HomeMy WebLinkAboutAPPROVED, 2110-0408 wind pressures(1). (M)k)) a) 10._0 qns James Philip Drago, Registered Architect 333 NE 24"' St, Boca Raton, Florida 33431......... Seal # AR009780 (561) 361-7161 office (954) 275-8834 cell (561) 361-8096 fax "WINDOW / DOOR REPLACEMENT LETTER" Date: September 9, 202-1 Project: Kos Door/Window Replacement Address: 9650 S Ocean Drive, #404, Jensen Beach, FL 34957 Dear: St Lucie County Building OfFiicial(s), I (James Drago, Registered Architect) have conducted a review of the proposed design pressures (PSF) for the above Commercial Property location to replace the doors and windows shown on the attached Floor Plan. Above 30' component height are as follows: (See attached Floor Plan for specific door and window size and design pressures) • ZONE 4 — 53.7 / -67.5 • ZONE 5 — m3.7 / -123.6 • Zone 5 is defined as 6.4' of building wall from building corners. • Zone 4 is defined as all other wall space. Design pressures calculated with • II occupancy category • 16o mph ultimate design wind speed • D asce exposure category • 1 wind directionally factor (Kd) • I topographical factor (Kzt) • 4 _ min. (least) building dimension • Igo' mean roof height, mrh + _36' _elevation of installation • Flat k i-o deg) roof slope Therefore, please accept this letter as a formal certification that to the best of my belief and professional judgment that the proposed design pressures (PSF) to replace the doors and windows installation will meet (or exceed) the minimum requirements setford by-the-202o Florida Building Code — Building, 7th Edition. Thank you in advan�e lt-)r )lour ARCHITECT S : in this matter. James Philip Drago, Regode ' d Architect AR #009780