PROPANE TANK BUOYANCY
MAX BUOYANCY = pw*g*Vtmk
= 1.94 slug/ft 3 * 32.2 ft/s2 * 66.84 ft 3
= 4176 LBS
NET BUOYANCY = MAX BUOYANCY — WEIGHT OF EMPTY TANK
= 4176 LBS — 871 LBS
= 3305 LBS
FORCE ON im CABLE = 3305 / 2 = 1653 LBS
TENSILE STRENGTH OF in CABLE = 9800 LBS / 5 = 1960 LE
FORCE ON AUGER ANCHOR = 1653 / 2 = 827 LBS
MIN. PULL—OUT RESISTANCE OF AUGER ANCHOR = 1360 LBS
1 LP TANK
I �
I �
L _
_ __...... .,gg
LONG W/ 6.0 HELIX
4 TOTAL
SCALE 1/4" = I' —
1 I -III -III-III -III - I I
(MAX COVER) 1'-
1
EXCAVATION SIZE:
1 1 12'L x 4'W x 4.5'D
" 7x19 GALV.
AIRCRAFT CABLE
STRAPPING BOLT
AUGER ANCHOR, 36'
LONG W/ 6"0 HELIX
FRONT ELEVATION
SCALE 1/4" = 1'-0"
Thompson Gas
1786 SW Biltmore St.
ort St. Lucie, FL 3498
Fort Pierce Engineering, Inc.
Dependable Mechanical, Electrical
& Plumbing Design
C.A. No. 28173
315 South 7th Street
Fort Pierce, FL. 34950
Phone: 772 672-4636
Fax: 772 672-4637
,�
r•`i^� � � a O �,
10
N •
•
S E. No. §0
DOWNi- RRLl,�
APPROVED: EJS
DRAWING NUMBER
mi-
LP500