HomeMy WebLinkAboutPROJECT DESCRIPTIONProject Information & Design Criteria Building Code: FBC 2020 7th Edition Project Name: Project Address: Type of Construction: CBS Frame BuildingDesigned Enclosed Open Partial) Enclosed Wind Speed 3 Sec. Gust): 160 M.P.H 170 M.P.H. Exposure: B Internal Pressure Coefficient: +/- 0.18 Importance Factor: 1.0 Mean Building Height: N/A ft. Exposure Coefficient: Overhang N/A Roof Pitch: N/A Com onents & Cladding Wind Pressure: Roof Dead Loa& ShinqIes Tile Framed Floor Live Load bLA P R F Dead Load NA P.S.F_ Impact Resistant ssembly- I Yes No A I O her O enin s: 1. RESERVE BLVD TO LEGENDS 2. TURN ON LEGENDS DRIVE 3. CONTINUE STRAIGHT TO ENCLAVE PLACE (THRU GATE& TURN LEFT ONTO ENCLAVE CIRCLE 5. LAST HOUSE AT END OF CUL DE SAC 1. CONSTRUCT (2) COLUMNS W/LIGHTS AND AN ATTACHED PLANTER - (1) ON EA SIDE OF THE DRIVEWAY APRON RECEIVED 1.14010 9PIAHTY Permitting Drawing List Sheet Number Sheet Name A-1 Cover Sheet, General Notes, Project Info & Location Map A-2 Notes S-1 Foundation Plan '` V�51jkeoopvxi 4T114 a) CU 0 4- CL U a) a) fY Z LL Z - W O _ p 0?� z� 0 p z z 0 w_ s 0 t= O d Q d J W= Q U Q z-�OOQz�o���j� B=0�z Z Li LLJLJ w=Uu-I-�UVOQ��OU� z_�wLU < IQU -W0EL UO���> �doz�=T_ �N�zzO _ z - o - z oCJ~w~�-�zQW`-c-O � w OU�z>p��gLL IU�cn� iu �LU 0����nLU o W= a 0 0 z�W 07 Z Ui W (n OmU�p-�z�� 0 a U U J z 0 0 o c9 0 O_ < LU O (� Q=( OL > W p zo = o_O J Q iL�U w0 U UI- Uz Wz OFa U~ Q D W Uz 2 FL p Qz °- 6LU �! p W U)02 5 Lu L0�zza_Luw Uw W Q ai lu D_ Q� z N O W O w = IL a- W(Z� LLJ IL. W W= t-a (0 U:E z 0 Lon o n (-) D J U L)) ( J 0 co L / O E U J CL_ > Cz �- O Co,l OI VJ 75 z O L U U s_ U > G� W Q / v Jw LL- 7/5/202 I 10: 1 1 :46 PM A- i Ga l e GENERAL NOTES: THE BUILDER SHALL REVIEW DRAWINGS IN THEIR ENTIRETY BEFORE STARTING WORK. THE BUILDER SHALL ACCEPT FULL RESPONSIBILITY FOR ANY ERROR OR OMISSIONS NOT REPORTED IMMEDIATELY IN WRITING TO ENGINEER OF RECORD. BY SUBMITTING THESE PLANS FOP PERMIT THE BUILDER ACCEPTS FULL RESPONSIBILITY FOR THE ACCURACY OF THE INFORMATION DEPICTED WITHIN AND IT IS ASSUMED THE BUILDER HAS READ AND UNDERSTANDS THE NOTES BELOW. DESIGN LOADS IN ACCORDANCE WITH 2O20 FBC 7TH EDITION CHAP. 16 ASSUMED SOIL BEARING CAPACITY MINIMUM: 2500 PSF STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND SITE DRAWINGS CONSULT ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS. ALL DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL BE CONSTRUED TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN FIELD. DO NOT SCALE DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. IF ANY DISCREPANCIES ARE DISCOVER THE ENGINEER OF RECORD MUST BE CONTACTED BEFORE THE COMMENCEMENT OF CONSTRUCTION. THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER BUILDING IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES TO ENSURE: SAFETY OF THE BUILDING AND ITS COMPONENTS DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS OR TIEDOWNS. THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. THE STRUCTURAL FRAMING SHOWN IS SCHEMATIC IN NATURE. HOWEVER, THE SUP PORTING ,r ING STRUCTURE HAS BEEN DESIGNED UNDER THE ASSUMPTION THE FRAMING SCHEME SHOWN WILL CLOSELY PARALLEL FINAL FLOOR DESIGNERS LAYOUT. PROVIDE SIGNED AND SEALED SHOP DRAWINGS AND CALCULATIONS FOR APPROVAL. REVIEW OF SHOP DRAWINGS IS REQUIRED AS THE ENGINEER CHECKS BEAM, WALL, COLUMN AND FOOTING CAPACITIES AGAINST KNOW LOADING. FAILURE TO PROVIDE SHOP DRAWINGS MAY RESULT IN ADDITIONAL ENGINEERING COSTS DURING CONSTRUCTION. W TH AC 318-05 BUILDING CODE CONCRETE HAS BEEN PERFORMED IN ACCORDANCEI I REQUIREMENTS FIR STRUCTURAL CONCRETE NORMAL WEIGHT CONCRETE (145 PCF) 28-DAY COMPRESSIVE STRENGTHS. PILING 5000 PSI WITHAO WATER -CEMENT RATIO SHALLOW FOUNDATIONS 2500 PSI. PILE SUPPORTED FOUNDATIONS 5000 PSI WITHAO WATER -CEMENT RATIO COLUMNS, BEAMS, AND ELEVATED SLABS, 3000 PSI. CONCRETE SLUMP SHALL BE AS FOLLOWS SLUMP IN INCHES MINIA MASSIVE SECTIONS, PAVEMENTS, AND SLABS 1-1/2" 4" HEAVY SLABS, BEAMS, WALLS 3" 5" THIN WALLS, COLUMNS 3-1/2" 6" MINIMUM CONCRETE CLEAR COVER SHALL BE: SLAB - 3/4" BEAMS AND COLUMNS - 1-1/2" TIE COLUMNS - 3/4" EXPOSED UNPROTECTED CONCRETE - 1-1/2" FORMED CONCRETE BELOW GRADE - 3" UNFORMED CONCRETE BELOW GRADE - 3" PLACING DRAWINGS AND BAR LISTS SHALL CONFORM TO A.C.L'S "MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES."(A.C.I. 315) DETAILS OF CONCRETE REINFORCEMENT SHALL BE IN ACCORDANCE WITH "MANUAL OF STANDARD PRACTICE FOR REINFORCED CONCRETE CONSTRUCTION." AS PUBLISHED BY THE CONCRETE REINFORCING STEEL INSTITUTE UNLESS OTHERWISE INDICATED. CONCRETE CONSTRUCTION TECHNIQUES SHALL CONFORM TO THE "SPECIFICATIONS F(�`R STRUCTURAL CONCRETE FOR BUILDINGS" (A.C.I. 301) ADEQUATE VERTICAL AND HORIZONTAL SHORING SHALL BE PROVIDED TO SAFELY SUPPORT ALL CONSTRUCTION LOADS CONCRETE BEAM SIZES MAY BE INCREASED AS REQUIRED FOR ARCHITECTURAL DETAILS OR TO FIT BLOCK COURSING. CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF A.C.I 301 AND ASTM C-94 FOR MEASURING, MIXING, TRANSPORTING, ETC. CALCIUM CHLORIDES SHALL NOT BE UTILIZED IN THE WORK. OTHER ADMIXTURES MAY BE USED ONLY WITH THE APPROVAL OF THE ENGINEER. FBC PROVIDES AN EXCEPTION FOR RESIDENTIAL CONSTRUCTION WHERE CONTROL JOINTS ARE NOT REQUIRED. HOWEVER, IN THAT EXCEPTION, IT SAYS THAT THE EXCEPTION IS ALLOWED WHERE THE OWNER ACKNOWLEDGES THAT CRACKS ARE ACCEPTABLE AND UNDERSTOOD. JOB SPECIFIC GENERAL NOTES: 1. HOUSE IS IN A NEGLIGIBLE WEATHER AREA 2. HOUSE IS IN A VERY HEAVY TERMITE AREA. 3. FLAME SPREAD FOR WALLS AND CEILING FINISHES SHALL BE LESS THAN 200. 4. FLAME SPREAD FOR INSULATION SHALL BE LESS THAN 25 5. SMOKE DEVELOPED INDEX SHALL BE LESS THE 450 FOR WALL FINISHES, CEILING FINISH AND INSULATION 6. GYPSUM BOARD SHALL CONFORM TO FBC R702.3 STANDARDS 7. TILE IN SHOWERS MUST BE BACKED BY "DURA ROCK" CONCRETE BOARD OR EQUAL 8. EGRESS WINDOWS COMPLY WITH 2O20 FBCR 7TH EDITION R310.2.1 EXCEPTION #1 MIN. NET CLEAR OPENING OF 5.0 S.F. 9. DRYER VENT TO OUTSIDE 10. LOW FLOW PLUMBING FIXTURES STRUCTURAL DESIGN IS IN ACCORDANCE WITH A.C.1530-05/ASCE 5-02/TMS 402-02, BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES AND THE COMMENTARY ON BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES. CONSTRUCTION SHALL BE IN ACCORDANCE WITH A.C.1530-05/ASCE 6-02/TMS 602-02, SPECIFICATIONS FOR MASONRY STRUCTURES AND THE COMMENTARY ON SPECIFICATIONS FOR MASONRY STRUCTURES. ,ALL BLOCK WALLS SHALL BE TWO CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE, F'm=1500 P.S.I. UNLESS OTHERWISE NOTED. BLOCK SHALL BE PLACED IN RUNNING BOND UNLESS OTHERWISE NOTED. LAY UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE PLACING CONCRETE FOR IN WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH ASTM C-476 AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3,000 P.S.I AT 28 DAYS. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8" COURSE AGGREGATE AND SHALL BE PLACED WITH A SLUMP OF 8" TO 10". USE MECHANICAL VIBRATION TO CONSOLIDATE GROUT. TYPE S MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270 HORIZONTAL AND VERTICAL MORTAR JOINTS SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO THE CELLS TO BE FILLED. ALLOW A MINIMUM OF 24 HOURS FOR MORTAR TO CURE PRIOR TO GROUTING CELLS. TENSION AND COMPRESSION LAPS = .002 X BAR DIAMETER X Fs (NOTE THAT Fs= 24 KSI MAXIMUM (A X Fy)) (THIS EQUATES TO 48 X BAR DIAMETER) REINFORCING BAR SHALL BE IN ALL WALL INTERSECTIONS AND AT EACH SIDE OF ALL OPENINGS. REINFORCING STEEL NOTES: REBAR SHALL BE ASTM A615 GRADE 60 DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE WITH THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. HORIZONTAL AND VERTICAL BARS SHALL LAP 60x BAR NO. SEE LAP SPLICE SCHEDULE UNSCHEDULED FIELD LAPS ARE SUBJECT TO'ENGIN`EERS REVIEW. TENSION LAP SPLICE SCHEDULE: PLAIN REINFORCEMENT BAR NO MASONRY SPLICE OTHER THAN TOP TOP BARS 3000 PS14000 PSI3000 PSI4000 PSI 3 - - 16,,, 16r, 21" 1Se 4 24'° 22" 191 2$1, 24," $ 30.,;... 27eri8++ 3 r, 30, 6 36" 35" 31,. 44;. 40" 7 42,, 48:,r 42:" 63" 54" PROVIDE CORNER BARS LAPPED AND TIED`TO EACH BEAM REBAR, TYPICAL AT ALL CDR NERS„THESE CORNER BARS SHALL BE THE SAME SIZE AS LONGITUDINAL BEAM BARS, SEE DETAILS FOR ADDITIONAL INFORMATION. CAREFULLY PLACED RIG WELL TIED WITH BAR: REINFORCEMENT SHALL BE CARE_fDLYSUPP SUPPORTED SUPPORTS AND SPACERS, FOOTINGS SHALL BE ASSEMBLED MATS WITH BARS EQUALLY SPACED AND REINFORCING STEEL IN FOOT A M Q WIRED TOGETHER AT EACH INTERSECTION' BEFORE CONCRETE IS PLACED'. DOWEL COLUMN AND WALL REINFORCING TO FOOTING WITH SAME SIZE AND NUMBER OF DOWELS: AS VERTICAL BARS ABOVE. DOWEL SHALL BE HOOKED ' L AT BOTTOM AND SHALL BE LAPPED 36 BAR DIAMETERS WITH THE COLUMN OR WALL REINFORCING ABOVE. TIMBER NOTES: ALL WOOD MEMBERS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION AND ITS SUPPLEMENT, (NDS), ALL WOOD FOR BEAMS, BEARING' WALLS, SOLE PLATES, TOP PLATES, BLOCKING, BRACING, LEDGERS, CRIPPLES, SILLS, ETC... SHALL BE SOUTHERN PINE NO. 2, KD-15 OR BETTER. MIN (3) 2"x UNDER ALL GIRDER BEARING LOCATIONS. SEE FLOOR PLAID MICRO LAM BEAMS SHALL BE MANUFACTURED BYTRUSAOIST CORP., OR AND APPROVED EQUIVALENT AND SHALL PROVIDE A MODULUS OF ELASTICITY OF 2,000,000, PSI, A MINIMUM FLEXURAL STRENCTH OF 2,925 PSI, AND A MINIMUM HORIZONTAL SHEAR STRESS OF 285 PSI: ALL WOOD IN CONTACTWITH CONCRETE ORCONCRETE BLOCK SHALL NE PRESSURE` TREATED. ACCEPTABLE TREATMENTS INCLUDE ACQ. (AMINE COPPER QUAT) COPPER BORON AZOLE, ACID COPPER CHROMATE, AND COPPER; CITRATE, BORATE BASED TREATMENTS SUCH AS ZINCBORATE AND SODIUM BORATE ARE ALSO ACCEPTABLE FOR INDOOR USES. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT CONTAINS MORE THE 1/2" OF HEARTWOOD AVOID INHALATION OF SAWDUST PRODUCED BY PRESSURE TREATED WOOD, WEAR'A DUST MASK AND WORK OUTDOORS. DISPOSE OF DUST AND SCRAP BY ORDINARY TRASH COLLECTION. DO NOT BURN. PRESSURE' TREATED WOOD MAY PRODUCE TOXIC FUMES. IN HIGHLY CORROSIVE ENVIRONMENTS` ALL WIND RESISTING, HARDWARE INCLUDING THE HURRICANE STRAPS SHALL BE MADE OF STAINLESS -STEEL OR SHALL BE DIPPED (AND SCRATCHES REPAINTED) IN COL -TAR EPDXY PAINT. HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. HANGERS OR STRAPS THAT DO NOT MATCH EXACTLYTO THE ONES SPECIFIED ON THE DRAWINGS IN STEELYIELD OR ULTIMATE STRENGTH, STEEL DIMENSIONS (LENGTH AND WIDTH), NUMBER AND DIAMETER OF HOLES FOR SAME SIZES OF NAILS OR BOLTS, AND/OR DO NOT HAVE THE SAME GENERAL, SHAPE WELL NOT BE ACCEPTABLE. NO POCKETS WILL BE ALLOWED IN CONCRETE OR STEEL MEMBERS FOR CONNECTION OF WOOD MEMBERS UNLESS CONNECTION DETAIL IS IN WRITING` PRIOR TO INSTALLATION'. ALL NAILS, SCREWS, AND BOLTS SHALL BE HOT -DIPPED GALVANIZED. R703.8 FLASHING APPROVED CORROSION RESISTANT FLASHING SHALL BE APPLIED SHINGLE -FASHION IN A MANNER TO PREVENT ENTRY OF WATER INTO THE WALL CAVITY OR PENETRATION OF WATER TOTHE BUILDING STRUCTURAL FRAMING COMPONENTS. SELF -ADHERED MEMBRANES USED AS FLASHING SHALL COMPLY WITH AAMA 711, THE FLASHING SHALL EXTENDTOTHE SURFACE OFTHE EXTERIOR WALL FINISH. APPROVED CORROSION -RESISTANT FLASHING SHALL BE INSTALLED AT ALL OF THE FOLLOWING LOCATIONS: 1. EXTERIOR WINDOW AND DOOR OPENINGS. FLASHINGAT EXTERIOR WINDOW AND DOOR OPENINGS SHALL EXTEND TO THE SURFACE OF THE EXTERIOR WALL FINISH OR TO THE WATER - RESISTIVE BARRIER FOR SUBSEQUENT DRAINAGE. 'FLASHING AT EXTERIOR WINDOW AND DOOR OPENINGS SHALL BE INSTALLED IN ACCORDANCE WITH ONE OR MORE OF THE FOLLOWING OR OTHER APPROVED METHOD: 1.1. THE FENESTRATION MANUFACTURER'S WRITTEN FLASHING` INSTRUCTIONS., 1.2. THE FLASHING MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS. 1.3. IN ACCORDANCE WITH 'FMA/AAMA 100, FMA/AAMA 200, OR FMA/WDMA 250. 1.4. IN ACCORDANCE WITH THE FLASHING METHOD OF A REGISTERED DESIGN PROFESSIONAL. 2. ATTHE INTERSECTION OF CHIMNEYS OR OTHER MASONRY CONSTRUCTION WITH FRAME OR STUCCO WALLS PROJECTING WITH : �.� LIPS ON BOTH SIDES UNDER STUCCO COPINGS. 3. UNDER AND AT THE ENDS OF MASONRY, WOOD OR METAL COPINGS AND SILLS, 4. CONTINUOUSLY ABOVE ALL PROJECTING WOOD TRIM.. 5 WHERE EXTERIOR PORCHES, DECKS OR STAIRS ATTACH TOA WALLOR FLOOR ASSEMBLY OF WOOD', FRAME CONSTRUCTION.. 6. AT WALL AN'D ROOF INTERSECTIONS. 7. AT BUILT-IN GUTTERS. FORMWORK SHORING, AND BRACING FOR ALL CONCRETE BEAMS, C I-lUIVINS, WALLS, AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH A.C;.I 347, "RECOMMENDED PRACTICE FOR CONCRETE FORMWORK". ANY AND ALL PLUMBING PIPE PENETRATIONS THROUGH FORMED VifORK SHOULD BE DONE SO THAT REINFORCING STEEL IS NOT DISRUPTED AND COVER FOR STEEL IS NOT AFFECTED ANY UTILITY PIPES PENETRATING FOOTERS TO BE PROPERLY SLEEVED TO AVOID PIPED UTILITIES FROM BEING SHEARED DURING SETTLEMENT OF STRUCT°I. RE ELECTRICAL PIPES INSIDE OF THE POURED COLUMNS SHALL NOT T:AI<E UP MORE THAN 10% OF THE CROSS -SECTIONAL AREA OF THE COLUMNS AND THEY DO NC T AFFECT THE COVER ON THE REINFORCING STEEL WELDED WIRE MESH: WELDED WIRE MESH SHALL BE ASTM A185, GRADE 65,;FREE FROM OIL, SCALE, AND RUST AND SHALL BE PLACED IN ACCORDANCE WITH ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES, WOODTRUSSES TO BE DESIGNED AND FABRICATED IN ACCORDANCE'WITH THE "NATIONAL DESIGN SPECIFICATIONS FOR SDTRESS-GRADE LUMBER AND IT FASTENINGS" BY NFPA TRUSS DESIGN SHALL COMPLY WITH TPI/WTCABCSI 1-03 "BUILDING COMPONENT SAFETY INFORMATION GUIDE TOGOOD PRACTICE FOR HANDLING, INSTALLING, & BRACING OF METAL PLATE CONNECTED WOODTRUSSES" AND TP11-02 "NATIONAL DESIGN STANDARD FOR METAL -PLATE - CONNECTED WOOD CONSTRUCTION TRUSS DESIGNS SHALL BE SIGNED AND SEALED' RYA PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTES FOR SHOP DRAWINGS. CONNECTOR PLATES SHALL BE A'MINIM'UM THICKNESSOFD.036" AND BE MANUFACTURED FROM STEEL MEETING THE REQUIREMENTS OF ASTM A446, GRADE A AND SHALL BE HOT -DIPPED' GALVANIZED. IN HIGHLY CORROSIVE ENVIRONMENTS, CONNECTOR PLATE AS WELL AS THE HURRICANE STRAPS AND LLTHE NAILS SHALL BE HOT DIPPED GALVANIZED TRIPLE ZINC - OR MADE STAINLESS A NC S 185 COATED OF ST INL STEEL. HANDLING, ERECTION, AND BRACING OF TRUSSES SHALL BE IN, ACCORDANCE WITH TRUSS PLATE INSTITUTE RECOMMENDATIONS. HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. CONNECTORS OR RAPS THAT DO NOT MATCH EXACTLY THE ONES SPECIFIED IN THE DRAWINGS O S STRAPS X N CI REGARDING STEEL YIELD OR ULTIMATE STRENGTH, STEEL GRADE, DIMENSIONS (LENGTH AND WIDTH), NUMBER AND DIAMETER OF HOLES FOR THE SAME SIZES OF NAILS R BOLTS. AND/OR DONUT HAVE M A _ _ ZE O _ / _ _ THESAME GENERALSHA'PE, WILL NOT BE ACCEPTABLE. THE CONTRACTOR i WILL BE RESPONSIBLE FOR KEEPINGTHE ROOF SAFELY IN ,PLACE IN PLACE IN THE EVENT OF HIGH WINDS TRANSIENT LOADING CONDITIONS DURING CONSTRUCTION 'FAILURE TO COMPLY WITH THESE PARAMETER WILL MAKE THE CONTRACTOR SOLELY RESPONSIBLE FOR ANYAND ALL CONSEQUENTIAL DAMAGES CAUSED BT THE HORIZONTAL THRUST DEVELOPED BY THE ROOF FRAMING DUE TO SUPERIMPOSED LOADING AND TRANSFERRED INTO THE BEAMS, WALLS, AND COLU M NS. CONTRACTOR SHALL SUBMIT SIGNED SEALED DRAWINGS OF ALTERNATE CONNECTION DETAILS AT TRUSSES/GIRDERS TOCOLUMNS AND WALLS FORAPPROVAL. THE ENGINEER AND ITS CONSULTANTS OR DESIGN PROFESSIONALS WILL NOT BE RESPONSIBLE FOR ANY DAMAGE CAUSED AS A CONSEQUENCE OF TERMITE INFESTATION, THE LOCATIONS OF GIRDERS AND TRUSSES SHOWN ON THE ROOF FRAMING PLAN WERE USED TO FACILITATE DESIGN OF FOUNDATIONS, WALLS, AND BEAMS. THE CONTRACTORSHALL SUBMIT TRUSS' SHOP DRAWINGS FOR REVIEW BYTHE STRUCTURAL ENGINEER OF RECORD PRIOR TO FABRICATION. THE TRUSS FABRICATOR SHALL PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION PLAN SHOWING COMPONENT' LAYOUT. a) cu 0 c 0 ;r Q L U N 0 4t N w z w Lu w zz w ~O = O oQ op<LU FLI O oz zz O =J OF- O Q Q Q w w Q U o N z U Lu O U U~ J Q Z-100QzUp���j� w Q L = 0� Z Lu c�UOQ�0pcn Lu zwwzQwWO°-Ug Lu UOP��>-��pz�==°- w u(Sz ON DIn _ z z E p - z _ In -'E=WP���z_pLu w <p0 -LupZo Oinz>Ou- In o ww O L wp z 4 �O�� < tNz LU O� Fp �rl IIn o O Luw�O �U Lu In � wV- j � Q � O _ >_ O',Ju - In 0 (D -' Q o�C � Lu :E 0- z � 1 U L U p Q � w 0 0InIn c0 0wf o�zU D In0 C z n Q p U= LuOO z O Luz U z Q z W U lu w U v U� o� 0 O z W Q Q wl_IL�/DQO��ZWL'U In F p= U z p w O w (L/ 0 =n,/ 0- w D w w w= i- Q cn U Z 0 (n p p [D U In I- J U 0 Ui Q E U D LL 0 V U u >1 > CL "> o a� 0 73 LY_ J S_. > D ®I A- U_j L V , 7/5/202 I 10: 1 I :50 PM A-2 Scale 3 S-1 Foundation 3/4" = 1'-0" 2 S-1 1' - 5 7/8" 1' - 4 3/8" co00 2'-6" 7/8" i d °o 1'-31/8" 1'-31/8" 1'-31/8" 1'-31/8" 1'-31/8" 3 3/8" 3 3/f 6' - 10" INTERIORGYP5UM BOARD PURRING OR CHANNEL RIGID INOUL.ATION JOINT REINFORCEMENT CMU BACKLIP LATH (OPTIONAL) LATH FA aTENER . TYPE & SFACING FERABTM C106 MORTAR 5CRATCH COAT MORTAR5E"NG BED ADHERED CONCRETE MASONRY VENEER MORTARJOINT WEEP SCREEP (OPTIONAL) COLUMN & PLANTER TO HAVE APPLIED STONE SEE DETAIL THIS PAGE STUCCO CAP ch --- #5 HORZ. TO 4 CORNERS OF 00 , CLMN FILLED W/3000# CEMENT BEAM BLK W/(1) #5 TIED TO (2) #5 FROM PLANTER SECTION Nco cf 0 , co #5 VERT. TYP. coFILLED W/3000# w CEMENT - , r 2" THICK APPLIED STONE MIN.3000# FIBERMESH CONCRETE nstallation Guide !or A-1hred Manufacturrd Stone Veneer. 51R Edition, I 1 Printing Section 1 1 /2" = 1'-0" 2" Front 1 /2" = 1'-0" I "v , 00 Planter Rebar 2' - #5 HORIZ. TO 2 ADJACENT CORNERS OF CLMN & (2) #5 HORIZ. FROM PLANTER FILLED W/3000# CEMENT r Rebar 2'-8" Grade 0" ndation '% -2' - 4" 1 Foundation -2' - 4" COLUMN & PLANTER TO HAVE APPLIED STONE SEE DETAIL THIS PAGE STUCCO CAP 00- - #5 HORZ. TO 4 CORNERS OF BEAM BLK W/(1) o -- CLMN FILLED W/3000# CEMENT #5 TIED TO (2) #5 #5 FROM PLANTER - STUCCO CAP AROUND SECTION L TOP OF PLANTER d' (2) 1/2" ELECTRICAL _ _ Planter R_ebar PIPES IN CENTER 2' - 811 CAVITY - #5 HORIZ. TO 2 ADJACENT CORNERS OF CLMN & (2) #5 #5 VERT. TYP. ro #5 o HORIZ. FROM PLANTER FILLED FILLED W/3000# #5 W/3000# CEMENT CEMENT Grade 2" THICK — - #5 VERT. TYP. o— Q" APPLIED STONE FILLED W/3000# CEMENT MIN. 3000# 6 45 FIBERMESH d CONCRETE - — r Foundation — -2' - 4„ 5 45 Section 2 1 /2" = 1'-0" to ❑ O Q .L U a� �Oo'oLw O�=Q p p O LU J w 0 z Q= Q Q U Q tj z U v~ O U z F z � Q z�00< 0a-a_0) w~_ w � z 0 Q O z U-Z 0 z620z aw. O p z� Q U g ww��Cw CL.JU UOF�7--°-> I=QpzF==p- w�N�NQ°/c07=N§zzO W H� J�zpu�Qp0 0Nz>OO�Lv-LLJLU w CL �� LL O� T- p� a W a Q 0 o O H O Z N w --IU p 0 z�w z 0 w QO�Uwa �z= zct- Qat-OvU�_z>-2o�LUc9 w 0= w w Q= z p} _ pLL Q 0 0�zcn�pb= O �U"-'wU z Q Q w z U l- Q p W IL W U O z W D w� w�pQO�zzp-wz� p=UF-cy�p�wUS� wcf�U' f� z z �z-cn =� fl. O w w czZ u MIS w= w J F-Q0nppCflU pF- U T) cq O CIO Q D J > 1� v I co V 75 V , U Q �J > D V) D — 7/5/202 1 1 0: 1 2:02 FM ® I Ca I e A5 Indicated