PROPERTY INFORMATION
Address: 4845 Watersong Way
City / State / Zip: Fort Pierce, FI 34949
Parcel #: 2532-500-0024-000/9
Zoning:
REVIEW COMMENTS
Owner(s):
Carlos Lanza (Tr)
Jurisdiction: SAINT LUCIE COUNTY
Lot#: 10 Block:
APPLICATION INFORMATION
Permit Number: 2012-0614 Stories:
Permit Type: BUILDING RESIDENTIAL (SFR UP TO 2 FLOORS)
CONTRACTOR INFORMATION
Contractor Name:
Carlos Lanza
Business Name:
Cl Contractors Corp
Business Addr:
8531 Sw 167 Terr
City / State / Zip:
Miami, FI 33157
REVIEWS AND COMMENTS
1
Automatic Sprinkler System? No
Fax Number:
Review Tvoe
Status Reviewed By Date Started
DOCUMENTS MISSING
PENDING Lashahna Ingram
12/28/2020
Comment:
NEEDS TO SUBMIT FILLED LANDS
12/28/2020
Comment:
SUB CONTRACTOR AGREEMENTS FOR ALL TRADES
12/28/2020
Comment:
NEEDS TO SUBMIT DRIVEWAY PERMIT
ENVIRONMENTAL REVIEW
INCOMPLETE Lynn Swartzel 12/30/2020
1/4/2021
Comment:
NEED COPY OF SURVEY WITH PROPOSED BUILDING.
FRONT COUNTER REVIEW
COMPLETE Lashahna Ingram 12/28/2020
Comment:
NOTIFIED FOR PICK UP PENDING
Comment:
PLANS EXAMINER REVIEW
1/14/2021 Comment:
1/14/2021 Comment:
Comment:
1/14/2021
Email: Clcontractors@Comcast.Ne
t
Date Completed Date Released
12/2812020 12/28/2020
INCOMPLETE William Durden 1/14/2021
SUBMITTED PLANS ARE NGVD. PLEASE REVISE PLANS TO REFLECT NAVD.
UNABLE TO REVIEW SECTION 322 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE FOR FLOOD
REQUIREMENTS. PLANS ARE IN NGVD.
UNABLE TO REVIEW SECTION 322 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE FOR FLOOD
REQUIREMENTS FOR THE LOWEST HORIZONAL STRUCTURAL MEMBER. PLEASE SUBMIT THE FDEP
DOCUMENTS FOR THE LOWEST HORIZONAL STRUCTURAL MEMBERS ELEVATION. SEE SECTION 107 OF
THE 2017 FLORIDA BUILDING CODE.
Planning & DevelopmentServices
Building t Codi ftulabon Diviiion
230Q Vlrglnla Avenue
fort,Plerea,.FL,, 34982
REVIEW COMMENTS
Page 2
Comment:
SUBMITTED PLANS ARE COPIES WITH DIGITAL SIGNATURE AND SEALS. • IF THE A DOCUMENT IS
SUBMITTED WITH A DIGITAL SIGNATURE THE DOCUMENT MUST BE SUBMIT AS A DIGITAL SUBMISSION
1/14/2021
WITH THE ORIGINAL SIGNATURE. IF THE DOCUMENTS ARE SUBMITTED IN PAPER FORM IT MUST HAVE
THE RAISED OR WET SEAL WITH THE ORIGINAL SIGNATURE. PLEASE RESUBMIT. SEE SECTION 107 OF
THE 2017 FLORIDA BUILDING CODE.
Comment:
PLANS ARE INUNDATED WITH CODE SECTIONS. PLEASE REMOVE THE SECTIONS THAT DO NOT PERTAIN
1/14/2021
TO THE CONSTRUCTION OF THE PROPOSED STRUCTURE. SEE SECTION 107 OF THE 2017 FLORIDA
BUILDING CODE.
Comment:
PAGE A1.01, NOTE SECTION SPECIFIES WINDOW AND DOORS BY OTHER, SEPARATE PERMIT. PLEASE
1/14/2021
REMOVE THIS SECTION AND ADD THE PRODUCT REVIEW AFFIDAVIT TO THE PLANS WITH THE
INSTALLATION INSTRUCTIONS COMPLETED. OR ADD THE PRODUCT APPROVALS FOR THE WINDOWS AND
DOORS. SEE SECTION 107.2.4 OF THE 2017 FLORIDA BUILDING CODE.
1/14/2021 Comment:
PLEASE SUBMIT A GEOTECHNICAL EVALUATION WITH THE FOUNDATION RECOMMENDATIONS. (SOIL
BORING TEST),SEE SECTION R401.4 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE.
1/14/2021 Comment:
• PLEASE FURNISH TRUSS ENGINEERING IN DUPLICATE PER CHAPTER 8 SECTION R802 SUBSECTION
R802.1.7.1 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE.
Comment:
• PLEASE FURNISH THE MANUFACTURES TRUSS PLACEMENT DRAWINGS IN DUPLICATE REVIEWED AND
1/14/2021
APPROVED BY THE DESIGN PERSON OF RECORD IN ACCORDANCE WITH 61 G15-30.005 OF THE FLORIDA
ADMINISTRATIVE CODE.
1/15/2021 Comment:
• ENERGY CALC'S INFORMATION BLOCK AT THE TOP OF THE PAGE ARE INCOMEPLETE. SEE SECTION
405.4.2 (1) OF THE 2017 FLORIDA ENERGY CODE.
Comment:
• LINE SEVEN ON THE ENERGY CALC'S ARE INCORRECT, MULTIPLE TYPES AND SIZES OF GLAZED
1/15/2021
OPENINGS ON PLANS. PLEASE CORRECT ENERGY CALC'S AS PER SECTION R401.3 OF THE 2017 FLORIDA
BUILDING CODE ENERGY CONSERVATION 6TH EDITION.
Comment:
• LINE EIGHT ON THE ENERGY CALC'S ARE INCORRECT, SEE PLAN DETAILS. PLEASE CORRECT ENERGY
1/1512021
CALC'S AS PER SECTION R401.3 OF THE 2017 FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH
EDITION.
Comment:
• LINE NINE ON THE ENERGY CALC'S ARE INCORRECT, SEE PLAN DETAILS. PLEASE CORRECT ENERGY
1/15/2021
CALC'S AS PER SECTION R401.3 OF THE 2017 FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH
EDITION.
Comment:
• LINE TEN ON THE ENERGY CALC'S ARE INCORRECT, SEE PLAN DETAILS. PLEASE CORRECT ENERGY
1/15/2021
CALC'S AS PER SECTION R401.3 OF THE 2017 FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH
EDITION.
Comment:
PLEASE ADD THE CUBIC VOLUME ON THE PLANS. THE PLANS SHOULD MATCH THE CUBIC VOLUME
SPECIFIED ON THE ENERGY CALC'S. THE CUBIC VOLUME NUMBER IS USED IN THE CALCULATIONS FOR
THE BLOWER DOOR TESTING. PLEASE CHECK WITH THE COMPANY THAT CALCULATED THE CUBIC
1/15/2021
VOLUME ON THE ENERGY CALC'S AND THE DESIGN PROFESSIONAL TO COLLATE THE CUBIC VOLUME.
THE NUMBER SHOULD INCLUDE THE ATTIC SPACE AS THE SPRAY FOAM INSULATION IS INSTALLED TO
THE ROOF DECK AND IS NOT VENTED. THIS IS CONSIDERED CONDITIONED SPACE. SEE SECTION
CHAPTER 2 DEFINITION OF CONDITION SPACE OF THE 2017 FLOR IDA ENERGY CODE.
1/15/2021 Comment:
PLEASE CLARIFY NOTE ON PAGE A1.02 FOR THE AS -BUILT ELEVATION DOCUMENTATION. WILL YOU BE
SUPPLYING AS BUILT DRAWINGS?
Comment:
PLANS CALL OUT AN ELEVATOR TO BE INSTALLED. PLEASE SUBMIT THE ELEVATORS MANUFACTURES
1/15/2021
SHOP DRAWINGS AND INSTALLATION INSTRUCTIONS. MEETING THE REQUIREMENTS OF R321 OF THE
2017 FLORIDA RESIDENTIAL BUILDING CODE.
Comment:
PLEASE ADD TO THE PLANS THE SQUARE FOOT CALCULATION FOR THE ENCLOSED AREAS BELOW
1/15/2021
FLOOD TO DETERMINE THE MINIMUM NUMBER OF FLOOD VENTS REQUIRED FOR EACH AREA ENCLOSED
BELOW FLOOD. SEE SECTION R322.2.2 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE.
1/16/2021 Comment:
NO DETAIL SHOW ON THE PLANS FOR THE STAIRS. PLEASE ADD THE STAIR DETAILS TO THE PLANS IN
COMPLIANCE WITH R311.7 AND CHAPTER 322 OF THE 2017 FLORIDA BUILDING CODE.
1/15/2021 Comment:
PLEASE SEE THE WALL SECTIONS ON PAGE A2.02 OF THE PLANS. I AM UNABLE TO DETERMINE
COMPLIANCE WITH R322.1.8 FOR FLOOD RESISTANT MATERIALS.
Comment:
ELEVATOR DETAILS SHOW WOOD CONVENTIONAL CONSTRUCTION. I AM UNABLE TO DETERMINE IF THE
ELEVATORS CONSTRUCTION WILL NEED TO MEET THE REQUIREMENTS OF R322.1.8 DUE TO MISSING OR
1/15/2021
INCORRECT ELEVATION INFORMATION. IF THE LOWER PORTION OF THE ELEVATOR TOWER IS BELOW
FLOOD IT WILL NEED TO MEET THE REQUIREMENTS OF R322.1.8 OF THE 2017 FLORIDA RESIDENTIAL
BUILDING CODE.
1/15/2021 Comment:
PLEASE SEE SECTION R322.3.6 OF THE 2017 FLORIDA BUILDING CODE. PLEASE ADD TO THE PLANS THAT
THE DESIGN AND METHODS OF CONSTRUCTION MEETS THE REQUIREMENT OF THIS SECTION.
1/15/2021 Comment:
PLANS SHOW HOLLOW CORE DECKING. PLEASE SUBMIT THE MANUFACTURERS SHOP DRAWINGS AND
PLACEMENT PLAN FOR REVIEW. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
Planning ii 06volopmeot terviC8 •
SuiidRig &'C6de:Regu1Mon Division
23gq Virginia Avenue,
fortPtem%,FL, 346k
REVIEW COMMENTS
Page 3
Comment: SEE PAGE E1.01. ELECTRICAL DRAWINGS SHOW ELECTRICAL ITEMS ATTACHED TO BREAKAWAY WALLS.
1/15/2021 PLEASE SUBMIT CORRECTED ELECTRICAL PAGE IN COMPLIANCE WITH R322.3.4 OF THE 2017 FLORIDA
RESIDENTIAL BUILDING CODE.
Comment: • PLEASE NOTE THAT THE COMMENTS ARE FOR THE CLARIFICATION OR CORRECTION OF THE
1/15/2021 SUBMITTED DOCUMENTS. ADDITIONAL REVIEW MAY BE REQUIRED AFTER SUBMITTING CORRECTED
DOCUMENTS.
1/15/2021 Comment: PLEASE NOTE ALL CORRECTION WILL NEED TO BE IDENTIFIED WITH A CORRECTION REPORT FROM THE
DESIGN PROFESSIONAL, AND CLOUDING THE AREAS CORRECTED FOR RESUBMISSION.
ZONING REVIEW INCOMPLETE Angela Vassar 1/7/2021
Comment: PLEASE PROVIDE TWO SIGNED AND SEALED SURVEYS SHOWING THE MEASUREMENTS OF THE
PROPOSED RESIDENCE. PER CHAPTER 11.05.01 OF THE ST LUCIE COUNTY LAND DEVELOPMENT CODE
ALL SURVEYS SHALL COMPLETELY DEPICT THE FOLLOWING:
17HE LOCATION OF THE PROPOSED DEVELOPMENT ACTIVITY
2.THE RELATIONSHIP OF THE ACTIVITY UNDER APPLICATION TO ALL ADJACENT PROPERTY LINES, AND AS
MAY BE REQUIRED FOR THE REVIEW OF THE APPLICATION, ALL ADJACENT STRUCTURES,
IMPROVEMENTS OR NATURAL FEATURES
3.A MINIMUM OF TWO (2) ELEVATIONS ALONG EACH ROADWAY ON WHICH THE PROPOSED ACTIVITY
BORDERS, THE EXISTING GROUND ELEVATION AT THE APPROXIMATE CENTER OF THE PROPOSED
STRUCTURE, THE EXISTING GROUND ELEVATION ALONG THE SIDE PROPERTY LINES ADJACENT TO THE
PROPOSED STRUCTURE, AND THE PROPOSED FINISHED FLOOR ELEVATION OF THE STRUCTURE UNDER
APPLICATION. ALL ELEVATIONS ARE TO BE BASED UPON NAVD; AND, EXCEPT FOR DETACHED SINGLE
1/7/2021 FAMILY RESIDENTIAL LOTS OR PARCELS OF LAND HAVING AN AREA OF ONE (1) ACRE OR LESS
4.THE LOCATION OF ALL NATIVE TREES OF 20 INCHES DBH AND GREATER, WITH THE SPECIFIC DIAMETER
AND TYPE OF TREE CLEARLY IDENTIFIED.
ALL SURVEYS SUBMITTED SHALL HAVE BEEN BE PREPARED, SIGNED AND SEALED BY A FLORIDA
REGISTERED LAND SURVEYOR, IN ACCORDANCE WITH THE CURRENT PROVISIONS OF CHAPTER 61G17-6,
FAC, EXCEPT THAT APPLICATIONS FOR INTERIOR MODIFICATIONS OR CONSTRUCTION, ROOFING
PERMITS NOT INVOLVING ANY STRUCTURAL ALTERATION OR ADDITIONS TO THE AREA COVERED BY THE
ROOF SURFACE, OR ANY OTHER PERMIT REQUIRED ACTIVITY THAT DOES NOT RESULT IN THE
EXPANSION OF ANY PORTION OF THE EXISTING STRUCTURES SHALL NOT BE REQUIRED TO SUBMIT
SURVEYS.
PLEASE SHOW THE COASTAL CONSTRUCTION CONTROL LINE ON THE SURVEY; PLEASE BE AWARE IF
ANY OF THE STRUCTURE LIES EAST OF THE COASTAL CONSTRUCTION CONTROL LINE A DEP PERMIT
WILL BE REQUIRED.
1/7/2021 Comment: PLEASE BE AWARE THESE ARE PRELIMINARY COMMENTS; THERE MAY BE MORE ZONING REVIEW
COMMENTS AFTER THE SURVEY IS OBTAINED.
1/7/2021 Comment: THE PLAN REVIEWER MAY HAVE ADDITIONAL COMMENTS.
i
Planning & Development Services REVIEW COMMENTS
Building R Code'Regula€ion Division
2300 Virginia Avenue
Fort Piece. FL. 34982
Page 3
Comment:
SEE PAGE E1.01. ELECTRICAL DRAWINGS SHOW ELECTRICAL ITEMS ATTACHED TO BREAKAWAY WALLS
1/15/2021
PLEASE SUBMIT CORRECTED ELECTRICAL PAGE IN COMPLIANCE WITH R322.3.4 OF THE 2017 FLORID
RESIDENTIAL BUILDING CODE. ),
Comment:
• PLEASE NOTE THAT THE COMMENTS ARE FOR THE CLARIFICATION OR CORRECTION OF THE
1/15/2021
SUBMITTED DOCUMENTS. ADDITIONAL REVIEW MAY BE REQUIRED AFTER SUBMITTING CORRECTED.
-
DOCUMENTS.
Comment:
PLEASE NOTE ALL CORRECTION WILL NEED TO BE IDENTIFIED WITH A CORRECTION REPORT FROM THE
1/15/2021
DESIGN PROFESSIONAL, AND CLOUDING THE AREAS CORRECTED FOR RESUBMISSION.
ZONING REVIEW INCOMPLETE Angela Vassar 1/7/2021
Comment:
PLEASE PROVIDE TWO SIGNED AND SEALED SURVEYS SHOWING THE MEASUREMENTS OF THE
PROPOSED RESIDENCE. PER CHAPTER 11.05.01 OF THE ST LUCIE COUNTY LAND DEVELOPMENT CODE
ALL SURVEYS SHALL COMPLETELY DEPICT THE FOLLOWING:
13HE LOCATION OF THE PROPOSED DEVELOPMENT ACTIVITY
23HE RELATIONSHIP OF THE ACTIVITY UNDER APPLICATION TO ALL ADJACENT PROPERTY LINES, AND AS
MAY BE REQUIRED FOR THE REVIEW OF THE APPLICATION, ALL ADJACENT STRUCTURES,
IMPROVEMENTS OR NATURAL FEATURES
3.A MINIMUM OF TWO (2) ELEVATIONS ALONG EACH ROADWAY ON WHICH THE PROPOSED ACTIVITY
r
BORDERS, THE EXISTING GROUND ELEVATION AT THE APPROXIMATE CENTER OF THE PROPOSED
STRUCTURE, THE EXISTING GROUND ELEVATION ALONG THE SIDE PROPERTY LINES ADJACENT TO THE
PROPOSED STRUCTURE, AND THE PROPOSED FINISHED FLOOR ELEVATION OF THE STRUCTURE UNDER
APPLICATION. ALL ELEVATIONS ARE TO BE BASED UPON NAVD; AND, EXCEPT FOR DETACHED SINGLE
FAMILY RESIDENTIAL LOTS OR PARCELS OF LAND HAVING AN AREA OF ONE (1) ACRE OR LESS
1/7/20121
47HE LOCATION OF ALL NATIVE TREES OF 20 INCHES DBH AND GREATER, WITH THE SPECIFIC DIAMETER
AND TYPE OF TREE CLEARLY IDENTIFIED.
ALL SURVEYS SUBMITTED SHALL HAVE BEEN BE PREPARED, SIGNED AND SEALED BY A FLORIDA
REGISTERED LAND SURVEYOR, IN ACCORDANCE WITH THE CURRENT PROVISIONS OF CHAPTER 61G17-6,
FAC, EXCEPT THAT APPLICATIONS FOR INTERIOR MODIFICATIONS OR CONSTRUCTION, ROOFING
PERMITS NOT INVOLVING ANY STRUCTURAL ALTERATION OR ADDITIONS TO THE AREA COVERED BY THE
ROOF SURFACE, OR ANY OTHER PERMIT REQUIRED ACTIVITY THAT DOES NOT RESULT IN THE
EXPANSION OF ANY PORTION OF THE EXISTING STRUCTURES SHALL NOT BE REQUIRED TO SUBMIT
SURVEYS.
PLEASE SHOW THE COASTAL CONSTRUCTION CONTROL LINE ON THE SURVEY; PLEASE BE AWARE IF
ANY OF THE STRUCTURE LIES EAST OF THE COASTAL CONSTRUCTION CONTROL LINE A DEP PERMIT
WILL BE REQUIRED.
Comment:
PLEASE BE AWARE THESE ARE PRELIMINARY COMMENTS; THERE MAY BE MORE ZONING REVIEW
1/7/2021
COMMENTS AFTER THE SURVEY IS OBTAINED.
1 /712021 Comment:
THE PLAN REVIEWER MAY HAVE ADDITIONAL COMMENTS.
Plannin9 E Develop ment Services
BtflIding & Coda Regulation Division
2300 Virglnla Avenues
FortPi ease, FL. V.482
REVIEW COMMENTS
I' Page 2
St1RMITTFI) PI ANS ARF CnPIFS WITH nIC;ITAI RIANATI IRF ANn RFAI R . IF THE A nnfa IMFNT 1A
SUBMITTED WITH A DIGITAL SIGNATURE THE DOCUMENT MUST BE SUBMIT AS A DIGITAL SUBMISSION
1/14/2021 WITH THE ORIGINAL SIGNATURE. IF THE DOCUMENTS ARE SUBMITTED IN PAPER FORM IT MUST HAVE
THE RAISED OR WET SEAL WITH THE ORIGINAL SIGNATURE. PLEASE RESUBMIT. SEE SECTION 107 OF
/T' HE 2017 FLORIDA BUILDING CODE.
Comm' ' enPLANS ARE INUNDATED WITH CODE SECTIONS. PLEASE REMOVE THE SECTIONS THAT DO NOT PERTAIN
1/1412021 TO THE CONSTRUCTION OF THE PROPOSED STRUCTURE. SEE SECTION 107 OF THE 2017 FLORIDA
BUILDING CODE.
�j—/ Comment: PAGE A1.01, NOTE SECTION SPECIFIES WINDOW AND DOORS BY OTHER, SEPARATE PERMIT. PLEASE
a�14/2021 REMOVE THIS SECTION AND ADD THE PRODUCT REVIEW AFFIDAVIT TO THE PLANS WITH THE
,00'` INSTALLATION INSTRUCTIONS COMPLETED. OR ADD THE PRODUCT APPROVALS FOR THE WINDOWS AND
DOORS. SEE SECTION 107.2.4 OF THE 2017 FLORIDA BUILDING CODE.
1/14/2021 Comment: PLEASE SUBMIT A GEOTECHNICAL EVALUATION WITH THE FOUNDATION RECOMMENDATIONS. (SOIL ✓
BORING TEST),SEE SECTION R401.4 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE.
1/14/202,1 ,oj / Comment: • PLEASE FURNISH TRUSS ENGINEERING IN DUPLICATE PER CHAPTER 8 SECTION R802 SUBSECTION
C"" V ! R802.1.7.1 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE.
Comments • PLEASE FURNISH THE MANUFACTURES TRUSS PLACEMENT DRAWINGS IN DUPLICATE REVIEWED AND✓
111412.021 APPROVED BY THE DESIGN PERSON OF RECORD IN ACCORDANCE WITH 61G15-30.005 OF THE FLORIDA
ADMINISTRATIVE CODE.
1/15/2021 Comment: ENERGY CALC'S INFORMATION BLOCK AT THE TOP OF THE PAGE ARE INCOMEPLETE. SEE SECTION'v
05.4.2 (1) OF THE 2017 FLORIDA ENERGY CODE.
r— C:ommentV • LINE SEVEN ON THE ENERGY CALC'S ARE INCORRECT, MULTIPLE TYPES AND SIZES OF GLAZED
1/15/2021 OPENINGS ON PLANS. PLEASE CORRECT ENERGY CALC'S AS PER SECTION R401.3 OF THE 2017 FLORIDA
BUILDING CODE ENERGY CONSERVATION 6TH EDITION.
Comment: • LINE EIGHT ON THE ENERGY CALC'S ARE INCORRECT, SEE PLAN DETAILS. PLEASE CORRECT ENERGY
1/15/2021 CALC'S AS PER SECTION R401.3 OF THE 2017 FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH W
EDITION.
Comment: • LINE NINE ON THE ENERGY CALC'S ARE INCORRECT, SEE PLAN DETAILS. PLEASE CORRECT ENERGY
1/15/2021 CALC'S AS PER SECTION R401.3 OF THE 2017 FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH �
EDITION.
Comment: • LINE TEN ON THE ENERGY CALC'S ARE INCORRECT, SEE PLAN DETAILS. PLEASE CORRECT ENERGY✓
1/15/2021 CALC'S AS PER SECTION R401.3 OF THE 2017 FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH
EDITION.
Comment: PLEASE ADD THE CUBIC VOLUME ON THE PLANS. THE PLANS SHOULD MATCH THE CUBIC VOLUME
SPECIFIED ON THE ENERGY CALC'S. THE CUBIC VOLUME NUMBER IS USED IN THE CALCULATIONS FOR,,,,'
THE BLOWER DOOR TESTING. PLEASE CHECK WITH THE COMPANY THAT CALCULATED THE CUBIC
1/15/2021 VOLUME ON THE ENERGY CALC'S AND THE DESIGN PROFESSIONAL TO COLLATE THE CUBIC VOLUME.
THE NUMBER SHOULD INCLUDE THE ATTIC SPACE AS THE SPRAY FOAM INSULATION IS INSTALLED TO
THE ROOF DECK AND IS NOT VENTED. THIS IS CONSIDERED CONDITIONED SPACE. SEE SECTION
CHAPTER 2 DEFINITION OF CONDITION SPACE OF THE 2017 FLORIDA ENERGY CODE. ✓
1/15/2021 SUPPLYING
` PLEASE CLARIFY NOTE ON PAGE A1.02 FOR THE AS -BUILT ELEVATION DOCUMENTATION. WILL YOU BE
V SUPPLYING AS BUILT DRAWINGS?
Comment: PLANS CALL OUT AN ELEVATOR TO BE INSTALLED. PLEASE SUBMIT THE ELEVATORS MANUFACTURES
1/15/2021 SHOP DRAWINGS AND INSTALLATION INSTRUCTIONS. MEETING THE REQUIREMENTS OF R321 OF THE
2017 FLORIDA RESIDENTIAL BUILDING CODE.
Comment: PLEASE ADD TO THE PLANS THE SQUARE FOOT CALCULATION FOR THE ENCLOSED AREAS BELOW
1/15/2021 FLOOD TO DETERMINE THE MINIMUM NUMBER OF FLOOD VENTS REQUIRED FOR EACH AREA ENCLOSE
BELOW FLOOD. SEE SECTION R322.2.2 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE.
1/15/2021 Comment: NO DETAIL SHOW ON THE PLANS FOR THE STAIRS. PLEASE ADD THE STAIR DETAILS TO THE PLANS IN
COMPLIANCE WITH R311.7 AND CHAPTER 322 OF THE 2017 FLORIDA BUILDING CODE. ,
1/15/2021 Comment: PLEASE SEETHE WALL SECTIONS ON PAGE A2.02 OF THE PLANS. I AM UNABLE TO DETERMINE � ��'
COMPLIANCE WITH R322.1.8 FOR FLOOD RESISTANT MATERIALS.
Comment: ELEVATOR DETAILS SHOW WOOD CONVENTIONAL CONSTRUCTION. I AM UNABLE TO DETERMINE IF THE
ELEVATORS CONSTRUCTION WILL NEED TO MEET THE REQUIREMENTS OF R322.1.8 DUE TO MISSING OR
1/15/2021 INCORRECT ELEVATION INFORMATION. IF THE LOWER PORTION OF THE ELEVATOR TOWER IS BELOW- /
FLOOD IT WILL NEED TO MEET THE REQUIREMENTS OF R322.1.8 OF THE 2017 FLORIDA RESIDENTIAL y
BUILDING CODE. '
1/15/2021 Comment: PLEASE SEE SECTION R322.3.6 OF THE 2017 FLORIDA BUILDING CODE. PLEASE ADD TO THE PLANS THAT
THE DESIGN AND METHODS OF CONSTRUCTION MEETS THE REQUIREMENT OF THIS SECTION.
1/151202.1 Commen PLANS SHOW HOLLOW CORE DECKING. PLEASE SUBMIT THE MANUFACTURERS SHOP DRAWINGS AND
PLACEMENT PLAN FOR REVIEW. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
/4 _
,r
Planning & Development Services
Building & Coda ReQUIB ion Division
2 300 Vic ginia Avenue*
Fort Pierce, FL. 34982
PROPERTY INFORMATION
Address: 4845 Watersong Way
City I State I Zip: Fort Pierce, FI 34949
Parcel #: 2532-500-0024-000/9
Zoning:
REVIEW COMMENTS
Owner(s):
Carlos Lanza (Tr)
Jurisdiction: SAINT LUCIE COUNTY
Lot#: 10 Block:
APPLICATION INFORMATION
Permit Number: 2012-0614 Stories:
Permit Type: BUILDING RESIDENTIAL (SFR UP TO 2 FLOORS)
CONTRACTOR INFORMATION
Contractor Name:
Carlos Lanza
Business Name:
Cl Contractors Corp
Business Addr:
8531 Sw 167 Terr
City / State / Zip:
Miami, FI 33157
REVIEWS AND COMMENTS
Page 1
Automatic Sprinkler System? No
Fax Number:
Review Type
Status Reviewed By Date Started
DOCUMENTS MISSING
PENDING Lashahna Ingram
12/28/2020
Comment:
NEEDS TO SUBMIT FILLED LANDS
12/28/2020
Comment:
SUB CONTRACTOR AGREEMENTS FOR ALL TRADES
12/28/2020
Comment:
NEEDS TO SUBMIT DRIVEWAY PERMIT
ENVIRONMENTAL REVIEW
INCOMPLETE Lynn Swartzel 12/30/2020
1/4/2021
Comment:
NEED COPY OF SURVEY WITH PROPOSED BUILDING.
FRONT COUNTER REVIEW
COMPLETE Lashahna Ingram 12/28/2020
Comment:
NOTIFIED FOR PICK UP PENDING
Comment:
PLANS EXAMINER REVIEW
1/14/2021 Comment:
1/14/202.1 Comment:
,Comment:
1 /14/2021
INCOMPLETE William Durden 1/14/2021
Email: Clcontractors@Comcast.Ne
t
Date Completed Date Released
12128/2020 12/28/2020
SUBMITTED PLANS ARE NGVD. PLEASE REVISE PLANS TO REFLECT NAVD. &'*'�
UNABLE TO REVIEW SECTION 322 OF THE 017 FLORIDA RESIDENTIAL BUILDING CODE FOR FLOOD
REQUIREMENTS. PLANS ARE IN NGVD.
UNABLE TO REVIEW SECTION 322 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE FOR FLOOD
REQUIREMENTS FOR THE LOWEST HORIZONAL STRUCTURAL MEMBER. PLEASE SUBMIT THE FDEP
DOCUMENTS FOR THE LOWEST HORIZONAL STRUCTU AL MEMBERS ELEVATION. SEE SECTION 107 OF
THE 2017 FLORIDA BUILDING CODE. , (J �)j . 0 C c L
Planning & Development Services REVIEW COMMENTS
Building&:Code Regulation Division
230D Virginia Avenue
Fort Pierce, FL. 34982
Page 2
Y
Comment.
SUBMITTED PLANS ARE COPIES WITH DIGITAL SIGNATURE AND SEALS. + IF THE A DOCUMENT IS
SUBMITTED WITH A DIGITAL SIGNATURE THE DOCUMENT MUST BE SUBMIT AS A DIGITAL SUBMISSION
1/14/2021
WITH THE ORIGINAL SIGNATURE. IF THE DOCUMENTS ARE SUBMITTED IN PAPER FORM IT MUST HAVE
THE RAISED OR WET SEAL WITH THE ORIGINAL SIGNATURE. PLEASE RESUBMIT. SEE SECTION 107 OF
THE 2017 FLORIDA BUILDING CODE. Response: New signed and sealed submitted
/
Comment:
PLANS ARE INUNDATED WITH CODE SECTIONS. PLEASE REMOVE THE SECTIONS THAT DO NOT PERTAIN
1/14/2021
TO THE CONSTRUCTION OF THE PROPOSED STRUCTURE. SEE SECTION 107 OF THE 2017 FLORIDA
BUILDING CODE. Response: Removed
Comment/
PAGE A1.01, NOTE SECTION SPECIFIES WINDOW AND DOORS BY OTHER, SEPARATE PERMIT. PLEASE
1/14/2021
REMOVE THIS SECTION AND ADD THE PRODUCT REVIEW AFFIDAVIT TO THE PLANS WITH THE
NSTALLATION INSTRUCTIONS COMPLETED. OR ADD THE PRODUCT APPROVALS FOR THE WINDOWS AND
DOORS. SEE SECTION 107.2.4 OF THE 2017 FLORIDA BUILDING CODE. Response: Product review on Sht. A2.00
1/14/2021 Comment:
PLEASE SUBMIT A GEOTECHNICAL EVALUATION WITH THE FOUNDATION RECOMMENDATIONS. (SOIL
BORING TEST),SEE SECTION R401.4 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE. Response: Attached
1/14/2021 �( Comment:
• PLEASE FURNISH TRUSS ENGINEERING IN DUPLICATE PER CHAPTER 8 SECTION R802 SUBSECTION
/
R802.1.7.1 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE. Response: Attached
Comment:/
• PLEASE FURNISH THE MANUFACTURES TRUSS PLACEMENT DRAWINGS IN DUPLICATE REVIEWED AND
1/14/2021
APPROVED BY THE DESIGN PERSON OF RECORD IN ACCORDANCE WITH 61G15-30.005 OF THE FLORIDA
ADMINISTRATIVE CODE. Response: Attached
1/15/2021 Comment/
• ENERGY CALC'S INFORMATION BLOCK AT THE TOP OF THE PAGE ARE INCOMEPLETE. SEE SECTION
/
405.4.2 (1) OF THE 2017 FLORIDA ENERGY CODE. Response: New energy caics attached
Comment:
• LINE SEVEN ON THE ENERGY CALC'S ARE INCORRECT, MULTIPLE TYPES AND SIZES OF GLAZED
1/15/2021
OPENINGS ON PLANS. PLEASE CORRECT ENERGY CALC'S AS PFR SFCTION R401.8 OF THE 2017 FI ORIDA
J
BUILDING CODE ENERGY CONSERVATION 6TH EDITION. All windows shown pg 5 with sizes, orientation and info
Comment:
• LINE EIGHT ON THE ENERGY CALC'S ARE INCORRECT, SEE PLAN DETAILS. PLEASE CORRECT ENERGY
1/15/2021
CALC'S AS PER SECTION R401.3 OF THE 2017 FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH
EDITION. Response: New energy calcs attached and corrected
Comment:
• LINE NINE ON THE ENERGY CALC'S ARE INCORRECT, SEE PLAN DETAILS. PLEASE CORRECT ENERGY
1/15/2021
CALC'S AS PER SECTION R401.3 OF THE 2017 FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH
/
EDITION. Response: New energy calcs attached and corrected
Comment: J
• LINE TEN ON THE ENERGY CALC'S ARE INCORRECT, SEE PLAN DETAILS. PLEASE CORRECT ENERGY
1/15/2021
CALC'S AS PER SECTION R401.3 OF THE 2017 FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH
EDITION. Response: New energy calcs attached and corrected
Comment:
PLEASE ADD THE CUBIC VOLUME ON THE PLANS. THE PLANS SHOULD MATCH THE CUBIC VOLUME
SPECIFIED ON THE ENERGY CALC'S. THE CUBIC VOLUME NUMBER IS USED IN THE CALCULATIONS FOR
d,
THE BLOWER DOOR TESTING. PLEASE CHECK WITH THE COMPANY THAT CALCULATED THE CUBIC
1/15/2021 �° o'
VOLUME ON THE ENERGY CALC'S AND THE DESIGN PROFESSIONAL TO COLLATE THE CUBIC VOLUME.
w Q
THE NUMBER SHOULD INCLUDE THE ATTIC SPACE AS THE SPRAY FOAM INSULATION IS INSTALLED TO
THE ROOF DECK AND IS NOT VENTED. THIS IS CONSIDERED CONDITIONED SPACE. SEE SECTION
/
CHAPTER 2 DEFINITION OF CONDITION SPACE OF THE 2017 FLOR IDA ENERGY CODE. See Sht. A1.00
1/15/2021 Comment:
PLEASE CLARIFY NOTE ON PAGE A1.02 FOR THE AS -BUILT ELEVATION DOCUMENTATION. WILL YOU BE
SUPPLYING AS BUILT DRAWINGS? Response: Note removed
Comment:
PLANS CALL OUT AN ELEVATOR TO BE INSTALLED. PLEASE SUBMIT THE ELEVATORS MANUFACTURES
1/15/2021
SHOP DRAWINGS AND INSTALLATION INSTRUCTIONS. MEETING THE REQUIREMENTS OF R321 OF THE
2017 FLORIDA RESIDENTIAL BUILDING CODE. Response: Shown Sht. A1.02
Commen A
PLEASE ADD TO THE PLANS THE SQUARE FOOT CALCULATION FOR THE ENCLOSED AREAS BELOW
1/15/2021 1`
FLOOD TO DETERMINE THE MINIMUM NUMBER OF FLOOD VENTS REQUIRED FOR EACH AREA ENCLOSED
/
BELOW FLOOD. SEE SECTION R322.2.2 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE. All above Flood
1/15/2021 Comment:/
NO DETAIL SHOW ON THE PLANS FOR THE STAIRS. PLEASE ADD THE STAIR DETAILS TO THE PLANS IN
COMPLIANCE WITH R311.7 AND CHAPTER 322 OF THE 2017 FLORIDA BUILDING CODE. Response: Sht. A6.00
1/15/2021 Comment-
PLEASE SEE THE WALL SECTIONS ON PAGE A2.02 OF THE PLANS. I AM UNABLE TO DETERMINE
0'/
COMPLIANCE WITH R322.1.8 FOR FLOOD RESISTANT MATERIALS. Response: Sht. A6.00
Comment:
ELEVATOR DETAILS SHOW WOOD CONVENTIONAL CONSTRUCTION. I AM UNABLE TO DETERMINE IF THE
ELEVATORS CONSTRUCTION WILL NEED TO MEET THE REQUIREMENTS OF R322.1.8 DUE TO MISSING OR
1/15/2021
INCORRECT ELEVATION INFORMATION. IF THE LOWER PORTION OF THE ELEVATOR TOWER IS BELOW
)j�"
FLOOD IT WILL NEED TO MEET THE REQUIREMENTS OF R322.1.8 OF THE 2017 FLORIDA RESIDENTIAL
BUILDING CODE. Response: Note on Sht. A2.00 added and areas raised above flood level
1/15/2021 Comment3l
PLEASE SEE SECTION R322.3.6 OF THE 2017 FLORIDA BUILDING CODE. PLEASE ADD TO THE PLANS THAT
THE DESIGN AND METHODS OF CONSTRUCTION MEETS THE REQUIREMENT OF THIS SECTION. See Sht. A2.00
1/15/2021 Comment:"/
PLANS SHOW HOLLOW CORE DECKING. PLEASE SUBMIT THE MANUFACTURERS SHOP DRAWINGS AND
PLACEMENT PLAN FOR REVIEW. SEE SECTION 107 OF THE 2017 FLORIDA BUILDING CODE. Response: Attached
Plattining & Development Servlclle
Building &Code ReWla6nblvsslon.
;230G 1/lrginla Auenue
Fort Pierce, FL 3499.2
REVIEW COMMENTS
Comment: SEE PAGE E1.01. ELECTRICAL DRAWINGS SHOW ELECTRICAL ITEMS ATTACHED TO BREAKAWAY WALLS.
1/15/2021 1PLEASE SUBMIT CORRECTED ELECTRICAL PAGE IN COMPLIANCE WITH R322.3.4 OF THE 2017 FLORIDA
I" RESIDENTIAL BUILDING CODE. Response: No breakaway walls required
Comment: • PLEASE NOTE THAT THE COMMENTS ARE FOR THE CLARIFICATION OR CORRECTION OF THE
1/15/2021 SUBMITTED DOCUMENTS. ADDITIONAL REVIEW MAY BE REQUIRED AFTER SUBMITTING CORRECTED
DOCUMENTS.
1/15/2021 Comment: PLEASE NOTE ALL CORRECTION WILL NEED TO BE IDENTIFIED WITH A CORRECTION REPORT FROM THE
DESIGN PROFESSIONAL, AND CLOUDING THE AREAS CORRECTED FOR RESUBMISSION.
ZONING REVIEW INCOMPLETE Angela Vassar 1/7/2021
Comment: PLEASE PROVIDE TWO SIGNED AND SEALED SURVEYS SHOWING THE MEASUREMENTS OF THE
'PROPOSED RESIDENCE. PER CHAPTER 11.05.01 OF THE ST LUC:IE (' MINTY LAND DEVELOPMENT CODE
ALL SURVEYS SHALL COMPLETELY DEPICT THE FOLLOWING: Response: New survey attached
1.THE LOCATION OF THE PROPOSED DEVELOPMENT ACTIVITY
2.THE RELATIONSHIP OF THE ACTIVITY UNDER APPLICATION TO ALL ADJACENT PROPERTY LINES, AND
AS MAY BE REQUIRED FOR THE REVIEW OF THE APPLICATION, ALL ADJACENT STRUCTURES,
IMPROVEMENTS OR NATURAL FEATURES
3.A MINIMUM OF TWO (2) ELEVATIONS ALONG EACH ROADWAY ON WHICH THE PROPOSED ACTIVITY
BORDERS, THE EXISTING GROUND ELEVATION AT THE APPROXIMATE CENTER OF THE PROPOSED
STRUCTURE, THE EXISTING GROUND ELEVATION ALONG THE SIDE PROPERTY LINES ADJACENT TO THE
PROPOSED STRUCTURE, AND THE PROPOSED FINISHED FLOOR ELEVATION OF THE STRUCTURE UNDER
APPLICATION. ALL ELEVATIONS ARE TO BE BASED UPON NAVD; AND, EXCEPT FOR DETACHED SINGLE
1/7/2021 FAMILY RESIDENTIAL LOTS OR PARCELS OF LAND HAVING AN AREA OF ONE (1) ACRE OR LESS
4.THE LOCATION OF ALL NATIVE TREES OF 20 INCHES DBH AND GREATER, WITH THE SPECIFIC
DIAMETER AND TYPE OF TREE CLEARLY IDENTIFIED.
ALL SURVEYS SUBMITTED SHALL HAVE BEEN BE PREPARED, SIGNED AND SEALED BY A FLORIDA
REGISTERED LAND SURVEYOR, IN ACCORDANCE WITH THE CURRENT PROVISIONS OF CHAPTER 61 G17-
6, FAC, EXCEPT THAT APPLICATIONS FOR INTERIOR MODIFICATIONS OR CONSTRUCTION, ROOFING
PERMITS NOT INVOLVING ANY STRUCTURAL ALTERATION OR ADDITIONS TO THE AREA COVERED BY THE
ROOF SURFACE, OR ANY OTHER PERMIT REQUIRED ACTIVITY THAT DOES NOT RESULT IN THE
EXPANSION OF ANY PORTION OF THE EXISTING STRUCTURES SHALL NOT BE REQUIRED TO SUBMIT
SURVEYS.
PLEASE SHOW THE COASTAL CONSTRUCTION CONTROL LINE ON THE SURVEY; PLEASE BE AWARE IF
ANY OF THE STRUCTURE LIES EAST OF THE COASTAL CONSTRUCTION CONTROL LINE A DEP PERMIT
WILL BE REQUIRED. Response: New survey attached
1/7/2021 Comment: PLEASE BE AWARE THESE ARE PRELIMINARY COMMENTS; THERE MAY BE MORE ZONING REVIEW
COMMENTS AFTER THE SURVEY IS OBTAINED.
1/7/2021 Comment: THE PLAN REVIEWER MAY HAVE ADDITIONAL COMMENTS.
Do not hesitate to call if we can be of further assistance.
Best regards,
Carlos Lanza, RA
Burgos Lanza & Associates