HomeMy WebLinkAboutENERGY CALCS & MANUAL J - 39 GRANDE CAMINO WAY FORM R405-2020 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: WYNNE THE ROYALE IMPACT Builder Name: WYNNE Street: WYNNE DEV. Permit Office: ST.LUCIE COUNTY City,State,Zip: FT.PIERCE,FL, Permit Number. Owner. Jurisdiction: Design Location: FL,Fort Pierce County: St.Lucie(Florida Climate Zone 2) 1. New construction or existing New(From Plans) 10. Wall Type01688.7 sgft.) Insulation Area 2. Single family or multiple family Detached a.Concrete Block-Int Insul, Exterior R=4.1 1448.70 ft2 b.Frame-Wood,Adjacent R=11.0 24D,00 ft 3. Number of units,if multiple family 1 c.NIA R= ft2 4. Number of Bedrooms 3 d.NIA R= ft2 5. Is this a worst case? Yes 11.Ceiling Types (1750.0 sqft.) Insulation Area a.Under Attic(Vented) R=30.0 1720.00 ft2 6. Conditioned floor area above grade(ft2) 1720 b.Knee Wall(Vented) R=19.0 30.00 ft2 Conditioned floor area below grade(ft2) 0 c.NIA R= ft2 7. Windows(155.4 sgft.) Description Area 12.Ducts R ft2 a. U-Factor: SgI,U=1.04 115.42 ft2 a.Sup:Attic,Ret:Attic,AH:Attic 6 155 SHGC: SHGC=0.29 b. U-Factor S91,U=1.11 40.00 ft2 13.Cooling systems kStulhr Efficiency SHGC: SHGC=0.27 a.Central Unit 34.8 SEER:15.00 c. U-Factor: NIA ft2 SHGC: 14,Heating systems kBtu/hr Efficiency Area Weighted Average Overhang Depth: 3.316 ft. a.Electric Heat Pump 34.8 HSPF:8.50 Area Weighted Average SHGC: 0.285 8. Skylights Area C. U-Factor.(AVG) NIA fL2 15.Hot water systems SHGC(AVG): NIA a.Electric Cap:50 gallons 9. Floor Types (1720.0 sgft.) Insulation Area EF:0.970 a.Slab-On-Grade Edge Insulation R=0.0 1720.D0 ft2 b. Conservation features b.NIA R= ft2 None c.NIA R= ft2 16.Credits None Glass/Floor Area: 0.090 Total Proposed Modified Loads: 52.81 PASS Total Baseline Loads: 52.96 I hereby certify that the plans and specifications covered by Review of the plans and O 'tIT this calculation are in compliance with the Florida Energy specifications covered by this 9� Code. calculation indicates compliance with the Florida Energy Code. PREPARED BY:QA Before construction is completed w 5 DATE: -�3-�Q this building will be inspected for compliance with Section 553.908 , I hereby certify that this building,as designed,.is'n compliance Florida Statutes. with the Florida Energy C0 �'Oj�WMF OWNER/AT: c BUILDING OFFICIAL: DATE. t �� DATE: - Compliance requires certification by the air handier unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.3.2.1. -Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 7.00 ACH50(R402.4.1.2)- 1/13/2021 3:16 PM EnergyGaugeO USA 7.0.00-FlaRes2020 FBC 7th Edition(2020) Compliant Software Page 1 of 5 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT PROJECT Title: WYNNE THE ROYALE IMPA Bedrooms: 3 Address Type: Street Address Building Type: User Conditioned Area: 1720 Lot# Owner Name: Total Stories: 1 Block/Subdivision: #of Units: 1 Worst Case: Yes PlatBook: Builder Name: WYNNE Rotate Angle: 90 Street: WYNNE DEV. Permit Office: ST.LUCIE COUNTY Cross Ventilation: No County: St.Lucie Jurisdiction: Whole House Fan: No City,State,Zip: FT.PIERCE, Family Type: Detached FL, New/Existing: New(From Plans) Comment: CLIMATE / Design Temp Int Design Temp Heating Design Daily Temp V Design Location TMY Site 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,Fort Pierce FL_VERO_BEACH_MUNI 39 90 70 75 299 62 Low BLOCKS Number Name Area Volume 1 Entire House 1720 13760 SPACES Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated 1 BEDROOM 343 2744 No 0 1 1 Yes Yes Yes 2 WIC 63 504 No 0 1 No Yes Yes 3 M.BATH 56 448 No 0 1 Yes Yes Yes 4 KITCHEN 172 1376 Yes 0 1 No Yes Yes 5 BATH 45 360 No 0 1 Yes Yes Yes 6 BEDROOM 2 204 1632 No 0 1 1 Yes Yes Yes 7 ENTRY 98 784 No 0 1 Yes Yes Yes 8 LAUNDRY 42 336 No 0 1 Yes Yes Yes 9 GREAT/DINING 528 4224 No 0 1 Yes Yes Yes 10 BEDROOM 3 169 1352 No 1 1 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab-On-Grade Edge Insulatio BEDROOM 52 ft 0 343 W 0 1 0 2 Slab-On-Grade Edge Insulatio WIC 1 ft 0 63 ft2 __ 0 1 0 3 Slab-On-Grade Edge Insulatio M.BATH 8 ft 0 56 ft' ____ 0 1 0 4 Slab-On-Grade Edge Insulatio KITCHEN 1 ft 0 172 ft' 0 1 0 5 SlabOn-Grade Edge Insulatio BATH 5 ft 0 45 ft' ___ 0 1 0 6 Slab-On-Grade Edge Insulatio BEDROOM 2 42.6 ft 0 204 ft' ___ 0 1 0 7 Slab-On-Grade Edge Insulatio ENTRY 6.3 ft 0 98 ft_— 0 1 0 1/13/2021 3:16 PM EnergyGaugeO USA 7.0.00-FlaRes2020 FBC 7th Edition(2020) Compliant Software Page 2 of 5 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 8 Slab-On-Grade Edge Insulatio LAUNDRY Eft 0 42 ft' -- 0 1 0 9 Slab-On-Grade Edge Insulatio GREAT/DINING 48 ft 0 528 ft' ---- 0 1 0 10Slab-On-Grade Edge Insulatio BEDROOM 3 13 ft 0 169 ft- __- 0 1 0 ROOF J Roof Gable Roof Red Solar SA Emitt Emitt Deck Pitch # Type Matenais Area Area Color Bart Absor. Tested Tested Insul. (deg) 1 Gable or Shed Metal 1813 ft' 286 W Light N 0.6 No 0.7 No 0 18.4 / ATTIC V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 Full attic Vented 150 1720 ft' N N CEILING # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 Under Attic(Vented) BEDROOM 30 Blown 343 ft' 0.1 Wood _ 2 Under Attic(Vented) WIC 30 Blown 63 IF 0.1 Wood 3 Under Attic(Vented) M.BATH 30 Blown 56 ft' 0.1 Wood 4 Under Attic(Vented) KITCHEN 30 Blown 172 ft2 0.1 Wood _ 5 Under Attic(Vented) BATH 30 Blown 45 ft2 0.1 Wood _ 6 Under Attic(Vented) BEDROOM 2 30 Blown 204 ft' 0.1 Wood 7 Under Attic(Vented) ENTRY 30 Blown 98 ft' 0.1 Wood _ 8 Under Attic(Vented) LAUNDRY 30 Blown 42 ft= 0.1 Wood 9 Under Attic(Vented) GREAT/DINING 30 Blown 528 ft' 0.1 Wood _ 10 Under Attic(Vented) BEDROOM 30 Blown 169 ft' 0.1 Wood 11 Knee Wall(Vented) GREAT/DINING 19 Blown 30 ft" 0.11 Wood WALLS Adjacent Space Cavity Width Height Sheathing Framing Solar Below 0 _ 1 N=>E Exterior Concrete Block-Int InsuBEDR00M 4.1 9 0 8 0 72.0 ft' 0 0 0.4 0 _2 S=>W Exterior Concrete Block-Int InsuBEDROOM 4.1 29 0 8 0 232.0 ft2 0 0 0.4 0 3 W=>N Exterior Concrete Block-Int InstEEDROOM 4.1 14 0 8 0 112.0 ft' 0 0 0.4 0 4 S=>W Exterior Concrete Block-Int Insul M.BATH 4.1 8 0 8 0 64.0 ft- 0 0 0.4 0 _5 N=>E Exterior Concrete Block-Int Insul BATH 4.1 5 0 8 0 40.0 ft' 0 0 0.4 0 _ 6 N=>E Exterior Concrete Block-Int InsBEDROOM 2 4.1 14 0 8 0 112.0 ft- 0 0 0.4 0 _ 7 NE=>SE Exterior Concrete Block-Int InsBEDROOM 2 4.1 2 10 8 0 22.7 ft� 0 0 0.4 0 8 E=>S Exterior Concrete Block-Int InsBEDROOM 2 4.1 9 0 8 0 72.0 ft' 0 0 0.4 0 _ 9 SE=>SW Exterior Concrete Block-Int InsBEDROOM 2 4.1 2 10 8 0 22.7 ft- 0 0 0.4 0 _10 S=>W Exterior Concrete Block-Int InsSEDR00M 2 4.1 14 0 8 0 112.0 ft' 0 0 0.4 0 11 NE=>SE Exterior Concrete Block-Int Insul ENTRY 4.1 1 5 8 0 11.3 ft' 0 0 0.4 0 1/13/2021 3:16 PM EnergyGauge®USA 7.0.00-FlaRes202O FBC 7th Edition(2020) Compliant Software Page 3 of 5 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT WALLS Adjacent Cavity Width Height Sheathing Framing Solar Below Space , 12 E=>S Exterior Concrete Block-Int Insul ENTRY 4.1 5 0 8 0 40.0 ft' 0 0 0.4 0 13 S=>W Exterior Concrete Block-Int InsuLAUNDRY 4.1 6 0 8 0 48.0 ft' 0 0 0.4 0 14 N=>E Exterior Concrete Block-Int InstOREAT/DINI 4.1 28 0 8 0 224.0 ft' 0 0 0.4 0 15 W=>N Exterior Concrete Block-Int Inst3REAT/DINI 4.1 20 0 8 0 160.0 ft2 0 0.4 0 16 N=>E Exterior Concrete Block-Int InsBEDROOM 3 4.1 13 0 8 0 104.0 ft' 0 0 0.4 0 17 N=>E Garage Frame-Wood BEDROOM 3 11 30 8 240.0 ft2 0.23 0.4 0 DOORS # Omt Door Type Space Storms U-Value Width Height Area Ft In Ft In 1 E=>S Insulated ENTRY None .32 3 6 8 20 ft' WINDOWS Orientation shown is the entered orientation => changed to Worst Case. / Wall Overhang V # Omt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening 1 W=>N 3 Metal Low-E Single Yes 1.04 0.29 N 32.4 W 1 It 0 in 1 It 5 in Drapes/blinds Exterior 5 2 S=>W 4 Metal Low-E Single Yes 1.04 0.29 N 6.9 ft2 It 0 in 1 It 5 in None None 3 E=>S 8 Metal Low-E Single Yes 1.04 0.29 N 23.2 IF 1 ft 0 in 1 ft 5 in None None 4 N=>E 14 Metal Low-E Single Yes 1.04 0.29 N 36.8 ft2 1 It 0 in 1 ft 5 in None None 5 W=>N 15 Metal Low-E Single Yes 1.11 0.27 N 40.0 ft' 10 ft 0 in 1 8 5 in None None 6 NEE 16 Metal Low-E Single Yes 1.04 0.29 N 16.2 IF 1 It 0 in 1 ft 5 in None None GARAGE # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 300 IF 300 ft2 30 ft 8 ft 11 INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000356 1605.3 88.07 165.35 .1263 7 HEATING SYSTEM # System Type Subtype Speed Efficiency Capacity Block Ducts 1 Electric Heat Pump/ Split Singl HSPF:8.5 34.8 kBtu/hr 1 sys#1 COOLING SYSTEM # System Type Subtype Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit/ Split Singl SEER:15 34.8 kBtulhr cfm 0.85 1 sy1 #1 1113(2021 3:16 PM EnergyGauge®USA 7.0.00-FlaRes2020 FBC 7th Edition(2020) Compliant Software Page 4 of 5 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Electric None Garage 0.97 50 gal 60.9 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft- DUCTS —Supply— —Return— Air CFM 25 CFM25 HVAC# V # Location R-Value Area Location Area Leakage Type Handler TOT OUT ON RLF Heat Cool 1 Attic 6 155 ft2 Attic 55 ft2 Default Leakage Attic (Default) (Default) 1 1 TEMPERATURES Programablffe7Cl�Thermostat:N Ian Feb Marff 11 Ceiling Fans:Cooling �0 D0 D0 Ve ting [ ]Jan Feb X Mar [X]Apr € M y Jun [ ]Jul [ ]Aug [ ]Sep Oct X Nov Dec I Ma t Jun [ I Jul 11 Aug I I Sep l�l Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 Heating(WEH) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 MASS Mass Type Area Thickness Furniture Fraction Space Default(8 lbs/sq.ft. 0 ft2 Oft 0.3 BEDROOM Default(8 lbs/sq.ft. ft2 ft 0.3 WIC Default(8 lbs/sq.ft. ft2 ft 0.3 M.BATH Default(8 lbs/sq.ft. ft2 ft 0.3 KITCHEN Default(81bs/sq.ft. ft2 ft 0.3 BATH Default(8 lbs/sq.ft. ft2 ft 0.3 BEDROOM 2 Default(8 lbs/sq.ft ft2 ft 0.3 ENTRY Default(8 lbs/sq.ft. ft2 ft 0.3 LAUNDRY Default(8 lbs/sq.ft. ft2 ft 0.3 GREAT/DINING Default(8 lbs/s .ft. W ft 0.3 BEDROOM 3 1/13/2021 3:16 PM EnergyGauge®USA 7.0.00-FlaRes202O FBC 7th Edition(2020) Compliant Software Page 5 of 5 2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 a AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: WYNNE THE ROYALE IMPACT Builder Name: WYNNE Street: WYNNE DEV. Permit Office: ST.LUCIE COUNTY City,State,Zip: FT.PIERCE,FL, Permit Number: U Owner. Jurisdiction: _ Design Location: FL, Fort Pierce U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air-permeable insulation shall The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. requirements Breaks or joints in the air barrier shall be sealed. The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit Ceiling/attic the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings,drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows,skylights The space between window/doorjambs and framing,and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above-garage subfloor decking,or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing,or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation,insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace wall . Shafts,penetrations Duct shafts,utility penetrations,and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit,or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spa s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls,or insulation that on installation readily conforms to available space shall Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air-sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub-floor,wall covering or Concealed When required to be sealed,concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids a. In addition,inspection of log walls shall be in accordance with the provisions of ICC-400. 1/13/2021 3:17 PM EnergyGauge®USA 7.0.00-FlaRes2020 FBC 7th Edition(2020) Compliant Software Page 1 of 1 FORM R405-2020 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 100 The lower the EnergyPerformance Index,the more efficient the home. WYNNE DEV., FT. PIERCE, FL, 1. New construction or existing New(From Plans) 10. Wall Type and Insulation Insulation Area 2. Single family or multiple family Detached a.Concrete Block-Int Insul, Exterior R=4.1 1448.70 ft2 b. Frame-Wood,Adjacent R=11.0 240.00 ft2 3. Number of units,if multiple family 1 c.N/A R= ft2 4. Number of Bedrooms 3 d.N/A R= fF 11.Ceiling Type and insulation level Insulation Area 5. Is this a worst case. Yes a.Under Attic(Vented) R=30.0 1720.00 ft2 6. Conditioned floor area(ft2) 1720 b.Knee Wall(Vented) R=19.0 30.00 ft2 7. Windows" Description Area c.NIA R= ft2 a. U-Factor: Sgl,U=1.04 115.42 ft2 12. Ducts,location&insulation level R ft2 a.Sup:Attic,Ret:Attic,AH:Attic 6 155 SHGC: SHGC=0.29 b. U-Factor: Sgl,U=1.11 40.00 ft2 SHGC: SHGC=0.27 13.Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a.Central Unit 34.8 SEER:15.00 SHGC: d U-FactSHGC: N/A ft2 14.Heating systems kBtu/hr Efficiency Area Weighted Average Overhang Depth: 3.316 ft. a.Electric Heat Pump 34.8 HSPF:8.50 Area Weighted Average SHGC: 0.285 8. Skylights Description Area 15.Hot water systems a. U-Factor(AVG): N/A ft2 a. Electric Cap:50 gallons SHGC(AVG): N/A EF:0.97 b. Conservation features 9. Floor Types Insulation Area None a.Slab-On-Grade Edge Insulation R=0.0 1720.00 ft2 Credits(Performance method) None b.N/A R= ft2 c.N/A R= ft2 1 certify that this home has complied with the Florida Energy Efficiency Code for Building SHEST Construction through the above energy saving features which will be installed (or exceeded) ,yyO� Ro in this home before final inspection. Otherwise, a new EPL Display Card will be completed based on installed Code com liant fea - � ,,,,,,.: -� -�..••� f� Builder Signature: Date: Address of New Home: c t(�i1 \Sl MM�c�n1 City/FL Zip: �Q A `Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage(EEM)incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. "Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 1/13/2021 3:16 PM EnergyGauge®USA 7.0.00-FlaRes2020 FBC 7th Edition(2020) Compliant Software Page 1 of 1 wrightsoft® Project Summary Job: Entire House Da QUICK CALCS, INC. 317 ST LUCIE UN,FT.PIERCE,FL 34946 PFure:772-466-6799 Fax 772466-6796 Email:QUICKCALCS@AOL,COM Project • • For. WYNNE DEVOLPMENT THE ROYALE,FT PIERCE,FL Notes: Design Information Fort Pierce,FL,US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 61 grAb Heating Summary Sensible Cooling Equipment Load Sizing Structure 19529 Btuh Structure 16243 Btuh Duds 5998 Btuh Duds 9055 Btuh Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh (gone) 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 25527 Btuh Use manufacturers data n Rate/swingg multiplier 0.95 Infiltration Equipment sensible load 24033 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2135 Btuh Ducts 2467 Btuh Central vent(0 cfm) 0 Btuh Heatin Cooling (none) Area(fF) 1609 1608 Equipment latent load 4603 Btuh Volume(T) 15336 15336 Air changes/hour 0.38 0.20 Equipment Total Load(Sen+Lat) 28635 Btuh Equiv.ANF(dm) 97 51 Req.total capacity at 0.70 SHR 2.9 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carder Trade CARRIERAIR CONDITIONING Trade CARRIERAIRCONDITIONING Model 25HBC536XO30 Cond 25HBC536A'030 AHRI ref 7914585 Coil FX4DN(B,F)037 AHRI ref 7914585 Efficiency 8.5 HSPF Efficiency 12.0 EER,15 SEER Heating input Sensible cooling 24360 Btuh Heating output 34600 Btuh@47-F Latentcooling 10440 Btuh Temperature rise 27 OF Total cooling 34800 Btuh Actual air flow 1160 cflrl Actual air flow 1160 cfm Airflowfador 0.045 dm/Btuh Airflowfador 0.046 chvBtuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.85 Capacity balance point=34 OF Backup: Input=7kW, Output=23009 Btuh,100 AFUE Calculations approved byACCAto meet all requirements of Manual J 8th Ed. C wriwktt-" — 2021-Jan1308:1422 �- RigfSdte6Unwsa120l9l9.02l RSU08101 Pagel ..0 r6\Wright ftHVAQWYNNEDEV-THEROALE.n Calc=W8 `Mr Doorfacas:N J wrightsoft° Right-J®Worksheet Jca Entire House Date: QUICK CALCS, INC. By. 317ST.LUCIELN.,Fr.PIERCE,FL34946Phore:772-466-6799 Fao T72-0G6-6796 Email:QU1CKCALCS@AOL.COM 1 Room name Endle House BEDROOM 2 ENxosdvall 1762 ft 32A It 3 Room height 9.4 f d 9.4 it healmol 4 Room dimensons 14D x 1&0 It 5 Room area 16315 1F 2520 fF Ty Corsturbon U-value Or HTM Am (fly Load Area (fe) Load number (BWhIH`-°F) (BWh4F) or penmeber (to (Bluh) or perimeter (t) (BWh) Heat Cool Gros NrPS Heat Cool Gross WP/S Heat Cool 6 4}! 13A4o s 0.143 ne 4.00 2.55 517 458 1835 1166 0 0 0 0 II---DC lXel n 1270 ne 3556 70.43 38 0 1344 2662 0 0 0 0 11130 0.390 ne 10.92 1131 21 21 229 238 0 0 0 0 l9/ 13A-0ccs 0.143 m 4A0 255 150 130 522 332 0 0 0 0 11 __G 1ASIom 1270 se 3556 70.95 20 0 711 1419 0 0 0 0 w 13A4ors 0.143 a 4m 2.55 40 40 160 102 0 0 0 0 w 13AAo s 0.143 sw 4.00 2S5 395 395 1581 1005 169 169 677 431 1344ocs 0.143 w 4.00 2.55 320 258 1034 657 132 108 432 275 1Xal m 1270 my 3556 70.43 38 0 1344 2662 0 0 0 0 tAcicm 1270 m 35M 4524 12 0 415 528 12 0 415 528 Ti 1Atl m 1270 rnv 35M 4524 12 0 427 543 12 0 427 543 P 12C-09a Q091 - 2.55 128 235 235 599 302 0 0 0 0 C 16A-30md 0.03E - 0.90 2.32 1632 1632 1462 3785 252 252 226 585 F 22A-V1 0.9m - 27.69 0.00 1632 176 4878 0 252 32 886 0 6 c)AEDe=mon 0 154 Envelope loslgain 1 116W 15400 3063 2515 12 a) Infllhation 2989 843 632 178 b) Roomverdlation 0 0 0 0 13 Internal gaim Ooupants@ 230 0 0 0 0 Appliancesother 0 0 SubWlal(lines6t)13) 19529 16243 3696 2693 Leme#emalload 0 0 0 0 Lestanster 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 19529 16243 3696 2693 15 Ductloads 31% 56% 5998 9055 31% 5VA 1135 1501 Total nmrn load 25527 25298 4831 4194 Air required(dm) 1160 1160 220 192 J Calculations approved bvACCAto meet all reauirements of Manual J 8th Ed. r-rid- ... R e®Udes1201919A21 RS 2021-J 1308:14?2 . urblWdgtmftNAQWYNNEDEV-THEROMLE.nP Calc=M18 FrontDoorfaces:N Page wrightwW Right-J@ Worksheet Job: Entire House °fir QUICK CALCS, INC. By. 317ST.LUpELN.,FLPIERCE,FL34946Prnre:772-466-6799Fa T72-4W.6796 Emil:QUK7(GLLCS@AOL.COM 1 Rcon reme WIC M457ER BATH 2 Exposedvall 0 It 9A ft 3 Room height 9.4 fl heaNmol 9A ft he dcuol 4 Room dimensions 7.0 x 9A ft 7.0 x 9.0 ft 5 Roon area 630 IF 63-0 IF Ty Corshudon 1.1-1131ue Or HTM Area (fly Load Area (q Load number (Bh1h4 T) or perimeter (1) (BWh) or perimeter (ft) (Btuh) Heat Cod Gross NIPS Heat Cool Gros NIPS Hear Cool 6 YI! 13A-0as 0.143 ire 4.00 2.55 0 0 0 0 0 0 0 0 I�--DC 1Ac1on 1270 re 35.56 70.43 0 0 0 0 0 0 0 0 11D0 0390 re 10.92 1131 0 0 0 0 0 0 0 0 W 13A4os 0.143 se 4.W 2.55 0 0 0 0 0 0 0 0 11 I--G 1Al lour 12M se 3&% 7025 0 0 0 0 0 0 0 0 W 1344ors C143 s 4.00 255 0 0 0 0 0 0 -0 0 W 13A-4ocs 0.143 sN 440 255 0 0 0 0 85 85 339 215 1344os 0.143 my 4p0 255 0 0 0 0 0 0 0 -0 tAclon 12M m 3556 70.43 0 0 0 0 0 0 0 - 0 1A41on 1270 = 3556 4524 0 0 0 0 0 0 0- 0 1Ac1am 1270 w 3556 4524 0 0 0 0 0 0 0 0 P 12C-Ow 0.091 - 255 128 0 0 0 0 0 0 0 0 C 16A30md 0.032 - 090 232 63 63 56 146 63 63 56 146 F 22A-U O-qm - 27.B9 0.00 63 0 0 0 63 9 249 0 6 c)AEDecmasion -15 43 Fsvelopeloss/gain 56 131 644 319 12 a) Irdlbabon 0 0 178 50 b) Room%entila4on 0 0 0 0 13 trltemal gains Omlpans@ 230 0 0 0 0 Appliancesbther 0 0 Subbbl(lirces6to13) 56 131 m 369 Lesexternalload 0 0 0 0 Les limmier 0 0 0 0 Redishibulion 0 0 0 0 14 Sublotal 56 131 822 369 15 Dud loads 31% 56% 17 73 31% 56% 253 206 Total room bad 74 204 1075 575 Airrequired(Qm) 3 9 1 49 26 Calculations approved bvACCAto meet all requirements of Manual J 8th Ed. -+ wr lssaoTt<- 2021JarM308:aagge 13gkSUte6l Urirarsa1201979.02t RSW8101 ..amerlslWngttsoftFNAL1WYNNEDEV-TFIEROWLEnp Calc=Ml8 FrortDoorlaomN wrightsoft- Right-J®Worksheet Job: Entire House Date: QUICK CALCS, INC. BY 317 ST.LUCIE LN.,Fr..PIERCE,FL 34946 Plore:T 2466-6799 Fax T/2466-6796 Errail:QUICKCALCS AOL.COM 1 Room name Ah BATH KITCHEN 2 Eposedwall 8.0 It 8.0 It 3 Room height 9.4 it heatl000l 9.4 ft heatl000l 4 Room dimensons 7.0 x 8.0 It 1.0 x 192.0 ft 5 Room area 56A IF 192.0 R2 Ty Construclion U-value Or HTM Area (fF) Load Area (fly Load number (Bhjh/fL°F) (BWhdt or penmeter O ft (BWh) or perimeter (ft) (BWh) Heat Cool Gros NIPS Heat Cool Gros NIPS Heat Cool 6 13A to s 0.143 ne 4.00 2.55 0 0 0 0 0 0 0 0 1Actam 1270 ne 35.56 70.43 0 0 0 0 0 0 0 0 �—D 11DO 0.390 ne 1092 11.31 0 0 0 0 0 0 0 0 13A-0o¢ 0.143 se 4A0 2.55 0 0 0 0 0 0 0 0 11 1Ac1om 1270 se 35.56 70.95 0 0 0 0 0 0 0 0 w 13A4ors 0.143 s 4.00 2.55 0 0 0 0 0 0 0 0 w 13A-4ors 0.143 sv 4.00 2.55 75 75 301 191 0 0 0 0 Ti13A4= 0.143 nw 4.00 2.55 0 0 0 0 0 0 0 0 tAclom 1270 nw 3556 70.43 0 0 0 0 0 0 0 0 1Ac1om 1270 nw 35.56 4524 0 0 0 0 0 0 0 0 1A-ciom 1270 nw 3556 4524 0 0 0 0 0 0 0 0 P 12C-Osv 0.091 - 2.55 128 0 0 0 0 75 75 192 96 C 16A30md 0.03: 0.90 2.32 56 56 5( 130 192 192 172 445 F 22A-NI 0989 - 27.69 0.00 5f 8 222 0 192 8 222 0 6 c)AED e=rim -38 S6 Envelope los9gain 573 283 585 486 12 a) Infiltrafion 158 45 0 0 b) Roomventllaton 0 0 0 0 13 Internal gaire: Oaupanls@ 230 0 0 0 0 Applimoslother 0 0 Subtotal(lines6b13) 731 328 5W 486 Les extamal load 0 0 0 0 Lesfr2rsfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 731 328 585 486 15 Ductloads 31% 56% 224 183 31% 56% 180 271 Total room load 955 511 765 756 Air required(ctm) 43 23 35 35 Calculations approved byACCAto meet all requirements of Manual J 8th Ed -rk-wVjaft cwm— 2021 Ja I308:1422 Aft RigttSute®Uriversal 201919.021 RSU08101 Page 3 ...0 rtslWnghsoft HVADWYNNEDEV-THEROMLE.np Calc=M18 Froft Doorfares:N wrightsoft° RighW@ Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST.LUCIE LN.,Fr.PIERCE,FL 34946 Ptnre:772-466-6799 Fax T72-466-6796 Emil:QUICKCALCS@AOL.COM 1 Room name BATH BEDROOM2 2 E:Vocedwall 5.0 It 302 It 3 Room height 9.4 ft heaV000l 9.4 It heav000l 4 Room dimensions 9.0 x 5D It 1D x 1905 It 5 Room area 45.0 if 190L fl° Ty Construction U-value Or HTM Area (IF) Load Area (ft0 Load number (BWh/fF-'q (BWhflF) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Grms N/PS Heat Cool Gros NrPS Heat Cool 6 y/ 13A-0as 0.143 ne 4.00 2.55 47 47 188 120 141 141 %5 359 II--D 1Aaiom 1270 ne 3556 70.43 0 0 0 0 0 0 0 0 11D0 0" ne 1092 11.31 0 0 0 0 0 0 0 0 13AA= 0.143 se 4.00 2.55 0 0 0 0 94 74 296 188 11 tAtlom 1270 se 3556 70.95 0 0 0 0 20 0 711 1419 W 13A-4= 0.143 s 4.00 2.55 0 0 0 0 40 40 160 102 W 13A-0as 0.143 sv 4.00 2.55 0 0 0 0 9 9 38 24 13A-0c6 0.143 nw 4.00 2.55 0 0 0 0 0 0 0 0 1Aclom 1270 nw 3556 70.43 0 0 0 0 0 0 0 0 1Aclom 1270 nw 3556 4524 0 0 0 0 0 0 0 0 to-ctom 1270 nw 3556 4524 0 0 0 0 0 0 0 0 P 12C-Ow 0.091 - 2,55 128 0 0 0 0 0 0 0 0 C 16A30md OD32 - 0.90 2.32 45 45 40 104 191 191 171 442 F 22A-Ipl 0.989 - 27.69 OAO 45 5 138 0 191 30 835 0 6 c)AEO exnnson -26 145 Envelope lossrgain 367 198 2775 2679 12 a) Infiltration 99 28 598 169 b) Room eenHlation 0 0 0 0 13 Internal gains: O=pants@ 230 0 0 0 0 Applianceslother 0 0 Subtotal(lines6m 13) 466 226 3373 2847 LesseAemal load 0 0 0 0 Leshansfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 466 226 3373 2547 15 Ductloads 31% 56% 143 126 31% 56% 1036 1587 Total room load 609 352 4409 4434 Air required(Qm) 28 16 200 203 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. wri9htsoft- 2021-Jan-1308:1422 .7CZA RigltSute@Urivers1201919.021 RSU08101 Page ...=en5lWdg%oftHVAQWYNNEDEV-THEROI'A.LE.np Calc=M)8 Frort Doorfaces:N wrightsofr Right®Worksheet Job: Entire House Dole: QUICK CALCS, INC. By. $17 ST.LUCIE LN,Fr.PIERCE,FL 34946 Phone:772466-6799 Pax 7n2466-6796 Email:QUICKC4LCS a@AOL.COM 1 Room name ENTRY LAUNDRY 2 E1gared call 76.0 R 13.03.0 itft 3 Room height 9A ft heaVcool 9.4 R heatloxl 4 Room dimensons 6.0 x 70.0 ft 7.0 x 6.0 ft 5 Room area 60.0 iF 42.0 IF Ty Construction U-value Or HTM Area Load number (BWhAF---F) (BNhR� or perimeter (ft) (Blum) or�perimeter (R) (Btifi) Heat Cool Gras NAPS Heat Cool Gross N/P,S Heal Cool 6 Y,J 13A-4os 0.143 ne 4.00 2.55 0 0 0 0 0 0 0 0 �C 1Aclom 1270 ne 3556 70.43 0 0 0 0 0 0 0 0 �D 11DO Mel) ne 1092 11.31 0 0 0 0 0 0 0 0 13A4os 0.143 se 4.00 2.55 56 56 226 144 0 0 0 0 11 1Ac1am 1270 se 35.56 70.95 0 0 0 0 0 0 0 0 W 13A4os 0.143 s 4.00 2.55 0 0 0 0 0 0 0 0 W 13A4os 0.143 sv 4.00 255 0 0 0 0 56 56 226 144 13A4os 0.143 nw 4.00 2.55 0 0 0 0 0 0 0 0 1Aclom 1270 nw 3556 70.43 0 0 0 0 0 0 0 0 1A-clom 127C nw 3556 4524 0 0 0 0 0 0 0 0 1Aclorn 127C nw 35M 4524 0 0 0 0 0 0 0 0 P 12C-Osv 0.091 - 255 128 94 94 240 121 66 66 168 84 C 16A-30md 0.032 - 0.90 2.32 60 60 54 139 42 42 38 97 F 22A-yl 0989 - 27.69 0.00 60 16 443 0 42 73 360 0 6 c)AEDexcurson 1 45 -37 Envelope loss/gain 962 358 791 298 12 a) Infiltration 119 33 lie 33 b) Roomuentilation 0 0 1 0 0 13 Intemalgains: Ooupants@ 230 0 0 0 0 Applianoestolher 0 0 Subtotal(lines6to 13) 1081 391 910 322 Leses:lemalload 0 0 0 0 Lessbansfer 0 0 0 0 Redutibution 0 0 0 0 14 Subtotal 1081 391 910 322 15 Dud loads 31% 56% 332 218 31% 56% 279 179 Total room load 1413 610 1189 501 Air required(dm) 64 28 54 23 Calculations approved bVACCAto meet all requirements of Manual J 8th Ed. -F wr79ti�o>R` 2021-Jan-1308:1422 i000h RigItSute®UdversW 201919.021 RSU08101 Page 5 ...uneM\Wdg%oft HVAC\WYNNEDEV-T}1EROYALE.np Calc=MJB Front Doorfaces:N wrightsoW Right-M)Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST.LUCIE LN.,FL PIERCE,FL 34946 PFere:772466-6799 Fa 772-466-6796 Email:QUICKC4LCS@AOL.COM 1 Room name SrFrINGROOM GREAT/DWING 2 Bpomdvall 30.0 It 25.0 ft 3 Room height 9.4 ft heaVcool 9.4 It heaVoDol 4 Room dimensore 20.0 x 10.0 ft 1.0 x 468.0 ft 5 Room area 200.0 ft= 468D IF Ty Construction U-value Or HT M Area ( i Load Area (ft� Load number (BWhfiF2F) (BWh4f) or perimeter (ft) (BWh) or perimeter (ft) Eluh) Heat Cool Gross N/P5 Heat Cool Gross N1P)S Heal Cool 6 V 13A4= 0.143 ne 4.00 2.55 94 73 292 186 235 197 790 502 I�---DG 1Ac1om 1270 re 3556 70.43 0 0 0 0 38 0 1344 2662 11D0 0.390 m 10.92 11.31 21 21 229 238 0 0 0 0 11/ 13A-4= 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 11 L—G 1Aclom 1270 se 35.56 70.95 0 0 0 0 0 0 0 0 W 13A-4om 0.143 s 4.00 2,55 0 0 0 0 0 0 0 0 W 13A4o 0.143 sw 4.00 2.55 0 0 0 0 0 0 0 0 13A4= 0.143 nw 4.00 255 188 150 601 382 0 0 0 0 tActom 1270 m. 3556 70.43 38 0 1344 2662 0 0 0 0 1Actom 1270 nw 35.56 4524 0 0 0 0 0 0 0 0 1Aciom 1270 my 35.56 4524 0 0 0 0 0 0 0 0 P 12C-Om 0.091 - 2.55 128 0 0 0 0 0 0 0 0 C 16A-Mmd 0A32 - 090 2.32 200 200 179 464 468 468 419 1086 F 22A-tpl 0989 - 27.69 0.00 200 30 831 0 468 25 692 0 6 c)AED e=rson 402 440 Envelope lossrgain 3477 4334 3245 3810 12 a) Infiltration 593 167 494 139 b) Roomverdlauon 0 0 0 0 13 Intemalgaim: O—pants@ 230 0 0 0 0 Appliancestother 0 0 Subbbl(lines6b13) 4070 4501 3739 3950 Lessextemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subbbl 4070 4501 3739 3950 15 Dudtoads 31% 56% 12501 2509 31% 56% 1148 2202 Total room load 5320 7010 4888 6151 Airrequimd(dm) 242 321 222 282 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. r°I wr/gt�tsoft- 2021Ja,1308:1422 Rigk-Sate®Uriv rsa1201919.021 RSU08101 Page ...0 ert�\Wrig%oft HVAMWYNNEDEV-THEROYALE.np CaIc=W8 Fmrt Door Paoas:N -�- wrightsoft® Duct System Summary job., 1 Entire House By. QUICK CALCS, INC. 317 ST.LUCIE LN.,Fr..PIERCE,FL 34946 PF m:772-466-6799 Fax 77246"796 Email:QUICKCALCS@40LCOM Project For. WYNNE DEVOLPMENT THE ROYALE,FT.PIERCE,FL Heating Cooling External static pressure 0 in H2O 0 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0 in H2O 0 in H2O Supply/return available pressure 0.000/0.000 in H2O 0.000/0.000 in H2O Lowest fiction rate 0 in/100ft 0 in1100ft Adual airflow 1160 cfm 1160 cfm Total effective length(TEL) 0 ft SupplyDetail Design Htg Clg Design Diam H x W Dud Actual Ftg.Egv Name (Etuh) (cfm) (cfm) FR (in) (in) Matt Ln(ft) Ln(ft) Trunk BATH h 352 28 16 0 0 Ox0 ShMt 0 0 BEDROOM h 2097 110 96 0 0 Ox0 ShMt 0 0 SEDROOM2 c 2217 100 102 0 0 Ox0 ShMt 0 0 BEDROOM2-A c 2217 100 102 0 0 OXO ShMt 0 0 SEOROOMI-A h 2097 110 96 0 0 Ox0 ShMt 0 0 ENTRY h 610 64 28 0 0 Ox0 ShMt 0 0 GREATIIOINING C 3076 111 141 0 0 Ox0 Shmt 0 0 GREAT/DINING-A c 3076 111 141 0 0 Ox0 ShMt 0 0 KITCHEN c 756 35 35 0 0 Ox 0 ShMt 0 0 LAUNDRY h 501 54 23 0 0 0x0 ShMt 0 0 M BATH h 511 43 23 0 0 Ox0 ShMt 0 0 MASTER BATH h 575 49 26 0 0 0x0 ShMt 0 0 SITING ROOM c 3505 121 161 0 0 Ox 0 ShMt 0 0 SITTING ROOMLA c 3505 121 161 0 0 OxO ShMt 0 0 WIC c 204 3 9 0 0 Ox 0 ShMt 0 0 Return Branch Detail Grille HtgT�Crm)jj�� lgStud/Joist DuctName Size(in) (cfm) (fpm) (in) (in) Opening(in) Mail Trunk rb1 I Ox0 1 1160 1160 0 1 0 D 0 Ox 0 1 ShMt wrightsoft— 2021Jarv1308:1423 .W..-i w.,�... Riga-Sute®UnwWI 201919.021 RSU08101 Pagel ACCA ...unertAWngH ftHVAQWYNNE DEV-THE ROYALE.ap Calc=MU8 Fron Door farces:N