HomeMy WebLinkAbout2422 oak dr faSTATE OF FLORIDA
DEPARTMENT OF HEALTH
ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEM
CONSTRUCTION INSPECTION AND FINAL APPROVAL
APPLICANT: Ron Raymond
AGENT: MICHAEL STUHR (ASHTON SEPTIC TANKS, INC.)
PROPERTY ADDRESS: 2422 Oak Dr Fort Pierce, FL 34949
APPLICATION #:A+P1605278
PERMIT #:56-SF-2210651
DOCUMENT #:F11718223
DATE PAID' 12/07/2020
FEE PAID:660.00
RECEIPT #:56-PID-4822898
LOT: 6 & 7
SUBDIVISION:
BLOCK: 3
Fort Pierce Shores ID#: 1436-601-0055-000-7
CHECKED [X] ITEMS ARE NOT IN COMPLIANCE WITH
STATUTE OR RUDE AND MUST BE CORRECTED.
TANK
INSTALLATION
SETBACKS
[ ]
[01]
TANK SIZE [11 1090.00 [21 300.00
[ ] [271
SURFACE WATER
FT
[ ]
[021
TANK MATERIAL Polypropylene
[ ] [281
DITCHES
FT
[ ]
[031
OUTLET DEVICE
[ ] [291
PRIVATE WELLS 91
FT
[ ]
[041
MULTI -CHAMBERED [ Y N ]
[ ] [301
PUBLIC WELLS
FT
[ ]
[051
OUTLET FILTER PolylokPL-68
[ ] (311
IRRIGATION WELLS
FT
[ ]
[061
LEGEND 1. 70-143-11DC4 2. 70-156-03SC3
[ ] [321
POTABLE WATER 30
FT
[ ]
[071
WATERTIGHT
[ ] [331
BUILDING FOUNDATIONS 5.5
FT
[ ]
[081
LEVEL
[ ] [341
PROPERTY LINES 9
FT
[ ]
[091
DEPTH TO LID
[ ] [351
OTHER
FT
DRAINFIELD INSTALLATION
FILLED / MOUND SYSTEM
[ ]
[101
AREA [1] 509.4 [21 SQFT
[ ] [361
DRAINFIELD COVER
[ ]
[111
DISTRIBUTION BOX HEADER X
[ ] [37]
SHOULDERS
[ ]
[121
NUMBER OF DRAINLINES 1. 6.00 2.
[ ] [381
SLOPES
[ ]
[131
DRAINLINE SEPARATION
[ ] [391
STABILIZATION
[ ]
[141
DRAINLINE SLOPE
[ ]
[151
DEPTH OF COVER
ADDITIONAL INFORMATION
[ ]
[161
ELEVATION [ ABOVE / BELOW ]BM 8.00
[ ] [401
UNOBSTRUCTED AREA
[ ]
[171
SYSTEM LOCATION
[ ] [411
STORMWATER RUNOFF
[ ]
[181
DOSING PUMPS 1.00
[ ] [421
ALARMS
[ ]
[191
AGGREGATE SIZE
[ ] [431
MAINTENANCE AGREEMENT
[ ]
(201
AGGREGATE EXCESSIVE FINES
[ ] [441
BUILDING AREA
[ ]
[211
AGGREGATE DEPTH
[ ] [451
LOCATION CONFORMS WITH SITE PLAN
FILL
/ EXCAVATION MATERIAL
[ ] [461
FINAL SITE GRADING
[ ] [471
CONTRACTOR MICHAEL W STUHR (ASHTO
[ ]
[221
FILL AMOUNT
[ ] [481
OTHER INFILTRATOR Quick4 Plus EQ36 LP
[ ]
[231
FILL TEXTURE
[ ]
[241
EXCAVATION DEPTH
ABANDONMENT
[ ]
[251
AREA REPLACED
[ ] [491
TANK PUMPED
[ ]
[261
REPLACEMENT MATERIAL
[ ] [501
TANK CRUSHED & FILLED
Comments: Comments
are on page 2.
CONSTRUCTION [ APPROVED / St. Lucie CHD DATE: 09/10/2021
DISAPPROVED Environmental Specialist III B n J Ingram (ENVIRONMENTAL HEALTH)
FINAL SYSTEM [ APPROVED / DISAPPROVED ]:�— t. Lucie CHD DATE: 10/22/2021
n nm pecia ist I Matthew S Vaja i Ada Department of H
(Explanation of Violations on following page)
DH 4016, 08/09 (Obsoletes all previous editions which may not be used)
Incorporated: 64E-6.003, FAC Page 2 of 3
EH Database v 1.0.1 AP160 5278 EID2210651
STATE OF FLORIDA
DEPARTMENT OF HEALTH
ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEM
CONSTRUCTION INSPECTION AND FINAL APPROVAL
Violation Number Comment
Comments
APPLICATION #:Ai`16052 8
PERMIT #:56-SF-2210651
DOCUMENT # : FI 1718223
DATE PAID :12/07/2020
FEE PAID:660.00
RECEIPT # :56-PI D-4822898
The system is sized for 3 bedrooms with a maximum occupancy of 6 persons (2 per bedroom), for a total estimated flow of 300
gpd.
New ST, filter, DT, liberty 1/3 hp pump, and 3x7+3x8 long BED DF installed. No violations, system ok to cover, contractor notified
by phone. Needs final inspection for mound system, alarm check, and final site grading.
Final inspection completed. Mound system, final site grading, and alarm checked.
Final inspection approved. Emailed copy to building department and contractor.
DH 4016, 08/09 (Obsoletes all previous editions which may not be used)
Incorporated: 64E-6.003, FAC Page 2 of 3
EH Database v 1.0.1 AP1605278 EID2210651