Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
APPROVED MANUAL J
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-08 00:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\DONOVAN R ESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Project Summary APRIL 8, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information DONOVAN RESIDENCE, PACE 2000, INC.For: 11770 PALOMINO DRIVE, FORT PIERCE, FL Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh27186 Struc ture Btuh20116 Ducts Btuh6185 Ducts Btuh6035 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh33370 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh24843 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh4323 Ducts Btuh2421 Central vent (0 cfm)Btuh0 CoolingHeating (none) 21162116Area (ft²)Equipment latent load Btuh6744 2085420854Volume (ft³) Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh31587 Equiv. AVF (cfm)56111 Req. total capacity at 0.70 SHR ton3.0 Heating Equipment Summary Cooling Equipment Summary Make Make Rheem Trade Trade RHEEM Model Cond RA1636AJ1NA AHRI ref Coil RH1T3621HTANJA AHRI ref 8080509 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW11.1 Sensible cooling Btuh25200 Heating output Btuh37963 Latent cooling Btuh10800 Temperature rise °F29 Total cooling Btuh36000 Actual air flow cfm1200 Actual air flow cfm1200 Air flow factor cfm/Btuh0.036 Air flow factor cfm/Btuh0.046 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.79 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-08 00:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\DONOVAN R ESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet APRIL 8, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House MASTER BEDROOM 2 Exposed wall 200.0 ft 36.0 ft 3 Room height 9.9 ft 10.3 heat/coolft 4 Room dimensions ft288.0x1.0 5 Room area 2116.0 ft²288.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 493 419 1679 918 175 155 621 339 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 20 0 364 300 20 0 364 300 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 12 0 218 180 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 21 0 388 320 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 13.2613.26 20 0 364 265 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 632 513 2054 1122 144 124 497 272 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 20 0 364 675 20 0 364 675 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 14.9914.99 48 48 874 720 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 30 0 546 847 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 21 0 388 602 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 433 383 1533 838 52 52 206 113 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 10 10 182 150 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 40 40 728 600 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 386 275 1101 602 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 15 0 273 507 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 10.6810.68 12 12 218 128 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 36 0 655 755 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 11.4411.44 48 44 874 549 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 2116 2116 3355 2895 288 288 457 394 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 2116 200 7605 0 288 36 1369 0 6 c) AED excursion 278 -241 Envelope loss/gain 23763 13249 3878 1852 12 a) Infiltration 3423 917 653 175 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 5950 1400 Subtotal (lines 6 to 13)27186 20116 4531 3427 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 27186 20116 4531 3427 15 Duct loads 23%30%6185 6035 23%30%1031 1028 Total room load 33370 26151 5562 4455 Air required (cfm)Air required (cfm)1200 1200 200 204 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-08 00:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 E:\Documnets\Wrightsoft HVAC\DONOVAN R ESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet APRIL 8, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M WIC M BATH 2 Exposed wall 10.0 ft 31.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft10.0x9.0 ft160.0x1.0 5 Room area 90.0 ft²160.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 93 93 372 203 112 100 399 218 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 12 0 218 180 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 13.2613.26 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 47 47 186 102 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 130 115 461 252 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 15 0 273 507 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 11.4411.44 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 90 90 143 123 160 160 254 219 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 90 10 380 0 160 31 1179 0 6 c) AED excursion -24 74 Envelope loss/gain 895 302 2970 1551 12 a) Infiltration 164 44 508 136 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1059 346 3478 1687 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1059 346 3478 1687 15 Duct loads 23%30%241 104 23%30%791 506 Total room load 1300 450 4269 2193 Air required (cfm)Air required (cfm)47 21 154 101 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-08 00:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 3 E:\Documnets\Wrightsoft HVAC\DONOVAN R ESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet APRIL 8, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M TOILET LIVING ROOM 2 Exposed wall 6.0 ft 19.0 ft 3 Room height 9.3 heat/coolft 11.0 heat/coolft 4 Room dimensions ft7.0x4.0 ft347.0x1.0 5 Room area 28.0 ft²347.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 13.2613.26 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 209 161 645 352 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 14.9914.99 0 0 0 0 48 48 874 720 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 19 19 74 41 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 37 37 149 81 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 11.4411.44 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 28 28 44 38 347 347 550 475 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 28 6 228 0 347 19 722 0 6 c) AED excursion -12 -118 Envelope loss/gain 496 148 2791 1429 12 a) Infiltration 98 26 368 99 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 150 Subtotal (lines 6 to 13)594 174 3159 1677 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 594 174 3159 1677 15 Duct loads 23%30%135 52 23%30%719 503 Total room load 729 227 3878 2180 Air required (cfm)Air required (cfm)26 10 139 100 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-08 00:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 4 E:\Documnets\Wrightsoft HVAC\DONOVAN R ESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet APRIL 8, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name FOYER BEDROOM 2 2 Exposed wall 8.0 ft 14.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft64.0x1.0 ft166.0x1.0 5 Room area 64.0 ft²166.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 20 20 80 44 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 13.2613.26 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 80 20 80 44 120 84 336 184 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 10.6810.68 12 12 218 128 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 0 0 0 0 36 0 655 755 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 11.4411.44 48 44 874 549 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 64 64 101 88 166 166 263 227 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 64 8 304 0 166 14 532 0 6 c) AED excursion 958 299 Envelope loss/gain 1578 1766 1867 1509 12 a) Infiltration 141 38 247 66 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 100 Subtotal (lines 6 to 13)1719 1804 2114 1675 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 142 42 14 Subtotal 1719 1804 2256 1717 15 Duct loads 23%30%391 541 23%30%513 515 Total room load 2110 2345 2769 2232 Air required (cfm)Air required (cfm)76 108 100 102 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-08 00:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 5 E:\Documnets\Wrightsoft HVAC\DONOVAN R ESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet APRIL 8, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name KITCHEN UTILITY RM 2 Exposed wall 0 ft 0 ft 3 Room height 10.0 heat/coolft 9.3 heat/coolft 4 Room dimensions ft15.0x13.0 ft9.0x8.0 5 Room area 195.0 ft²72.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 13.2613.26 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 11.4411.44 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 195 195 309 267 72 72 114 99 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 195 0 0 0 72 0 0 0 6 c) AED excursion -123 -49 Envelope loss/gain 309 144 114 49 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1600 650 Subtotal (lines 6 to 13)309 1744 114 699 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 29 23 70 27 14 Subtotal 338 1767 184 726 15 Duct loads 23%30%77 530 23%30%42 218 Total room load 415 2298 226 944 Air required (cfm)Air required (cfm)15 105 8 43 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-08 00:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 6 E:\Documnets\Wrightsoft HVAC\DONOVAN R ESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet APRIL 8, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name CLST 3 BEDROOM 3 2 Exposed wall 0 ft 13.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft9.0x2.0 ft203.0x1.0 5 Room area 18.0 ft²203.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 13.2613.26 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 121 101 404 221 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 20 20 364 300 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 11.4411.44 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 18 18 29 25 203 203 322 278 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 18 0 0 0 203 13 494 0 6 c) AED excursion -2 -122 Envelope loss/gain 29 23 1584 676 12 a) Infiltration 0 0 213 57 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 1000 Subtotal (lines 6 to 13)29 23 1797 1733 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -29 -23 26 21 14 Subtotal 0 0 1823 1755 15 Duct loads 23%30%0 0 23%30%415 526 Total room load 0 0 2238 2281 Air required (cfm)Air required (cfm)0 0 80 105 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-08 00:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 7 E:\Documnets\Wrightsoft HVAC\DONOVAN R ESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet APRIL 8, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH 2 CLST 4 2 Exposed wall 19.0 ft 2.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft6.0x13.0 ft2.0x10.0 5 Room area 78.0 ft²20.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 13.2613.26 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 121 121 484 265 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 56 46 183 100 19 19 74 41 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 10 10 182 150 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 11.4411.44 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 78 78 124 107 20 20 32 27 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 78 19 722 0 20 2 76 0 6 c) AED excursion -50 -5 Envelope loss/gain 1696 572 182 63 12 a) Infiltration 311 83 33 9 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 50 0 Subtotal (lines 6 to 13)2007 705 215 72 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 112 40 -215 -72 14 Subtotal 2119 745 0 0 15 Duct loads 23%30%482 223 23%30%0 0 Total room load 2601 968 0 0 Air required (cfm)Air required (cfm)94 44 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-08 00:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 8 E:\Documnets\Wrightsoft HVAC\DONOVAN R ESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet APRIL 8, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 4 DINING RM 2 Exposed wall 13.0 ft 27.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft13.0x13.0 ft142.0x1.0 5 Room area 169.0 ft²142.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 93 52 207 113 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 21 0 388 320 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 13.2613.26 0 0 0 0 20 0 364 265 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 158 107 427 234 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 30 0 546 847 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 21 0 388 602 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 121 101 404 221 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 20 20 364 300 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 11.4411.44 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 169 169 268 231 142 142 225 194 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 169 13 494 0 142 27 1027 0 6 c) AED excursion -119 -177 Envelope loss/gain 1530 633 3573 2398 12 a) Infiltration 213 57 442 118 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1000 0 Subtotal (lines 6 to 13)1743 1690 4015 2516 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 147 67 21 17 14 Subtotal 1890 1757 4036 2533 15 Duct loads 23%30%430 527 23%30%918 760 Total room load 2320 2284 4954 3293 Air required (cfm)Air required (cfm)83 105 178 151 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-08 00:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 9 E:\Documnets\Wrightsoft HVAC\DONOVAN R ESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet APRIL 8, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name HALL WH CLST 2 Exposed wall 0 ft 0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft15.0x4.0 ft2.0x3.0 5 Room area 60.0 ft²6.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 13.2613.26 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 28.2328.23 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 11.4411.44 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 60 60 95 82 6 6 10 8 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 60 0 0 0 6 0 0 0 6 c) AED excursion -5 -1 Envelope loss/gain 95 77 10 8 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)95 77 10 8 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -95 -77 -10 -8 14 Subtotal 0 0 0 0 15 Duct loads 23%44%0 0 23%44%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-08 00:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 10 E:\Documnets\Wrightsoft HVAC\DONOVAN R ESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet APRIL 8, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name CLST 2 2 Exposed wall 2.0 ft 3 Room height 9.3 heat/coolft 4 Room dimensions ft5.0x2.0 5 Room area 10.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 .G 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 .G 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 .G 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 11 G 2 glazing, clr low-e 0.650 n 18.20 13.26 0 0 0 0 W 13A-4ocs 0.143 e 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 e 18.20 33.77 0 0 0 0 G 2 glazing, clr low-e 0.650 e 18.20 14.99 0 0 0 0 G 2 glazing, clr low-e 0.650 e 18.20 28.23 0 0 0 0 G 2 glazing, clr low-e 0.650 e 18.20 28.23 0 0 0 0 W 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 G 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 W 13A-4ocs 0.143 w 4.00 2.19 19 19 74 41 G 2 glazing, clr low-e 0.650 w 18.20 33.77 0 0 0 0 G 2 glazing, clr low-e 0.650 w 18.20 10.68 0 0 0 0 G 2 glazing, clr low-e 0.650 w 18.20 20.97 0 0 0 0 G 2 glazing, clr low-e 0.650 w 18.20 11.44 0 0 0 0 C 16X19-0md 0.408 -1.59 1.37 10 10 16 14 F 22A-tph 1.358 -38.02 0.00 10 2 76 0 6 c) AED excursion -4 Envelope loss/gain 166 50 12 a) Infiltration 33 9 b) Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)199 59 Less external load 0 0 Less transfer 0 0 Redistribution -199 -59 14 Subtotal 0 0 15 Duct loads 23%44%0 0 Total room load 0 0 Air required (cfm)0 0 2021-Apr-08 00:28:55 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\DONOVAN R ESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Duct System Summary APRIL 8, 2021Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information DONOVAN RESIDENCE, PACE 2000, INC.For: 11770 PALOMINO DRIVE, FORT PIERCE, FL CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm1200cfm1200 Total effective length (TEL)ft180 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st3135.032.9VlFx0x06.01.00044942601hBATH 2 st1115.025.0VlFx0x07.01.0001021002232cBEDROOM 2 st1115.015.8VlFx0x07.01.000105802281cBEDROOM 3 st3135.030.5VlFx0x07.01.000105832284cBEDROOM 4 st3135.031.9VlFx0x08.01.0001511784954hDINING RM st2115.028.1VlFx0x07.01.000108762345cFOYER st1115.017.1VlFx0x07.01.000105152298cKITCHEN st4135.045.3VlFx0x07.01.0001001393878hLIVING ROOM st2115.032.3VlFx0x07.01.0001011544269hM BATH st2115.030.8VlFx0x04.01.0001026729hM TOILET st2115.033.7VlFx0x04.01.00021471300hM WIC st4135.041.7VlFx0x07.01.0001021002227cMASTER BEDROOM st4135.044.6VlFx0x07.01.0001021002227cMASTER BEDROOM-A st1115.015.8VlFx0x06.01.000438944cUTILITY RM Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 339 304 1.000 622 10.0 0x0 VinlFlx st2 st2 Peak AVF 642 544 1.000 817 12.0 0x0 VinlFlx st3 Peak AVF 355 300 1.000 651 10.0 0x0 VinlFlx st1 st1 Peak AVF 558 656 1.000 836 12.0 0x0 VinlFlx 2021-Apr-08 00:28:55 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 E:\Documnets\Wrightsoft HVAC\DONOVAN R ESIDENCE.rup Calc = MJ8 Front Door faces: S Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 12000 1200 0 0 0 0 x0 0 VlFx ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� �����������������������������������������������������