HomeMy WebLinkAboutGENERATOR PAD DETAILEXISTING POLE MOUNTED
TRANSFORMERS
EXISTING OVERHEAD
UTILITY DROP
NEW RACK WITH ATS
AND EXISTING
CONTROL CABINET
EXISTING UTILITY POLE
WITH METER CAN
EXISTING VAULT
EXISTING WET WELL
EXISTING CHAIN
LINK FENCE
EXISTING CONCRETE PAD
3'-0"
NEW GENERATOR
AND PAD
09/15/2021
2 OF 2GENERATOR SITEPLAN, DETAILS &NOTESDATEDESIGNEDDRAWNCOMPLETE ELECTRIC, INC.637 SEBASTIAN RD.SEBASTIAN, FL. 32958(772) 388-0533EC 0001911DATEREVISIONMARKDATE:
SHEET
E-210/27/20201REVISED PER ST. LUCY COUNTY BUILDING REVIEW1" = 10'-0"
2 ENLARGED GENERATOR PLAN
N
W
S
E
GENERATOR ANCHORING
ELECTRICAL GENERAL NOTES:
1.THE ELECTRICAL CONTRACTOR SHALL VERIFY AND COORDINATE ALL ELECTRICAL
SERVICE ROUGH IN AND INSTALLATION DETAIL WITH THE LOCAL UTILITY POWER
COMPANY.
2.THIS ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH THE FLORIDA
BUILDING CODE 7TH EDITION (2020), LOCAL ORDINANCE, AND THE NATIONAL
ELECTRIC CODE THIRTEENTH EDITION NFPA 70 (2017).
3.ALL ELECTRICAL WORK FOR THE ENTIRE PROJECT SHALL BE PERFORMED IN A
NEAT AND CRAFTSMAN LIKE MANNER BY PERSONS SKILLED IN THE ELECTRICAL
TRADE, AND SHALL BE DONE UNDER THE SUPERVISION OF A MASTER
ELECTRICIAN LICENSED IN THE STATE OF FLORIDA.
4.THIS ELECTRICAL INSTALLATION SHALL BE PROTECTED FROM PHYSICAL DAMAGE
AND SECURELY SUPPORTED AND FASTENED, WITH WORKING SPACE PER NEC
110.26.
5.PVC SCHEDULE 40 CONDUIT SHALL BE USED UNDERGROUND, IN OR BELOW
CONCRETE AND WHERE EXPOSED NOT SUBJECT TO DAMAGE. PVC SCHEDULE 80
CONDUIT SHALL BE USED WHERE EXPOSED, SUBJECT TO DAMAGE.
6.ALL MATERIAL SHALL BE NEW, FREE FROM DEFECT AND SHALL BE LISTED AND
BEAR THE LABEL OF A RECOGNIZED TESTING LABORATORY.
7.DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW EXACT LOCATIONS OF
DEVICES AND EQUIPMENT. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT
LOCATIONS.
8.GROUNDING PER NEC ARTICLE 250.
9.INSTALL LOAD CENTERS AND DISCONNECTS SO THAT AT LEAST 3 1/2FEET OF
WORKING SPACE CAN BE MAINTAINED PER NEC 110.26.
10.ALL MATERIALS SHALL BE NEW AND SHALL BEAR U.L. LABELS WHERE
APPLICABLE.
11.ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID
INTERFERENCE WITH THE PROCESS OF CONSTRUCTION.
12.PROVIDE FAULT CURRENT MARKER PER NEC 110.24 AND ARC-FLASH DECALS PER
NEC 110.16.
13.EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE
ENVIRONMENT IN WHICH THEY ARE TO BE INSTALLED. ALL COMPONENTS OF THE
ELECTRICAL SYSTEM LOCATED OUTDOORS OR INDOORS WHERE EXPOSED TO
SIGNIFICANT MOISTURE SHALL BE WEATHERPROOF, NEMA 3R, AS A MINIMUM
INDICATED ON THE CONTRACT DRAWINGS OR NOT.
14.PROVIDE TYPED PANEL DIRECTORIES FOR ALL NEW PANELBOARDS, AND
EXISTING PANELBOARDS AFFECTED BY THIS PROJECT. DIRECTORIES SHALL
REFLECT PROJECT AS-BUILT CONDITIONS FOR ALL BRANCH CIRCUITS.
DIRECTORIES SHALL INCLUDE WHERE EACH PANEL IS FED FROM. ADDITIONALLY,
EACH BRANCH CIRCUIT LOAD DESCRIPTION SHALL INCLUDE THE ROOM
NUMBER(S) FOR EACH LOAD SERVICE. ROOM NUMBERS SHALL BE BASED ON
ACTUAL ROOM SIGNAGE INSTALLED IN FIELD. COORDINATE EXACT ROOM
NUMBERS WITH A/E AND OWNER PRIOR TO COMPLETION OF PANEL DIRECTORIES.
15.PROVIDE ENGRAVED PLASTIC LAMINATE NAME TAGS ON EACH SWITCHBOARD,
SWITCHGEAR, DISTRIBUTION PANEL, PANELBOARD, MOTOR CONTROL CENTER,
SAFETY SWITCH, ENCLOSED CIRCUIT BREAKER, CABINET, STEP-DOWN
TRANSFORMER, TRANSFER SWITCH , ETC., AND ANY OTHER MAJOR COMPONENT
OF THE ELECTRICAL SYSTEM.
16.PROVIDE ENGRAVED PLASTIC LAMINATE NAME TAGS FOR EACH DISTRIBUTION
BREAKER OR BRANCH CIRCUIT BREAKER IN SWITCHGEAR, SWITCHBOARDS,
MOTOR CONTROL CENTERS AND OTHER DISTRIBUTION EQUIPMENT. NAME TAG
SHALL INCLUDE LOAD DESCRIPTION AND ROOM NUMBER FOR EACH LOAD
SERVICE.
17.PROVIDE LABELS ON THE INSIDE OF EACH DEVICE COVER PLATE, IDENTIFYING
THE PANES(S)/CIRCUIT NUMBERS(S).
18.PROVIDE NEATLY, HANDWRITTEN IDENTIFICATION ON THE EXTERIOR COVER OF
ALL JUNCTION AND PULL BOXES, WIREWAYS. IDENTIFYING THE PANEL(S)/CIRCUIT
NUMBERS(S) CONTAINED WITHIN.
TOP VIEW
LEFT ELEVATION FRONT ELEVATION
DRILL
DRILL
1/4"
DEEPER
THAN
ANCHOR
EMBEDMENT
CLEAN DRIVE TIGHTEN
3-5 X
DRILL BIT SIZE: 1/2"TIGHTENING
TORQUE: 45ft.lbs.
MIN. ANCHOR
EMBEDMENT: 2-1/2"
1/4" MIN.88"
38"
8" MIN.
38"88"
NOTE:
1.THE USE OF A CARBIDE DRILL BIT
CONFORMING TO ANSI STANDARD B212.15 IS
RECOMMENDED.
2.ANCHOR BOLTS TO BE 3/8"DIA.x3-3/4"LONG
UNLESS OTHERWISE NOTED.
1/2" = 1'-0"
3 GENERATOR PAD DETAIL
N.T.S.
1 OVERALL SITE PLAN
N
W
S
E
1
2 COMMENTS. PERMIT No. 2109-07111
NEW GENERATOR FOR:OCEAN RESORTS5101 N. HIGHWAY A1AFORT PIERCE, FL. 349491
F:\GENERATOR DRAWINGS\08-27-2021 Ocean Resorts Lift Station\08-27-2021 Ocean Resorts Lift Station.dwg, 10/27/2021 3:54:12 PM