NOTICE OF ACCEPTANCE (NOA) www.miamidade.sov/economy
Polyglass USA Inc.
1111 W.Newport Center Drive
Deerfield Beach,FL 33442
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami-Dade County RER-Product Control Section to be
used in Miami-Dade County and other areas where allowed by the Authority Having Jurisdilctionl(AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami-Dade County Product Control Section
(in Miami-Dade County) and/or the AHJ(in areas other than Miami-Dade County)reserve the right to have this
product or material tested for quality assurance purposes.If this product or material fails to perform in the accepted
manner,the manufacturer will incur the expense of such testing and the AHJ may immediateely revoke,modify,or
suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance,
if it is determined by Miami-Dade County Product Control Section that this product or material fails to meet the
requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: Polyglass Polystick Underlayments
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo,city,state and following
statement: "Miami-Dade County Product Control Approved",unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials,use, and/or manufacture of the product or process.Misuse of this NOA as an endorsement of any product,
for sales,advertising or any other purposes shall automatically terminate this NOA.Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, F}orida, and followed
by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then
it shall be done in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or i�s distributors and
shall 3e available Tor Inspection at Me Jou s to at the request of the Building Official.
Reviewed
This OA renews andr�e�v'ises NOA No.14- 717.08 and consists of pages 1 through 8.
The srbmitted docura
( tion was reviewe by Gaspar J Rodriguez.
Code CompHance
05/11/17 File copy
® NOA No.: 15-0410.04
MAMIMOE I Expiration Date: 09/13/21
-- Approval Date: 08/11/16
Page 1 of 8
f
I
I
ROOFING COMPONENT APPROVAL
Category: Roofing
Sub-Category: Underlayment
Material: SBS ,APP Self-Adhering Modified Bitumen
I
i
PRODUCTS DESCRIPTION:
Test Product
Product Dimensions Specification Description
Polystick IR-Xe 65'x 3'33/8" ASTM D 1970 A fine granular/sand top surface self-adhering,APP
Manufacturing Or 65'x 3' polymer modified,fiberglass reinforced,bituminous
Location#1  60 mils thick sheet material for use as an underlayment in sloped roof
assemblies. Designed as an ice e&rain shield.
Polystick Dual Pro 61 x 3 3-s/s TAS 103 and A rubberized asphalt self-adhering,glass-fiL..Jpolyester
Manufacturing 60 mils thick ASTM D 1970 reinforced waterproofing membra Ire. Designed as a
Location#2
metal roofing and roof tile uni erla ent. y
Polystick Tile Pro 61'x 3'33/s" TAS 103 and A rubberized asphalt self-adhering,glass-fiber/polyester
Manufacturing 60 mils thick ASTM D 1970 reinforced waterproofing membrane.Designed as a metal
Location#2 roofing and roof tile underlays ent.
Polystick TU Max 658"x 3'3-3/8" TAS 103 and A rubberized asphalt self-adhering I polyester reinforced
Manufacturing 60 mils thick ASTM D 1970 waterproofing membrane. Designed as a a roof tile
Location#1  underlayment.
Polystick TIT P 32'10"x T3-- TAS 103 and A rubberized asphalt waterproofing membrane;.glass +,
Nlanufacturang 130 mils thick ASTM D 1970 fiber./polyester reinforced,with a.gr�anular surface;
Location#2 designed for use as a tile roof underlayment,
Polystick TV Plus 65'x 3'33/8" TAS 103 and A rubberized asphalt self-adhering, glass-fiber/polyester
(Surface Printing) 80 mils thick ASTM D 1970 reinforced waterproofing membrane.Designed as a metal
Manufacturing roofing and roof tile underlayment.
Location#1 
Polystick MTS 65'8"x 3'33/8" TAS 103 A homogeneous,rubberized as half waterproofing g i p rp ofing
Manufacturing 60 mils thick membrane,glass fiber reinforced with polyolefinic film
Location#2 on the upper surface for use as an underlayr at for metal
roofing,roof tile, slate tiles and shi Ingle underlayment.
Polystick MTS Plus 65'8" x 3'33/8" TAS 103 A homogeneous,rubberized asphalt waterp-; ifing
Manufacturing 60 mils thick membrane,glass fiber reinforced with polyolefinic film
Location#2 on the upper surface for use as an underlayment for metal
roofing,roof tile, slate tiles and shingle underlayment.
Elast( TAS 103 and Polyester reinforced, SBS moi ified bitumen membrane
Mang acturingReviewed ASTM D 6164 with a sanded back face and 'granule top surface. For
Location#2 or use in roof tile underlayment syste s.
Code C ompHance
05/11/17
NHf�91-�tiIDEE�IJE�Tt I
OA No.: 15-0410.04
Expiration Date: 09/13/21
Approval Date: 08/11/16
Page 2 of 8
i
MANUFACTURING PLANTS:
I
1. Hazelton,PA
2. Winter Haven,FL
EVIDENCE SUBMITTED
Test Agency Test Identifier Test Name/Renort i Date
Trinity ERD P10870.09.08-R1 TAS 103 12/04/08
P10870.04.09 TAS 103/ASTM D4798 &G155 04/13/09
P33360.06.10 ASTM D1970 07/01/10
P33370.03.11 TAS 103 03/02/11
P33370.04.11 ASTM D 1623 04/26/11
P36900.09.11 TAS 103/ASTM D4798 &(j155 09/01/11
P37300.10.11 TAS 110/ASTM D4798 &D1970 10/19/11
P40390.08.12-2 ASTM D 1623 ; 08/07/12
P37590.07.13-1 ASTM D6164 1 07/02/13
P45270.05.14 TAS 103,TAS 110&ASTM D1623 05/12/14
P46520.10.14 ASTM D1623 10/03/14
P44360.10.14 TAS 103 &TAS 110 10/07/14
P43290.10.14 ASTM D 1970&TAS 110 10/17/14
PLYG-SC10130.06.16-3 TAS 103 &TAS 110 06/27/16
PLYG-10130.06.16-1 ASTM D1970&TAS 110 06/27/16
PRI Asphalt Technologies PUSA-035-02-01 TAS 103 09/29/06
PUSA-055-02-02 TAS 103 I 12/10/07
PUSA-089-02-01 TAS 103/ASTM D4798 &G155 ;-7/06/09
Momentum Technologies,Inc. JX20H7A TAS 103/ASTM D4798 &G155 ,')4/01/08
RX14E8A TAS 103/ASTM D4798 8 G155 11/09/09
DX23D8B TAS 103/ASTM D4798 &G155 02/18/10
DX23D8A TAS 103/ASTM D4798 8 G155 02/18/10
LABELING:
I. All membranes or packaging shall bear the imprint or identifiable marking of the manufacturer's name or logo, city
and state of manufacturing facility and the following statement: "Miami-Dade County Product Control Approved"
or the Miami-Dade County Product Control Seal as shown below.
MIAMIOADE COUNTY
BUILDING PERMIT REQUIREMENTS:
Application for building permit shall be accompanied by copies of the following:
1.Th s NoticePgZF(5t (5d
2. other document equired by the Building Official or applicable building code in order to properly evaluate the
ins allation of this44 rials.
Code CompHance
05/11/17
==MADE COUNT�f. I
NOA No.: 15-0410.04
_ Expiration Date: 09/13/21
Approval Date: 08/11/16
Page 3 of 8
INSTALLATION PROCEDURES: i
i
Deck Type 1: Wood,non-insulated
Deck Description: Min. 19/32"plywood or wood plank 1
System Type E(1): Anchor sheet mechanically fastened to deck,membrane adhered
Anchor/Base Sheet: One or more plies of ASTM D 226 Type H or ASTM D 2626.
Fastening: Per FBC 1518.2& 1518.4 Nails and tin caps 12" grid, 6" o.c. at a minimum 4"head lap. (for
base sheet only)
Membrane: Polystick IR-Xe,Polystick Dual Pro,Polystick Tile Pro,Polystick TU Max,Polystick
TU P,Polystick TU Plus,Polystick MTS or Polystick MTS Plus,slf-adhered.
Surfacing:
See General Limitations Below.
Deck Type 1: Wood,non-insulated
Deck Description: Min. 19/32"plywood or wood plank
System Type E(2): Anchor sheet mechanically fastened to deck,membrane adhered
Anchor/Base Sheet: One or more plies of ASTM D 226 Type H or ASTM D 2626.
Fastening: Per FBC 1518.2& 1518.4 Nails and tin caps 12" grid, 6"o.c. at a minimum 4"head lap. (for
base sheet only)
Membrane: Elastoflex S6 G,hot asphalt applied
Surfacing: See General Limitations Below.
4 Deck Type 1: Wood,non-insulated
Deck Description: Min. 19/32"plywood or wood plank
System Type E(3): Base sheet mechanically fastened to deck, subsequent cap membrane self- adhered.
Anchor/Base Sheet: One or more plies of ASTM D 226 Type 11 or ASTM D 2626. `
Fastening: Per FBC 1518.2 & 1518.4 Nails and tin caps 12" grid, 6" o.c. at a minimum 4"head lap. (for
base sheet only) 'I
Ply Sheet: Polystick MTS Plus,self-adhered with minimum 3"horizontal laps and minimum 6"vertical
laps.
Membrane: Polystick TU Plus,self-adhered.
Surfacing: See General Limitations Below.
Reviewed
for
Code CompHanee
05/11/17
NOA NO.: 15-0410.04
MUM
e Expiration Date: 09/13/21
Approval Date: 08/11/16
Page 4 of 8
INSTALLATION REQUIREMENTS:
1. All nails in the deck shall be carefully checked for protruding heads. Re-fasten any loose deck panels, and
sweep the deck thoroughly to remove any dust and debris prior to application. f'
2. Place the underlayment over metal drip edge in accordance with RAS 111.
3. Place the first course of membrane parallel to the eave,rolling the membrane to obtain maximum contact.
Remove the release film as the membrane is applied. All side laps shall be a minimum of a-'/2" and end laps
shall be a minimum of 6". Roll the membrane into place after removing the release strip. Vertical strapping of
the roof with Polystick is acceptable. Membrane shall be back nailed in accordance with applicable building
code.
4. When applying the membrane in the valley,start at the low point and work to the high point,rolling the
membrane from the center outward in both directions.
5. For ridge applications,center the membrane and roll from the center outward in both directions.
6. Roll or broom the entire membrane surface so as to have full contact with the surface,giving special attention
to lap areas. 1
7. Flash vent pipes, stacks, chimneys and penetrations in compliance with Roof Assembly c I ent Product Control
Notice of Acceptance.
S. All protrusions or drains shall be initially taped with a 6"piece of underlayment. The flashing tape shall be
pressed in place and formed around the protrusion to ensure a tight fit. A second layer of Polystick shall be
applied over the underlayment.
GENERAL.LIMITATIONS:
1. Fire classification is not part of this acceptance.
2. Polystick Dual Pro,Polystick Tile Pro,Polystick TU Plus,Polystick MTS and Polystick MTS Plus may be
used in asphaltic shingles,wood shakes and shingles,non-structural metal roofing,roof tile system: t ad quarry
slate roof assemblies.
Polystick TU P may be used in all the previous assemblies listed except metal roofing.
Polystick IR-Xe may be used in all the previous assemblies listed except metal roofing and roof tile systems.
Polystick TU Max may be used in non-structural metal roofing and roof tile systems.-
Elastoflex S6 G may be used in roof tile systems only.
3. Deck requirements shall be in compliance with applicable building code.
4. Polystick IR-Xe,Polystick Dual Pro,Polystick Tile Pro,Polystick TU Max,Polystick TU P,Polystick TU
Plus,Polystick MTS and Polystick MTS Plus shall be applied to a smooth, clean and dry surface. The deck
shall be free of irregularities.
5. Polystick IR-Xe,Polystick Dual Pro,Polystick Tile Pro,Polystick TU Max,Polystick TU P,Polystick TU
Plus,Polystick MTS and Polystick MTS Plus shall not be adhered directly over a prle-existing roof membrane
as a recover system.
6. Polystick IR-Xe,Polystick Dual Pro,Polystick Tile Pro,Polystick TU Max,Polys�Inck lV P,Polystick TU
Plus,Polystick MTS and Polystick MTS Plus shall not be left exposed as a temporary roof for longer than the
amount of days listed in the table below after application. Polyglass reserves the right to revise or alter product
expos u i /^ too e eed the pre eeding maximum time limitations.
Exposure Limitations(Days)
TS IR-Xe I lastoflex TU TU P Tile Pro Dual Pri U Max MTS Plus
nflln S6 G Plus
Winer nen, LV 0 180 180 180 180 180 1 1 180 180
Ilaz lton h/ 90 N/A 180 N/A N/A N/A 180 N/A
I
NOA No.: 15-0410.04
cg37L�j i
Expiration Date: 09/13/21
Approval Date: 08/11/16
Page 5 of 8
i
7. All products listed herein shall have a quality assurance audit in accordance with the Flori�a Building Code and
Rule 61G20-3 of the Florida Administrative Code.
8. In roof the application, data for the attachment resistance of roof tiles shall be as set forth L the roof file
manufacturer's Notice of Acceptance.
Polystick Tile Pro,Polystick TU Max,Polystick.TU Plus or Elastoflex S6 G may be Jed in both adhesive
set and mechanically fastened roof tile applications.
li Polystick Dual Pro is limited to-mechanically fastened roof tile applications.
Polystick MTS and Polystick MTS Plus are limited to mechanically faened with the limitations outlined in
st
Section 9. I
Polystick TU P may be used in mechanically fastened roof tile applications with the exception of mortar set tile
applications.
9. When loading roof tiles on roof tile underlayment for(direct-to-deck)tile assemblies,the i aximum roof slope
shall be as follows: (See Table Below) c
Tile Profile Polystick MTS Elastoflex Polystick TU Plus,TU P, Polystick Polystick
S6 G Tile Pro,Dual Pro TU iMaxl M1 Plus
Flat Tile Prohibited 4:12 6:12 6112 I 5:12
without battens l
Profiled Tile Prohibited 4:12 6:12 6:'i12 { 4:12
without battens
The above slope limitations can be exceeded only by using battens in accordance with'the Ipproved Tile System
Notice of Acceptance and applicable Florida Building Code requirements. When battens arse required,they shall
be utilized during loading and installation of tiles.
10. Care should be taken during the loading procedure to keep foot traffic to a minimum and to avoid dropping of
file directly on the underlayment.Refer to Polyglass' Tile loading detail below for loading procedure—two tiles
laid perpendicular to slope followed by a maximum four tile stack parallel to the slope,for a total of 6 tiles—for
all underlayments except Polystick MTS which shall be loaded onto battens. I
Roofing Tiles
(6 Max Per Stack)
7t;l
m 12
6 �
N s
i
". Ro`Of�OC �ffEd YJlfh
�- POLYST7CKTU Plus'
Reviewed
f®r
Code Compliance
05/11/17
NOA No.: 15-0410.04
r � ee' e Expiration Date: 09/13/21
Approval Date: 08/11/16
Page 6 of 8
i
11. Refer to roofing system Product Control Notice of Acceptance for listed approval,of this p-, luct with
prepared
specific prepared roofing products. Polystick IR-Xe,Polystick Dual Pro,Polystick Tile Iro,Polystick TU
Max,Polystick TU P,Polystick TU Plus,Polystick MTS,Polystick MTS Plus or Elastoflex Sf,;^may be
used with any approved roof covering Notice of Acceptance listing Polystick IR-Xe,Polystick Dual Pro,
Polystick Tile Pro,Polystick TU Max,Polystick TU P,Polystick TU Plus,Polystick MTS,Polystick MTS
Plus or Elastoflex S6 G as a component part of an assembly in the Notice of Acceptance.
If Polystick IR-Xe,Polystick Dual Pro,Polystick Tile Pro,Polystick TU Max,Polystick TU P,Polystick
TU Plus,Polystick MTS,Polystick MTS Plus or Elastoflex S6 G are not listed,a request may be made to the
Authority Having Jurisdiction(AHJ)or the Miami-Dade County Product Control Section for approval provided
that appropriate documentation is provided to detail compatibility of the products,wind uplift resistance,and fire
testing results.
POLYGLASS GENERAL APPLICATION GUIDELINES FOR POLYSTICK 1YrEMBRANES
PLEASE CHECK WITH LOCAL BUILDING CODES REGARDING LIMITATIONS OF SPECIFIC APPLICATIONS.
LOCAL CODES MAY SUPERSEDE POLYGLASS REQUIREMENTS AND RECOMMENDATIONS.
i
1. Polyglass does accept the direct application of Polystick underlayment membranes to wood�decks. Installers are
cautioned to refer to applicable local building codes prior to direct deck installation to ensure this is acceptable.
Please also refer to applicable Product Data Sheets of the corresponding products.
2. All rolls,with the exception of Polystick TU Plus should be back-nailed in selvage edge seam as per Polyglass
Back Nailing Guide. Nails shall be, 11 gauge ring shank type,applied with a minimum 1 5/sl"metal c.•,k as
required in Miami-Dade County or simplex type nail as otherwise allowable in other regions,at a 7. v
um rate
of 12" o.c. Polystick TU Plus should be back nailed in designated area marked"nail area,area paar"on
the face of membrane,with the above stated nails and/or disks.The head lap membrane is t coverea being
back-nailed. (Please refer to applicable local building codes prior to installation.)
3. All seal lap seams(selvage laps)must be rolled with a hand roller to ensure full contact.
4. All fabric over fabric; and granule over granule end laps, shall have a 6"wide,uniform layer of Polyglass
Polyplus 55 Premium Modified Flashing Cement,Polyglass Polyplus 50 Premium MB Flashing Cement,
XtraFlex 50 Premium Modified Wet/Dry Cement,Polyglass PG500 MB Flashing Cement,applied in between
the application of the lap.The use of mastic between the laps does not apply to Polystick M S.
5. A maximum of 6 tiles per stack are allowed when loading tile on the underlayments.Refer to the Polyglass Tile
Loading Guidelines. See General Limitations#9 and#10.
ttens as required b the tile manufacturers NOA must be used ed on all projects for
6. Battens and/or Counter-battens, q y p J
pitch/slopes of TV12" or greater. It is suggested that on pitch/slopes in excess of 6 1/4"%12",precautions should be
taken,such as the use of battens to prevent tile sliding during the loading process.
7. Minimum cure time after membrane installation&before loading of roofing tiles is Forty-Eight(48)Hours.
8. Polystick membranes may not be used in any exposed application such as crickets,exposed valleys,or exposed
roof to wall details.
9. Repair �Xfrranes is to e accomplished by applying Polyglass Polyplus 55 Premium Modified
Flashin l'� ss Polyplus 0 Premium MB Flashing Cement,XtraFlex 50 Premiiun Mon:_'.ed
Wet/Dry Cemef-Qrolyglass PG500 MB Flashing Cement to the area in need of repairlfollored by a patch of the
P t' r ul be set and hand rolled in lace over the area needingsuch rep, = .Patchinin g shd 1 �° V1�06 i ches in either direction. The repair should be insta in such a way so g
that water wolsm p Atl7l to or over he top of all laps of the patch. I
NOA No.: 15-0410.04
Expiration Date: 09/13/21
Approval Date: 08/11/16
Page 7 of 8 .
' I
. I
10. All self-adhered membranes must be rolled to ensure full contact with approved substratesi Polyglass requires a
minimum of 401bs for a weighted roller for the rolling of the field membrane. an rlollers are acceptable for
rolling of patches or small areas of the roof. Brooming may be used where slope prohibits�of
olling.
11. All approved substrates should be dry, clean and properly prepared,before any application Polystick
membranes commences. An approved substrate technical bulletin can be furnished upon request.It is
recommended to refer to applicable building codes prior to installation to verify accepitabl I substrates.
12. The Polyglass Miami-Dade Notice of Acceptance(NOA) approval for Polystick membranes can be furnished
upon request by our Technical Services Department by calling 1 (800) 894-4563.
13. Questions in regards to the application of Polyglass products should be directed to our,Technical Services
Department at 1 (800) 894-4563. i
i
14. Polyglass recommends that applicators follow good roofing practices and applicable procedures as c, .iined by
the National Roofing Contractors Association(NRCA).
PLEASE CHECK WITH LOCAL BUILDING CODES REGARDING LIMITATIONS OF SPECIFI IC APPLICATIONS.
LOCAL CODES MAY SUPERSEDE POLYGLASS REQUIREMENTS AND RECOMMENDATIONS.
END OF THIS ACCEPTANCE