli s testing
rnefhod meets thejequirertients in;aecordance,with.$ection R403.3 3.
is the air handler un/t installed :dunn , testrn YES , o9 g 0
Q Performance/ERI Method. cfm25-'(out or Total)..
To qualify :usfng:,this method;. Qn. must not be greater than, the
proposed duct leakage Qn specified on Form R405-2020-or R406-202-0
,Leakage -.Type selected on>Farrrm Qn specified on "Form R405 2020'
R405=2020 (EnergyCalc)r,R4.66-2020 (EnergyCalc) or- R466-2020.'
Proposed Qn 0.04
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section
553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes.
Testing Company .4 .
Company Name: Phone:
I hereby verify that the above duct leakage testing results are in accordance .with the Florida Building Code requirements with the
selected compliance path as stated above, either the Prescriptive Method or Performance Method.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #:
Issuing Authority:
H/1/2021 4:58:29 PM EnergyGaugeO USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction: 661000 Permit #:
Job Information
Builder: ADAMS HOMES Community: Lot: NA
Address: 5375 Lugo Street
City: Fort Pierce State: FL Zip: 34951
-Air 'Leakage,Test R@SUItS Passing,,results must meet either the performance Prescriptive, or ERl Method-
0. PRESCRIPTIVE METHOD -The building or'dwelling unitshall be tested and verified as having an air leakage rate i6f r ot'exceeding 7 air
changes per hour at a pressure: of'0.2 incfi•wg: (5q Pascals) in Climate Zones 1 and 2.
0. PERFORMANCE; or ERI METHOD -The building or dwelling unifishall beitestedI and verified.as having an air leakage rate of not exceeding
,the selected ACH(50) value, as shown on Form R405-2020 (Performance)'or R406-202t)' (ERI), section ab`eled as'infiltrationsub section'ACH50
ACH(50) specified on; Form R405-2020-Energy;Ca/c {Performance) or R406-2020 (ERI): 5.500
x 60 _ 17119 Method for calculating buildinq volume:
CFM(50) Building Volume ACH(50)
Q Retrieved from architectural plans
1-1 PASS • Code software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester:
Printed Name of Tester:
License/Certification #:
Date of Test:
Issuing Authority:
9/1/2021 4:58:18 PM EnergyGaugeOO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 7th Edition (2020)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: 5375 Lugo Street Permit Number:
Fort Pierce , FL , 34951
IVIArvUA I UK Y KtQUIKtMENTS - See individual code sections for full details.
V
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
SECTION R402 BUILDING THERMAL ENVELOPE
• ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and
R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
9/1/2021 4:58 PM EnergyGauge® USA '7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
R403.1 Controls. SECTION R403 SYSTEMS
❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system,
including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise
sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire
system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn =
duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C)
or below 55°F (13°C) shall be insulated to a minimum of R-3.
❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are
installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall
❑ be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for
circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The
controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no
demand for hot water.
R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when heated water is used in the occupancy.
9/1/2021 4:58 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3'% inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to.60°C).
R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of
combustion types of service water -heating systems to be turned off.
R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of RA9, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment.
❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based
on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation
methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the
outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design
conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other
factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical
ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have
an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is
installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMU IV
(CFM)
HRV or ERV
Any
1.2 cfm/watt
Any
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916
9/1/2021 4:58 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
EjR403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
2. calculated total sensible load but not less than 80 percent of that load.
When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403.
R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
9/1/2021 4:58 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5
QR403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as.from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
❑ R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
❑ R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the
requirements ofAPSP-14.
F1 R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements:
1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house
is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day.
2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air.
3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13,
conform to the following requirements:
1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct.
2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct.
3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an
efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
9/1/2021 4:58 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5