2021-0167E0-1-E0-1
ELECTRICAL SPECIFICATIONS ELECTRICAL SHEET INDEX Project: PART 1 - GENERAL E0.1 ELECTRICAL NOTES, LEGEND & INDEX LIGHTING FIXTURE SCHEDULE A. THE CONTRACTOR SHALL SUPPLY AND INSTALL ALL NEW ELECTRICAL WORK INDICATED. E1.1 SITE POWER PLAN LAMPS CONSTRUCTION SHALL BE IN ACCORDANCE WITH DRAWINGS AND APPLICABLE SPECIFICATIONS. TYPE MANUFACTURER CATALOG NUMBER DESCRIPTION DIMMING VOLTS MOUNTING REMARKS IF A PROBLEM IS ENCOUNTERED IN COMPLYING WITH THIS REQUIREMENT, CONTRACTOR SHALL NOTIFY E2.1 LIGHTING PLAN Qty Type Total Wattage THE ARCHITECT/ENGINEER AS SOON AS POSSIBLE AFTER DISCOVERY OF THE PROBLEM AND SHALL NOT PROCEED WITH THAT PORTION OF THE WORK UNTIL ARCHITECT/ENGINEER HAS DIRECTED E2.2 EMERGENCY PHOTOMETRIC PLAN -4 0 WHERE CORRECTIVE ACTION TO BE TAKEN. RENOVATION Al H.E. WILLIALMS GH -L540/840-HA-FA-DIM-UNV MODULAR LED HIGHBAY WITH FROSTED ACRYLIC LENS AND HIGH AMBIANT OPERATING TEMP INCL LED 372.2 SHOWN ON PLAN UNV SURFACE 1,3 B. THE CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO BID AND FAMILIARIZE HIMSELF WITH ALL CONDITIONS AFFECTING ELECTRICAL AND COMMUNICATIONS INSTALLATION AND MAKE PROVISIONS AS TO E3.1 POWER PLAN Al EM H.E.WILLIALMS GH-4-L540/840-HA-FA-EM/20W-DIM-UNV MODULAR LED HIGHBAYWITH FROSTED ACRYLIC LENS AND HIGH AMBIANT OPERATING TEMP & EM INCL LED 372.2 0-10V WHERE UNV SURFACE 1,3 THE COST THEREOF. FOR SHOWN ON PLAN C. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC E4.1 EQUIPMENT SCHEDULE AND DETAILS 0-10V WHERE CODE (AS ADOPTED BY THE AUTHORITY HAVING JURISDICTION) AND ALL CODES AND ORDINANCES OF THE C H.E.WILLIALMS GH-2-L360/840-HA-FA-DIM-UNV MODULAR LED HIGHBAY WITH FROSTED ACRYLIC LENS AND HIGH AMB[ANT OPERATING TEMP INCL LED 272.6 SHOWN ON PLAN UNV SURFACE 1,3 AUTHORITY HAVING JURISDICTION. THE SPECIFICATION, CODES AND STANDARDS LISTED BELOW ARE E4.2 EQUIPMENT SCHEDULE AND DETAILS UTILIZED IN THIS PROJECT. CEM H.E.WILLIALMS GH-2-L360/840-HA-FA-EM/20W-DIM-UNV MODULAR LED HIGHBAY WITH FROSTED ACRYLIC LENS AND HIGH AMBIANT OPERATING TEMP & EM INCL LED 272.E 0-10V WHERE 1. NATIONAL ELECTRICAL CODE (NFPA-70) E5.1 ELECTRICAL RISER DIAGRAM SHOWN ON PLAN UNV SURFACE 1,3 2. CODE FOR SAFETY TO LIFE (NFPA_101) CONTENDER 0-10V WHERE 3. STANDARD FOR THE INSTALLATION, MAINTENANCE AND USE OF LOCAL PROTECTIVE SIGNALING D BEGHELLI USA BS100LEDX-4HT-WT40-120-277V 4' LED VAPORPROOF INCL LED 100 SHOWN ON PLAN UNV SURFACE 1 SYSTEMS (NFPA-72) 4. UNDERWRITERS' LABORATORIES (UL) BOATS DEM BEGHELLI USA BS100LEDX-4SA-WT40-120-277V 4' LED VAPORPROOF WITH EM INCL LED 100 5. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA) 0-10V WHERE SHOWN ON PLAN UNV SURFACE 1 6. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) 7. FEDERAL SPECIFICATION (FED. SPEC.) ELECTRICAL LEGEND E H.E.WILLIALMS GH-2-L360/840-HA-FA-DIM-UNV MODULAR LED HIGHBAY WITH FROSTED ACRYLIC LENS AND HIGH AMB[ANT OPERATING TEMP INCL LED 125.9 0-10V WHERE UNV SURFACE 1,3 8. INSULATED POWER CABLE ENGINEERS ASSOCIATION (IPCEA) SHOWN ON PLAN 9. FLORIDA BUILDING CODE. FBC 2014 EDITION 10. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE) TELEPHONE OUTLET WITH 3/4" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING. EEM H.E.WILLIALMS GH-2-L360/840-HA-FA-EM/20W-DIM-UNV MODULAR LED HIGHBAY WITH FROSTED ACRYLIC LENS AND HIGH AMBIANT OPERATING TEMP & EM INCL LED 125.9 0-10V WHERE SHOWN ON PLAN UNV SURFACE 1,3 11. ST. LUCIE COUNTY BUILDING CODE. (AMENDMENTS TO FLORIDA BUILDING CODE FBC 2014) MOUNT 18" A.F.F. TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED. 5701 ENVIRONMENTAL DRIVE 12. ADDITIONALLY, DESIGNS, WORK PRACTICES AND CONDITIONS MUST CONFORM WITH THE DATA OUTLET WITH 3/4" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING. ST. LUCIE COUNTY, FLORIDA X. BEGHELLIUSA VA4-R-SA POLYCAROBNATE LED EXITWTTH BATTERY INCL LED 2 N/A UNV UNIVERSAL 1,2 OCCUPATIONAL SAFETY AND HEALTH ACT OF 1970 (OSHA) D. DO NOT SCALE THE ELECTRICAL DRAWINGS. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS MOUNT 18" A.F.F. TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED. FOR EXACT LOCATION OF ALL EQUIPMENT. CONFIRM WITH OWNER'S REPRESENTATIVE. TELEPHONE/DATA OUTLET WITH 3/4" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING. E. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE MOUNTED ABOVE COUNTER, SEE ARCHITECTURAL DRAWING FOR SPECIFIC REQUIREMENTS. CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM LIGHTING SCHEDULE NOTES: AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER. TELEPHONE/DATA OUTLET WITH 3/4" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING. F. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FROM A v MOUNT 18" A.F.F. TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED. 1. PROVIDE SUBMITTALS FOR ARCHITECT/ENGINEER REVIEW PRIOR TO ORDERING. NO SUBSTITUTIONS ALLOWED. PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE. G. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE TELEPHONE/DATA OUTLET WITH 3/4" CONDUIT RUN TO THE NEAREST STUD WALL AND 2. FINISH COLOR SELECTED BYARCHTTECT REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED ❑0 STUBBED OUT FROM WALL 6" ABOVE CEILING. PROVIDE BRASS COVER PLATE AND THERE BY. CARPET FLANGE. H. ALL REQUIRED INSURANCE SHALL BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY AND 3. PROVIDE WITH CORD AND NEMA TWISTLOCK PLUG PROPERTY DAMAGE FOR THE DURATION OF THE WORK. TELEVISION RECESSED OUTLET. LEGRAND "TVIWMTVSSWCC2". CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS AND TESTING. CONTRACTOR MOUNT AT 18" A.F.F. TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED. TO OBTAIN PERMIT AND APPROVED SUBMITTALS PRIOR TO BEGINNING WORK OR ORDERING EQUIPMENT. THE TERM "PROVIDE" USED IN THE CONSTRUCTION DOCUMENTS AND SPECIFICATIONS SHALL MEAN THAT 20 AMP SINGLE RECEPTACLE (NEMA 5-20R) MOUNTED AT 18" A.F.F. TO CENTER LINE OF THE CONTRACTOR IS TO FURNISH, INSTALL AND CONNECT COMPLETE. �Y OUTLET UNLESS NOTED OTHERWISE. PART 2 - PRODUCTS 'li' 20 AMP DUPLEX RECEPTACLE (NEMA 5-20R) MOUNTED AT 18" A.F.F. TO CENTER LINE OF A. MINIMUM WIRE SIZE SHALL BE #12 A.W.G. (EXCEPT AS NOTED OTHERWISE FOR CONTROL WIRING). ALL 11 OUTLET UNLESS NOTED OTHERWISE. CONDUCTORS SHALL BE 98% CONDUCTIVITY, COPPER WITH "THHN-THWN" INSULATION UNLESS OTHERWISE 20 AMP QUADRUPLEX RECEPTACLE (NEMA 5-20R) MOUNTED AT 18" A.F.F. TO CENTER LINE S S u e S NOTED. OF OUTLET UNLESS NOTED OTHERWISE. B. ELECTRICAL METALLIC TUBING (EMT) SHALL BE OF BEST QUALITY STEEL, SMOOTH INSIDE AND OUT No,: Date: Description: AND SHALL BE HOT-DIPPED GALVANIZED. �GFI 20 AMP DUPLEX RECEPTACLE (NEMA 5-20R) WITH GROUND FAULT CIRCUIT INTERRUPTER, - - C. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS MOUNT AT 18" A.F.F. TO CENTER LINE OF OUTLET. UNLESS NOTED OTHERWISE. A. I. IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURES FOR OTHER CLASSIFIED AREAS. 20 AMP DUPLEX RECEPTACLE (NEMA 5-20R) MOUNTED ABOVE COUNTER D. RIGID NONMETALIC CONDUIT SHALL BE SCHEDULE 40 PVC. TT SEE ARCHITECTURAL DRAWINGS FOR SPECIFIC REQUIREMENTS. L: ALL MATERIALS SHALL BE NEW AND BEAR UNDERWRITERS' LABELS WHERE APPLICABLE. 20 AMP DUPLEX RECEPTACLE (NEMA 5-20R) WITH ISOLATED GROUND, MOUNT AT 18" A.F.F. F. PANELBOARDS: 41 TO CENTERLINE OF OUTLET UNLESS OTHERWISE NOTED. 1. CURRENT CARRYING BUSES SHALL BE COPPER. GROUND BUS BARS SHALL BE COPPER. ldftl 20 AMP QUADRUPLEX RECEPTACLE (NEMA 5-20R) WITH ISOLATED GROUND, MOUNT AT 18" GEN ERA N 0 T E S 2. ALL CIRCUIT BREAKERS SHALL BE BOLT ON. PLUG-IN BREAKERS ARE NOT ACCEPTABLE. A.F.F. TO CENTERLINE OF OUTLET UNLESS OTHERWISE NOTED. 3. CIRCUIT BREAKERS USED AS SWITCHES IN FLUORESCENT OR HID LIGHTING CIRCUITS SHALL BE LISTED AND MARKED "SWD" ❑® 20 AMP DUPLEX RECEPTACLE (NEMA 5-20R), RECESS FLOOR MOUNTED. PROVIDE BRASS 4. ALL CIRCUIT BREAKERS FEEDING MECHANICAL EQUIPMENT SHALL BE HACR TYPE. COVER PLATE AND CARPET FLANGE. 5. A.I.C. RATINGS SHALL BE AS INDICATED ON PANELBOARD SCHEDULES. 1@1 20 AMP DUPLEX RECEPTACLE (NEMA 5-20R), CEILING MOUNTED. L 0 W VOLTAGE SWITCH D ETA I L 6. ALL PANELBOARDS SHALL BE FURNISHED WITH PLASTIC LAMINATE NAMEPLATES WITH 1/4" A. ALL EQUIPMENT TO BE BY INTELLIGENT LIGHTING CONTROLS, INC. ENGRAVED LETTERING FOR PANEL IDENTIFICATION. SPECIAL-PURPOSE RECEPTACLE ON-SITE SYSTEM COMMISSIONING SHALL BE REQUIRED. 7. ALL PANELBOARDS SHALL BE PROVIDED WITH TYPE-WRITTEN DIRECTORY OF BRANCH CIRCUIT DESIGNATIONS. J JUNCTION BOX O COMMISSIONING OF SYSTEMS VIA MODEM WITHOUT ON-SITE SUPPORT G. DISCONNECT SWITCHES SHALL BE H.P. RATED, HEAVY DUTY, QUICK-MAKE, QUICK-BREAK. ENCLOSURES SHALL NOT BE ACCEPTED. SHALL BE NEMA-1 FOR INDOOR LOCATIONS, NEMA 3R FOR OUTDOOR LOCATIONSOR AS OTHERWISE NOTED. OP NISTALLNGLE GINN EXACT CMANNER TION XASODIRECTED BYWER NFURNITURE IOOSU SUPPLIER. FURNITURE SYSTEM H. MOTOR STARTERS SHALL BE MANUAL OR MAGNETIC AS INDICATED ON THE ELECTRICAL DRAWINGS, WITH B. ELECTRICAL CONTRACTOR TO PROVIDE CAT-5 DATA CABLE. TM WIRING DEVICES GENERAL PURPOSE RECEPTACLES AND WALL SWITCHES COLOR SHALL BE COORDINATED DOUBLE GANG JUNCTION BOX FOR TELEPHONE/DATA CONNECTION TO MODULAR FURNITURE SEE CAT-5 REQUIREMENTS SHEET 8c RJ45 CONNECTOR DETAIL. LightSync OVERLOAD RELAYS IN EACH PHASE.G2 Dataline Switch Detail WITH CLIENT. ( ) OT�o SYSTEM. INSTALL IN EXACT MANNER AND LOCATION AS DIRECTED BY FURNITURE SUPPLIER. EXTEND (2) 3/4" EMPTY CONDUITS FROM JUNCTION BOX TO ABOVE TEST ALL CABLE LENGTHS AND TERMINATION'S W/CAT-5 TESTER. 79 Switch Insert PART 3 - EXECUTION CEILING AND TERMINATE WITH INSULATING BUSHING 6" FROM WALL. Decors Type A. COLOR CODING OF CONDUCTORS SHALL BE AS FOLLOWS: Address C. ALL LOW VOLTAGE COMMUNICATION CABLE & HARDWIRE LOW 15 Position 1. Wheels (2) Cut-out 1. 208/120 VOLTS, 3 PHASE, 4-WIRE SYSTEM: UNGROUNDED CONDUCTORS: 1 BLACK, 1 RED AND 1 Q TELE/POWER POLE FOR TELEPHONE/DATA/POWER CONNECTION TO MODULAR FURNITURE VOLTAGE CONTROL WIRING TO BE INSTALLED PER NATIONAL o o BLUE. GROUNDED (NEUTRAL) CONDUCTOR; WHITE. GROUNDING CONDUCTORS SHALL BE GREEN. 8 WIRE SYSTEM (SEE DETAIL THIS SHEET). INSTALL IN EXACT MANNER AND LOCATION O 0 2. 480/277 VOLT, 3-PHASE, 4-WIRE SYSTEM: UNGROUNDED CONDUCTORS: 1 BROWN, 1 YELLOW, AND AS DIRECTED BY FURNITURE SUPPLIER, WIREMOLD CATALOG # 25DTP-4D W/IVORY FINISH. ELECTRICAL CODE FOR CLASS-2 LOW VOLTAGE WIRING. 1 PURPLE. GROUNDED (NEUTRAL) CONDUCTORS; GREY. GROUNDING CONDUCTORS SHALL BE GREEN. a t0) 3. BRANCH CIRCUIT WIRING (#6 AND SMALLER) SHALL BE COLOR CODED BY CONTINUOUS INSULATION ❑® SPECIAL PURPOSE RECEPTACLE MOUNTED BELOW RAISE FLOOR. D. CLASS-2 LOW VOLTAGE WIRING SHALL NOT BE MIXED WITH OR COLOR AND FEEDERS AND SERVICES (#4 AND LARGER) SHALL BE CODED AT ALL JUNCTION OR ti O " PULL POINTS (EXCEPT LB'S OR LBD'S) USING COLOR MARKERS OR PLASTIC TAPE MANUFACTURED EF EXHAUST FAN. SEE MECHANICAL DRAWINGS FOR SPECIFICATIONS. RUN IN LINE VOLTAGE RACEWAYS. SEPARATE LOW VOLTAGE RUNS � � 1 .17 1• FOR THE PURPOSE. FROM LINE VOLTAGE BY A MINIMUM DISTANCE OF 1 -FOOT. 3 o C 3.249 B. WIRING METHODS SINGLE POLE, 20 AMP, SWITCH. MOUNT 46" A.F.F. TO CENTERLINE OF SWITCH UNLESS 1 .71 1. ALL CONDUCTORS SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING (EMT) UNLESS OTHERWISE NOTED. E. CAT-5 DATA CABLE RUNS TO BE INSTALLED IN A DAISY CHAIN 1.83 OTHERWISE NOTED, SPECIFIED OR AS SPECIFICALLY PROHIBITED BY THE AUTHORITY HAVING FROM ONE PANEL OR DEVICE TO THE NEXT. NO "STAR" OR "T" ` JURISDICTION. ALL FITTINGS AND COUPLINGS FOR EMT CONDUIT SHALL BE ALL STEEL $3 3-WAY, 20 AMP, SWITCH. MOUNT 46" A.F.F. TO CENTERLINE OF SWITCH UNLESS O RAIN TIGHT COMPRESSION TYPE OR ALL STEEL CONCRETE TIGHT SET SCREW TYPE. OTHERWISE NOTED. CONFIGURATIONS ALLOWED WITHOUT POWER SUPPLY REPEATERS. 0 2. SCHEDULE 40 PVC CONDUIT, WITH FITTINGS AND COUPLINGS APPROPRIATE FOR THE USE, SHALL BACK FRONT BE INSTALLED UNDERGROUND OR BELOW SLABS ON GRADE. $o SINGLE POLE, 20 AMP, SWITCH WITH DIMMER. MOUNT 46" A.F.F. TO CENTERLINE OF SWITCH F. ALL CLASS-2 & CAT-5 DATA CABLE RUNS TO BE PROVIDED AND DEPTH 1-1/8" HOLE FOR FOR #6-32 3. TYPE MC CABLE WITH ALUMINUM ARMOR AND INTERNAL GROUND IS ACCEPTABLE FOR UNLESS OTHERWISE NOTED. INSTALLED WITH THE APPROPRIATE JACKET TYPE OR CONDUIT RJ-45/CAT-5 JACK (2) #6-32 THREADED SE AS GENERAL BRANCH WALLS CIRCUIT OR ABOVE SUSP NDED WIRING R CIRCUITS AMPERES CEILIINGA D ASAPPROV D BY OR LESS AND CONCEALED THE HAVING N $M MOTOR RATED SWITCH FOR THE INSTALLATION ENVIRONMENT OR CONDITIONS ON SITE. JURISDICTION. C. ELECTRICAL SYSTEM SHALL BE COMPLETE AND EFFECTIVELY GROUNDED AS REQUIRED BY THE LATEST VACANCY SENSOR SWITCH, WATTSTOPPER, MOUNT 46" A.F.F. TO CENTERLINE OF SWITCH G. EACH LIGHTING RELAY PANEL REQUIRES A DEDICATED 120V. EDITION OF THE N.E.C. AND LOCAL CODES. UNLESS OTHERWISE NOTED. OR 277V. CIRCUIT FOR CONTROL POWER TRANSFORMERS. D. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS $ TWO POLE, 30 AMP SWITCH. MOUNT ADJACENT EQUIPMENT TO BE CONTROLLED. WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTED BY ENGINEER/ARCHITECT. H. ADDITIONAL ILC POWER OR DATA REPEATING DEVICES MAY BE REQUIRED E. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS ® FACTORY MOUNTED DISCONNECT/STARTER (SEE MECHANICAL SCHEDULE) FOR PROPER SYSTEM OPERATION, BASED ON THE ACTUAL NUMBER OF CONSTRUCTION. F. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF POWER AND TELEPHONE 1p AB FUSIBLE DISCONNECT SWITCH A = POLES, B= FRAME SIZE, C= FUSE RATING AND DISTANCE OF LightSync DEVICES TO BE INSTALLED ON CAT-5 COMPANIES, AND SHALL BE FULLY COORDINATED WITH THEM PRIOR TO COMMENCEMENT OF WORK. DATA LINE. CONTACT AMY LEE C�? SESCO LIGHTING 954-474-9888. G. PROVIDE AND INSTALL CONDUIT, CONDUCTORS, PULL WIRES, BOXES, COVER PLATES, AND WIRING B DEVICES, FOR ALL OUTLETS AS INDICATED. 1=1 A FUSIBLE MOTOR STARTER DISCONNECT SWITCH A = POLES, B= NEMA SIZE, C= FUSE RATING H. MATERIALS, PRODUCTS, AND EQUIPMENT, INCLUDING ALL COMPONENTS THEREOF, SHALL BE NEW AND SUCH AS APPEAR ON THE UL LIST OF APPROVED ITEMS AND SHALL MEET OR EXCEED THE REQUIREMENTS OF NEC, NEMA, AND IECE. GROUNDING ELECTRODE & CONDUCTOR SYSTEM CONTRACTOR SHALL SUBMIT AT LEAST FIVE (5) SETS OF SHOP DRAWINGS OR CUT SHEETS OF LIGHTING T1 FIXTURES, SWITCHES, AND OTHER ELECTRICAL ITEMS FOR APPROVAL BY ENGINEER/ARCHITECT. TRANSFORMER CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED OF HIS WORK. K. ALL LAY-IN LIGHTING FIXTURES SHALL BE SECURED TO THE SUSPENDED CEILING GRID AT EACH CORNER. p ELECTRICAL PANELBOARD L. CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS AND PROVIDE ALL NECESSARY CONTROL WIRING. 0- TELEPHONE WOOD BACKBOARD M. ALL ELECTRICAL POWER WIRING FOR THE HVAC SYSTEM INCLUDING WIRING THRU LINE VOLTAGE CONTROL DEVICES SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. LIGHTING CONTROL SYSTEM WP WEATHERPROOF N. THE CONTRACTOR SHALL CONFIRM WITH THE ELECTRICAL UTILITY COMPANY ANY AND ALL REQUIREMENTS C TIME CLOCK SUCH AS: METERING EQUIPMENT REQUIREMENTS AND METERING EQUIPMENT LOCATION, TRANSFORMER T/ SIZE AND LOCATION OR SERVICE POINT, CONDUIT ENTRY AND LUG SIZE RESTRICTIONS. THE CONTRACTOR Architect: NE RISER SHALL SCHEDULE ALL REQUIRED DOWN TIME FOR THE OWNERS CONFIRMATION. RE RELOCATED ANY CONFLICTS AND DESCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE E EXISTING TO REMAIN 0. PROCEEDING WITH ANY WORK. PER NEC 210.8(B)(2) ALL 15- AND 20-AMPERE, 125-VOLT RECEPTACLES IN NONDWELLING-TYPE KITCHENS A.F.F. ABOVE FINISH FLOOR O ° O ° O ° TO BE GFCI PROTECTED. P•BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE DROP OF 3% DESIGN LOAD. FBC 2014 O CEILING MOUNTED DUAL TECHNOLOGY MOTION SENSOR BY WATTSTOPPER. FBC ENERGY CONSERVATION SECTION 405.7.3. o 0 o Q. FEEDER CONDUCTORS SHALL BE SIZED FOR A MAXIMUM OF 2% VOLTAGE DROP PER 405.7.3. OLV CEILING MOUNTED LOW VOLTAGE DUAL TECHNOLOGY MOTION SENSOR BY WATTSTOPPER. D O N A D I O line G2 LV Switch G2 LV Switch G2 LV Switch v. O CEILING MOUNTED DAY LIGHTING SENSOR. SENSOR TO CONTROL THE DIMMING OF ALL FIXTURES & Associates, Architects P.A. a a I Oa d DS WITHIN 15 OF THE WINDOWS WITH IN ROOM. 200191h Avenue,suite 308 ' o Vero Beach,FL 32960 •• (typical of up to 4) a e Fax.772.562.8600 www.donadio-arch.com License No.AA0002238 ILC APPRENTICE II Consultant: RELAY PANEL O CAT5 CABLE WITH RJ45 CONNECTORS ELECTRICAL NOTES Drawing Title: EXISTING CONDITIONS EXTERIOR ELEVATIONS Reference North Drn: Drawing File: Digitally signed by Bradly L ISSUED FOR PERMIT ONLY 06-23-21 MT Bradly LBrown P.E. NOT FOR PRICING OR CONSTRUCITON Chd: XREF File: AJ D DN: en=Bradly L Brown P.E., KAMM CONSULTING PROJECT#: 2021-0167 Project No.: Plot File: PROJECT MANAGER: JOHN MAYR o=Kamm Consulting Inc., 2020-33 m m 1408 Orange Avenue Brown ou=F L# 58232, Fort Pierce,Florida 34950 Sheet No.: Phone 954.448.0792 Cert. No.: 12456 email=jmayr kammconsultin jmayr@kammconsulting.com OIIs11 Certification of Authorization#8189 PRINCIPAL Date Signed: g.com, c=US 08-12-21 E091 Bradly L Brown Florida License#58232 date POE * Date: 2021 .08.12 15:19:20 _0^' signed Copyright ©2020,Donadio&Associates,Architects,P.A.,All Rights Reserved