FORM R405-2014
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX' = 74
The lower the EnergyPerformance Index, the more efficient the home.
278 Bermuda Beach Drive, Fort Pierce, FL, 34949
1. New construction or existing Existing(Projecte 9. Wall Types Insulation Area
2. Single family or multiple family Single-family a.Concrete Block-Int Insul,Exterior R=4.2 2244.70 ft2
b.Concrete Block-Int Insul,Adjacent R=4.2 577.33 ft2
3. Number of units,if multiple family 1 c. N/A R= ft2
4. Number of Bedrooms 0 d.N/A R= ft2
5. Is this a worst case? No 10.Ceiling Types Insulation Area a.Roof Deck(Unvented) R=30.0 3029.00 ft2
6. Conditioned floor area(ft2) 3029 b. N/A R= ftZ
7. Windows" Description Area c. R= ft 2
a. U-Factor: Dbl,U=0.66 628.33 ftZ 11•Ductcts R ft
a.Sup:Attic,Ret:Attic,AH:AHU1 6 762
SHGC: SHGC=0.21 b.Sup: Attic,Ret:Attic,AH:AHU2 6 447
b. U-Factor: N/A ft2
SHGC: 12. Cooling systems kBtu/hr Efficiency
c. U-Factor: N/A ft2 a.Central Unit 35.0 SEER:23.00
SHGC: b.Central Unit 22.8 SEER:24.50
d. U-Factor: N/A ft2 13. Heating systems kBtu/hr Efficiency
SHGC: a. Electric Strip Heat 27.3 COP:1.00
Area Weighted Average Overhang Depth: 4.000 ft. b. Electric Strip Heat 17.1 COP:1.00
Area Weighted Average SHGC: 0.210
8. Floor Types Insulation Area 14. Hot water systems Cap: 1 gallons
a.Slab-On-Grade Edge Insulation R=0.0 3029.00 ft2 a.Electric EF:0.99
b.N/A R= ft2
c. N/A R= ft' b. Conservation features
None
15.Credits Pstat
I certify that this home has complied with the Florida Energy Efficiency Code for Building o� SrgT�,
Construction through the above energy saving features which will be installed (or exceeded) O�,
in this home before final inspection. Oth rwise, a new EPL Display Card will be completed �<i3,, = == f�
based on installed Cod o plian tures.
Builder Signature: Date: 5
Address of New ome ' �z�'�c��,G� cV) OV,_ City/FL Zip:Far{ Q{e �/ - �'V �°�}y�
3
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at (321)
638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support
staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
4/12/2017 315 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1
FORM R405-2014
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: Reynolds Residence EG Builder Name:
Street: 278 Bermuda Beach Drive Permit Office:
City,State,Zip: Fort Pierce,FL,34949 Permit Number.
Owner: Reynolds Jurisdiction: St.Lucie County
Design Location: FL,Fort Pierce County:: St.Lucie(Florida Climate Zone 2)
1. New construction or existing Existing(Projecte 9. Wall Types(2822.0 sqft.) Insulation Area
2. Single family or multiple family Single-family a.Concrete Block-Int Insul, Exterior R=4.2 2244.70 ft2
b.Concrete Block-Int Insul,Adjacent R=4.2 577.33 ft2
3. Number of units,if multiple family 1 c.WA R= ft2
4. Number of Bedrooms 0 d.N/A R= ft2
5. Is this a worst case? No 10.Ceiling Types (3029.0 sqft.) Insulation Area a.Roof Deck(Unvented) R=30.0 3029.00 ft2
6. Conditioned floor area above grade(ft2) 3029 b.N/A R= ft2
Conditioned floor area below grade(ft2) 0 c.11.Duct
R= ft2
s R ft2
7. Windows(628.3 sqft.) Description Area a.Sup:Attic,Ret:Attic,AH:AHU1 6 762
a. U-Factor. Dbl,U=0.66 628.33 ft2 b.Sup: Attic,Ret:Attic,AK AHU2 6 447
SHGC: SHGC=0.21
b. U-Factor. N/A ft2 12.Cooling systems kBtu/hr Efficiency
SHGC: a.Central Unit 35.0 SEER:23.00
b.Central Unit 22.8 SEER:24.50
c. U-Factor N/A ft2
SHGC: 13.Heating systems kBtulhr Efficiency
d. U-Factor: N/A ft2 a.Electric Strip Heat 27.3 COPA.00
SHGC: b.Electric Strip Heat 17.1 COPA.00
Area Weighted Average Overhang Depth: 4.000 ft.
Area Weighted Average SHGC: 0.210 14.Hot water systems
ns
8. Floor Types (3029.0 sqft.) Insulation Area a.Electric Tankless Cap: 1 galb
EF:0.99090
a.Slab-On-Grade Edge Insulation R=0.0 3029.00 ft2 b. Conservation features
b.WA R= ft2 None
c.N/A R= ft2 15.Credits Pstat
Glass/Floor Area: 0.207 Total Proposed Modified Loads: 66.20 PASS
Total Baseline Loads: 89.67
1 hereby certify that the plans and specifications covered by Review of the plans and 0�� gTt�
this calculation are in compliance with the Florida Energy specifications covered by this ♦+g; _ p� ,
Code- Digitally calculation indicates compliance - = .�
Thomas Platania p ys t.
Platania CAC1815254 with the Florida Energy Code. �' y.,,._:;, �••,: -` `'':,•��„ O
CAC 181 25�#"'�' Date:2017.04.12 15:2207.04'00
PREPARED BY: Before construction is completed v l
DATE: this building will be inspected for € s
compliance with Section 553.908
Florida Statutes. •rti
I hereby certify that thi �ing, designed,is in compliance �caa
with the Florida Energy �00 WE ,
OWNER/AGEN BUILDING OFFICIAL: -_-
DATE: DATE.-
Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.2.2.1.
Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage
test report in accordance with R402.4.1.2.
Compliance requires a roof absorptance test and a roof emittance test in accordance with R405.7.2
4/12/2017 3:15 PM EnergyGaugeO USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 7
FORM R405-2014
PROJECT
Title: Reynolds Residence EG Bedrooms: 0 Address Type: Street Address
A Building Type: User Conditioned Area: 3029 Lot#
Owner: Reynolds Total Stories: 1 Block/SubDivision:
#of Units: 1 Worst Case: No PlatBook:
Builder Name: Rotate Angle: 90 Street: 278 Bermuda Beach Dri
Permit Office: Cross Ventilation: No County: St.Lucie
Jurisdiction: St.Lucie County Whole House Fan: No City,State,Zip: Fort Pierce,
Family Type: Single-family FL, 34949
New/Existing: Existing(Projected)
Comment:
CLIMATE
IECC Design Temp Int Design Temp Heating Design Daily Temp
v Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,Fort Pierce FL_VERO_BEACH_MUNI 2 39 90 70 75 299 62 Low
BLOCKS
Number Name Area Volume
1 AHU-1 Main Area 1909 15272
2 AHU-2 Master 1120 8960
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated
1 Exist Bedroom 1 252 2016 No 0 1 Yes Yes Yes
2 Bath 1 52 416 No 0 1 Yes Yes Yes
3 Clos 1 36 288 No 0 1 Yes Yes Yes
4 Laundry 113 904 No 0 1 Yes Yes Yes
5 Hall 81 648 No 0 1 Yes Yes Yes
6 Bath 2 56 448 No 0 1 Yes Yes Yes
7 Clos 2 25 200 No 0 1 Yes Yes Yes
8 Exist Bedroom 2 161 1288 No 0 1 Yes Yes Yes
9 Kitchen 378 3024 Yes 1 1 Yes Yes Yes
10 AHU2 12 96 No 0 1 Yes Yes Yes
11 Exist Great Room 743 5944 No 3 1 Yes Yes Yes
12 Master Bedroom 279 2232 No 0 1 Yes Yes Yes
13 Master Bath 298 2384 No 0 1 Yes Yes Yes
14 Master WIC 148 1184 No 0 1 Yes Yes Yes
15 Hall Clos 12 96 No 0 1 Yes Yes Yes
16 Exist Study 211 1688 No 0 1 Yes Yes Yes
17 AHU1 9 72 No 0 1 Yes Yes Yes
18 Study Clos 18 144 No 0 1 Yes Yes Yes
19 WC 27 216 No 0 1 Yes Yes Yes
20 Hall 118 944 No 0 1 Yes Yes Yes
4/12/2017 3:15 PM EnergyGaugeO USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 7
FORM R405-2014
FLOORS
# Floor Type Space Perimeter Perimeter R-Value Area Joist R Value Tile Wood Carpet
1 Slab-On-Grade Edge Insulatio Exist Bedroom 1 45.4 ft 0 252 ft2 _ 1 0 0
2 Slab-On-Grade Edge Insulatio Bath 1 1 ft 0 52 ft2 _ 1 0 0
3 Slab-On-Grade Edge Insulatio Clos 1 5.8 ft 0 36 ft2 _ 1 0 0
4 Slab-On-Grade Edge Insulatio Laundry 10.9 ft 0 113 ft2 _ 1 0 0
5 Slab-On-Grade Edge Insulatio Hall 2 1 ft 0 81 ft2 _ 1 0 0
6 Slab-On-Grade Edge Insulatio Bath 2 1 ft 0 56 ft2 _ 1 0 0
7 Slab-On-Grade Edge Insulatio Clos 2 1 ft 0 25 ftZ _ 1 0 0
8 Slab-On-Grade Edge Insulatio Exist Bedroom 2 27.3 It 0 161 ft2 _ 1 0 0
9 Slab-On-Grade Edge Insulatio Kitchen 20.4 ft 0 378 ft2 _ 1 0 0
10SIab-On-Grade Edge Insulatio AHU2 2.8 ft 0 12 ft2 _ 1 0 0
11Slab-On-Grade Edge Insulatio Exist Great Room 62.2 ft 0 743 ft2 _ 1 0 0
12SIab-On-Grade Edge Insulatio Master Bedroom 11.6 ft 0 279 ft2 _ 1 0 0
13SIab-On-Grade Edge Insulatio Master Bath 44.8 ft 0 298 ft2 _ 1 0 0
14SIab-On-Grade Edge Insulatio Master WIC 6.9 ft 0 148 ft2 — 1 0 0
15SIab-On-Grade Edge Insulatio Hall Clos 8 It 0 12 ft2 — 1 0 0
16SIab-On-Grade Edge Insulatio Exist Study 29.1 ft 0 211 ft2 _ 1 0 0
17SIab-On-Grade Edge Insulatio AHU1 1 ft 0 9 ft2 _ 1 0 0
18SIab-On-Grade Edge Insulatio Study Clos 1 ft 0 18 ft2 _ 1 0 0
19SIab-On-Grade Edge Insulatio WC 4 ft 0 27 ft2 _ 1 0 0
20SIab-On-Grade Edge Insulatio Hall 1 1 ft 0 118 ft2 _ 1 0 0
ROOF
Roof Gable Roof Solar SA Emitt Emitt Deck Pitch
# Type Materials Area Area Color Absor. Tested Tested Insul. (deg)
1 Hip Metal 3122 ft2 0 ft2 Unfinishe 0.35 Yes 0.4 Yes 30 14
/ ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Unvented 0 3029 ft2 N N
4/12/2017 3:15 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 olt 7
FORM R405-2014
CEILING
# Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type
1 Under Attic(Unvented) Exist Bedroom 1 0 Blown 252 ft2 0.11 Wood
2 Under Attic(Unvented) Bath 1 0 Blown 52 ft2 0.11 Wood
3 Under Attic(Unvented) Clos 1 0 Blown 36 ft2 0.11 Wood
4 Under Attic(Unvented) Laundry 0 Blown 113 ft2 0.11 Wood
5 Under Attic(Unvented) Hall 2 0 Blown 81 ft2 0.11 Wood
6 Under Attic(Unvented) Bath 2 0 Blown 56 ft2 0.11 Wood
7 Under Attic(Unvented) Clos 2 0 Blown 25 ft2 0.11 Wood
8 Under Attic(Unvented) Exist Bedroom 2 0 Blown 161 ft2 0.11 Wood
9 Under Attic(Unvented) Kitchen 0 Blown 378 ft2 0.11 Wood
10 Under Attic(Unvented) AHU2 0 Blown 12 ft2 0.11 Wood
11 Under Attic(Unvented) Exist Great Room 0 Blown 743 ft2 0.11 Wood
12 Under Attic(Unvented) Master Bedroom 0 Blown 279 ftz 0.11 Wood
13 Under Attic(Unvented) Master Bath 0 Blown 298 ft2 0.11 Wood
14 Under Attic(Unvented) Master WIC 0 Blown 148 ft2 0.11 Wood
15 Under Attic(Unvented) Hall Clos 0 Blown 12 ft2 0.11 Wood
16 Under Attic(Unvented) Exist Study 0 Blown 211 ft2 0.11 Wood
17 Under Attic(Unvented) AHU1 0 Blown 9 ftZ 0.11 Wood
18 Under Attic(Unvented) Study Clos 0 Blown 18 ft2 0.11 Wood
19 Under Attic(Unvented) WC 0 Blown 27 ft2 0.11 Wood
20 Under Attic(Unvented) Hall 1 0 Blown 118 ft2 0.11 Wood
WALLS
Adjacent Space Cavity Width Height Sheathing Framing Solar Below
o
_ 1 SE=>SW Exterior Concrete Block-Int lnstHxist Bedroo 4.2 13 3 8 0 106.0 ft2 0 0 0.5 0
2 SW=>N Exterior Concrete Block-Int lnstHxist Bedroo 4.2 19 0 8 0 152.0 ft2 0 0 0.5 0
3 NW=>NE Exterior Concrete Block-Int InsiHxist Bedroo 4.2 13 3 8 0 106.0 ft2 0 0 0.5 0
4 SE=>SW Exterior Concrete Block-Int Insul Clos 1 4.2 5 10 8 0 46.7 ft2 0 0 0.5 0
5 SE=>SW Exterior Concrete Block-Int Insul Laundry 4.2 11 0 8 0 88.0 ft2 0 0 0.5 0
_6 NE=>SE Garage Concrete Block-Int Insul Laundry 4.2 12 1 8 0 96.7 ft2 0 0 0.5 0
7 SE=>SW Garage Concrete Block-Int Insul Hall 2 4.2 4 6 8 0 36.0 ft2 0 0 0.5 0
8 SE=>SW Garage Concrete Block-Int Insul Bath 2 4.2 5 10 8 0 46.7 ft2 0 0 0.5 0
9 SE=>SW Garage Concrete Block-Int Insul Clos 2 4.2 2 6 8 0 20.0 ft2 0 0 0.5 0
10 NE=>SE Exterior Concrete Block-Int InsiHxist Bedroo 4.2 13 6 8 0 108.0 ft2 0 0 0.5 0
11 NW=>NE Exterior Concrete Block-Int InsiHxist Bedroo 4.2 13 11 8 0 111.3 ft2 0 0 0.5 0
12 SE=>SW Garage Concrete Block-Int InsiHxist Bedroo 4.2 11 5 8 0 91.3 ft2 0 0 0.5 0
13 NE=>SE Exterior Concrete Block-Int Insul Kitchen 4.2 3 4 8 0 26.7 ft2 0 0 0.5 0
14 SW=>N Exterior Concrete Block-Int Insul Kitchen 4.2 13 6 8 0 108.0 ft2 0 0 0.5 0
15 NW=>NE Exterior Concrete Block-Int Insul Kitchen 4.2 3 7 8 0 28.7 ft2 0 0 0.5 0
16 NE=>SE Exterior Concrete Block-Int Insul AHU2 4.2 2 11 8 0 23.3 ft2 0 0 0.5 0
17 E=>S Exterior Concrete Block-Int Ins&dst Great R 4.2 18 9 8 0 150.0 ft2 0 0 0.5 0
18 SW=>N Exterior Concrete Block-Int Ins&bdst Great R 4.2 3 10 8 0 30.7 ft2 0 0 0.5 0
19 W=>N Exterior Concrete Block-Int Ins&bcist Great R 4.2 34 6 8 0 276.0 ft2 0 0 0.5 0
_20 NW=>NE Exterior Concrete Block-Int Insbbdst Great R 4.2 5 2 8 0 41.3 ft2 0 0 0.5 0
4/12/2017 3:15 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 7
FORM R405-2014
WALLS
Adjacent Io Space Cavity Width Height Sheathing Framing Solar Below Wall Type
_21 NW=>NE Exterior Concrete Block-Int InsMaster Bedro 4.2 11 8 8 0 93.3 ft2 0 0 0.5 0
22 NE=>SE Exterior Concrete Block-Int InstlNaster Bath 4.2 15 8 8 0 125.3 ft2 0 0 0.5 0
23 SW=>N Exterior Concrete Block-Int InsdNaster Bath 4.2 9 5 8 0 75.3 ft2 0 0 0.5 0
24 NW=>NE Exterior Concrete Block-Int InstMaster Bath 4.2 19 9 8 0 158.0 ft2 0 0 0.5 0
25 NE=>SE Exterior Concrete Block-Int InstMaster WIC 4.2 6 11 8 0 55.3 ft2 0 0 0.5 0
26 SE=>SW Garage Concrete Block-Int InstMaster WIC 4.2 12 1 8 0 96.7 ft2 0 0 0.5 0
27 SE=>SW Exterior Concrete Block-Int Insul Hall Clos 4.2 6 3 8 0 50.0 ft2 0 0 0.5 0
28 SW=>N Exterior Concrete Block-Int Insul Hall Clos 4.2 1 10 8 0 14.7 ft2 0 0 0.5 0
_29 SE=>SW Exterior Concrete Block-Int InsuExist Study 4.2 13 8 8 0 109.3 ft2 0 0 0.5 0
30 SW=>N Exterior Concrete Block-Int InsuExist Study 4.2 15 5 8 0 123.3 ft2 0 0 0.5 0
31 NE=>SE Garage Concrete Block-Int InsuExist Study 4.2 15 0 8 0 120.0 ft2 0 0 0.5 0
32 SW=>N Exterior Concrete Block-Int Insu6tudy Clos 4.2 0 8 8 0 5.3 ft2 0 0 0.5 0
33 NE=>SE Exterior Concrete Block-Int Insul WC 4.2 4 0 8 0 32.0 ft2 0 0 0.5 0
_34 NE=>SE Garage Concrete Block-Int Insul Hall 1 4.2 8 9 8 0 70.0 ft2 0 0 0.5 0
DOORS
# Omt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 E=>S Wood Exist Great R None .39 3 8 24 ft2
2 NE=>SE Wood Hall 1 None .46 2 10 7 19.8 ft2
3 SE=>SW Wood Hall 2 None .46 2 10 7 19.8 ft2
WINDOWS
Orientation shown is the entered orientation => changed to As Built rotated 90 degrees).
Wall Overhang
V/ # Omt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening
1 SW=>NW 2 TIM Low-E Double Yes 0.66 0.21 50.0 ft2 4 ft 0 in 0 ft 8 in Drapes/blinds None
2 NW=>NE 3 TIM Low-E Double Yes 0.66 0.21 20.0 ft2 4 ft 0 in 0 ft 8 in Drapes/blinds None
3 NE=>SE 10 TIM Low-E Double Yes 0.66 0.21 13.0 ft2 4 ft 0 in 0 ft 8 in Drapes/blinds None
4 NW=>NE11 TIM Low-E Double Yes 0.66 0.21 6.5 ft2 4 ft 0 in 0 ft 8 in Drapes/blinds None
5 SW=>NW14 TIM Low-E Double Yes 0.66 0.21 48.7 ft2 4 ft 0 in 0 ft 8 in Drapes/blinds None
6 E=>S 17 TIM Low-E Double Yes 0.66 0.21 40.0 ft2 4 ft 0 in 0 ft 8 in Drapes/blinds None
7 E=>S 17 TIM Low-E Double Yes 0.66 0.21 24.0 ft2 4 ft 0 in 1 ft 9 in Drapes/blinds None
8 W=>N 19 TIM Low-E Double Yes 0.66 0.21 26.0 ft2 4 ft 0 in 0 ft 8 in Drapes/blinds None
9 W=>N 19 TIM Low-E Double Yes 0.66 0.21 43.8 ft2 4 ft 0 in 0 ft 8 in Drapes/blinds None
10 W=>N 19 TIM Low-E Double Yes 0.66 0.21 100.0 ft2 4 ft 0 in 2 ft 1 in Drapes/blinds None
11 W=>N 19 TIM Low-E Double Yes 0.66 0.21 100.0 ft2 4 ft 0 in 3 ft 6 in Drapes/blinds None
12 NW=>NE20 TIM Low-E Double Yes 0.66 0.21 2.7 ft2 4 ft 0 in 0 ft 8 in Drapes/blinds None
13 NW=>NE20 TIM Low-E Double Yes 0.66 0.21 24.0 ft2 4 ft 0 in 0 ft 11 in Drapes/blinds None
14 NW=>NE21 TIM Low-E Double Yes 0.66 0.21 40.0 ft2 4 ft 0 in 0 ft 8 in Drapes/blinds None
15 NW=>NE24 TIM Low-E Double Yes 0.66 0.21 35.0 ft2 4 ft 0 in 0 It 8 in Drapes/blinds None
16 NW=>NE24 TIM Low-E Double Yes 0.66 0.21 35.6 ft2 4 ft 0 in 0 ft 8 in Drapes/blinds None
17 SE=>SW29 TIM Low-E Double Yes 0.66 0.21 13.0 ft2 4 ft 0 in 0 It 8 in Drapes/blinds None
18 SW=>NW30 TIM Low-E Double Yes 0.66 0.21 6.1 ft2 4 ft 0 in 0 ft 8 in Drapes/blinds None
4/12/2017 3:15 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 7
FORM R405-2014
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation
1 577.2 ft2 577.2 ft2 72 ft 8 ft 1
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000254 2019.3 110.86 208.49 .1855 5
HEATING SYSTEM
# System Type Subtype Efficiency Capacity Block Duds
1 Electric Strip Heat None COP:1 27.3 kBtu/hr 1 sys#1
2 Electric Strip Heat None COP:1 17.06 kBtu/hr 2 sys#2
COOLING SYSTEM
# System Type Subtype Efficiency Capacity Air Flow SHR Block Duds
1 Central Unit Split SEER:23 35 kBtu/hr 1167 cfrn 0.8 1 sys#1
2 Central Unit Split SEER:24.5 22.8 kBtu/hr 760 cfm 0.8 2 sys#2
HOT WATER SYSTEM
# System Type SubType Location EF Cap Use SetPnt Conservation
1 Electric Tankless Laundry 0.99 1 gal 55.1 gal 120 deg None
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
None None ft2
DUCTS
—Supply— —Return— Air CFM 25 CFM25 HVAC#
V # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool
1 Attic 6 762 ft2 Attic 762 ft2 Default Leakage AHU1 (Default) (Default) 1 1
2 Attic 6 447 ft2 Attic 447 ft2 Default Leakage AHU2 (Default) (Default) 2 2
4/12/2017 3:15 PM Ene Ga e®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 6 of 7
rgY u9 P 9
FORM R405-2014
TEMPERATURES
Programable Thermostat:Y Ceiling Fans:
Cooling Jan Feb [r]Mar f Apr I Ma rl Jun X Jul X Au rl
Se r Oct N
Nov Dec
Heating [X]Jan Feb l�J Mar AP
May Jun 4 Jul 4 Au Sep Oct Nov Dec
Venti [[ ]]Jan Feb [X]Mar A r May Jun [ Jul [ Aug Se Oct Nov Dec
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
4/12/2017 3:15 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 7 of 7
FORM R405-2014
Florida Department of Business and Professional Regulations
Residential Whole Building Performance and Prescriptive Methods
R ADD ESS 278 Bermuda Beach Drive Permit Number:
Fort Pierce, FL,34949
MANDATORY REQUIREMENTS See individual code sections for full details.
401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
[Section 553.9085, Florida Statues]requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate compliance for the building.A copy of the EPL display card can be found in Appendix C.
R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.1 through R402.4.4.
O R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The
sealing methods between dissimilar materials shall allow for differential expansion and contraction.
• R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in
accordance with the manufacturers instructions and the criteria listed in Table 402.4.1.1,as applicable to the method of construction.
Where required by the code official,an approved third party shall inspect all components and verify compliance.
• R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air
changes per hour in Climate Zones 1 and 2,and 3 air changes per hour in Climate Zones 3 through 8.Testing shall be conducted with
a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Where required by the code official,testing shall be conducted by an
approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors,fireplace and stove doors shall be closed, but not sealed,beyond the intended weatherstripping or
other infiltration control measures,
2.Dampers including exhaust, intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended
infiltration control measures,
3.Interior doors,if installed at the time of the test,shall be open;
4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed,
5. Heating and cooling systems,if installed at the time of the test,shall be turned off,and
6.Supply and return registers,if installed at the time of the test,shall be fully open.
O R402.4.2 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air.
O R402.4.3 Fenestration air leakage.Windows,skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
per square foot(1.5 Us/m2),and swinging doors no more than 0.5 cfm per square foot(2.6 Us/m2),when tested according to NFRC 400 or
AAMAANDMA/CSA 101/I.S.2/A440 by an accredited,independent laboratory and listed and labeled by the manufacturer.
Exception: Site-built windows,skylights and doors.
O R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not
more than 2.0 cfm(0.944 L/s)when tested in accordance with ASTM E 283 at a 1.57 psf(75 Pa)pressure differential.All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
O R403.1.1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
0 R403.1.3 Heat pump supplementary heat(Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls
that,except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load.
R403.2.2 Sealing(Mandatory)AII ducts,air handlers,and filter boxes and building cavities that form the primary air containment
passageways for air distribution systems shall be considered ducts and plenum chambers,shall be constructed and sealed in accordance
with Section C403.2.7.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post-construction
or rough-in testing below.
Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section
553.99,Florida Statutes, or as authorized by Florida Statutes,to be"substantially leak free"by either of the following:
1. Post-construction test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area
when tested at a pressure differential of 0.1 inches w.g.(25 Pa)across the entire system, including the manufacturer's air handler enclosure.All
register boots shall be taped or otherwise sealed during the test.
2. Rough-in test:Total leakage shall be less than or equal to 4 cfm(113 L/min)per 100 square feet(9.29 m2)of conditioned floor area when tested
at a pressure differential of 0.1 inches w.g. (25Pa)across the system,including the manufacturer's air handler enclosure.All registers shall be
taped or otherwise sealed during the test. If the air handler is not installed at the time of the test,total leakage shall be less than or equal to 3 cfm
(85 L/min)per 100 square feet(9.29 m2)of conditioned floor area.
Exceptions:
1. The total leakage test is not required for ducts and air handlers located entirely within the building envelope.
2. Duct testing is not mandatory for buildings complying by Section R405 of this code.
4/12/2017 3:15 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Com Page 1 of 3
FORM R405-2014
MANDATORY REQUIREMENTS - (Continued)
❑ R403.2.3 Building Cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums.
❑ R403.3 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105'F(41'C)
or below 55"F(1YC)shall be insulated to a minimum of R-3.,
R403.3.1 Protection of piping insulation.
❑ R403.4.1 Circulating hot water systems(Mandatory). Circulating hot water systems shall be provided with an automatic or readily
accessible manual switch that can turn off the hot-water circulating pump when the system is not in use.
❑ R403.4.3 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3'/z inches(89 mm)in the hot water distribution line and cold water line located as close as possible
to the storage tank.
❑ R403.4.4 Water heater efficiencies(Mandatory).
O R403.4.4.1 Storage water heater temperature controls
R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls
capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum
temperature setting range shall be from 100°F to 140"F(38'C to 60"C).
R403.4.4.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied
to electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s)
of combustion types of service water heating systems to be turned off.
O R403.4.4.2 Water heating equipment Water heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation,Commercial Provisions,for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water
heating category. Solar water heaters shall met the criteria Section R403.4.42.1.
R403.4.4.2.1 Solar water heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors,
and SRCC Standard TM-1,Solar Domestic Hot Water System and Component Test Protocol,Collectors in installed solar water
heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal,and
2. Be installed at an orientation within 45 degrees of true south.
❑ R403.5 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code,Residential or Florida Building Code.Mechanical,as applicable,or with other approved means of ventilation.
Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating.
•❑ R403.6 Heating and cooling equipment(Mandatory). The following sections are mandatory for cooling and heating equipment.
O R403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies,
based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and
indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1.This code does not allow designer safety factors,provisions for future expansion or other factors
which affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation
such as standard kitchen and bathroom exhaust systems.
• R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the
calculated total load, but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section 403.6,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
4/12/2017 3:15 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Com Page 2 of 3
FORM R405-2014
MANDATORY REQUIREMENTS - (Continued)
O R403.6.1.1 Cooling equipment capacity.(continued) The published value for AHRI total capacity is a nominal, rating-test value and
shall not be used for equipment sizing.Manufacture's expanded performance data shall be used to select cooling-only equipment.This
selection shall be used to select cooling-only equipment. This selection shall be based on the outdoor design dry bulb temperature for the
load calculation(or entering water temperature for water-source equipment),the blower cfm provided by the expanded performance data,
the design value for entering wet bulb temperature and the design value for entering dry bulb temperature.
Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space.
Exceptions
1. Attached single-and multi-family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2. When signed and sealed by a Florida-registered engineer, in attached single-and multi-family units,the capacity of
equipment may be sized in accordance with good design practice.
O R403.6.1.2 Heating equipment capacity
R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section
R403.6.1.1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load.
R403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.6.1.
R403.6.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.6.1.
O R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis,such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
❑ R403.7 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections
C403 and C404 of the Commercial Provisions in lieu of Section R403.
❑ R403.8 Snow melt system controls(Mandatory). Snow and ice-melting systems, supplied through energy service to the building, shall
include automatic controls capable of shutting off the system when the pavement temperature is above 55'F,and no precipitation is falling
and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40'F.
❑ R403.9 Swimming pools, inground spas and portable spas(Mandatory). The energy requirements for residential pools and
inground spas shall be as specified in Sections R403.9.1 through R403.9.3 and in accordance with ANSI/APSP-15. The energy
requirements for portable spas shall be in accordance with ANSI/APSP-14.
O R403.9.1 Pool and spa heaters. All pool heaters shall be equipped with a readily accessible on-off switch that is mounted
outside the heater to allow shutting off the heater without adjusting the thermostat setting.
R403.9.1.1 Gas and oil-fired pool and spa heaters. All gas-and oil-fired pool and space heaters shall have a minimum
thermal efficiency of 82 percent for heaters manufactured on or after April 16,2013 when tested in accordance with ANSI Z 21.56.
Pool heaters fired by natural gas or LP gas shall not have continuously burning pilot lights.
R403.9.1.2 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160,Table 2, Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is
required to verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard.
O R403.9.2 Time switches. Time switches or other control method that can automatically turn off and on heaters and pumps according to a
preset schedule shall be installed on all heaters and pumps.Heaters,pumps and motors that have built in timers shall be deemed in
compliance with this equipment.
Exceptions:
• 1. Where public health standards require 24-hour pump operations.
2. Where pumps are required to operate solar-and waste-heat-recovery pool heating systems.
3. Where pumps are powered exclusively from on-site renewable generation.
O R403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor-retardant cover on or
at the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Outdoor pools deriving over 70 percent of the energy for heating from site-recovered energy,such as a heat pump or
solar energy source computed over an operating season.
❑ RR404.1 Lighting equipment(Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be
high-efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps.
Exception: Low-voltage lighting shall not be required to utilize high-efficacy lamps.
O R404.1.1 Lighting equipment(Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights
❑ R405.2 Performance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated to a minimum of R-6.
O R405.2.1 Performance ONLY. Ceilings shall have minimum insulation of R-19.Where single assemby of the exposed deck and beam type or
concrete deck roofs do not have sufficent space, R-10 is allowed.
4/12/2017 3:15 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Com Page 3 of 3
FORM R405-2014
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Reynolds Residence EG Builder Name:
Street: 278 Bermuda Beach Drive Permit Office:
City,State,Zip: Fort Pierce,FL,34949 Permit Number:
Owner: Reynolds Jurisdiction: St. Lucie County
Design Location: FL, Fort Pierce
COMPONENT CRITERIA CHECK
Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope.
Exterior thermal envelope contains a continuous barrier.
Breaks or joints in the air barrier shall be sealed-
Air-permeable insulation shall not be used as a sealing material.
Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the
insulation and any gaps in the air barrier shall be sealed.
Access openings, drop down stairs or knee wall doors to unconditioned
attic spaces shall be sealed.
Corners and headers shall be insulated and the junction of the foundation
Walls and sill plate shall be sealed.
The junction of the top plate and the top or exterior walls shall be sealed.
Exterior thermal envelope insulation for framed walls shall be installed in
substantial contact and continuous alignment with the air barrier.
Knee walls shall be sealed.
Windows, skylights and doors The space between window/doorjambs and framing and skylights and
framing shall be sealed.
Rim joists Rim joists are insulated and include an air barrier.
Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside
and cantilevered floors) of subfloor decking.
The air barrier shall be installed at any exposed edge of insulation.
Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently
attached to the crawlspace walls.
Exposed earth in unvented crawl spaces shall be covered with a Class I
vapor retarder with overlapping joints taped.
Shafts, penetrations Duct shafts, utility penetrations, and flue shaft openings to exterior or
unconditioned space shall be sealed.
Narrow cavities Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled
by insulation that on installation readily conforms to the available cavity
spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spaces.
Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be
air tight, IC rated, and sealed to the drywall.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in
exterior walls, or insulation that on installation readily conforms to available
space shall extend behind piping and wiring.
Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air
barrier installed separating them from the showers and tubs.
Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or
air sealed boxes shall be installed.
HVAC register boots HVAC register boots that penetrate building thermal envelope shall be
sealed to the sub-floor or drywall.
Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have
gasketed doors
4/12/2017 3:16 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1
Load Short Form Job: Reynolds Residence Re...
��0 �n��' Digitally signed Thomas Date: April 12,2017
_..w�. Thomas Platania g y g �r
we are tee .isrfrrg piece' AHU-1 Main Area Platania CAC By: Scott Pingleton
ProCalcs, LLC
CAC1815254 Date:�017_04121521• -04•
�-���
P.O.Box 882032,Port Saint Lucie, FL 34988 Phone.772-882-5700 Email:tom@procalcs.net Web.www.ProCalcs.Net License:CAC)615254 RTIN#0105474
Project Information
For: Reynolds
278 Bermuda Beach Drive, Fort Pierce, FL 34949
Design Information
Htg clg Infiltration
Outside db (°F) 42 90 Method Simplified
Inside db (°F) 70 75 Construction quality Semi-loose
Design TD (°F) 28 15 Fireplaces 0
Daily range - L
Inside humidity (%) 50 50
Moisture difference(gr/lb) 23 61
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Lennox
Trade Trade LENNOX
Model Cond XC25-036-230-**
AHRI ref Coil CBX40UHV-036*++TDR
AHRI ref 5947286
Efficiency 100 EFF Efficiency 14.0 EER, 23 SEER
Heating input 8.0 kW Sensible cooling 28000 Btuh
Heating output 27297 Btuh Latent cooling 7000 Btuh
Temperature rise 47 °F Total cooling 35000 Btuh
Actual air flow 525 cfm Actual air flow 1167 cfm
Air flow factor 0.019 cfm/Btuh Air flow factor 0.042 cfm/Btuh
Static pressure 0.60 in H2O Static pressure 0.60 in H2O
Space thermostat Load sensible heat ratio 0.84
ROOM NAME Area Htg load Clg load HtgAVF CIgAVF
(ft2) (Btuh) (Btuh) (cfm) (cfm)
Exist Bedroom 1 252 5754 3127 111 130
Bath 1 52 68 48 1 2
Clos 1 36 594 164 11 7
Laundry 113 1182 890 23 37
Hall 2 81 107 76 2 3
Bath 2 56 74 53 1 2
Clos 2 25 33 24 1 1
Exist Bedroom 2 161 3113 1238 60 51
Kitchen 378 3214 4323 62 180
AHU 2 12 287 76 6 3
Exist Great Room 746 12882 18038 248 750
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wri htsoft 2017-Apr-1215:13:34
9 Right-Suite60 Universal 2017 17.0.21 RSU23702 Page 1
...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
AHLI-1 Main Area 1911 27308 28058 525 1167
Other equip loads 0 0
Equip. @ 1.00 RSM 28058
Latent cooling 5454
TOTALS 1911 27308 33513 525 1167
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wri htsoft 2017-Apr-1215:13:34
9 Right-SuiteQ Universal 2017 17.0.21 RSU23702 Page 2
._s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
i
Load Short Form Job: Reynolds Residence Re...
/�H[/I, Date: April 12,2017
A
w�.�,.m�•m�==��q r,=a• -2 Master By: Scott Pingleton
ProCalcs, LLC
P.O.Box 882032,Port Saint Lucie,FL 34988 Phone:772-882-5700 Email tom(gDprocalcs.net Web:www.ProCalcs.Net License:CAC1815254 RTIN#0105474
Project
• Information
For: Reynolds
278 Bermuda Beach Drive, Fort Pierce, FL 34949
-- Design Information
Htg Clg Infiltration
Outside db (°F) 42 90 Method Simplified
Inside db (°F) 70 75 Construction quality Semi-loose
Design TD (°F) 28 15 Fireplaces 0
Daily range - L
Inside humidity (%) 50 50
Moisture difference (gr/lb) 23 61
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Lennox
Trade Trade LENNOX
Model Cond XC25-024-230-02
AHRI ref Coil CBX32MV-024/030"++TDR
AHRI ref 7042645
Efficiency 100 EFF Efficiency 16.0 EER, 24.5 SEER
Heating input 5.0 kW Sensible cooling 18240 Btuh
Heating output 17061 Btuh Latent cooling 4560 Btuh
Temperature rise 58 °F Total cooling 22800 Btuh
Actual air flow 269 cfm Actual air flow 760 cfm
Air flow factor 0.018 cfm/Btuh Air flow factor 0.044 cfm/Btuh
Static pressure 0.60 in H2O Static pressure 0.60 in H2O
Space thermostat Load sensible heat ratio 0.86
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ftz) (Btuh) (Btuh) (cfm) (cfm)
Master Bedroom 279 2128 3941 38 175
Master Bath 298 5802 5860 104 260
Master WIC 148 1289 1585 23 70
Hall Clos 12 779 191 14 8
Exist Study 211 3897 3536 70 157
AHU 1 9 11 8 0 0
Study Clos 18 89 86 2 4
WC 27 416 340 7 15
Hall 1 118 622 1583 11 70
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wri htsoft 2017-Apr-1215:13:34
9 Right-SuiteO Universal 2017 17.0.21 RSU23702 Page 3
...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces_ E
AHU-2 Master 1119 15034 17131 269 760
Other equip loads 0 0
Equip. @ 1.00 RSM 17131
Latent cooling 2747
TOTALS 1119 15034 19877 269 760
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wri htsoft 2017-Apr-12 15: ge 4
- 9 Right-SuiteQ�Universal 2017 17.0.21 RSU23702 Page 4
.-- ...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
BuildingAnalysis Job: Reynolds Residence Re
TF y Date: April 12,2017
AHU-1 Main Area Scott Pin y= s
B leton
We are the missing piece'
ProCalcs, LLC
P.O.Box 882032,Port Saint Lucie.FL 34988 Phone:772-882-5700 Email:tomrgprocalcs.net Web:www.ProCalcs.Nel License:CAC1815254 RTIN#0105474
Project
. • • •
For: Reynolds
278 Bermuda Beach Drive, Fort Pierce, FL 34949
Design Conditions
Location: Indoor: Heating Cooling
Fort Pierce, FL, US Indoor temperature(°F) 70 75
Elevation: 25 ft Design TD (T) 28 15
Latitude: 270N Relative humidity (%) 50 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 23.2 61.5
Dry bulb(T) 42 90 Infiltration:
Daily range(°F) - 15 ( L ) Method Simplified
Wet bulb(T) - 78 Construction quality Semi-loose
Wind speed(mph) 15.0 7.5 Fireplaces 0
Heating
Component Btuh/ft2 Btuh % of load
Walls 4.0 3517 12.9 Wa Duds
Glazing 18.5 9223 33.8
Doors 10.9 262 1.0 - pn
Ceilings 1.2 2252 8.2
Floors 3.0 5776 21.2 r
Infiltration 2.4 3338 12.2
Ducts 2938 10.8 Gaming
Piping 0 0 , Floors
Humidification 0 0
Ventilation 0 0 odw cuing.
Adjustments 0
Total 27308 100.0
Component Btuh/ft2 Btuh % of load
Walls 1.9 1683 6.0 ntemal Gains
Glazing 34.4 17162 61.2
Doors 11.3 271 1.0
Ceilings 0.9 1668 5.9 ___Ducts
Floors 0 0 0 t
Infiltration 0.7 957 3.4 nfittration
Ducts 1997 7.1
Ventilation 0 0 Ceilings
Internal gains 4320 15.4 Other
Blower 0 0 Glazing
Adjustments 0
Total 1 1 280681 100.0
Latent Cooling Load= 5454 Btuh
Overall U-value= 0.278 Btuh/ft2-°F
WARNING: window to floor area ratio=26.1%- more than 25%.
Wrl f7tSoft 2017-Apr-1215:13:34
A&K9 Right-Suite®Universal 2017 17.0.21 RSU23702 Page 1
�C�Lal� ...s Residence\Working Dwgs\Reynolds Residence.rup Cale=MJ8 Front Door faces: E
Building Analysis Job: Reynolds Residence Re
ti ,r Date: April 12,2017
�' AHU-2 Master
By: Scott Pingleton
We are Ilse in piece
ProCalcs, LLC
P.O.Box 882032.Port Saint Lucie,FL 34988 Phone:772-882-5700 Email:tom@procaics.net Web:www.ProCalcs.Net License:CAC1815254 RTIN#0105474
Project • •
For: Reynolds
278 Bermuda Beach Drive, Fort Pierce, FL 34949
Design Conditions
Location: Indoor: Heating Cooling
Fort Pierce, FL, US Indoor temperature(OF) 70 75
Elevation: 25 ft Design TD (°F) 28 15
Latitude: 27°N Relative humidity 50 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 23.2 61.5
Dry bulb(OF) 42 90 Infiltration:
Daily range(OF) - 15 ( L ) Method Simplified
Wet bulb(OF) - 78 Construction quality Semi-loose
Wind speed(mph) 15.0 7.5 Fireplaces 0
Heating
Component Btuh/ft' Btuh % of load
Walls 4.0 3923 26.1 pucts
Glazing 18.5 2414 16.1
Doors 10.9 210 1.4 Ir,filtration
Ceilings 1.2 1319 8.8
Floors 3.1 3472 23.1 _..
Infiltration 2.4 2008 13.4
Ducts 1689 11.2
Piping 0 0 Glazing Floors
Humidification 0 0 A
Ventilation 0 0 �r he
Adjustments 0
Total 15034 100.0
Component Btuh/ftz Btuh % of load
Walls 1.7 1655 9.7 Wall
Glazing 29.0 3788 22.1
Doors 11.3 218 1.3
Ceilings 0.9 977 5.7 Glazing n
Floors 0 0 0 „
Infiltration 0.7 575 3.4 . Internal Gains
Ducts 1158 6.8
Ventilation 0 0 ,"
Internal gains 8760 51.1 Other'
Blower 0 0 Ceilings
Adjustments 0 Infiltration
Total 17131 100.0 Ducts
Latent Cooling Load= 2747 Stuh
Overall U-value = 0.242 Btuh/ft2-°F
Data entries checked.
�+ wrightsoft 2017-Apr-1z 15: 34
Right-Suite®Universal 2017 17.0.21 RSU23702 Page 2
9
s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
Project Summary Job: Reynolds Residence Re...
Date: April 12,2017
we are the miss�rg psece B Scott Pin AHU-1 Main Area y: g
leton
'
ProCalcs, LLC
P.O.Box 882032,Port Saint Lucie,FL 34988 Phone:772-882-5700 Email:tom@procalcs.net Web:www.ProCalcs.Net License:CAC1815254 RTIN#0105474
Project Information
For: Reynolds
278 Bermuda Beach Drive, Fort Pierce, FL 34949
Notes: Neese Roofing
488 S. Market Ave
Fort Pierce, FL 34982
Jay Medina
Design Information
Weather: Fort Pierce, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 42 °F Outside db 90 °F
Inside db 70 °F Inside db 75 °F
Design TD 28 °F Design TD 15 °F
Daily range L
Relative humidity 50 %
Moisture difference 61 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 24369 Btuh Structure 26061 Btuh
Ducts 2938 Btuh Ducts 1997 Btuh
Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh
(none) (none)
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 27308 Btuh Use manufacturer's data y
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 28058 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Semi-loose
Fireplaces 0 Structure 3224 Btuh
Ducts 2230 Btuh
Central vent (0 cfm) 0 Btuh
Heating Cooling (none)
Area (ft2) 1911 1911 Equipment latent load 5454 Btuh
Volume (ft3) 15287 15287
Air changes/hour 0.43 0.23 Equipment total load 33513 Btuh
Equiv.AVF (cfm) 108 58 Req. total capacity at 0.80 SHR 2.9 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make Lennox
Trade Trade LENNOX
Model Cond XC25-036-230-**
AHRI ref Coil CBX40UHV-036*++TDR
AH R I ref 5947286
Efficiency 100 EFF Efficiency 14.0 EER, 23 SEER
Heating input 8.0 kW Sensible cooling 28000 Btuh
Heating output 27297 Btuh Latent cooling 7000 Btuh
Temperature rise 47 °F Total cooling 35000 Btuh
Actual air flow 525 cfm Actual air flow 1167 cfm
Air flow factor 0.019 cfm/Btuh Air flow factor 0.042 cfm/Btuh
Static pressure 0.60 in H2O Static pressure 0.60 in H2O
Space thermostat Load sensible heat ratio 0.84
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
Wrl htsoft 2017-Apr-1215:13:34
g Right-Suited Universal 2017 17.0.21 RSU23702 page 1
...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
Project Summary Job: Reynolds Residence Re...
1 Date: April 12,2017
- AHV-2 Master By: Scott Pingleton
We wre the mss sing�sece
ProCalcs, LLC
P.O.Box 882032, Port Saint Lucie,FL 34988 Phone:772-882-5700 Email:tom@procalcs.net Web:www.ProCalcs.Net License:CAC1815254 RTIN#0105474
Proiect Information
For: Reynolds
278 Bermuda Beach Drive, Fort Pierce, FL 34949
Notes: Neese Roofing
488 S. Market Ave
Fort Pierce, FL 34982
Jay Medina
Design Information
Weather: Fort Pierce, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 42 °F Outside db 90 °F
Inside db 70 °F Inside db 75 °F
Design TD 28 °F Design TD 15 °F
Daily range L
Relative humidity 50 %
Moisture difference 61 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 13345 Btuh Structure 15973 Btuh
Ducts 1689 Btuh Ducts 1158 Btuh
Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh
(none) (none)
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 15034 Btuh Use manufacturer's data y
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 17131 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Semi-loose
Fireplaces 0 Structure 1458 Btuh
Ducts 1289 Btuh
g gg Central vent (0 cfm) 0 Btuh
Heating Coo1119 (none)
Area (ftz) 1119 Equipment latent load 2747 Btuh
Volume (ft3) 8953 8953
Air changes/hour 0.44 0.23 Equipment total load 19877 Btuh
Equiv.AVF (cfm) 65 35 Req. total capacity at 0.80 SHR 1.8 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make Lennox
Trade Trade LENNOX
Model Cond XC25-024-230-02
AHRI ref Coil CBX32MV-024/030*++TDR
AHRI ref 7042645
Efficiency 100 EFF Efficiency 16.0 EER, 24.5 SEER
Heating input 5.0 kW Sensible cooling 18240 Btuh
Heating output 17061 Btuh Latent cooling 4560 Btuh
Temperature rise 58 °F Total cooling 22800 Btuh
Actual air flow 269 cfm Actual air flow 760 cfm
Air flow factor 0.018 cfm/Btuh Air flow factor 0.044 cfm/Btuh
Static pressure 0.60 in H2O Static pressure 0.60 in H2O
Space thermostat Load sensible heat ratio 0.86
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wri htsoft 2017-Apr-1215:13:34
g Right-SuiteO Universal 2017 17.0.21 RSU23702 Page 2
...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
Right-J®Worksheet Job: Reynolds Residence Remodel
Date: April 12,2017
-�~-~-� AHU-1 Main Area
By: Scott Pingleton
ProCalcs, LLC
P.O.Box 882032,Port Saint Lucie,FL 34988 Phone:772-882-5700 Email tom@procalcs.net Web.www.ProCalcs.Net License: CAC1815254 RTIN#0105474
1 Room name AHU-1 Main Area Exist Bedroom 1
2 Exposed wall 174.8 ft 45.4 ft
3 Room height 8.0 ft 8.0 ft heat/cool
4 Room dimensions 1.0 x 251.9 ft
5 Room area 1910.9 ft' 251.9 ft'
Ty Construction U-value Or HTM Area (ft2) Load Area (ft) Load
number (Btuh/ft''F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cool
6 %fBlk wall, stucco ext 0.143 ne 4.00 1.92 158 145 579 277 0 0 0 0
I.�; 2 glazing,cir low-e 0.660 ne 18.48 23.24 13 0 245 308 0 0 0 0
Blk wall,stucco ext 0.143 a 4.00 1.92 150 621 248 119 0 0 0 0
2 glazing,clr low-e 0.660 a 18.48 22.98 40 16 739 919 0 0 0 0
1 1 2 glazing,clr low-e 0.660 a 18.48 33.59 24 5 444 806 0 0 0 0
'h 11 DO 0.390 a 10.92 11.31 24 24 262 271 0 0 0 0
IW Blk wall,stucco ext 0.143 se 4.00 1.92 240 240 962 460 106 106 423 202
�-G 2 glazing,cir low-e 0.660 se 0.00 0.00 0 0 0 0 0 0 0 0
Blk wall,stucco ext 0.143 sw 4.00 1.92 290 192 768 367 152 102 410 196
10D-b 0.660 sw 18.48 19.98 49 42 899 972 0 0 0 0
2 glazing,clr low-e 0.660 sw 0.00 0.DO 0 0 0 0 0 0 0 0
2 dazinq.clr lave 0.660 sw 18.48 14.99 50 50 924 750 50 50 924 750
W Blk wall,stucco ext 0.143 w 4.00 1.92 276 6 261 12 0 0 0 0
2 glazing,cir lave 0.660 w 18.48 26.27 44 33I 809 1149 0 0 0 0
2 glazing,clr lave 0.660 w 18.48 34.14 100 15 1848 3414 0 0 0 0
2 glazing,dr low-e 0.660 w 18.48 36.18 100 0 1848 3618 0 0 0 0
W Blk wall.stucco ext 0.143 rrw 4.00 1.92 287 233 935 447 106 86 343 164
10D-b 0.660 nw 18.48 24.98 20 0 371 502 20 0 371 502
10D-b 0.660 nw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 nw 18.48 23.24 7 0 122 154 0 0 0 0
2 glazing,cir low-e 0.660 rrw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 r v 0.00 0.00 0 0 0 0 0 0 D 0
2 glazing,cir,low a 0.660 rrw 18.48 31.24 3 0 49 84 0 0 0 0
L-C 2 glazing,cir kHv2 0.660 nw 18.48 31.24 24 0 444 750 0 0 0 0
R Blk wall,stucco ext 0.143 - 0.00 0.00 0 0 0 0 0 0 0 0
--{J 11 DO 0.390 n 0.00 0.00 0 0 0 0 0 0 0 0
C 16X30-0ml 0.408 1.18 0.87 1911 1911 2252 1668 252 252 297 220
F 22A4pm 1.180 33.04 0.00 1911 175 5776 0 252 45 1501 0
6 c)AED excursion 3137 622
Envelope loss/gain 21031 20785 4268 2656
12 a) Infiltration 3338 957 866 248
b) Room ventilation 0 0 0 0
13 Internal gains Occupants @ 230 4 920 D 0
Appliances/other 3400 0
Subtotal(lines 6 to 13) 24369 26D61 5135 2904
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 24369 26061 5135 2904
15 Dud loads 12% 8% 2938 1997 12% 8% 619 223
Total room load 27308 28058 5754 3127
Air required(cfm) 525 1167 111 130
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrigflt50fY Right-Suite® Page Universal 2017 17.0.21 RSU23702 2017-Apr-12 15: ge 1
1
...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
-DC.;.: Right-J®Worksheet Job: Reynolds Residence Remodel
'I'IF, AHU-1 Main Area Date: April 12,2017
�~-�-�-•^�
By: Scott Pingleton
' ProCalcs, LLC
P.O.Box 882032,Port Saint Lucie,FL 34988 Phone:772-882-5700 Email.tom@procalcs.net Web:www.ProCalcs.Net License:CAC1815254 RTIN#0105474
1 Room name Bath 1 Clos 1
2 Exposed wall 0 ft 5.8 ft
3 Room height 8.0 ft heat/cool 8.0 ft heat/cod
4 Room dimensions 1.0 x 51.5 ft 1.0 x 35.9 ft
5 Room area 51.5 ft' 35.9 ft'
Ty Construction U-value Or HTM Area (ft') Load Area (ft� Load
number (BtuWft?'F) (Btuh/ft) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cod
6 Blk wall. stucco ext 0.143 ne 4.00 1.92 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 ne 18.48 23.24 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.1431 a 4.00 1.92 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 a 18.48 22.98 0 0 0 0 0 0 0 0
11 I 2 glazing,clr kwv- I 0.660 a 18.48 33.59 0 0 0 0 0 0 0 0
L� 11 DO 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0
W Blk wall, stucco ext 0.143 se 4.00 1.92 0 0 0 0 47 47 187 89
2 glazing,clr low-e 0.660 se 0.00 0.00 0 0 0 0 0 0 0 0
Blk wall,stucco ext 0.143 sw 4.00 1.92 0 0 0 0 0 0 0 0
1OD-b 0.660 sw 18.48 1R98 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 sw 0.00 0.00 0 0 0 0 0 0 0 0
2 dazina.clr low-e 0.660 sw 18.48 14,99 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.1431 w 4.00 1.92 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.6601 w 18.48 22.99 0 0 0 0 0 0 OI 0
2 glazing,clr low-e 0.660 w 18.48 26.27 0 0 D 0 0 0 0 0
[_-:2 2 glazing, low-e le 0.660 w 18.48 34.14 0 0 0 0 0 0 0 0
l- 2 glazing,clr lave 0.660 w 18.48 36.18 0 0 0 0 0 0 0 0
W Blk wall stucco ext 0.143 nw 4.00 1.92 0 0 0 0 0 0 0 0
1OD-b 0.660 nw, 18.48 24.98 0 0 0 0 0 0 0 0
1OD-b 0.660 nw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 rrw 18.48 23.24 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 nw 0.00 0.DO 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.6601 nw 0.00 0.00 0 01 01 0 01 0 0 0
1--G 2 glazing.cir low-e 0.660 rrw 18.48 31.24 0 0 0 0 0 0 0 0
L- G 2 dazing,cir low-e 0.660 nw 18.48 31.24 0 0
� 0 0 D 0 0 0
P Blk wall,stucco ext 0.143 - 0.00 0.00 0 0 0 0 0 0 0 0
11DO 0.390 n 0.00 0.00 0 0 0 0 0 0 0 0
C 16X30.0ml 0.408 1.18 0.87 52 52 61 45 36 36 42 31
F 22A-tpm 1.180 33.04 0.00 52 0 0 0 36 6 190 0
6 c)AED excursion 0 0
Envelope loss/gain 61 45 419 121
12 a) Infiltration 0 0 111 32
b) Room ventilation 0 0 0 0
13 Irltemal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 61 45 530 153
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistnbution 0 0 0 0
14 Subtotal 61 45 530 153
15 Duct loads 12% 8% 7 3 1211 8% 64 12
Total room load 68 48 594 164
Air required(cfm) 1 2 11 7
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
_ 4t+- wrightsoft 2017-Apr-12 15:13:34
Right-Suite®Universal 2017 17.0.21 RSU23702
Page 2
...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
Ri ht�1®Worksheet Job: Reynolds Residence Remodel
9
AHU-1 Main Area Date: April 12,2017
By: Scott Pingleton
ProCalcs, LLC
P.O.Box882032,Port Saint Lucie,FL 34988 Phone:772-882-5700 Email:tom@procalcs.net Web.www.ProCalcs.Net License:CAC1815254 RTIN#0105474
• 1 Room name Laundry Hall 2
2 Exposed wall 10.9 ft 0 ft
3 Room height 8.0 ft heat/ccd &0 ft heat/cool
4 Room dimensions 1.0 x 113.3 ft 1.0 x 80.9 ft
5 Room area 113.3 ft' 80.9 ft'
Ty Construction U-value Or HTM Area (ft') Load Area (ft� Load
number (Btuh/W"F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cool
6 t_GBlk wall.stucco ext 0.143 ne 4.00 1.92 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 ne 18.48 23.24 0 0 0 0 0 0 0 0
W Blk wall, stucco ext 0.143 a 4.00 1.92 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 a 18.48 22.98 0 0 0 0 0 0 0 0
11 2 glazing,clr low- I 0.660 a 18.48 33.59 0 0 0 01 0 0 0 0
L-D 11 DO 0,390 a 10.92 11.31 0 0 0 0 0 0 0 0
IW BIk wall..stucco ext 0.143 se 4.00 1.92 88 88 352 168 0 0 0 0
1--G 2 glazing,cir low-e 0.660 se 0.00 0.00 0 0 0 0 0 0 0 0
BIk wall,stucco ext 0.143 sw 4.00 1.92 0 0 0 0 0 0 0 0
10D-b 0.660 sw 18.48 19.98 0 0 0 0 0 0 0 0
2 glazing,cir law-e 0.660 sw O.00 0.00 0 0 0 0 0 0 0 0
2 dazina.clr low-e 0.660 sw 18.48 14.99 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 w 4.00 1.92 0 01 01 01 01 0 0 0
2 glazing,clr low-e 0.660 w l 18.48 26.27 0 0 OI 0 0 0 0 0
2 glazing,clr low-e 0.660 w 18.48 34.14 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 w 18.48 36,18 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 nw 4.00 1.92 0 0 0 0 0 0 0 0
1013-b 0.660 nw 18.48 24.98 0 0 0 0 0 0 0 0
10D-b 0.660 row 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 rrw 18.48 23.24 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 rrw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 nw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing, clr low-e 0.660 nw 18.48 31.24 0 0 0 0 0 0 0 0
(- G 2 glazinq,cir lave 0.660 nw 18.48 31.24 0 0 0 0 0 0 0 0
R Blk wall,stucco ext 0.143 - 0.001 0.00 0 0 0 0 0 01 01 OI
11 DO 0.390 n 0.00 0.00 0 0 0 0 0 0 0 0
C 16X30-0ml 0.408 1.18 0.87 113 113 133 99 81 81 95 71
F 22A-tpm 1.180 33.04 0.00 113 11 361 0 81 0 0 0
6 c)AED excursion 0 0
Envelope loss/gain 846 267 95 71
12 a) Infiltration 209 60 0 0
b) Room ventilation 0 01 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 500 0
Subtotal(lines 6 to 13) 1055 827 95 71
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 1055 827 95 71
15 Duct loads 12% 8% 127 63 17°6 8% 11 5
Total room load 1182 890 107 76
Air required(cfm) 23 37 2 3
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrigF,ttsOft 2017-Apr-12 15-
Right-Suite® Page Universal 2017 17.0.21 RSU23702 ge 3
3
...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
Right-JO Worksheet Job: Reynolds Residence Remodel
w m., AHU-1 Main Area Date: April 12,2017
By: Scott Pingleton
ProCalcs, LLC
P.O.Box 882032, Port Saint Lucie, FL 34988 Phone:772-882-5700 Email.tom@procalcs.net Wab:www.ProCaics.Net License:CAC1815254 RTIN#0105474
1 Room name Bath 2 Clos 2
2 Exposed wall O ft O ft
3 Room height 8.0 ft heat/cad 8.0 ft heat/cool
4 Room dimensions 1.0 x 56.3 ft 1.0 x 25.1 ft
5 Room area 56.3 ft' 25 1 ft2
Ty Construction U-value Or HTM Area (fe) Load Area M Load
number (Btuh/ft?°F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cod Gross N/P/S Heat cod Gross N/P/S Heat Cod
6 UU Blk wall,stucco ext 0.143 ne 4.00 1.92 0 0 0 0 0 0 0 0
-G 2 glazing,clr low-e 0.660 ne 18.48 23.24 0 0 0 0 0 0 0 0
W Bik wall,stucco ext 0.143 a 4.00 1.92 0 0 0 0 0 0 0 0
�-G 2 glazing,cir low-e 0.660 a 18.48 22.98 0 0 0 0 0 0 0 0
1 1 G-G 2 glazing,clr low-e 0.660 a 18.48 33.59 0 0 0 0 OI 0 0 0
L-D 11 DO 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0
IW - Blk wall,stucco ext 0.143 se 4.00 1.92 0 0 0 0 0 0 0 0
r-G 2 glazing,cir low-e 0.660 se 0.00 0.00 0 0 0 0 0 0 0 0
TE� Blk wall,stucco ext 0.143 sw 4.00 1.92 0 0 0 0 0 0 0 0
1OD-b 0.660 sw 18.48 19.98 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 sw 0.00 0.DO 0 0 0 0 0 0 0 0
2 dazino.cir low-e 0.660 sw 18.48 14.99 0 O 0 0 0 0 0 0
W Bik wall, stucco ext 0.143 w 4.00 1.92 01 0 01 0 0 0 0 0
�--G 12 glazing,cir low-e0.660 w 18.48I 26.27 0 0 OI 0 0� 0 0 0
C. 2 glazing,cir low-e 0.660 w 18.48 34.14 0 0 0 0 0 0 0 0
L-G 2 glazing,cir low-e 0.660 w 18.48 36.18 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 rtw 4.00 1.92 0 0 0 0 0 0 0 0
1OD-b 0.660 rav 18.48 24.98 0 0 0 0 0 0 0 0
1OD-b 0.660 nw, 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 nw, 18.48 23.24 0 0 0 0 0 0 0 0
2 glazing,cir law-e 0.660 nw, 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 nw, 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing, cir low-e 0.660 nw 18.48 31.24 0 0 0 0 0 0 0 0
I-G 2 glazing,clr k7w2 0.660 nw 18.48 31.24 0 0 0 0 0 0 0 0
P Bik wall,stucco ext 0.143 - 0.00 0.00 0 0 0 0 0 0 0 0
L--D 11DO 0.390 n 0.00 0.00 0 0 0 0 0 0 0 0
C 16X30-0ml 0.408 1.18 0.87 56 56 66 49 25 25 30 22
F 22A4pm 1.180 33.04 0.00 56 0 0 0 25 0 0 0
6 c)AED excursion 0 0
Envelope loss/gain 66 49 30 22
12 a) Infiltration 0 0 0 0
b) Room ventilation 0 0 10 0
13 Internal gaans Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 66 49 30 22
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 66 49 30 22
15 Duct loads 12% 8% 8 4 1211. 8% 4 2
Total room load 74 53 33 24
Air required(cfm) 1 2 1 1
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrigFttsOft Right-Suite®Universal 2017 17.0.21 RSU23702 2017-Apr-1215: 4
Page 4
...s ResidenceMorking Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
Right-JOWorksheet Job: Reynolds Residence Remodel
-��--�-�-- AHU-1 Main Area Date: April 12,2017
By: Scott Pingleton
ProCalcs, LLC
P.O.Box 882032,Port Saint Lucie, FL 34988 Phone:772-882-5700 Email:tom@procalcs.net VAb:www.ProCalcs.Net License:CAC1815254 RTIN#0105474
1 Room name Exist Bedroom 2 Kitchen
2 Exposed wall 27.3 ft 20.4 ft
3 Room height 8.0 ft heat/cool 8.0 ft heat/cool
4 Room dimensions 1.0 x 160.6 ft 1.0 x 378.0 ft
5 Room area 160.6 ft2 378.0 ft'
Ty Construction U-value Or HTM Area (ft') Load Area (ft� Load
number (BtuWW"F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cod Gross N/P/S Heat Cad Gross N/P/S Heat Cool
6 W Blk wall,stucco ext 0.143 ne 4.00 1.92 108 94 378 181 27 27 107 51
- G 2 glazing,clr low-e 0.660 ne 18.48 23.24 13 0 245 308 0 0 0 0
W Blk wall,stucco ext 0.143 a 4.00 1.92 0 0 0 0 0 01 0 0
11 I {-G 2 glazing,clr low-e 0.660 a 18.48 33.59 0 0I 0 0 0 01 0 0
L--D 11 DO 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 se 4.00 1.92 0 0 0 0 0 0 0 0
L-G 2 glazing,clr low-e 0.660 se 0.00 0.00 0 0 0 0 0 0 0 0
W Bilk wall,stucco ext 0.143 sw 4.00 1.92 0 0 0 0 108 59 236 113
1OD-b 0.660 sw 18.48 19.98 0 0 0 0 49 42 899 972
2 glazing, clr low-e 0.660 sw 0.00 0.00 0 0 0 0 0 0 0 0
2 dazino.clr low-e 0.760 sw 18.48 14.99 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 w 4.00 1.92 0 0 0 0 0 0 0 0
-G 2 glazing,clr low-e 0.660 w 18.48 22.99 0 0 0 0 0 0 0 0
--G 2 glazing,clr low-e 0.660 w I 18.48 26.27 0 OI 0 0 0 0 0 0
I--C 2 glazing,dr low-e 0.660 w 18.48 34.14 0 0 0 0 0 0 0 0
�G 2 glazing,clr low-e 0.660 w 18.48 36.18 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 riw 4.00 1.92 111 105 418 200 29 29 115 55
10D-b 0.660 rrw 18.48 24.98 0 0 0 0 0 0 0 0
1OD-b 0.660 rrvv 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 nw 18.48 23.24 7 0 122 154 0 0 0 0
2 glazing,clr low-e 0.660 nw 0.00 0.DO 0 0 0 0 0 0 0 0
,- G 2 glazing,clr low-e 0.6601 rrw 0.00 0.00 0 0 0 0 0 0 0 0
k--G 2 glazing,clr low-e
01
01
00
1 48
1.24
L--G 2 glazing.clr laws I 0.660) rnv I 10.00 31.24 0 O) 0 0 OI 0 OI O
P Blk wall,stucco ext 0.143
L--D 11DO 0.390 n 0.00 0.00 0 0 0 0 0 0 0 0
C 16X30-0ml 0.408 1.18 0.87 161 161 189 140 378 378 445 330
F 22A-tpm 1.180 33.04 0.00 161 27 903 0 378 20 675 0
6 c)AED excursion 17 152
Envek)pe loss/gain 2256 1001 2479 1674
12 a) Infiltration 521 149 389 112
b) Room ventilation 0 0 0 0
13 1rfemal gains Occupants @ 230 0 0 1 230
Appliances/other 0 2000
Subtotal(lines 6 to 13) 2778 1150 2868 4016
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 2778 1150 28M 4016
15 Duct loads 12% 8% 335 88 129 8% 346 308
Total room load T7 -3113 1238 3214 4323
Air required(cfm) 60 51 62 180
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
+4+- wrightsoft 2017-Apr-12 1513.34
^-Lc� Right-Suile®Universal 2017 17.0.21 RSU23702 Page 5
...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
Right-J®Worksheet Job: Reynolds Residence Remodel
w..... m.. AHU-1 Main Area Date: April 12,2017
By: Scott Pingleton
ProCalcs, LLC
P.O.Box 882032,Port Saint Lucie,FL 34988 Phone:772-882-5700 Email:tom@procalcs.net Web:www.ProCalcs.Net License:CAC1815254 RTIN#0105474
1 Room name AHU2 Exist Great Room
2 Exposed wall 2.8 ft 62.2 ft
3 Room height 8.0 ft heat/cool 8.0 ft heat/cod
4 Room dimensions 1.0 x 11.8 ft 1.0 x 745.8 ft
5 Room area 11.8 ft2 745.8 ft'
Ty Construction U-value Or HTM Area (ft2) Load Area (ftl Load
number (BtuNW"F) (BWNW) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cool
6 Blk wall,stucco ext 0.143 ne 4.00 1.92 23 23 93 45 0 0 0 0
2 glazing,clr low-e 0.660 ne 18,48 23.24 o 0 0 0 0 0 0 0
W, Blk wall,stucco ext 0.143 e 4.00 1.92 0 0 0 0 150 62 248 119
1 1 I 1__ 12 glazing,clr low- I 0.6601
a 18.48 33.59 0 0 0 0 24I 15 444 806
L-D 11Do 0.390 a 10.92 11.31 0 0 0 0 24 24 262 271
W Blk wall,stucco ext 0.143 se 4.00 1.92 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 se 0.00 0.00 0 0 0 0 0 0 0 0
Blk wall,stucco ext 0.143 sw 4.00 1.92 0 0 0 0 30 30 122 58
10D-b 0,660 sw 18.48 19.98 0 0 0 0 0 0 0 0
2 glazing, clr low-e 0.660 sw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazino,clr low-e 0.660 sw 18.48 14.99 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0,1431 w 4.00 1.92 01 01 01 01 276 61 26 12
k--C'12 glazing,clr low-e 0.660I w 18.48I 26.27 0 0 0 0 26 26 481 I 149
44 33 809 1149
k--G 2 glazing,clr low-e 0.660 w 18.48 34.14 0 0 0 0 100 15 1848 3414
C, 2 glazing,clr low-e 0.660 w 18.48 36.18 0 0 0 0 100 0 1848 3618
W Blk wall,stucco ext 0.143 nw 4.00 1.92 0 0 0 0 41 15 58 28
10D-b 0.660 nw, 18.48 24.98 0 0 0 0 0 0 0 0
10D-b 0.660 nw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 nw 18.48 23.24 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 nw 0.00 0.00 0 0 0 0 0 0 0 0
rG 2 glazing,clr low-, 0.660 nw 0.00 0.00 0 0 0 0 0 0 0 0
O 2 glazing,clr laws 0.660 r1w 18.48 31.24 0 0 0 0 3 0 49 84
�G 2 qlazinq,clr low-e 0.660 nw, 18.48 31.24 0 0 0 0 24 0 444 750
P Blk wall,stucco ext 0.143 - 0.00 0.00 0 0 0 0 0 0 0 0
L-D 11DO 0.390 n 0.00 0.00 0 0 0 0 0 0 0 0
C 16X30-0ml 0.408 1.18 0.87 12 12 14 10 746 746 879 651
F 22A-tpm 1.180 33.04 0.00 12 3 94 0 746 62 2054 0
6 c)AED excursion 0 2346
Envelope loss/gain 201 55 10310 14825
12 a) Infiltration 56 16 1186 340
b) Room ventilation 0 01 1 10 0
13 Internal gains Occuparrts @ 230 0 0 3 690
Appliances/other 0 900
Subtotal(lines 6 to 13) 256 71 11496 16754
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 256 71 11496 16754
15 Duct loads 12% 8%1 31 5 12% 8% 1386 1284
Total room load 287 76 12882 18038
Air required(cfm) 6 3 248 750
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrightsOft Right-Suite®Universal 2017 17.0.21 RSU23702 2017-Apr-12 15 Page 6
...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
Right-JO Worksheet Job: Reynolds Residence Remodel
,�'_...e... AHU-2 Master Date: April 12,2017
By: Scott Pingleton
ProCalcs, LLC
P.O.Box 882032,Port Saint Lucie,FL 34988 Phone-772-882-5700 Email:tom@procalcs.net Web www.ProCalcs.Net License:CAC1815254 RTIN 90105474
• 1 Room name AHU-2 Master Master Bedroom
2 Exposed wall 105.1 ft 11.6 ft
3 Room height 8.0 ft 8.0 ft heat/cool
4 Room dimensions 1.0 x 279.1 ft
5 Room area 1119.1 ft' 279.1 ft'
Ty Construction U-value Or HTM Area (ft') Load Area (M Load
number (BtuNW'F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cod
6 Blk wall,stucco ext 0.143 ne 4.00 1.92 213 213 854 409 0 0 0 0
I G 2 glazing,cir kNv-e 0.660 ne 0.00 0.00 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 e 0.00 O.DO 0 0 0 0 0 0 0 0
11 2 glazing,cir low-e 0.660 a 0.00 0.00 OI 0 0 0 OI 0 0 0
D 11 DO 0.390 a 0.00 0.00 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 se 4.00 1.92 159 146 585 280 0 0 0 0
I-(, 2 glazing,clr low-e 0.660 se 18.48 14.99 13 13 245 199 0 0 0 0
Bilk wall,stucco ext 0.143 sw 4.00 1.92 219 213 852 408 0 0 0 0
1OD-b 0.660 sw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 sw 18.48 14.99 6 6 116 94 0 0 0 0
2 dazing.cir low-e 0.660 sw 0.00 0.00 0 0 0 0 O 0 0 0
W Blk wall,stucco ext 0.143 w 0.00 0.00 0 0 0 0 0 0 0 0
4--G 2 glazing,cir low-e I 0.660 w ( 0.00 0.00 OI OI 0 OI O) 0 0 O
2 glazing,clr low-e 0.660 w 0.00 0.00 0 0 0 0 0 0 0 0
G 2 glazing,cir low-e 0.660 w 0.00 0.00 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 nw 4.00 1.92 251 140 560 268 93 53 213 102
1OD-b 0.660 rnv 0.00 0,00 0 0 0 0 0 0 0 0
1OD-b 0.660 nw 18.48 24,98 40 0 743 1004 40 0 743 1004
2 glazing,cir low-e 0.660 rrw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 nw 18.48 23.24 35 0 650 818 0 0 0 0
-- G 2 glazing,clr low-, 0,660 nw 18.48 23,24 36 0 660 831 0 0 0 0
cli
lir
rtee
14 I PGlkl9 0 0 Blk wall,stucco ext 03 - 4.00 1.09 7 268 10711 I1 OI 0 0
I-D 11DO 0.390 n 10.92 11.31 19 19 210 218 0 0 0 0
C 16X30-0mi 0.408 1.18 0.87 1119 1119 1319 977 279 279 329 244
F 22A-tpm 1.180 33.04 0.00 1119 105 3472 0 279 12 383 0
6 c)AED excursion 843 162
Envelope loss/gain 11338 6638 1667 1511
12 a) Irrfikration 2008 575 222 64
b) Room ventilation 0 0 0 0
13 Irltemal gains' Occupants @ 230 0 0 0 0
Appliances/other 8760 2100
Subtotal(lines 6 to 13) 13345 15973 1889 3675
Less external load 0 0 D 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 13345 15973 1889 3675
15 Duct loads 13% 7/0 1689 1158 13% 7/0 239 286
Total room load 15034 17131 2128 3941
Air required(cfm) 269 760 38 175
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
+t+ wrightsoft 2017-Apr-1215 13:34
Right-Suite@ Universal 2017 17.0.21 RSU23702 Page 7
...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
n QM Right-�JO Worksheet Job: Reynolds Residence Remodel
AHU-2 Master Date: April 12,2017
By: Scott Pingleton
ProCalcs, LLC
P.O.Box 882032,Port Saint Lucie,FL 34988 Phone:772-882-5700 Email:tom@procalcs.net Nkb:www.ProCalcs.Net License:CAC1815254 RTIN#0105474
1 Room name Master Bath Master WIC
2 Exposed wall 44.8 ft 6.9 ft
3 Room height 8.0 ft heat/cod 8.0 ft heat/cool
4 Room dimensions 1.0 x 298.0 ft 1.0 x 147.5 ft
5 Room area 298.0 ft2 147.5 ft'
Ty Construction U-value Or HTM Area (ft') Load Area (ft� Load
number (Btuh/ft?°F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cod
6 Blk wall,stucco ext 0.143 ne 4,00 1.92 126 126 503 240 56 56 223 106
2 glazing,cir low-e 0.660 ne 0.00 0.00 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 a 0.00 0.00 0 0 0 0 0 0 0 0
�--G 2 glazing,cir low-e 0.660 a 0.00 0.00 0 0 0 0 0 0 0 0
11 l- C� 2 glazing,clr low-e I 0.660 a 0.00 0.00 0 0 0 01 0 OI O I 0
�����ppppp 11DO 0.390 e 0.00 0.00 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 se 4.00 1.92 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 se 18.48 14.99 0 0 0 0 0 0 0 0
Blk wall,stucco ext 0,143 sw 4.00 1.92 75 75 302 145 0 0 0 0
1OD-b 0.660 sw 0.00 0.DO 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 sw 18.48 14.99 0 0 0 0 0 0 0 0
2 dazino,cir low-e 0.660 sw 0.00 0.00 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 w 0.00 0.00 0 0 0 0 0 0 0 0
kI- 2 glazing,cir low-e I 0.6W w 0.DO 0.00 0 0 OI 0 0 0 0 OI
-G 2 glazing,clr low-e
I---G 2 glazing,cir low-e 0.660 w 0.00 0.00 0 0 0 0 0 0 0 0
L_.G 2 glazing,cir low-e 0.660 w 0.00 0.00 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 ryw 4.00 1.92 158 87 348 166 0 0 0 0
1OD-b 0.660 nw 0.00 0.00 0 0 0 0 0 0 0 0
10D-b 0.660 rw 18.48 24.98 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0,660 nw 0,00 0,00 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 rrw 18.48 23.24 35 0 650 818 0 0 0 0
r--G 2 glazing,clr low-e 0.660 rrw 18.48 23.24 36 0 6601 831 01 0 0 0
2 glazing,
r low-e
nw 0.00 0.00
P. I Blkiwalll,stucco ext 0.143 nw I 4.00 10.00 0.09 OI 0 OI 0 97I 97I 387 100
t---D 11 DO 0.390 n 10.92 11.31 0 0 0 0 0 0 0 0
C 16X30-0ml 0.408 1.18 0.87 298 298 351 260 148 148 174 129
F 22A-tpm 1.180 33.04 000 298 45 1481 0 148 7 229 0
6 c)AED excursion 659 0
Envelope loss/gain 4296 3119 1012 340
12 a) Infittration 855 245 132 38
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 2100 1100
Subtotal(lines 6 to 13) 5150 5464 1145 1478
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 5150 5464 1145 1478
15 Duct loads 13% 7% 652 396 13% 7% 145 107
Total room load 5802 5860 1289 1585
Air required(cfm) 104 260 23 70
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wright50ft Right-Suite@ Universal 2017 17.0.21 RSU23702 2017-Apr-12 1 Page
8
...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
Right-JO Worksheet Job: Reynolds Residence Remodel
-�-� -�-� AHU-2 Master Date: April 12,2017
By: Scott Pingleton
ProCalcs, LLC
P.O.Box 882032,Port Saint Lucie,FL 34988 Phone*772-882-5700 Email:tom@procalcs.net Web_www.ProCalcs.Net License:CAC1815254 RTIN 90105474
1 Room name Hall Clos Exist Study
2 Exposed wall 8.0 ft 29.1 ft
3 Room height 8.0 ft heat/cod 8.0 It heat/cool
4 Room dimensions 1.0 x 12.4 ft 1.0 x 211.0 ft
5 Room area 12A ft2 211.0 ft2
Ty Construction U-value Or HTM Area (fe) Load Area (ft� Load
number (Btuh W'F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cod
6 VjJ Blk wall, stucco ext 0.143 ne 4.00 1.92 0 0 0 0 0 0 0 0
L� 2 glazing, clr laves 0.660 ne 0.00 0.00 0 0 0 0 0 0 0 0
W, Blk wall,stucco ext 0.143 a 0.00 0.00 0 0 0 0 0 01 0 0
11
I 2 glazing,cir low-e 0.660I a 0.00I 0.00 0 01 OI OI 0� OI 0 01
2 glazing,clr low-e 0.660 a 0.00 0.00 0 0 0 0 0 0 0 0
L p 11 DO 0.390 a 0.00 o.00l 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 se 4.00 1.92 50 50 201 96 109 96 384 184
2 glazing,clr low-e 0.660 se 18.48 14.99 0 0 0 0 13 13 245 199
VV Blk wall,stucco ext 0.143 sw 4.00 1.92 14 14 58 28 124 117 470 225
1OD-b 0.660 sw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 sw 18.48 14.99 0 0 0 0 6 6 116 94
2 dazino.cir lave 0.660 sw 0.00 0.00 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 w 0.00 0.00 0 0 0 0 0 0 0 0
0.660 W
I� 2 glazing,cir lave 0.660 w ( 0.0o1 0.00 0 0 01 0 0 0I 0 0
2 glazing,cir low-e 0.660 w 0.00 0.00 0 0 0 0 0 0 0 0
--G 2 glazing,clr low-e 0.660 w 0.00 0,DO 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 nw 4.00 1.92 0 0 0 0 0 0 0 0
1OD-b 0.660 nw 0.00 0.00 0 0 0 0 0 0 0 0
1OD-b 0.660 nw 18.48 24.98 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 rrw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 r w 18.48 23.24 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 rtw 18.48 23.24 0 0 0 D 0 0 0 0
----r 2 glazing,
( 01
P Blk stucco ext I 0.143 4.00 10.09 OI OI 0 OI 120 120I 4811 1311
L-D 11 DO 0.390 n 10.92 11.31 0 0 0 0 0 0 O 0
C 16X30-0ml 0.408 1.18 0.87 12 12 15 11 211 211 249 184
F 22A-tpm 1.180 33.04 0.Do 12 8 264 0 211 29 961 0
6 c)AED excursion 0 22
Envelope loss/gain 537 134 2905 1038
12 a) Infiltration 154 44 554 159
b) Room ventilation 0 0 0 0
13 Internal gains Occupants @ 230 0 0 0 0
Appliances/other 0 2100
Subtotal(lines 6 to 13) 691 178 3459 3297
Less external load 0 0 0 0
Less transfer 0 0 D 0
Redistribution 0 0 0 0
14 Subtotal 691 178 3459 3297
15 Duct loads 13% 7% 87 13 13% 7/0 438 239
Total room load T79 191 3897 3536
Air required(cfm) 14 8 70 157
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�6 44- wright9oft Right-Suite®Universal 2017 17.0.21 RSU23702 2017-Apr-12 1 4 Page
...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJ8 Front Door faces: E
( nr Right-.1®Worksheet Job: Reynolds Residence Remodel
AHU-2 Master Date: Apri11Z,zo»
ProCalcs, LLC By: Scott Pingleton
P.O.Box 882032,Port Saint Lucie,FL 34988 Phone:772-882-5700 Email tom@procalcs.net Web:www.ProCalcs.Net License:CAC1815254 RTIN 90105474
1 Room name AHU1 Study Clos
2 Exposed wall 0 ft 0.7 ft
3 Room height 8.0 ft heat/cod 8.0 ft heat/cool
4 Room dimensions 1.0 x 8.5 ft 1.0 x 18.0 ft
5 Room area 8.5 ft2 18.0 ft'
Ty Construction U-value Or HTM Area (w) Load Area M Load
number (Btuh/ft'-F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cod
6 Blk wall,stucco ext 0.143 ne 4.00 1.92 0 0 0 0 0 0 0 0
2 glazing,
clr low-e 0.660 ne 0.00 0.00 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 a 0.00 0.00 0 01 0 0 0 0 0 0
2 glazing,clr low-e 0.660 a 0.00 0.00 0 0 0 0 11 12 glazing,clr low-e 0.660 e l 0.00 0.00 0 0 0 O 0I 01 00 00 00
11 DO 0.390 a 0.00 0.00 0 0 0 0 0 0 0 0
W1 Blk wall,stucco ext 0.143 se 4.00 1.92 0 0 0 0 0 0 0 0
1--G 2 glazing,clr low-e 0.660 se 18.48 14.99 0 0 0 0 0 0 0 0
Blk wall,stucco ext 0.143 sw 4.00 1.92 0 0 0 0 6 6 23 11
10D-b 0.660 sw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,dr low-e 0.660 sw 18.48 14.99 0 0 0 0 0 0 0 0
2 dazino.clr low-e 0.660 sw 0.00 0.00 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 w l 0.00 0.00 0 0 o OI 0 0 0 0
2 glazing,clr low-e 0.660 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 w 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr law-e 0.660 w 0.00 0.00 0 0 0 0 0 0 0 0
W Blk wall. stucco ext 0.143 nw 4.00 1.92 0 0 0 0 0 0 0 0
10D-b 0.660 rry 0.00 0.00 0 0 0 0 0 0 0 0
10D-b 0.660 rnv 18.48 24.98 0 0 0 0 0 0 0 0
2 glazing,cir low-e 0.660 nw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,dr low-e 0.660 nw 18.48 23.24 0 0 0 O 0 0 0 0
2 glazing,clr low-e 0.660 nw 18.48 23.24 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 nw 0.00 0.00 0 0 0 0 OI o 0 0
2 glazing,clr low-e 0.660 nwr 0.00 0.00 0 0 0 0 0 0 0 0
P Blk wall,stucco ext 0.143 - 4.00 1.09 0 0 0 0 0 0 0 0
�
11 DO 0.390 n 10.92 11.31 0 0 0 0 0 0 0 0
C 16X30-Oml 0.408 1.18 0.87 9 9 10 7 18 18 21 16
F 22A-tpm 1.180 33.04 0.00 9 0 0 0 18 1 22 0
6 c)AED excursion 0 0
Envelope loss/gain 10 7 66 27
12 a) Infiltration 0 0 13 4
b) Room ventilation 0 0 0 0
13 Internal gains Occupants @ 230 0 0 0
0
Appliances/other 0 50
Subtotal(lines 6 to 13) 10 7 79 80
Less extemal load 0 0 0 0
Less transfer o 0 0 0
Redistribution 0 0 0 0
14 Subtotal 10 7 79 80
15 Duct loads 13% 7% 1 1 13% 7% 10 6
_T
Total room load 11 8 89 86
Air required(cfm) 0 0 2 4
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
4+f-' wrightsoft Right-Suite®Universal 2017 17.0.21 RSU23702 2017-Apr-12 15:13:34
Page 10
...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJB Front Door faces: E
Right-J®Worksheet Job: Reynolds Residence Remodel
AHU-2 Master Date: April 12,2017
ProCalcs, LLC By: Scott Pingleton
•
P.O.Box 882032,Port Saint Lucie,FL 34988 Phone: 772-882-5700 Email:tom@procalcs.net Web:www.ProCalcs.Net License:CAC1815254 RTIN#0105474
1 Room name WC Hall 1
2 Exposed wall 4.0 ft 0 ft
3 Room height 8.0 ft heat/cool 8.0 ft heat/cool
4 Room dimensions 1.0 x 26.5 ft 1.0 x 118.1 ft
5 Room area 26.5 ft2 118.1 ft'
Ty Construction U-value Or HTM Area (fN) Load Area M Load
number (Btuh/ft'°F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cod Gross N/P/S Heat cod Gross N/P/S Heat too,
ol
6 Blk wall,stucco ext 0.143 ne 4.00 1.92 32 32 129 62 0 0 0
2 glazing,clr low-e 0.660 ne 0.00 0.00 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 e 0.00 0.00 0 0 0 0 0 0 0
11 !--G 2 glazing,clr low-e I 0.660 a O.00I 0.00 OI 0 0 0 OI o O I O
L_D 11D0 0.390 a 0.00 0.00 0 0 0 0 0 0 0 0
IW - Blk wall,stucco ext 0.143 se 4.00 1.92 0 0 0 0 0 0 0 0
�---G 2 glazing, clr low-e 0.660 se 18.48 14.99 0 0 0 0 0 0 0 0
Blk wall,stucco ext 0.143 sw 4.00 1.92 0 0 0 0 0 0 0 0
10D-b 0.660 sw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 sw 18.48 14.99 0 0 0 0 0 0 0 0
2 dazino.clr low-e 0.660 sw 0.00 0.00 0 0 0 0 0 0 0 0
W Blk wall,stucco ext 0.143 w 0.00 0.00 0 0 0 0 0 0 0 0
G 2 glazing, clr low-e 0.660 w 0.00 0.00 0 0 0 0 0 0 0 0
k--' 2 glazing, clr low-e 0.660 w 0.00 0.00 0 0 0 0 0 o OI 0
f G 2 glazing,clr low-e 0.660 w 0.00 0.00 0 0 0 0 0 0 0 0
L-G 2 glazing,clr low-e 0.660 w 0.00 0.00 0 0 0 0 0 0 0 0
W Blk wall. stucco ext 0.143 nw 4.00 1.92 0 0 0 0 0 0 0 0
10D-b 0.660 nw 0.00 0.00 0 0 0 0 0 0 0 0
10D-b 0.660 nw 18.48 24.98 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0,660 aw 0.00 0.00 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.660 nw 18.48 23.24 0 0 0 0 0 0 0 0
rG 2 glazing, clr low-e 0.660 nw 18.48 23.24 0 0 0 0 0 0 0 0
I C. 2 glazing,clr low-e 0.660 nw, O.00 I 0.00 0 0 0 OI o OI OI o
I� 2 glazing,clr low-e 0.660 nw 0.00 0.00 0 0 0 0 0 0 0 0
F Blk wall,stucco ext 0.143 4.00 1.09 0 0 0 0 70 51 203 55
L-D 11 DO 0.390 n 10.92 11.31 0 0 0 0 19 19 210 218
C 16X30-0ml 0.408 1.18 0.87 27 27 31 23 118 118 139 103
F 22A-tpm 1.180 33.04 0.00 27 4 132 0 118 0 0 0
6 c)AED excursion 0 0
Envelope loss/gain 293 85 553 376
12 a) Infiltration 77 22 0 0
b) Room ventilation 0 0 0 0
13 Internal gains Occupants @ 230 0 0 0 0
Appliances/other 210 1100
Subtotal(lines 6 to 13) 369 317 553 1476
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 369 317 553 1476
15 Duct loads 13% 7% 47 23 13% 7% 70 107
Total room load 416 340 622 1583
Air required(cfm) 7 15 11 70
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�� wrightsOft Right-Suite®Universal 2017 17.0.21 RSU23702 2017 Apr 12 1Pa19 a 11
...s Residence\Working Dwgs\Reynolds Residence.rup Calc=MJS Front Door faces: E