HomeMy WebLinkAboutComment ResponseL. Hugh Anglin P.E.
Rodriguez & Anglin Professional Design, Inc.
8404 NW 59th Street
Tamarac, FL 33321
Email: haftware@yahoo.com
To: St. Lucie County Building Department
Re: Permit #1905-0020
Comment Response
AUG 19 20ZI
BOgROOW
August 18, 202bU1rtor�'` }. o N�y�
AlAf
20p0 pS09 0 E24IS1ONL'RS
99392 S
1. SHEET S-101- The ramp shows a curb symbol at the passenger loading zone (covered drop off), this is not
consistent with the Site Plan designed by Ladyko Design Group and does not meet accessibility
requirements.
Curb symbol removed at the passenger loading zone (covered drop off)
2. SHETS S-101-Thickened edge details (1), (2) and (3)-the Reinforcement in Footers is inconsistent with
Wall Sections (G), (F) and (G) on sheet s-104.
Sheet S-101-The Reinforcements of Thickened edge detail in Footers 1 #5 continuous top and 2 #5
Bottom continuous.
Sheets S104- Wall Section (G) 1 #5 Rebar top Continuous and 2 #5 Rebar bottom continuous.
3. Sheet S-104 -The Roof Deck material is inconsistent- Seethe Typical Exterior Wall Section on the right of
the sheet. Two different notes call out different roof sheathing materials. Note 1- "5/8" PLYWOOD ROOF
DECK W/8D @ 6" O.C.". Note 2- "MINIMUM 22 GUAGE STEEL ROOFING PANELS SHALL BE SECURED 6"
O.C. TO STRUCTURAL SUPPORTS SPACED A MAXIMUM DISTANCE OF 5' O.C...."
These are different notes one for Plywood roofing deck and the other for roofing panels. However, Per
our conversation on August 17th I explained they were two separate notes. As to not complicate the......'
review process, the roofing panel note has been removed and the architectural drawings take precedence
on the roofing panel composition.
4. Sheet S-104 -There is an unknown/untagged u-block with reinforcing in the typical exterior wall sections,
please call out the height of this beam and size of reinforcing.
Sheet S-104 UBLOCK is 8"CMU Bond Beam w/1 #5 Rebar continuous. Tie Beam height @ 12'-0
PIKE
GENERAL CONSTRUCTI
1515 N. University Drive, Suite#102B
Coral Springs, Florida 33071
Phone: (954) 688-9522
Transmittal
RECEIVED
MAY 01 2019
ST. Lucie County, Permitting
4N INC.
Main Office: 4131 S. US 1 Bldg.#2 Suite#3
Fort Pierce, Florida 34982
Email: Pikegcconstruction@Gmail.com com Phone: (772) 742-8906
LIC.:CGC1527409
r
From:
Phone:i906
❑ Urgent ❑ For Review ❑ Please Comment ❑ Please Reply ❑ Estimate
Requested
Comments:
Documents Enclos
6w /ate
1
SAVANNAPUB, INC.
Memo ARCHITECTURE I DEVELOPMENT I PHILANTHROPY
To: St Lucie County, Planning & Development Services, Building & Code
Regulation Division
From: Audie Robinson, Director, Email: savannapub@gmail.com
SAVANNAPUB, Inc.
Phone: 813-313-7707 Date: April 14, 2021
Ref: United Pentecostal Fire cc: Petal T. Pike
Ministries Trinity Int. Inc.
Subject: Building Review Comment/Responses — Permit # 1905-0020
To Whom It May Concern,
Please see below the responses to the outstanding building review comments
Comments
Responses
1
(1004.1) OCCUPANT COUNT
The area of the platform less ramp, landing and
A) INCLUDE THE CORRECT OCCUPANT COUNT FOR THE
stairs is 206SF, which is 164/15= 12 occupants
PLATFORM (15 NET).
or 12 additional
B) INCLUDE ALL STORAGE, MECHANICAL.
C) BATHROOMS SERVING BOARD ROOM, SECRETARY,
Note: FBC 202 Restrooms, Mechanical,
BUSINESS AREAS ARE PART OF THE GROSS
Storage is not to be Included in net area
AREA.
Calculations of Occupied areas.
Therefore, total new occupant load is
132+20+48+46=246 occupants.
2
2) (1005.2) PLEASE PROVIDE THE QUANTITIES AND
Complied. See revised Life Safety, A05 — Exit 1
MINIMUM REQUIRED WIDTH FOR EGRESS
= 36"/.2 = 180 Persons
COMPONENTS- AISLE WIDTH, EXIT WIDTH, MINIMUM
Exit 2 = 36"/.2 = 180 Persons
NUMBER OF EXITS.
Total Egress = 360 Persons
Total Occupant Load of the Sanctuary is 142.
Aisle width = 45" + 45" + 60" = 150"
225 + 225 + 300 = 750 Persons
3
(1005.3) PLEASE SHOW THE EGRESS CAPACITY FOR
Complied. See revised Life Safety, A05
EACH OF THE EXIT DOORS.
4
(1007.11) PLEASE SHOW THE DISTANCE BETWEEN EXIT
See revised Life Safety, A05
DOORS AND THE LENGTH OF THE MAXIMUM
Distance between exit doors is 34'-4".
OVERALL DIAGONAL DIMENSION OF THE AREA SERVED.
Maximum diagonal is 55'-0"
5
(1009.1) ACCESSIBLE MEANS OF EGRESS REQUIRED. A
Complied.
4" STEP IS SHOWN AT MULTIPLE EXITS.
See revised Life Safety, A05
4" steps have been removed.
6
PLEASE PROVIDE RAMP DIMENSIONS AND DETAILS AT
Complied. See revised Life Safety, A05
THE PLATFORM. LENGTH; HEIGHT, SLOPE,
HANDRAILS. SEE SECTION (1012.1)
SAVANNAPUB I PO Box 773553 Ocala, FL 344771 savannapub.com Isavannapub@gmail.com 1813-313-7707
Memo
SAVANNAPUB, INC.
ARCHITECTURE I DEVELOPMENT I PHILANTHROPY
7
PLEASE PROVIDE THE MINIMUM FIRE PERFORMANCE
Complied. See revised Life Safety, A05
AND SMOKE DEVELOPMENT OF INTERIOR
FINISHES. (801.1)
8
1401, EXTERIOR WALLS) MORE INFORMATION
See Sheets A601 & A901.
REQUIRED- COMPLETE WALL SECTIONS, SECTIONS &
See also A101, A105, A106, A501, A502, A561,
DETAILS FOR THE CROSS, SECTIONS & DETAILS FOR
A601, A901.
THE COVERED WALKWAY & DRIVE THROUGH.
3/4/2021
Comment: ([A] 107.2.4) EXTERIOR WALL ENVELOPE.
CONSTRUCTION DOCUMENTS FOR ALL BUILDINGS
SHALL
DESCRIBE THE EXTERIOR WALL ENVELOPE IN
SUFFICIENT DETAIL TO DETERMINE COMPLIANCE WITH
THIS CODE. THE CONSTRUCTION DOCUMENTS SHALL
PROVIDE DETAILS OF THE EXTERIOR WALL
ENVELOPE AS REQUIRED, INCLUDING FLASHING,
INTERSECTIONS WITH DISSIMILAR MATERIALS,
CORNERS, END DETAILS, CONTROL JOINTS,
INTERSECTIONS AT ROOF, EAVES OR
PARAPETS, MEANS OF DRAINAGE, WATER -RESISTIVE
MEMBRANE AND DETAILS AROUND OPENINGS.
9
([A]107.2.1) STRUCTURAL DRAWINGS ARE INCOMPLETE,
Complied. Walk way & stairs removed.
PROVIDE A COMPLETE SET OF DRAWINGS,
See A101, A105, A106, A501, A502, A561,
SPECIFICATIONS & DETAILS FOR REVIEWGENERAL
A601, A901.
NOTES & SPECIFICATIONS
CONCRETE
STEEL
WOOD
MASONRY
SLABS & FOUNDATION
REINFORCEMENT
SOIL
ALUMINUM BUILDING STRUCTURE
ALL COLUMNS, BEAMS, PIERS SPECIFIED
VERTICAL MASONRY REINFORCEMENT IS INCOMPLETE
WINDOW BUCKS
CROSS/STEEPLE DESIGN, DRIVE THROUGH, COVERED
WALK
RAMPS, STAIRS
COMPLETE FRAMING PLAN OF PLATFORM
10
SHEET S-101 COVERED WALK FTG SHOWS STEEL
Walk way has been removed.
REBAR IN CONTACT WITH ALUMINUM. ALUMINUM
IS IMBEDDED IN CONCRETE. REVISE AS NEEDED.
([A]107.2.1)
11
MANEUVERING CLEARANCES ARE NOT PROVIDED AT
Complied. See revised Life Safety, A05
RESTROOM DOORS. (404.2.4)
12
PROVIDE ACCESSIBLE ROUTE TO PLATFORM. (206.1)
Complied. See revised Life Safety, A05
SAVANNAPUB I PO Box 773553 Ocala, FL 344771 savannapub.com Isavannapub@gmail.com 1813-313-7707
IN
Memo
SAVANNAPUB, INC.
ARCHITECTURE I DEVELOPMENT I PHILANTHROPY
13
PLEASE SHOW THE NUMBER AND LOCATION OF
Complied. See revised Life Safety, A05
WHEELCHAIR SPACES IN THE ASSEMBLY AREA.
(221.1)
14
THE PLUMBING FIXTURE COUNT DOES NOT USE THE
Complied.
CORRECT NUMBER OF OCCUPANTS, AS SHOWN
246 Occupants
IN THE OCCUPANT LOAD CALCULATION. (2902)
MALE = 123 (1/125WC & 1/200LAV) = 1 WC,
LAV 1
FEMALE = 123 (1/65WC & 1/200LAV) = 2 WC,
LAV 1
TOTAL REQUIRED: 3 WC, LAV 2,
1 DRINKING FOUNTAIN, 1 SERVICE SINK
PROVIDED: 4 WC, 1 URINAL, 5 LAV
1 SERVICE SINK, 1 DRINKING FOUNTAIN
15
PROVIDE DRINKING FOUNTAIN SPECIFICATION AND
Complied. See revised Life Safety, A05
FORWARD APPROACH. (602.1)
16
PLEASE PROVIDE THE LATEST SITE PLAN TO THE
Complied. See GC
BUILDING DEPT FOR REVIEW. ([A]107.2.1)
17
INCOMPLETE PRODUCT APPROVAL NUMBERS
Complied. See Product Approval Affidavit
PROVIDED, SOFFIT IS NOT VALID, SHUTTER NOT
PROVIDED. HIGHLIGHT THE ATTACHMENT METHOD FOR
EACH PRODUCT.
AS AN ALTERNATIVE COMPLETE THE ST LUCIE COUNTY
PRODUCT REVIEW AFFIDAVIT. ([A]107.2.1)
G :)i';1 y
dos£ so9jN41
Y�
"ARao
4/14/21
Respectfully,
Audie Robinson, NCARB, LEED® AP, DBE, CFRM
Director
SAVANNAPUB, INC
Architecture I Development I Philanthropy
Cell: +1 (813) 313 7707 1 Email: savannapub@gmail.com
SAVANNAPUB I PO Box 773553 Ocala, FL 344771 savannapub.com Isavannapub@gmail.com 1813-313-7707
K���avea
I °�a 5- aaaa FHB 19 2021
P, nitting Compartment SAVAN NAP U B, INC.
�C1ecounty
Memo 4 ' ARCHITECTURE I DEVELOPMENT I PHILANTHROPY
To: St Lucie County, Planning & Development Services, Building & Code
Regulation Division
From:
Audie Robinson, Director, Email:
SAVANNAPUB, Inc.
savannapub@gmail.com
Phone:
813-313-7707 Date:
February 15, 2021
Ref:
United Pentecostal Fire cc:
Ministries Trinity Int. Inc.
Petal T. Pike
Subject:
Building Revi ew Comment/Responses —
1906 —OOZO
To Whom It May Concern,
Please see below the responses to the outstanding building review comments
Comments
Responses
1
Occupant Count & Dimensions are correct
The occupant load has been resolved on
on the plans
the plan by showing the seats and aisles.
The sanctuary has 148 occupants and the
other spaces has 48. Therefore, the total
occupant load is 196.
2
Accessibility (ADA) requirements are met-
The Civil site plans shows the required
Site Plan updated- Engineering/Water
accessible parking. The Architectural
Quality Department still has not approved.
sheets indicate the required accessibility
details.
3
Copy of the Fire Sprinkler & Alarm permit
Since the occupant load is less than 300,
no fire sprinkler system is required for this
building. Per FBC, 2017, 907.2.1 — Group
with an occupant load less than 300 is not
required to have a fire alarm.
4
Construction Type is correct on the plans
The construction Type is reflected on the
Life Safety plan as Type VB.
5
For the product approvals, we can move to a
This project has elected to have the
deferred submittal if you choose.
product approvals as deferred submittals