Loading...
HomeMy WebLinkAbout500UG TANK TIE DOWN - 2020STORAGE TANK IS ADEQUATELY ANCHORED TO PREVENT FLOATATION, COLLAPSE OR LATERAL MOVEMENT DURING THE BASE FLOOD EVENT. ALL WORK SHALL BE IN ACCORDANCE WITH NFPA 54-58, NATIONAL FUEL GAS CODE AND FLORIDA FUEL GAS CODE 2020 & FLORIDA BUILDING CODE 2020. TANKS INSTALLED IN TRAFFIC AREAS SHALL BE PROTECTED WITH GALV. STEEL SCHED. 80 PIPE BOLLARDS (4"0) 6' LONG X 3' BURY DEPTH WITH CAP 0 3' O.C. SIDE ELEVATION GRASS COVER 17LB. ANODE BAG PROPANE TANK BUOYANCY MAX BUOYANCY = pw*g*Vtmk = 1.94 slug/ft 3 * 32.2 ft/s2 * 66.84 ft 3 = 4176 LBS NET BUOYANCY = MAX BUOYANCY — WEIGHT OF EMPTY TANK = 4176 LBS — 871 LBS = 3305 LBS FORCE ON im CABLE = 3305 / 2 = 1653 LBS TENSILE STRENGTH OF in CABLE = 9800 LBS / 5 = 1960 LE FORCE ON AUGER ANCHOR = 1653 / 2 = 827 LBS MIN. PULL—OUT RESISTANCE OF AUGER ANCHOR = 1360 LBS 1 LP TANK I � I � L _ _ __...... .,gg LONG W/ 6.0 HELIX 4 TOTAL SCALE 1/4" = I' — 1 I -III -III-III -III - I I (MAX COVER) 1'- 1 EXCAVATION SIZE: 1 1 12'L x 4'W x 4.5'D " 7x19 GALV. AIRCRAFT CABLE STRAPPING BOLT AUGER ANCHOR, 36' LONG W/ 6"0 HELIX FRONT ELEVATION SCALE 1/4" = 1'-0" Thompson Gas 1786 SW Biltmore St. ort St. Lucie, FL 3498 Fort Pierce Engineering, Inc. Dependable Mechanical, Electrical & Plumbing Design C.A. No. 28173 315 South 7th Street Fort Pierce, FL. 34950 Phone: 772 672-4636 Fax: 772 672-4637 ,� r•`i^� � � a O �, 10 N • • S E. No. §0 DOWNi- RRLl,� APPROVED: EJS DRAWING NUMBER mi- LP500