HomeMy WebLinkAboutEngineering Submittal-DigiCert, Williams Residence, Generac 22KW Generator,10.26.21Model/Tag:22 KW Generac Wind Speed: 170 Exposure: D Risk Category:2 Engineering Submittal Wind Load Certification October 26, 2021 Williams Residence116 Island Dune WayJensen Beach, FL 34957 Job Name & Location: Design Parameters: FBC 2020 & ASCE 7-16 806 Delaware Ave. (772) 267-1399 Fort Pierce, FL 34946 benchmarkengineeringtc@gmail.com Benchmark engineering of the treasure coast LLc. Model/Tag:22 KW Generac Design Parameters W 30 in (Min) WL 15 in WS 15 in L 48 in (Max) HRTU 29 in (Max) HC 30 in (Max) HFW 44.5 in WCM 454 lb (Min)Fasteners: VWIND 170 mph Exp D Required Fastener Resistance on Critical Side Max Ht.15 ft FR=1,141 LB Wind Loading Per ASCE 7-16: Wind Pressure Al Rack to Slab on Grade Fastener QH=.00256 (KZ)(KZT)(KD)(VWIND)^2 (4) 1/4"x2" Tapcons @:2020 lb per (25% Manf. KZ 1.03 Min. Number of Legs per Side 4 each Pull-Out KZT 1.0 Total Number of Legs per Stand 8 each Rating KD 0.85 Number of Fasteners per Base Plate:4 each VWIND 170 mph QH=64.8 lb/ft^2 Gen to Rack Fastener 3/8" SS Thru-Bolts @:1650 lb per (25% SS Lateral Force Min. Number of Fasteners Near Corners:4 each Proof Rating) FWL=QH (GCR) AF GCR 1.9 AF 4.8 ft^2* FWL=595 lb Uplift FWU=QH (GCR) AF GCR 1.5 AF 10.0 ft^2 FWu=972 lb Sum Moments Notes:1. Certification is for specified attachments only MWL=26,470 in lb 2. Prefab slab on grade shall be 4" thick min. MWU=14,574 in lb 3. Fasteners may be upsized or increased without comment MWCM =-6,810 in lb M=34,234 in lb Bowdoin G. Hutchinson P.E. FL # P.E. 70878