HomeMy WebLinkAboutAPPROVED, Philip Beekman Hip & ridge NOA5/11/2021 Florida Building Code Online
FL *
FL5374-116
Application Type
Revision
Code Version
2020
Application Status
Approved
Comments
Archived
Product Manufacturer East Coast Metals, Inc.
Address/Phone/Email 7905 W. 20th Avenue
Hialeah, FL 33014
(305) $85-9991
acastellanos@eastcoast-metaLs.com
Authorized Signature Tom Castellanos
mstellanosoeastcoast-metats.com
Technical Representative Tom Castellanos
Address/Phone/Emall 790E W. 20th Avenue
Hialeah, FL 33014
(30S) 885-9991
tom0eastcoast-metats.com
Quality Assurance Representative Andrew Castellanos
Address/Phone/Email 7905 W. 20th Avenue
Hialeah, FL 33014
(305) 885-9991
andrew@eastcoast-metals.com
Category Roofing
Subcategory Roofing Accessories that are an Integral Part of the Roofing System
Compliance Method Evaluation Report from a Florida Registered Architect or a Ucensed Florida
Professional Engineer
Evaluation Report - Hardcopy Received
Florida Engineer or Architect Name who developed the Robert Nlerninen
Evaluation Report
Florida License PE-59166
Quality Assurance Entity Architectural Testing, Inc., an Intertek Company
Quality Assurance Contract Expiration Date 12/31/2023
Validated By John W. Knezevtch, PE
Validation Checklist - Hardcopy Received
Certificate of Independence
Referenced Standard and Year (of Standard)
FRSA/TRI (09-18)
2018
RAS 118
2020
RAS 119
2020
RAS 120
2020
SSTO 11
1997
TAS 101
1995
https:llftoridabuilding.orglprl"ppjU.aspx?param=wGEVXCWANtVSv8n7GDFXfrAzV6GMEbUpLHfA5CWUPE%3d 112
5/11/2021
Florida Building Code Online
Equivalence of Product Standards
Certified By
Sections from the Code
Product Approval Method Method 1 Option 0
Date Subn-fitted 09/29/2020
Date Validated 10/05/2020
Date Pending FBC Approval 10/12/2020
Date Approved 12/15/2020
Summary of Products
FL
Model, Number or Name
Description
5374.2
TRIMLOCK and TRIMLOCK PLUS
Preformed hip & ridge anchor designed for use with adhesive -
set roof We.
limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
fU374 66 112020 09 29 FINAL ER ECM Mint
Approved for use outside HVHZ: Yes
Lga F1.5374-116,01'
Impact Resistant: N/A
Verified By: Robert Nieminen PE-59166
Design pressure: +N/A/-178
Created by Independent Third Party: Yes
Other* 1.) Refer to Evaluation Report Section 5 for Limits of
Evaluation Reports
Use. 2.) The design pressure herein pertains to use in non-
EL5374 R6 AE 2029 Q2 29 FINA idin
HVHZ jurisdictions In conjunction with Table 1A of FRSA/M
Lock 537-4-R6.pdf
(09-18). Refer to Tables 2A and 26 In the Evaluation Report for
Created by Independent Third Party: Yes
all options and associated allowable design pressures.
ED ED
Contact us :: 2601 Stair Stone Road. JJ#AbA= FL 32399 Phom! 850-467-1824
The State of Florida is an AAAEO employer. Cony it 2007,2013 State of Florida. :: EftKYJJ*J&MWt :: ACCRAIWAY Statement :: Refund statement
Under Florida law, email addresses are public records. U you do not want your *,mad address released In response to a Public -records request, do not Send electronic
mail to this entity. Instead, contact the office by phone or by traditional mall. Ir you have any questions, please contact 850.487.1395. *Pursuant to Section 455.27S(l),
Florida Statutes, effective October 1, 2012, kensees licensed under Chapter ass, F.S. must provide the Department with an emall address It they have am. The emaile,
provided may be used for official communication with the licensee. Howew emall addresses are public record. if you do not wish to supply a personal address, plane
provide the Department with an email address which can be made available to the public. lb determine if you are a scancee under Chapter 4SS, F.S, please dick hem.
Product Approval Accepts:
M Fail 99 E
Credit Card
safe
https:llftoridabtfilding.org/prlpr_appjd.aspx?param--wGEVXQwtDqtVSv8n7ODFXfrAzV6GMEbUpLWA5CWUPEII*3d 212
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nleminen,
P.E. for use of the product under the Florida Building Code. The products described herein have been evaluated for
compliance with the 7* Edition (2020) Florida Building Code sections noted herein.
DEscRtpTm: TRIMLOCK and TRIMLOCK PLUS Hip & Ridge Anchor
LABEUNr.: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted
herein.
CownNuEo CompuANcE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance or production facility location(s) changes, or Code provisions that relate to the product(s) change.
Acceptance of our Evaluation Reports by the named client constitutes agreement to notify NEMO ETC, LLC of any
changes to the product(s), the Quality Assurance or the production facility location(s). NEMO ETC, LLC requires a
complete review of its Evaluation Report relative to updated Code requirements with each Code Cycle.
MvERTisEmENr. The Florida Product Approval Number (FL#) preceded by the words "NEMOJetc. Evaluated" may be
displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its
entirety.
INsPEcnoN: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 7.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DC4 ME1983
:4 ass
The facsimile seat appearft was authorized by Robert
Nieminen, P.E. on 09/29/2020. This 4m not serve as an
etectronically signed do—n-t.
CMni`KATt0N Of INOVENDENCE:
1. NEW ETC, LLC does not have, nor does it intend to acquire or will It acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMO ETC, LLC is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nleminen, P.E. does not have, nor Will acquire, a financial Interest In any other entity Involved in the approval process of the
product.
S. This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nleminen, P.E. are, in any way, the Desigrier of Record for any
project on which this Evaluation Report, or previous versions thereat Is/was used for permitting or design guidance unless retained
specifically for that purpose.
02019, NEMO ETC, LLC
NNEMOletc.
Product Category- Roofing
Sub -Category: Roofing Accessories that are an Integral Part of the Roofing System
Compliance Statement: TRIMLOCK and TRIMLOCK PLUS, as produced by East Coast Metals, have demonstrated
compliance with the following sections of the 71 Edition (2020) Florida Building Code through testing in
accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations
/ Conditions of Use set forth herein.
1518.8.1
1523.6.5.2.2
1504.2.2.1
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
Florida TEC (TST7393)
NEW (TST6049)
PRI(TSTS878)
PRI(TSTS878)
PRI (TSTS878)
PRI (TSTS878)
PRI (TSTS878)
PRI (TSTS878)
PRi (TSTS878)
East Coast Metals
Intertek/ATI (QUA1944)
lntertek/A'n (QUA1944)
rropemr
Installation, non-WHZ
Installation, WHZ
Static uplift resistance
Overturning resistance
Static Uplift Resistance
Static Uplift Resistance
Static Uplift Resistance
TAS 101
Tensile adhesion
TAS 101
TAS 101
TAS 101
TAS 101
TAS 101
TAS 101
TAS 101
Metal Quality
Quality Control
Quality Control
MafidaLd-
FRWRI (09-18)
2018
RAS 118,119 & 120
2020
TAS 101
1995
SaCCI SSM 11
1997
ECM-SC6795.12.14-1
ECM-SC679S.12.14-2
S10-628R
4i-ECM-20-SSCRT
ECM-001-02-01
ECM-003-02-01
ECM-004-02-01
ECM-DOS-02-01
ECM-006-02-01
ECM-007-02-01
ECM-009-02-01
Will Certifications
Participation Letter
Florida BCIS
4.1 TRIMLOCK.,
Pre -formed metal channel designed for use as a hip and ridge
base to which roof tiles are bonded in FBC Approved roof the
adhesive. TRIMLOCK is characterized by its profiled and
perforated upper horizontal flange designed to receive and
allow for interlock with the overlying the adhesive.
TRIMLOCK Is available in 119-3/8-Inch L+ 3/r) length by 3, 3.5,
4, 5 or 6-Inch L+ 3/8-inch) heights with 1.5-Inch L+ 1/164nch)
deck -flanges.
02/27/2015
02/27/2015
IW27/2010
09/29/2020
09122/2001
06/13/2008
06/13/2008
06/13/2008
06/1312WS
06/13/2008
06/13/2008
Various
03/21/2015
Current
NEMO ETC, ELC Evaluation Report E10MM.08-ItS,
Certificate olAuthorkation 432455 7- EDITION (2020) F13C NON-HVHZ & HVHZ EVALUATION FL5374-RS
TRIMLOCK and TRINILOCK PLUS Hip & Ridge Anchor Revision s: 09/2912=
Page 2 of 7
•
4.2 TRIMLOCK PLUS:
Pre -formed metal channel designed for use as a hip and ridge
base to which roof tiles are bonded In FBC Approved roof tile
adhesive. TRIMLOCK PLUS is characterized by Its profiled and
perforated upper horizontal flange designed to receive and
allow for interlock with the overlying tile adhesive and its
perforated deck flanges, designed for installation atop the roof
underlayment via placement In FBC Approved roof tile adhesive,
which flows -through and interlocks with the underlying
adhesive.
TRIMLOCK PLUS is available in 119-3/8-Inch (t 3/8")length by 3,
3.5, 4, 5 or 6-inch (+ 3/8-Inch) heights with 1.S-inch (± 1/16-Inch)
deck -flanges.
4.4 TRIMLOCK and TRIMLOCK PLUS are fabricated of the following metals:
> Gatvalume Steel: Min. 0.019 + 0.002-inch, ASTM A792, AZSS, min. 35 KSI.
> Aluminum: Min. 0.032 + 0.002-inch, ASTIVI 8209,3003-H14, min. 21 KSI.
> Stainless Steel: Min. 0.019 + 0.002-inch, ASTMI A240/A480, T304, min. 35 KSL
5.1 This Is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting
or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report pertains to above -deck roof components. Roof decks and structural members shall be in
accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
5.3 This Evaluation Report does not include evaluation of fire classification. Refer to FOC 1505 or R902 for
requirements and limitations regarding roof assembly fire classification. Refer to FBC 2603 for requirements and
limitations concerning the use of foam plastic insulation.
5.4 This Evaluation Report does not include evaluation of roof edge termination.
5.5.1 For TRIMLOCK, refer to FBC RAS 118, Drawing 13, Detail 3; RAS 119, Drawing 12, Detail 3; or RAS 120, Drawing 15,
Detail 3. For TRIMLOCK PLUS, refer to the installation instructions herein.
5.5.2 Installations of TRIMLOCK are prescriptive by RAS 118, 119 and 120, and the data in Tables 1A and 18 is
supplemental to these prescriptive allowances.
Installations of TRIMLOCK PLUS are limited to projects having a required moment resistance (Mr) or uplift
resistance (F,), as determined in accordance with RAS 127, not greater than the data in Tables 1A and 18.
NEMO ETC, LLC Evaktation Report E10240.08.08-M
Cert6wte ofAuthodtatbn 432455 7- EDITION (2020) FBC NON-HVHZ & HVHZ EVALUATION FL5374-R6
TRIMLOCK and TRIMLOCK PLUS Hip & Ridge Anchor Revision S: 09/29/2020
Page 3 of 7
Hip & Ridge Anther
z
Tile,
Adhesive
'Allowable Performance
Placement
Moment Based
Uplift,flased
"llin
�Wtal Type
.1— .
Type
.1111:� '' . : I � :
. (SeiS.7)
mi (ft-lbf),
P., filif)
Galvalume,
ICP Adhesives & Sealants -Polyset
TRIMLOCK
aluminum or
clay or
AN-160' or DAP Foam 'Touch 'n Seal
Independent
271
159
stainless steel
concrete
StormBond 2 Two -Component Roof
Tile Adhesive"
Galvalume",
ICP Adhesives & Sealants 'Polyset
TRIMLOCK
aluminum or
clay or
AM-16W or DAP Foam 'Touch'n
Independent
177
165
PLUS
stainless steel
concrete
Seal StormBond 2 Two -Component
Roof Tile Adhesive
lfip$Aldge_
e
es I've
.'Allowable
placement
Metal
4:
(See 5.7)
r: 'Mf (ft4bf
TRIMLOCK
GatvalumeO,
1CP Adhesives & Sealants -Polyset
or
aluminum or
clay or
AH-160' or DAP Foam "Touchn
Interdependent
9S
88
TRIMLOCK
stainless steel
concrete
Seal StormBond 2 Two -Component
PLUS
I
Roof Tile Adhesive
TRIMLOCK
GalvalumeO,
clay or
ICP Adhesives & Sealants "Polyset
Interdependent
99
94
stainless steel
concrete
RTA-1"
TRIMLOCK
aluminum
clay or
ICP Adhesives & Sealants "Polyset
Interdependent
90
94
concrete
RTA-r
TRIMLOCK
Gaivalumes,
aluminum or
clay or
ICP Adhesives & Sealants "Polyset
Interdependent
90
84
PLUS
stainless steel
concrete
RTA-1'
I
TRIMLOCK
GalvalumeO or
clay or
DuPont de Nemours 'TILE BOND"
Interdependent
123
117
stainless steel
concrete
Roof rile Adhesive
TRIMLOCK
aluminum
clay or
DuPont de Nemours 'TILE BOND""
Interdependent
79
73
concrete
Roof Tile Adhesive"
TRIMLOCK
GaivalumeO,
aluminum or
clay or
DuPont de Nemours "TILE BOND"'
Interdependent
79
73
PLUS
stainless steel
concrete
Roof Tile Adhesive
TRIMLOCK
Gatvaiume® or
clay or
DAP Foam DAP Foam 'Touch 'n Seal
Interdependent
146
139
stainless steel
concrete
StormBond Roof Tile Adhesive
TRIMLOCK
Aluminum
clay or
DAP Foam DAP Foam 'Touch'n Seat
Interdependent
58
S4
concrete
StormBond Roof rile Adhesive"
TRIMLOCK
Gaivalume*,
clay or
DAP Foam DAP Foam 'Touch'n Seal
PLUS
aluminum or
concrete
Storm8ond Roof Tile Adhesive'
Interdependent
S8
54
I stainless steel
I
I
I
I
I I
MEMO ETC, LLC Evaluation Report E10240.09.09-R5
C"ftate ClAuthodZ060ft #32455 74" EDITION (2020) FOC NON41VHZ & HVHZ EVALUATION FL5374-R6
TRIMLOCK and TRIMLOCK PLUS Hip & Ridge Anchor Revision S- 09/29/2020
Page 4 of 7
MIN
5.6.1 For TRIMLOCK, refer to FRSA/TRI Florida High Wind Concrete and Coy Roof Tile Installation Manual, Sixth Edition.
For TRIMLOCK PLUS, refer to the installation instructions herein
5.6.2 Installations are limited to projects having hip and ridge design pressure requirements, determined in accordance
with Table 1A of FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition, not
greater than the following values.
Tile
Desigrt,
Metal Type
Type
Placement
(See 5.7)
GalvalumeO
clay or
ICP Adhesives & Sealants 'Polyset AH-160" or
TRIMLOCK
aluminum or
DAP Foam "Touchn Seal StormBond 2 Two-
Independent
173
stainless steel
concrete
Component Roof Tile Adhesive"
GalvalumeO
clay or
tCP Adhesives & Sealants "Polyset AH-160" or
I
TRIMLOCK PLUS
aluminum or
DAP Foam 'Touchn Seal StormSond 2 Two-
Independent
178
I
stainless steel
concrete
Component Roof Tile Adhesive
'Hip gc Ridge Andeor'.
Tile
Ali
Allowable
LIP
Meta- I Type
"yl
;Pla nt came
Isee sm
TRIMLOCK or
Galvalumem
clay or
ICP Adhesives & Sealants "PolVset AH-160' or
TRIMLOCK PLUS
aluminum or
concrete
DAP Foam 'Touchn Seat StormBond 2 Two-
Interdependent
98
stainless steel
Component Roof Tile Adhesive'
TRIMLOCK
GatvalumeO or
clay or
ICP Adhesives & Sealants 'Polyset RTA-V
Interdependent
110
stainless steel
concrete
TRIMLOCK
aluminum
clay or
ICP Adhesives & Sealants "Polyset RTA-V
Interdependent
93
concrete
Galvalume,
day or
TRIMLOCK PLUS
aluminum or
ICP Adhesives & Sealants "PoIVset RTA-1"
Interdependent
93
stainless steel
concrete
TRIMLOCK
Galvalume* or
day or
DuPont de Nemours 'TILE BONDTM Roof Tile
Interdependent
152
stainless steel
concrete
Adhesive
TRIMLOCK
aluminum
clay or
DuPont de Nemours 'TILE BOND"' Roof Tile
Interdependent
92
concrete
Adhesive
Galvalume*,
TRIMLOCK PLUS
aluminum or
clay or
DuPont de Nemours `TILE BOND' Roof Tile
Interdependent
82
stainless steel
concrete
Adhesive'
TRIMLOCK
Galvalume* or
day or
DAP Foam DAP Foam 'Touch'n Seat StormBond
Interdependent
148
stainless steel
concrete
Roof Tile Adhesive
TRIMLOCK
Aluminum
day or
DAP Foam DAP Foam "Touch 'n Seal StormSond
Interdependent
61
concrete
Roof Tile Adhesive"
GalvalumeO ,
day or
DAP Foam DAP Foam "Touch'n Seal StormBond
TRIMLOCK PLUS
aluminum or
Interdependent
61
stainless steel
concrete
Roof Tile Adhesive"
I
I
I
NEW ETC, LLC Evaluation Report E10240.09.08-RS
Certykate ofAuthodwtibn 932455 7- EDITION (2020) FSC NON41VI9 & HVHZ EVALUATION FLS374-R6
TRIMLOCK and TRIMLOCK PLUS Hip & Ridge And Revision 5: 09/29/2020
Page 5 of 7
MEMO etc.
5.7 Refer to the the adhesive manufacturer's published installation instructions for adhesive paddy placement details.
➢ "INDEPENDENT" paddy placement: Each individual the is bonded to the hip & ridge anchor in its own, single
foam paddy or continuous foam ribbon; the head laps are not bonded. Allowable performance data for
"INDEPENDENT" paddy placement has a 2 to 1 margin of safety applied to ultimate performance.
➢ "INTERDEPENDENT" paddy placement: Each individual the is bonded to the hip & ridge anchor in a foam
paddy, and a second foam paddy bonds the the head lap, or two tiles are bonded to the hip & ridge anchor
using a single foam paddy. Allowable performance data for "INTERDEPENDENT" paddy placement has a 4 to
I margin of safety applied to ultimate performance.
6.1 The roof deck shall be minimum 15/32-inch plywood (non-HVHZ) or minimum 19/324nch plywood {HVHZ)
attached in accordance with FBC Chapter 23 to the satisfaction of the Authority Having Jurisdiction.
6.2 TRIMLOCK or TRIMLOCK PLUS shall be free of dust, debris, oils or other bond -breaking substance prior to
placement of adhesive.
6.3 TRIMLOCK shall be Installed using min. 11 ga. x 19-inch long x 3/8-inch head diameter galvanized annular ring
shank nails spaced 6-inch o.c. along both deck -flanges. Fasteners shall be positioned Yinch from the outside edge
of each deck -flange, set In a bed plastic roof cement. For FBC HVHZ, refer to FBC RAS 118, Drawing 13, Detail 3;
RAS 119, Drawing 12, Detail 3; or RAS 120, Drawing 15, Detail 3.
6.4 TRIMLOCK PLUS shall be installed atop the Approved roof underlayment in continuous 2-inch wide ribbons of the
adhesive centered beneath each 1.5-inch wide deck flange. Place the TRIMLOCK PLUS into the wet adhesive and
allow it to set-up prior to installation of roof tiles.
View of Tile Adhesive Placement for TRIMLOCK PLUS Installation
6.4.1 It is critical that the bond between the TRIMLOCK PLUS, the tile adhesive and the underlayment is not disturbed
prior to or during placement of the ridge tiles.
NEMO ETC, LLC Evaluation Report E10240.09.08-M
Certiftate of Authorization 432455 7- EDITION (2020) FBC NON-HVHZ & HVHZ EVALUATION FL5374-R6
TRIMLOCK and TRIMLOCK PLUS Hip & Rkige Anchor Revision 5: 09/29/2020
Page 6 of 7
ODEMO letc.
6.4.2 Data herein for TRIMLOCK PLUS relates to installation over a TWO-PLY underlayment system, as detailed in the
FRSA/TR1 Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition, using a hot -asphalt -
applied, ASTM D6380, Class M cap sheet (commonly called a '30/90 system').
Alternate underlayment systems are those having a current Florida Statewide Product Approval and/or approved
on a local -level by the Authority Having Jurisdiction, listed specifically for use With the selected Approved the
adhesive.
6.5 Tile shall be installed atop the hip & ridge anchor in accordance with the tile adhesive manufacturer's Approved,
published installation Instructions, subject to the limitations outlined in Section S herein. The exposed edges shall
be packed and pointed with Approved mortar or weather blocking adhesive in accordance with FRSA/TRI Florida
High Wind Concrete and Clay Roof rile Installation Manual, Sixth Edition or RAS 118, RAS 119, RAS 120
requirements.
Hip / Ridge Tile
MR, ........... 1
. . ..... ..
Tile Adhesive
Trim Lock Plus
Mortar or Weather Block
Adhesive
Ile Adhesive
View of TRIMLOCK PLIJS Installation after Weather Blocked
I I
As required by the Building Official or Authority Having Jurisdiction in order to property evaluate the installation of
this product.
Architectural Testing, Inc., an Intertek Company — QUA1844, (847) 718-6307; nauraalcheikh0intertek.com
MEMO ETC, LLC Evaluation Report E10240.08.0845
CCM&OW OfAUM"katfon #32455 7- EDITION (2020) FBC NON-HVHZ & HVHZ EVALUATION FL5374-R6
TRIMLOCK and TRIMLOCK PLUS Hip & Ridge Anchor Revision 5: 09/29/2020
Page 7 of 7