Lucas A. Turner, P.E.
FL PE #58201
Evaluation Report 1068C
June 28, 2019
Product Description: Series 6100 PVC Single Hung, Large Missile Impact Wind Zone 3,
53 1/8” x 76” max. unit size +/-50 psf
Manufacturer: Custom Window Systems, Inc. 1900 SW 44th Ave, Ocala, FL 34474
Statement of Compliance: This report evaluates the above-listed product per the requirements
of FAC Product Approval Rule Chapter 61G20-3.005 (4). This product complies with the
requirements of the 6th Edition (2017) Florida Building Code, not including the High Velocity
Hurricane Zone or Wind Zone 4. The product testing standards performed are outlined below.
Technical Documentation:
1) This report, prepared by Lucas A. Turner, P.E., at 2428 Old Natchez Trc Trl, Camden, TN
2) Approval drawing CWS-1068C, signed and sealed by Lucas A. Turner, P.E.
3) Test Reports NCTL-210-3964-07/08, by National Certified Testing Laboratories, Orlando,
FL, and Test Report CWS-007-02-01, from PRI Construction Materials Technologies,
Tampa, FL, with testing performed: ASTM E 1886 ‘05, ASTM E 1996 ‘05/09 (large
missile impacts in accordance with Wind Zone 3), and AAMA/WDMA/CSA
101/I.S.2/A440 ’08/11
4) Supplemental Calculations to support CWS-1068C, signed and sealed by Lucas A. Turner,
P.E.
Installation: Units must be installed according to approval document CWS-1068C.
Limitations of Use: This product:
May be used up to the sizes and daylight openings with glazing as indicated in CWS-
1068C
Achieves design pressures of +/-50 psf for flange and fin
Is Large Missile impact resistant and does not require the use of shutters
May not be used in the High Velocity Hurricane Zone or Wind Zone 4 areas
Requires Dupont Butacite PVB Interlayer
Requires ATN PVC frames with current listing as AAMA 303 Certified Profile Licensee
Certification of Independence: I do not have, nor do I intend to acquire, nor will I acquire, a
financial interest in Custom Window Systems or in any company manufacturing or distributing
products for which this report is being issued. I do not have, nor do I intend to acquire, nor will I
acquire, a financial interest in any other entity involved in the testing or approval process of this
product.