HomeMy WebLinkAboutReview CommentsH. STEVE CLARK, ARCHITECT
ALTAMONTE SPRINGS, FLORMA
Email: G1ea60f1v amaiLcom
To: Saint Lucie Building Department
September 2012019
2300 Virginia Avenue
Ft Pierce, FL 34982 PERMIT # 1905-0020
RE: A New CBS Building — United Pentecostal Fire Ministry Trinity International
202 East Midway Road, Fort Pierce Florida 34982
�(D a
***RESPONSE- REVIEW COMMENTS 6/19/2019***
To whom it may concern:
Item No.1 Mechanical Plans ( Edited 6/20/2019) Heat Load provided
Item No. 2 Calculations included in submission 5/1/2019
Item No. 3 3 Sets of Truss Drawings with shop drawings were included in submission on 5/1/2019'
Item No. 4 Construction Type is III (Cmu wjuiood truss roof) noted on Sheet 1
Item No. 5 Fire Partition UL344 is detailed on wall Section and material noted on Sheet 2 Note (F)
Item No. 6 Fire Partition UL 327 is detailed on wall Section and material noted on Sheet 2 Note (E)
Item No. 7 Fire Stop Penetration -noted in notes on Sheet 1
Item No. 8 Door Egress capacity is noted on life safety plan on Sheet 3 and other locations
Item No. 9 Fire blocking and draft stopping noted and shown on the plans
Item No.10 Flame and Spread requirements for insulation are noted on plans
Item No.11 Interior walls and Ceiling. Finish are Class A
Item No. 121b rvgln Sanctuary, Classrooms and Offices. Ceramic Tile flooring throughout other
location not identified. CT has no Fiber
Item No. 13 Wood Trim, Wood Base, Chair Rail, and covered mold to be painted with walls.
Item No. 14 Occupant Load has been tabulated and shown on Sheet 1
Item No.15 Section 1006 requires 2 exits for (Sanctuary A3) 4 are provided, 2 exits required for Business area of
Building and 2 are provided. SEE SHEET 1. (8)
Item No.16 Seating in the Sanctuary is non -fixed and noted on Sheet 1. in Life Safety Data
Item No.17 Capacity and width of Egress Component are shown on Sheet 3.
Item No.18 Dimension are given on life safety plan and all are less than required
Item No.19 Emergency lighting is shown in the Electrical Room
Item No. 20 Fire Emergency panic hardware at doors are noted on the plans
Item No. 21 Ramp details has been added to plans. SHEET 1.
Item No. 22 Aisles in Sanctuary are shown on Floor Plan Sheet 1(B) and Life Safety Plan Sheet 3 (C). Min Required
(1029.6) 42" Wide, shown on plan 60" Wide this is more than adequate.
Item No. 23 Owner has eliminated Aluminum Covered Walkway
Item No. 24 Truss to Truss connections shown at Boston Hip detail. SEE SHEET 3 (G)
Item No. 25 Framed Opening at DBi doors in fire partition has been added
Item No. 26 Infill Detail for Arch at Arched windows has been added SEE.SHEET 3 (E)
Item No. 27 Framing Detail for Arch construction at drop has been added
Item No. 28_ Boston Hip Detail has been added. SEE SHEET 3 (G)
Item No. 29 Cast Crete is noted on- lintel schedule: TOP OF SHEET 2.
476 SPANISH TRACE DRIVE ALTAMONTE SPRINGS, FWRWA 32714
ARCHTIECI URAL REGISTRATION: AR 0011463