HomeMy WebLinkAboutAPPROVED, Widman Residence - Stamped full permit set - Rev1(1)SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-1
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
TITLE SHEET
PROJECT LOCATION
PROJECT INFORMATION
x 37 X 365W LG365N1K-A6
MONOCRYSTALLINE PV MODULES
x 1 X SOLAREDGE SE10000H-US INVERTER
x DC SYSTEM SIZE: 13.505 KW STC
x AC SYSTEM SIZE: 10.000 KW STC
x ARRAY AREA: 721.63 SF
x AHJ: SAINT LUCIE COUNTY
x APN: 3419-530-0073-000-5
THIS PROJECT CONSISTS OF THE INSTALLATION OF (37) PHOTOVOLTAIC MODULES WITH (1) UTILITY INTERACTIVE INVERTER. PV MODULES WILL BE
MOUNTED TO AN EXISTING COMP SHINGLE ROOF TOP USING QUICKMOUNT L-MOUNT ATTACHMENTS AND QUICKMOUNT RAIL.
THE ATTACHMENT SYSTEM IS SPECIFICALLY DESIGNED TO WITHSTAND WIND LOADS AND SEISMIC LOADS ON EXISTING ROOFTOPS. REFER TO
CODE COMPLIANT INSTALLATION MANUAL FOR DETAILED INFORMATION AND WATER PROOFING SPECIFICATIONS.
PLAN SET LEGENDS & ABBREVIATIONS
MSP
SUB
AC
DC
SLC
INV
MAIN SERVICE PANEL
SUB SERVICE PANEL
AC DISCONNECT
DC DISCONNECT
SOLAR LOAD CENTER
INVERTER
JB JUNCTION BOX
ECB ENPHASE COMBINER BOX
RS RAPID SHUTDOWN DEVICE
(E) EXISTING
(N) NEW
EXT EXTERIOR
INT INTERIOR
EMT ELECTRICAL METALLIC TUBING
RMT RIGID METALLIC TUBING
VOC VOLTAGE OPEN CIRCUIT
VMP VOLTAGE AT MAX. POWER
ISC SHORT CIRCUIT CURRENT
IMP CURRENT AT MAX. POWER
M MONITORING METER
NTS NOT TO SCALE
SHEET INDEX
SHEET
NO.
INDEX
NO.PAGE TITLE
01 PV-1 TITLE SHEET
02 PV-1.1 GENERAL NOTES
03 PV-2 SITE PLAN
04 PV-3 ROOF PV LAYOUT
05 PV-4 STRING LAYOUT
06 PV-5 ATTACHMENT DETAIL
07 PV-6 ELECTRICAL LINE DIAGRAM
08 PV-7 SAFETY PLACARD
09 PV-8 MODULE DATASHEET
10 PV-9 INVERTER DATASHEET
11 PV-10 OPTIMIZER DATASHEET
12 PV-11 RACKING DATASHEET
13 PV-12 ATTACHMENT DATASHEET
14 PV-13 ATTACHMENT DATASHEET
15 PV-14 COMPLIANCE CERTIFICATE
16 PV-15 SEALANT DATASHEET
17 PV-16 SEALANT DATASHEET
18 PV-17 SEALANT DATASHEET
VICINITY MAP
SCALE: NTS
AERIAL VIEW
SCALE: NTS
SCOPE OF WORK
APPLICABLE CODES
ALL WORK TO COMPLY WITH THE FOLLOWING CODES:
x 2020 FLORIDA BUILDING CODE
x 2020 FLORIDA RESIDENTIAL CODE
x 2020 FLORIDA MECHANICAL CODE
x 2017 NATIONAL ELECTRICAL CODE
x 2020 FLORIDA GREEN CODE
x 2020 FLORIDA PLUMBING CODE
x 2020 FLORIDA ENERGY CODE
x 2020 FLORIDA FIRE CODE
DESIGN CRITERIA:
ROOF TYPE: - ASPHALT SHINGLE
ROOF FRAME: - 2"X4" TRUSS @24" O.C.
SNOW LOAD : - 0 PSF
WIND SPEED :- 160 MPH
WIND EXPOSURE:- C
EXPOSURE CATEGORY:- II
COORDINATES :- 27.321919, -80.336305
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-1.1
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
NOTES
GENERAL NOTES:
x PHOTOVOLTAIC SYSTEM EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE
WITH 2011 NEC, AND THE 2012 IRC/IBC, AND APPLICABLE REQUIREMENTS OF
THE SERVICE UTILITY AND AUTHORITY HAVING JURISDICTION. PHOTOVOLTAIC
SYSTEM EQUIPMENT WILL BE POSTED WITH APPLICABLE WARNINGS,
SIGNAGE AND PLAQUES PER NEC 690.17, 705.10 AND 705.12.
x PHOTOVOLTAIC SOURCE AND OUTPUT CIRCUITS SHALL COMPLY WITH THE
WIRING METHODS AND INSTALLATION AND MARKING REQUIREMENTS OF NEC
690.31(E).
x BREAKER LABELED "PHOTOVOLTAIC ELECTRIC POWER SOURCE" AND
"BREAKERS ARE BACK FED" PER NEC 705.12. BREAKER ALSO LABELED
"MAXIMUM AC OUTPUT CURRENT AND OPERATING AC VOLTAGE" PER NEC
690.54. BREAKER SHALL BE POSITIONED AT THE OPPOSITE (LOAD) END FROM
THE INPUT FEEDER OR MAIN CIRCUIT BREAKER LOCATION, AND LABELED
"WARNING INVERTER OUTPUT CONNECTION DO NOT RELOCATE THIS
OVERCURRENT DEVICE", PER NEC 705.12(D)(7).
x LABEL "PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT SWITCH." SWITCH TO
BE LOCKED PER 2011 NEC. SWITCH TO BE VISIBLE BLADE DISCONNECT PER
UTILITY REQUIREMENTS AND CONFORM TO NEC 705.22.
x BI-DIRECTIONAL METER TO BE INSTALLED BY UTILITY.
x DEDICATED PHOTOVOLTAIC COMBINER SUB-PANEL. LABEL "LOADS NOT TO BE
x ADDED TO THIS PANEL."
x ALL LABELS EXPOSED TO SUNLIGHT MUST BE ENGRAVED AND ATTACHED PER
APPROVED METHOD.
x EXISTING EQUIPMENT IS NOTED WITH A DASHED LINE. SOLID LINES DENOTE
EQUIPMENT INSTALLED BY ELECTRICAL CONTRACTOR.
x WIRE MAY BE RUN SHORT DISTANCES OUTSIDE OF CONDUIT IF WIRE READS
"SUNLIGHT RESISTANT."
x THE GROUNDING ELECTRODE CONDUCTOR SHALL BE CONTINUOUS AND
TERMINATE WITH AN IRREVERSIBLE CONNECTION TO THE AC GROUNDING
ELECTRODE SYSTEM PER NEC 250.64.
x AMBIENT TEMPERATURE ADJUSTED FOR CONDUITS EXPOSED TO SUNLIGHT
ON OR ABOVE ROOFTOPS PER TABLE 310.15 (B)(2)(c). CONDUIT ELEVATED MIN.
3 1/2"; ADDER 30 DEG F.
x ALL EXTERIOR EQUIPMENT TO BE NEMA 3R.
x THE PHOTOVOLTAIC POWER SOURCE SHALL BE LABELED WITH THE
FOLLOWING WARNING AT EACH JUNCTION BOX, COMBINER BOX, DISCONNECT
AND DEVICE WHERE ENERGIZED, UNGROUNDED CIRCUITS MAY BE EXPOSED
DURING SERVICE: WARNING: ELECTRIC SHOCK HAZARD. THE DC
CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNGROUNDED AND MAY
BE ENERGIZED.
AHJ NOTES:
x THE CONTRACTOR SHALL SCHEDULE A PRE-CONSTRUCTION MEETING WITH
THE ELECTRICAL INSPECTOR AND ALL INSTALLERS PRESENT. AT THE
PRE-CONSTRUCTION MEETING THE CONTRACTOR SHALL PROVIDE A
COMPLETE SET OF APPROVED DRAWINGS AND A COMPLETE PERMIT PACK
CONTAINING ALL MANUFACTURES SPECIFICATIONS FOR ALL EQUIPMENT,
COMPONENTS, LABELS, AND ANY/ALL ANCILLARY MATERIALS TO BE
INSTALLED.
x AT THE PRE-CONSTRUCTION MEETING THE ELECTRICAL INSPECTOR SHALL
REVIEW ALL DRAWING AND DOCUMENTS TO VERIFY ALL COMPONENTS TO BE
INSTALLED CORRESPOND WITH THE APPROVED DOCUMENTS, ALL
APPLICABLE LISTINGS, AND ALL MANUFACTURES SPECIFICATIONS.
x AT THE PRE-CONSTRUCTION MEETING THE ELECTRICAL INSPECTOR SHALL
VERIFY THE CREDENTIALS OF ALL WORKERS PRESENT ON THE JOB SITE. ALL
WORKERS ON THE JOB SITE SHALL MEET THE REQUIREMENTS OF "QUALIFIED
PERSONS" AS DEFINED BY NFPA 70 AND NFPA 70E.
x AT THE PRE-CONSTRUCTION MEETING ACCEPTABLE DOCUMENTATION
WOULD INCLUDE NABCEP PV INSTALLER SPECIALIST CERTIFICATION, NABCEP
PV INSTALLATION PROFESSIONAL CERTIFICATION OR EQUIVALENT. ANY
EQUIVALENT DOCUMENTATION SHALL BE RECOLONIZED BY THE
DEPARTMENT OF LABOR OR THE DEPARTMENT OF EDUCATION AND SHALL
INCLUDE TRAINING IN ALL APPLICABLE OSHA REQUIREMENTS INCLUDED IN
THE NABCEP CERTIFICATION PROGRAM.
x UPON SATISFACTORY COMPLETION OF PRE-CONSTRUCTION MEETING WORK
SHALL BE ALLOWED TO BEGIN.
x THE CONTRACTOR SHALL SCHEDULE A ROUGH INSPECTION. A ROUGH
INSPECTION SHALL BE PERFORMED PRIOR TO THE INSTALLATION OF ANY
PANELS.
x AT THE ROUGH INSPECTION THE INSPECTOR SHALL EXAMINE ALL CONDUITS,
BOXES, BUILDING WIRING, SERVICE CONNECTIONS, COMBINER BOXES,
INVERTERS, RAILING/RACKING COMPONENTS AND CONNECTIONS, ALL
FLASHINGS, AND ANY OTHER EQUIPMENT OR COMPONENTS WHICH FALL
UNDER THE USUAL CATEGORIZATION OF A ROUGH INSPECTION.
x AT THE ROUGH INSPECTION THE INSPECTOR SHALL CONFIRM ALL SERVICE
GROUNDING AND BONDING COMPLY WITH CURRENT STANDARDS.
x AT THE ROUGH INSPECTION THE CONTRACTOR SHALL SUPPLY THE
INSPECTOR WITH ANY/ALL PPE REQUIRED BY OSHA.
x AT THE ROUGH INSPECTION THE CONTRACTOR SHALL PROVIDE THE
INSPECTOR WITH SAFE ACCESS TO THE ROOF AND ATTIC TO PERFORM
HIS/HER DUTIES.
x UPON APPROVAL OF ROUGH INSPECTION, WORK SHALL BE ALLOWED TO
CONTINUE.
x UPON COMPLETION OF ALL WORK THE CONTRACTOR SHALL SCHEDULE A
FINAL INSPECTION.
x AT THE FINAL INSPECTION THE SYSTEM SHALL BE ENERGIZED FOR A SHORT
PERIOD OF TIME TO ALLOW FOR INSPECTION. A SHORT PERIOD OF TIME
SHALL BE DEFINED AS LESS THE TWO HOURS.
x UPON APPROVAL OF THE FINAL INSPECTION AND SUBMITTAL OF ALL
ADDITIONAL DOCUMENTATION REQUIRED BY THE COUNTY COMMERCE
COMMISSION AND THE UTILITY PROVIDER THE SYSTEM THEN SHALL BE
ALLOWED TO BE ENERGIZED AND REMAIN IN ITS NORMAL OPERATING
CONDITION.
ELECTRICAL NOTES:
x COMED REQUIRES AN INTERCONNECTION AGREEMENT PRIOR TO SYSTEM
START UP. PROVIDE COPY OF THE APPLICATION WITH COMED.
x ALL ELECTRIC WORK SHALL BE INSTALLED BY LICENSED SOLAR CERTIFIED
ELECTRICAL CONTRACTOR.
x ALL ELECTRIC SHALL BE IN CONDUIT. ALL ELECTRIC IN ATTICS SHALL BE 18
INCHES BELOW THE ROOF SHEATHING.
x CALL FOR PRECONSTRUCTION INSPECTION.
x SCHEDULE A ROUGH INSPECTION PRIOR TO PANEL INSTALLATION.
x CALL TO SCHEDULE A FINAL ELECTRIC INSPECTION.
x INSTALLER CERTIFICATES FOR QUALIFIED PERSONS. A LICENSED
ELECTRICAL CONTRACTOR SHALL BE ON THE SITE AT ALL TIMES. OTHER
CERTIFICATES INCLUDE NABCEP, UL CERTIFIED, ALL OTHER CERTIFICATE
SHALL BE FROM A GOVERNING BODY RECOGNIZED BY THE US DEPARTMENT
OF LABOR OR THE FLORIDA DEPARTMENT OF EDUCATION STATING QUALIFIED
PERSON FOR DISTRIBUTED GENERATION.
DESIGN CRITERIA:
ROOF TYPE: - ASPHALT SHINGLE
ROOF FRAME: - 2"X4" TRUSS @24" O.C.
SNOW LOAD : - 0 PSF
WIND SPEED :- 160 MPH
WIND EXPOSURE:- C
EXPOSURE CATEGORY:- II
COORDINATES :- 27.321919, -80.336305
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-2
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
SITE PLAN
1 SITE PLAN
PV-2 SCALE: 1/16" = 1'-0"
(37) PV SOLAR MODULES (TYP.)
3' FIRE SETBACK
(TYP.)
FIRE ACCESS POINT
(E) MAIN SERVICE PANEL,
200A RATED, 240V
RESIDENCE
(E) FENCE
(E) GATE
EXISTING
DRIVEWAY
(E) 1-STORY
HOUSE
x ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE
THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS
OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION
IN LOCATIONS WHERE THE ACCESS POINT DOES NOT CONFLICT WITH
OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS.
(37) SOLAREDGE POWER OPTIMIZER
P400 BELOW EACH PV MODULE (TYP.)SE TRANQUILLA AVEPROPERTY LINEPROPERTY LINEP
R
O
P
E
R
T
Y
L
I
N
E
PROPERTY LINE18" FIRE SETBACK
(TYP.)
24" WIND ZONE 2
WIND ZONE 1
24" WIND ZONE 3
MSPPVMINVUMJB1'-6"
1'-6"
5'-9"
1'
15'
1'-6"
9'-5"
11'-4"
41'-11"
11'-3"
7'-9"
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-3
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
1 ROOF PV LAYOUT
SCALE: 1/8" = 1'-0"PV-3
NUMBER OF MODULES: 37
MODULE TYPE: LG365N1K-A6 365W
MODULE WEIGHT: 41 LBS / 18.6 KG.
MODULE DIMENSIONS: 68.5" X 41"
MODULE AREA: 19.50 SF
UNIT WEIGHT OF MODULES: 41/19.50 = 2.10 LBS
MODULE TYPE, DIMENSIONS & WEIGHT INVERTER HAVE RAPID
SHUTDOWN REQUIREMENTS PER
NEC 2017 SECTION 690.12
ROOF
PV LAYOUT
ROOF DESCRIPTION
ROOF TYPE COMP SHINGLE
ROOF ARRAY
TILT AZIMUTH RAFTER
SIZE
RAFTER
SPACING
#1 18°225°2"x4" 24" O.C
#2 18°135°2"x4" 24" O.C
ARRAY AREA & ROOF AREA CALC'S
ROOF # OF
MODULES
ARRAY
AREA
(Sq. Ft.)
ROOF
AREA
(Sq. Ft.)
ROOF
AREA (%)
#1 6 117.02 239.59 49
#2 31 604.61 930 65
(E) BACK OF RESIDENCE(E) FRONT OF RESIDENCESE TRANQUILLA AVE(E) MAIN SERVICE PANEL,
200A RATED, 240V
(N) 1-SOLAREDGE
SE10000H-US INVERTER
(N) PV PERFORMANCE
METER
(E) UTILITY METER
FIRE ACCESS POINT
(E) ROOF VENT (TYP.)
(E) ROOF FRAMING
SEE ROOF INFO
3/4 " EMT CONDUIT RUN ON
ROOF/UNDER EAVE/ IN ATTIC
(N) JUNCTION BOX
ARRAY #1
(6) SOLAR MODULES
(13) ATTACHMENTS
@ 48" O.C. MAX.
ARRAY #2
(31) SOLAR MODULES
(68) ATTACHMENTS @ 48" O.C. MAX.
(37) SOLAREDGE POWER OPTIMIZER
P400 BELOW EACH PV MODULE (TYP.)
3' FIRE SETBACK
(TYP.)
18" FIRE SETBACK
(TYP.)
24" WIND ZONE 2
WIND ZONE 1
24" WIND ZONE 3
MSPPVMINVUMJBSHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-4
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
STRING
LAYOUT
1 STRING LAYOUT
PV-4
(37) LG365N1K-A6 365W MODULES
(1) SOLAREDGE SE10000H-US INVERTER LOCATED AT EACH MODULE
(02) STRING OF 12 MODULES CONNECTED IN SERIES
(01) STRING OF 13 MODULES CONNECTED IN SERIES
SCALE: 1/8" = 1'-0"
BILL OF MATERIAL
QUANTITY DESCRIPTION
MODULES 37 LG LG365N1K-A6 365W SOLAR MODULES
INVERTER 1 SOLAREDGE SE10000H-US INVERTER
OPTIMIZER 37 SOLAREDGE POWER OPTIMIZERS P400
PV METER 1 PV PERFORMANCE METER
ATTACHMENT 81 QUICKMOUNT L-MOUNT
RAILS 22 QUICKMOUNT QRAIL LIGHT
SPLICE 16 QUICKMOUNT SPLICE
MID CLAMP 66 QUICKMOUNT QRAIL BONDING MID CLAMP
END CLAMP 16 QUICKMOUNT UNIVERSAL END CLAMP
END CAP 16 QUICKMOUNT END CAP
GROUNDING LUG 4
QUICKMOUNT GROUND LUG ASSEMBLY, 6-12 AWG
(E) BACK OF RESIDENCE(E) FRONT OF RESIDENCESE TRANQUILLA AVE1 1 1 1 1 1
1
1
1
1
1
1
2 2
32
32
32
32
32
32
32
32
32
32
33
3
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-5
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
1 ATTACHMENT DETAIL
PV-5 SCALE: NTS
1.1 ATTACHMENT DETAIL (ENLARGED VIEW)
PV-5 SCALE: NTS
ATTACHMENT &
EQUIPMENT ELEVATION
PV MODULE
SEE ENLARGED
VIEW (1.1 / PV-5)(E) COMP SHINGLE
2"x4" RAFTE
R @ 24 " O.C.
QUICKMOUNT RACKING
SYSTEM
PV MODULE
GROUNDING END/MID CLAMP
ALUMN. "L" BRACKET
W/3/8" SS BOLT & NUT
QUICKMOUNT L-MOUNT
5/16"x3.5" SS LAG BOLT
WITH MIN 212" THREAD
EMBEDMENT, SEALED
PENETRATION
(E) COMP SHINGLE
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-6
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
ELECTRICAL LINE
DIAGRAM
1 ELECTRICAL LINE DIAGRAM
PV-6 SCALE: NTS
LG SOLAR LG365N1K-A6 365W
VMP= 35.1V VOC= 41.8V
ISC= 10.92A IMP= 10.41A
CEC PTC POWER= 338.2W
SOLAREDGE SE10000H-US (240V) (SI1)INVERTER
MAX DC VOLTAGE: 480V
MAX INPUT POWER: 15.5KW
MAX INPUT CURRENT: 27A
MAX AC OUTPUT CURRENT: 42A
CEC WEIGHTED EFFICIENCY: 99%
@ 240VAC NEMA 6, UL 1741 LISTED
x PV BREAKER IS TO BE LOCATED AT THE OPPOSITE
END OF THE BUS BAR FROM THE MAIN BREAKER.
WIRE TAG # CONDUIT
WIRE QTY
(CARRY
CURRENT)
WIRE GAUGE
(AWG)WIRE TYPE TEMP.
RATING
WIRE
LOCATION
ADJUSTED
WIRE TEMP
WIRE
AMP
TEMP. CORRECTION
PER TABLE
310.15(B)(2)(a):
CONDUIT FILL PER
TABLE
310.15(B)(3)(a):
WIRE
OCP.
TERMINAL 75°C
RATING INVERTER QTY.AC OUTPUT
CURRENT NEC 690.8(A)STRING
AMPS
GROUND
SIZE
GROUND
TYPE
OCPD
CHECK
1 NONE 2 10 PV WIRE 90°C ROOF 55°C 40 X 0.76 X 1 = 30.4 35 1 X 15 X 1.25 = 18.75 #6 SBC N/A
2 3/4" EMT 6 10 THWN-2 90°C WALL 55°C 40 X 0.76 X 0.8 = 24.32 35 1 X 15 X 1.25 = 18.75 #8 THWN-2 20A 2P
3 3/4" EMT 36 THWN-290°C ATTIC 33°C 75 X 0.96 X 1 = 72.0 65 1 X 42 X 1.25 = 52.5 #8 THWN-2 60A 2P
LOW MEAN TEMP
PER ASHRAE
HANDBOOK
MFR VOLTAGE TEMP
COEFFICIENT (Voc)
VOLTAGE LOW
TEMP. CORR. (oC)
HIGH AMBIENT
TEMP (oC)
CONDUIT
HEIGHT (in)
ROOF TOP
ADDED TEMP PER
Table
310.15(B)(C)(OC)
ADJUSTED
TEMP
ROOF 0°C
-0.26 1.065
33°C 0.5-3.5 22°C 55°C
WALL 0°C 33°C N/A 0°C 33°C
ATTIC 0°C 33°C N/A 0°C 33°C
METHOD TO CONTINUE SERIES/BRANCH
ARRAY TYP. PV WIRE ARRAY TYP. PV WIRE
TYP. CONDUIT
MAX PV VOLTAGE & CURRENT CALCS:
RECORD LOW TEMP (In Celsius)0°C
AMBIENT TEMP (HIGH TEMP 2%) (In Celsius)33°C
MODULE TEMPERATURE COEFFICIENT OF Voc -0.26%/°C
VOLTAGE CORRECTION 1.065
VCORRECTION * VOC (1.065 * 41.8)44.52 V
MAX PV CONTINUOUS CURRENT PER STRING
(1.25 X Isc X # STRINGS)13.65A
120% RULE
BUS BAR
200
MAIN BREAKER
150
ALLOWED MAX
PV OCPD
90
(37) LG365N1K-A6 365W MODULES
(1) SOLAREDGE SE10000H-US INVERTER LOCATED AT EACH MODULE
(02) STRING OF 12 MODULES CONNECTED IN SERIES
(01) STRING OF 13 MODULES CONNECTED IN SERIES
JUNCTION BOX
600 V, NEMA 3
UL LISTED
(3) #10 AWG THWN-2 + RED
(3) #10 AWG THWN-2 - BLACK
(1) #10 AWG GND
3/4" EMT CONDUIT
(1) #10 AWG USE-2/PV WIRE + Red IN FREE AIR
(1) #10 AWG USE-2/PV WIRE - Black IN FREE AIR
(1) #6 BARE COPPER GND
=
DC AC
(N) SOLAR EDGE
SE10000H-US[S|1]
WITH DC
DISCONNECT & AFCI
EXISTING GROUNDING
ELECTRODE SYSTEM
G
N
M
TO UTILITY GRID
BI-DIRECTIONAL UTILITY
METER 1-PHASE, 3-W,
120V/240V
(3) #6 AWG THWN-2
(1) #8 AWG GND
3/4" EMT CONDUIT
SolarEdge Power Optimizer P400 Rated
DC Input Power - 400 watts
Maximum Input Voltage - 80 Vdc
MPPT Range - 8 to 80 Vdc
Maximum Input Current - 12.5 Adc
Maximum Output Current - 15 Adc String
Limitations - 8 to 25 Optimizers,
6000 watts STC per string maximum
150 A
21
=
=
12
(N) PV
PERFORMANCE
METER
60A
2 POLE 60A PV
BREAKER BACKFEED
(E) 200A MAIN
SERVICE PANEL
1PH,120/240V,3W,
TOP MAIN BREAKER
(E) MAIN
BREAKER, 150A=
=
=
=
21
=
=
12
=
=
=
=
21
=
=
13
=
=
=
=
### #
"##
## "## # ##
# ####
#
#
###
######
# # #!
##"#
#
#
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-7
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
SAFETY
PLACARD
1 SAFETY PLACARD
PV-7 SCALE: NTS
LABEL LOCATION:
INTERIOR AND EXTERIOR DC CONDUIT EVERY 1O FT,
AT EACH TURN, ABOVE AND BELOW PENETRATIONS,
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
PER CODE(S): 690.31(G)(4)
LABEL LOCATION:
UTILITY SERVICE ENTRANCE/METER, INVERTER/DC
DISCONNECT IF REQUIRED BY LOCAL AHJ, OR
OTHER LOCATIONS AS REQUIRED BY LOCAL AHJ.
PER CODE(S): 605.11.1
PHOTOVOLTAIC AC DISCONNECT
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
IF A GROUND FAULT IS INDICATED
NORMALLY GROUNDED
CONDUCTORS MAY BE
UNGROUNDED AND ENERGIZED
ELECTRICAL SHOCK HAZARD
WARNING
LABEL LOCATION:
INVERTER(S), DC DISCONNECTS.
PER CODE(S): 690.35(F)
PV SYSTEM DISCONNECT
FOR UTILITY OPERATION
SOLAR AC DISCONNECT
ELECTRICAL SHOCK HAZARD
WARNING
LABEL LOCATION:
INVERTER(S), AC DISCONNECT(S), AC
COMBINER PANEL (IF APPLICABLE).
PER CODE(S): 690.17(E)
CAUTION:
SOLAR ELECTRIC
SYSTEM CONNECTED
WARNING
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
LABEL LOCATION:
ADJACENT TO PV BREAKER (IF
APPLICABLE).
PER CODE(S): 705.12(D)(4)
1
2
3
4
5
6
LABEL LOCATION:
MAIN SERVICE DISCONNECT
LABEL LOCATION:
SOLAR AC DISCONNECT
7
8
9
LABEL LOCATION:
UTILITY AC DISCONNECT
PLAQUE SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITH
POP-RIVETS OR SCREWS.
10
!
DO NOT ADD LOADS
PHOTOVOLTAIC SYSTEM
COMBINER PANEL
WARNING
LABEL LOCATION:
PHOTOVOLTAIC AC COMBINER (IF
APPLICABLE).
PER CODE(S): 705.12(D)(2)(3)(c)
!
!
!
CAUTION
POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE
FOLLOWING SOURCES WITH DISCONNECT AS SHOWN
EQUIPMENT AT
1 METER AND MAIN SERVICE
2 INVERTER
3 PV METER
EQUIPMENT AT EACH MODULE
-MICROINVERTER
MIN.6"x6" PLACARD TO GO ON MAIN SERVICE PANEL
SOLAR PV SYSTEM
EQUIPPED WITH RAPID
SHUTDOWN
SOLAR
ELECTRIC PV
PANELS
LABEL LOCATION:
ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE DISCONNECTING
MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED.
PER CODE(S): NEC 2019: 690.56(C)(1)(a), NEC 2017: 690.56(C)(1)(a)
LABEL LOCATION:
POINT OF INTERCONNECTION
(PER CODE: NEC 705.12(D)(4))
!11
SE TRANQUILLAAVE123
### #
"##
## "## # ##
# ####
#
#
###
######
# # #!
##"#
#
#
MODULE
DATA SHEET
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-8
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
INVERTER
DATA SHEET
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-9
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
OPTIMIZER
DATA SHEET
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-10
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
RACKING
DATA SHEET
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-11
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
ATTACHMENT
DATA SHEET
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-12
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
ATTACHMENT
DATA SHEET
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-13
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
COMPLIANCE
CERTIFICATE
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-14
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-15
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
SEALANT
DATA SHEET
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-16
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
SEALANT
DATA SHEET
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
11" X 17"
PV-17
MERAKI DESIGN &
CONSTRUCTION LLC
PROJECT ADDRESS
REVDATEDESCRIPTION
REVISIONS
09/3/2021FOR REVIEW
1801 CEDAR DR,
COCONUT CREEK,FL 33063
Tel: (954) 993-6757
LIC. NO.: CVC 57098
421 SE TRANQUILLA AVEPORT ST. LUCIE, FL 34983, USAPHONE: (772) 871-6626WIDMAN, RUDOLPH110/8/2021SEALANT
210/21/2021SEALANT
SEALANT
DATA SHEET