HomeMy WebLinkAboutHVAC PlansHVAC SCHEDULES AND NOTES:
New HVAC Units shall be Trane or equal split system DX Units,
14.00 SEER min., with Heat Strip as indicated.
Units No. 1, 2, 3 shall be split system 5 ton units. Trane 4TTB3060
with matching 060 AHU, with 10 KW Heat Strip, 208/230/1/60.
Mount new units on plenum stand with pan with drain and float
switch for unit shut down. Provide condensate drain run to sump
at building exterior or to landscape area with gooseneck.
Install all units to be completely accessible.
Refer to Architectural Sections for ceiling height restrictions - all
equipment and materials shall fit in the space provided. Make
modifications as required to accomplish same.
Verify fire ratings - provide fire dampers for all penetrations in
fire rated assemblies,
Registers/grills/Diffusers shall be Metalaire or equal unless
otherwise scheduled - all aluminum construction unless
otherwise required to meet fire ratings.
SAR's (supply air registers) shall be metal air or equal.
SAD's (supply air diffusers) shall be series 5000, M-2, S-4, D-5, of
the sizes shown. S-1: one way; S-2: two way, etc" Unless
otherwise noted, SAD's shall be 9" x 9" (up to 125 cfm); 12" x 12"
(130 to 290 cfm); 24" x 24" for 300 cfm and larger.
SAR's shall be as scheduled on the plans.
Rag's shall be type RH of the sizes shown on the plans. Provide
1" T/A filters at unit.
Exhaust fans shall be Greenheck or equal SP series with cfm
indicated at 0.25 " SP. Run exhaust thru wall with wp scupper or
to soffit with screened grille or thru roof with gooseneck as
noted. Maintain 10' separation from any O/A intake" Do not run
to front entry or within 25' from any exit door or to any sidewalk.
Paint all HVAC grilles/registers/diffusers white.
Provide outside make up air for each unit - Set cfm at Manual "N"
requirement. Maintain minimum 10' separation from exhaust
openings
Provide thermostat for each unit - Honeywell, Trane or equal "on
-Auto" fan and "Heat/Cool" settings. Stage together for
operation in Sanctuary with alternating operation of Units for
unoccupied hours.
Ductwork shall have joints and seams sealed with approved tape
applied with adhesive to make joints airtight. Ducts shall be
reinforced foil faced 1-1/2" fiberglass insulation board (R-6
minimum). Flex duct shall be UL 181 Thermaflex or equal with
foil back insulation. Provide spin -in connection with diverter and
volume damper for each flex take -off from the main trunk
ductwork.
The Contractor shall furnish a complete matched component
HVAC system in accordance with these drawings, local codes, and
the latest editions of NFPA 90A & 90B, ANSI 8-9.1 Mechanical
Refrigeration, SMACNA, ASHRAE, and State of Florida Energy
Efficiency Code for Building Construction - FlaCom- FBC 2017 (6th
Edition).
The Contractor shall obtain all required permits and inspections
from governing agencies and furnish a written guarantee that all
work shall be free from defects in materials and workmanship for
a period of one year from the date of equipment start up and
final acceptance, Manufacturer's instructions and guarantees
shall be given to the owner.
The contractor shall be responsible for balancing the HVAC
system to meet the criteria on the plans and shall return to the
site to re -balance the HVAC system after occupancy to satisfy
specific individual requirements.
Provide duct smoke detector per Mechanical and Building Code
requirements.
CODES: FBCIFMC 2017 (67H EDITION)
V try eVS 6,700 `' ►A.
T� Ji ,
Nailor
1 1/2 HR. LABEL • VERT. OR HORIZONTAL cT e
FOR USE IN DYNAMIC OR STATIC SYSTEMS GOOUS
Industries Inc"
MODEL D0120 TYPE B
DUAL
FICATIONS:
• UL
5 ClassiIfed Fire Damper. 1 112 hr. label. (File 4 9492).
• CA�I�I/ULC-S112
Ere Damper Assemblies. �I �- • ,~/
• meits
ds
at,) the requirements of UL and NFPA 90A for fire
pers n dynamic HVAC systems.
• Ma44444ts
a
the requirements for BOCA, SBCCI, UBC, IBC and !
dated local building codes.
- M
is all the requirements of NBC. OUCi SIZE `
cahomia
State Fire Marshal Listing No. 03225-M5:113. I'a (3) J
aryiaNewraxmardasranr�misarwAppaa�
Cat ra46o-ee-sA.
• Mi>EIimum
vahactty 2000 fpm ® 4" w.g. \, �
The D
120 curtain fire. damper is UL approved for use where local DUCT51j 1q f6j
buildin
codes require the protection of HVAC ductwork pene(ralions in INTERIP.CNING
walls
partitions or floors that have a fire resistance rating of up to 2 CmnAmI BI MES-----,
hours_
where
Dam
he D0120 is classified for use in dynamic "laps en' systems --_�_---}--4
the HVAC system remains oporalive in the event of a fire.
closure under airflow is assured. s
Type
for hi
lire dampens lace the curtain blade
f>e p pack out or the airstream
er free area and reduced pressure drop.----Y._ = `�
STAR
ARD SPECIFICATION:
FRAM
Ul LISTED 1221
ll 1/4' (106) wide, 22 ga. (0.85) roll -formed Gf.,O: EUSIOLE LINK -1,r
galvam-ul steel (RE'PLACFABLD ! .-
BLAO
S: Curtain type interlocking blades, 22 ga. (0.65) _
'
roll formed G60 galvanized steel. forTMN BIAOC _ �� _ m
ENC
I Of.KING RAMP
SURE: 22 ga (0.85) galvanized steel.
PUSIB
E LINK: 165r (74`C) standard. UL Listed.
2127E (100"C) available.
CLOStFE Stainless steel closure springs and galvanized steel
MINIM
MAXIMUM
to _kmg ramps. GIAINLESS STEEL
M SIZE: 6" x 4" 1152 x 102) Ou3siIRE.paled
SIZE: Single Section
I
Vertical or Horizontal mount: 24' x 21" (F,tO x 533). BOLL -m.MEO ...
Multiple Section Assembly mnnte
Vertical mount: 72' x 21" (1829 x 533) or 36" x 45'
(914 x 1143). Sea role 2.
Horizontal muunk Contact factory.
OP ',
INS: MODEL D0720Y-YEH7lCAI_ MOUNT
L] NO
-standard temperature fusible link. Specify
Q PuI
wit
Tab Release. Pennits simple reset of spring loaded damper____
access door is located on opposite side of locking ramp. __ _
(
dwg. ACC-PTR for itelaIIs) .�� 1
S�-
I� F
ory Sleeve. AvaiLaMe in 10 (3.5) through 22 ga. (0.85) galvanized steel �.A
a���
lengths required for application. Specify: length.
NO-ft
�n
S: X
1. See
p
sizing chart for relationship of duct size and damper size.
vi
sorb SC and SC2. ( --
2. Irl virtu
2 hid
dual secllon5 of multiple section assembly not to exceed 10 x ( ..._ _
24'(4
3. Run
7%610) STAINLESSSTEEL 6UNTAIN9L,UE
irfg code and UL Classification require damper Installation III CLOSURE SPRING LOCKfNG RAMP
acc
rxxe with manufacturers instructions. Refer to docurnerd IOM-FDINST.
by members of S.M.W.LA.MODEL Do120H - HORIZONTAL MOUNT
LE TYPE: Dimensions are in inches (mm),
T:
AlMlaoufcturr.J
ENGINEER:
DATE
,
95EPIE5 SIIPf:R5FDE$
DRAWING NO_
CONTRACTOR:
_
10-6-Of
f0 2-16`B5
D0100_2
„ DYNAMIC CURTAIN TYPE FIRE DAMPER
Nails Indusldn in,. reserves Iha right to change any inlomlalion concerning produ:;t or pricing withoul notice
Nailor" DYNAMIC CURTAIN TYPE FIRE DAMPER
1 1/2 HR. LABEL +VERT. OR HORI7_.
Industries Inc. FOR USE IN DYNAMIC OR STATIC SYSTEMS C �� us
MODEL: D0130 (TYPES CR & CO)
3YPE CO
QUALIFICATIONS: FLAr ovAL
. DL 655 8 CAN/ULC-S412 CLASSIFIED DYNAMIC FIRE. DAMPER. rice cR
1 1/2'hr. label (File 4 R9492). ROUND ��..
• Mdgta all the requirements of UL and NFPA W, 90A and 101 for fire \
dtlRlpe s in dynamic HVAC systems, as well as IBC and NBC -..�
(0teda) Building Code requirements.
• C4f New York Board of Standards and Appeal,, Cal. No. 4b0-58-SA,
0 0 pp+'a ..
. Cagfomrn State Fire Marshal. Free Damper Lfs}jng No. 322,4-0935:0113. _ W\
. M"fir um velocity: 4000 fpm @ 4" w�g. (20 pairs _@ T kPa).
Model DO13AT curtain fire damper is UL approved for use where local v4'/4•I.,) `
bulld!fag, codes require the protection of HVAC ductwork penetrations in ULusTEB I!it[nL.ocKING
walls, partitions or floors that have a fire resistance rating of up to 2 hours. rUSIBLE LINK cuRrpiN BUOES
The 00 0 is d-ifed fc. use :n dynar Uc'lans on" systemaor:�. the IREPLACEAREl ---
VAF, y tem remains operative m the event of a tire. Damper closure - -
- der �aaa{{r1low is assured. Type.CR round and CO oval fire dampers use r
t n§IW I collars to place the curtain blade pack and damper frame out of
the aligt earn, providing 100 % free area.
STAN ARd'. CONSTRUCTION: - -- 1
Frame 4 114" (108) wide 22 ga. (0,85) roll -formed G60 get. steel. 1
Cli9TAP1
Blades: Cunam type interlocking blades, 22 ga. (0.85) RUDE I W
I roll -formed G60 galvanized steel. LOOKING _ -
Enclosdre: 22 ga. (0.85) gal,.,,.d sleet RAMP �'T'I/--- o
Fuel ISILlnk: 165'F 7a^G) Sta dad. UL Listed 2127E 400'C available I ! !'a
( ( ) 3' 761 - ) (021
Blade Oiosure: Stainless scal closure spnn, G and , alv .feel lock n .SIVNLESS
q„ q g ramps. STEEL JJI I MIN a
Sizes (D ct W x H): SIDSURE
SPRING
Mo4el
ebn ref
s nyM
Secl�ari
M It PI Se ion
_
Mlnlmurn
NI -inn -
In I
Nadzonial
Ven WI
1'Inriz.
ewn!
22
f002)d,a.
4'1102)d,a.
3V(787)dia_
2W(508)dia.
<34'(864)dia.
OR
33,44
4'(1 OF ilia.
-
717 (508)dia.
-
-
5 x i'
S' x 4-
34' x 31'
22' x 2T
R 72 20
0.1
22
(127 x102)
(12, x102)
(86,1 x787)
(559 x508)
(1829 081
-
cc
33 d4 ..-
5 4
-
22 x 20'--
1127 102j
(559x508)
FRAME LJfI I -1-A �.
..-411.111091--,..I -�f
MOUNTING
VERTICAL MOUNT DOLLAR
CO IndlVldi I a Lions of mulllpl section assembly o1 to exceed 24 (610) in Vi dtn up to -�
O V -
48' (12t9) Wido Assemblies larper than 48(121 ) In width will ba made up of indviduai
sections Trot` to exceed 18- (45/) wide
U Non- tandard temperture fusible link Specify _ 1
❑ Facta Sleeve Available m 10 (3.5) through 22 ga. (0,85) galy steel and in
Inn s required for application Specify: _ length. ,-, ga. -- --
O Lin U sealed. Suitable for low pressure systems.
❑ HP 5 elect. Suitable fOr-diurnmigh pressure Systems. Externally STAINLESSSTEEL CUPIAIN BLADE
Caulk d. (Up t06 W.q. (1.5 kPaj). GLOSUPESPRING LOCKINGRAMP
DYNAM C VELOCITY/PRESSURE RATING: HORIZONTAL MOUNT
C] 24 2 00 fpm @ 4• w.g. (Standard) NOTES:
U 34 3 0 fpm @ 4" w.g. 1. See sizing chart for relationship of duct size and
(Optional) dem er size. Refer to drawin 00100-MSSC.
d4 4 00 fpm @ 4" w,g, P 9
SCHEDULE TYPE: For instahation instructions, see IOM-FDINST,
non Icr SI!NSHINr INN nAMPFRC Dimensions are in inches (rrm),
'4 Na par Ind1w rea Inc. reeerves One right to change any No I"l gn c-'eni I 0 wodur oI p ing without ut,cr,
0/A CAL Cs
PER FMC 2017 (6rE� Edition) TABLE 403.3.1.1
SANTUARY.. 143 PERSONS @ 5 CFM/PERSON .... 715 CFM
, 350 CFM x 2 = 700 CFM 0/A PROVIDED (SEE NOTE BELOW)
ENTRYAREA .. 270 SF x 10/1000 .. 2.7 PERSONS x 5 .... 13.5 CFM
OFFICE AREAS.. 720 SF x 5/1000 .. 3.6 x 5 .... 18 CFM
TOTALS: SANTUARY= 71S/2 UNITS = 357.5 CFM EACH UNIT
OFFICE + ENTRY = 18 + 13.5 CFM = 31.5 CFM.. 300 CFM PROVIDED
NOTE: 300 - 31.5 = 268.5 CFM OVERFLOW FOR EXTRA SANTUARYCFM
�
I
�
NOTE: 0"125"x 1 " WIDE CLIP ANGLE
WITH (2) - #12-24, SKIS TO UNIT AND
WITH (1) - %"x 1-3/4"EMBED 'TAPCON
TO CONCRETE PAD - (TYPICAL EACH CORNER)
Q
c
A jc
tJNIT CASING
PROOFHURRICANE INSTALLATION
-1
0//
35C
HVAC PLAN
AA- 11)
m
'C
SCALD ! II . I I,OII
9
--� (P L AL WELCH INC.
MECHANICAL ELECTRICAL CIVIL ENGINEERING
1984 S.W. BILTMORE ST. SUITE #114
PORT ST. LUCIE, FL 34984
PHONE (772) 785-9888 E-MAIL PWELCHINC(a,AOL.COM
WELCH, P.E. FLA REG NO. 29945
I
l i
MAY 2 0 2020 L(3;1, county, Pe.f_i itting
9h
•
•
•
i
SHEET NUMBER
m