HomeMy WebLinkAboutNOA Aluminum Horizontal Sliding Windows. NOA No. 20-0813.06 Expiration Date: April 11, 2022 Approval Date: October 08, 2020 10/01/20 Page 1 MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590 F (786) 315-2599 NOTICE OF ACCEPTANCE (NOA) www.miamidade.gov/building Lawson Industries, Inc. 8501 NW 90 Street Medley, FL 33166 SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed and accepted by Miami-Dade County RER - Product Control Section to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ). This NOA shall not be valid after the expiration date stated below. The Miami-Dade County Product Control Section (In Miami-Dade County) and/ or the AHJ (in areas other than Miami-Dade County) reserve the right to have this product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance if it is determined by Miami-Dade County Product Control Section that this product or material fails to meet the requirements of the applicable building code. This product is approved as described herein, and has been designed to comply with the Florida Building Code, including the High Velocity Hurricane Zone. DESCRIPTION: Series “HS-8700 (Flange Frame)” Aluminum Horizontal Sliding Window – L.M.I. APPROVAL DOCUMENT: Drawing No. L8700-0901, titled “HS-8700 Horizontal Rolling Flange Impact Window”, sheets 1 through 10 of 10, dated 05/30/09, with revision F, dated 07/31/20, prepared by manufacturer, and signed and sealed by Thomas J. Sotos, P.E., bearing the Miami–Dade County Product Control Revision stamp with the Notice of Acceptance number and expiration date by the Miami–Dade County Product Control Section. MISSILE IMPACT RATING: Large and Small Missile Impact Resistant LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state, series, and following statement: "Miami-Dade County Product Control Approved", unless otherwise noted herein. RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building code negatively affecting the performance of this product. TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials, use, and/ or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This NOA revises NOA No. 19-0708.09 and consists of this page 1 and evidence pages E-1, E-2, E-3, E-4 and E-5, as well as approval document mentioned above. The submitted documentation was reviewed by Manuel Perez, P.E. Manuel Perez, P.E. Product Control Examiner NOA No. 20-0813.06 Expiration Date: April 11, 2022 Approval Date: October 08, 2020 E - 1 Lawson Industries, Inc. NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED 1. EVIDENCE SUBMITTED UNDER PREVIOUS NOA’s A. DRAWINGS 1. Manufacturer's die drawings and sections. (Submitted under NOA No. 02-0227.05) 2. Drawing No. L8700-0901, titled “HS-8700 Horizontal Rolling Flange Impact Window”, sheets 1 through 10 of 10, dated 05/30/09, with revision E dated 06/21/19, prepared by manufacturer, signed and sealed by Thomas J. Sotos, P.E. (Submitted under NOA No. 19-0708.09) B. TESTS 1. Test reports on: 1) Air Infiltration Test, per FBC, TAS 202-94 2) Uniform Static Air Pressure Test, Loading per FBC TAS 202-94 3) Water Resistance Test, per FBC TAS 202-94 4) Large Missile Impact Test per FBC, TAS 201-94 5) Cyclic Wind Pressure Loading per FBC, TAS 203-94 6) Forced Entry Test, per FBC 2411 3.2.1, TAS 202-94 along with marked-up drawings and installation diagram of a series HS-8700 flange frame aluminum horizontal sliding window, XO and XOX configurations, prepared by Fenestration Testing Laboratory, Inc., Test Report No. FTL-10715, dated 05/08/19, signed and sealed by Idalmis Ortega, P.E. (Submitted under NOA No. 19-0708.09) 2. Test reports on: 1) Air Infiltration Test, per FBC, TAS 202-94 2) Uniform Static Air Pressure Test, Loading per FBC, TAS 202-94 3) Water Resistance Test, per FBC, TAS 202-94 4) Forced Entry Test, per FBC 2411.3.2.1, and TAS 202-94 along with marked-up drawings and installation diagram of an aluminum horizontal sliding window, XOX (1/4-1/2-1/4 and 1/3-1/3-1/3) configuration, prepared by Hurricane Engineering & Testing, Inc., Test Reports No. HETI-10-3049 and HETI-10-3051, dated 03/23/11, signed and sealed by Candido F. Font, P.E. (Submitted under NOA No. 11-0705.10) 3. Test reports on: 1) Uniform Static Air Pressure Test, Loading per FBC TAS 202-94 along with marked-up drawings and installation diagram of 8 specimens of an aluminum horizontal sliding window, XOX (1/4-1/2-1/4 and 1/3-1/3-1/3) configuration, prepared by Hurricane Engineering & Testing, Inc., Test Reports No. HETI-10-3047, HETI-10-3053, HETI-10-3057, HETI-10-3130, HETI-10-3223 and HET-10-3225, all dated 03/23/11, and signed and sealed by Candido F. Font, P.E. (Submitted under NOA No. 11-0705.10) Manuel Perez, P.E. Product Control Examiner NOA No. 20-0813.06 Expiration Date: April 11, 2022 Approval Date: October 08, 2020 E - 2 Lawson Industries, Inc. NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED 1. EVIDENCE SUBMITTED UNDER PREVIOUS NOA’s (CONTINUED) B. TESTS (CONTINUED) 4. Test reports on: 1) Large Missile Impact Test per FBC, TAS 201-94 2) Cyclic Wind Pressure Loading per FBC, TAS 203-94 along with marked-up drawings and installation diagram of an aluminum horizontal sliding window, XOX (1/4-1/2-1/4 and 1/3-1/3-1/3) configuration, prepared by Hurricane Engineering & Testing, Inc., Test Reports No. HETI-10-3048, HETI-10-3049I, dated 11/09/10, HETI-10-3050, HETI-10-3052B, HETI-10-3056, HETI-10-3131, HETI-10-3224 and HETI-10-3226, all dated 03/23/11, and signed and sealed by Candido F. Font, P.E. (Submitted under NOA No. 11-0705.10) 5. Test reports on: 1) Large Missile Impact Test per FBC, TAS 201-94 2) Cyclic Wind Pressure Loading per FBC, TAS 203-94 along with marked-up drawings and installation diagram of an aluminum horizontal sliding window, XOX configuration, prepared by Hurricane Engineering & Testing, Inc., Test Report No. HETI-10-3251, dated 04/25/11, signed and sealed by Rafael E. Droz-Seda, P.E. (Submitted under NOA No. 11-0705.10) 6. Test reports on: 1) Air Infiltration Test, per FBC, TAS 202-94 2) Uniform Static Air Pressure Test, Loading per FBC TAS 202-94 3) Water Resistance Test, per FBC TAS 202-94 4) Large Missile Impact Test per FBC, TAS 201-94 5) Cyclic Wind Pressure Loading per FBC, TAS 203-94 6) Forced Entry Test, per FBC 2411 3.2.1, TAS 202-94 along with marked-up drawings and installation diagram of 8 specimens of an aluminum horizontal sliding window, XO configuration, prepared by Hurricane Engineering & Testing, Inc., Test Reports No. HETI-08-2033, HETI-08-2034, HETI-08-2035, HETI-08-2036, HETI-08-2037, HETI-08-2038, HETI-08-2116A and HETI-08-2116B, all dated 02/28/08, and signed and sealed by Candido F. Font, P.E. (Submitted under NOA No. 09-0706.05) Manuel Perez, P.E. Product Control Examiner NOA No. 20-0813.06 Expiration Date: April 11, 2022 Approval Date: October 08, 2020 E - 3 Lawson Industries, Inc. NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED 1. EVIDENCE SUBMITTED UNDER PREVIOUS NOA’s (CONTINUED) B. TESTS (CONTINUED) 7. Test reports on: 1) Air Infiltration Test, per FBC, TAS 202-94 2) Uniform Static Air Pressure Test, Loading per FBC TAS 202-94 3) Water Resistance Test, per FBC TAS 202-94 4) Large Missile Impact Test per FBC, TAS 201-94 5) Cyclic Wind Pressure Loading per FBC, TAS 203-94 6) Forced Entry Test, per FBC 2411 3.2.1, TAS 202-94 along with marked-up drawings and installation diagram of 8 specimens of an aluminum horizontal sliding window, XO configuration, prepared by Fenestration Testing Laboratory, Inc., Test Reports No. FTL-3097, FTL-3098 and FTL-3364, dated 12/06/01, 12/11/01 and 01/28/02, respectively, all signed and sealed by Luis Antonio Figueredo, P.E. (Submitted under NOA No. 02-0227.05) C. CALCULATIONS 1. Anchor verification calculations and structural analysis, complying with FBC, prepared by Lawson Industries, Inc., dated 05/28/09, revised on 07/10 and updated on 01/25/12, signed and sealed by Thomas J. Sotos, P.E. (Submitted under NOA No. 12-0127.08) 2. Glazing complies with ASTM E1300-09 D. QUALITY ASSURANCE 1. Miami-Dade Department of Regulatory and Economic Resources (RER). E. MATERIAL CERTIFICATIONS 1. Notice of Acceptance No. 19-0305.02 issued to Kuraray America, Inc. for their “Trosifol® Ultraclear, Clear and Color PVB Glass Interlayers” dated 05/09/19, expiring on 07/08/24. 2. Notice of Acceptance No. 17-0712.05 issued to Eastman Chemical Company (MA) for their “Saflex Clear and Color Glass Interlayers” dated 09/07/17, expiring on 05/21/21. Manuel Perez, P.E. Product Control Examiner NOA No. 20-0813.06 Expiration Date: April 11, 2022 Approval Date: October 08, 2020 E - 4 Lawson Industries, Inc. NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED 1. EVIDENCE SUBMITTED UNDER PREVIOUS NOA’s (CONTINUED) F. STATEMENTS 1. Statement letter of conformance, complying with the FBC 6th Edition (2017), dated June 24, 2019, issued, signed and sealed by Thomas J. Sotos, P.E. (Submitted under NOA No. 19-0708.09) 2. Statement letter of no financial interest, dated June 24, 2019, signed and sealed by Thomas J. Sotos, P.E. (Submitted under NOA No. 19-0708.09) 3. Proposal No. 18-1697 issued by the Product Control Section, dated January 04, 2019, signed by Manuel Perez, P.E. (Submitted under NOA No. 19-0708.09) 4. Laboratory compliance letter for Test Reports No. HETI-10-3047, HETI-10-3048, HETI-10-3049, HETI-10-3049I, HETI-10-3050, HETI-10-3051, HETI-10-3052B, HETI-10-3053, HETI-10-3056, HETI-10-3057, HETI-10-3130, HETI-10-3131, HETI-10-3223, HETI-10-3224, HET-10-3225 and HETI-10-3226, all issued by Hurricane Engineering & Testing, Inc., dated 11/09/10, 03/23/11 and 04/25/11, signed and sealed by Candido F. Font, P.E. (Submitted under NOA No. 11-0705.10) 5. Laboratory compliance letter for Test Report No. HETI-10-3251, issued by Hurricane Engineering & Testing, Inc., dated 04/25/11, signed and sealed by Rafael E. Droz-Seda, P.E. (Submitted under NOA No. 11-0705.10) 6. Laboratory compliance letter for Test Reports No. HETI-08-2033, HETI-08-2034, HETI-08-2035, HETI-08-2036, HETI-08-2037, HETI-08-2038, HETI-08-2116A and HETI-08-2116B, all issued by Hurricane Engineering & Testing, Inc., dated 01/15/08 through 02/28/08, and signed and sealed by Candido F. Font, P.E. (Submitted under NOA No. 09-0706.05) 7. Laboratory compliance letter for Test Reports No. FTL-3097, FTL-3098 and FTL-3364, all issued by Fenestration Testing Laboratory, Inc., dated 12/06/01, 12/11/01 and 01/28/02, and signed and sealed by Luis Antonio Figueredo, P.E. (Submitted under NOA No. 02-0227.05) G. OTHERS 1. Notice of Acceptance No. 17-1212.17, issued to Lawson Industries, Inc. for their Series “HS-8700 (Flange-Frame) Aluminum Horizontal Sliding Window – LM.I.” approved on 02/01/18 and expiring on 04/11/22. Manuel Perez, P.E. Product Control Examiner NOA No. 20-0813.06 Expiration Date: April 11, 2022 Approval Date: October 08, 2020 E - 5 Lawson Industries, Inc. NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED 2. NEW EVIDENCE SUBMITTED A. DRAWINGS 1. Drawing No. L8700-0901, titled “HS-8700 Horizontal Rolling Flange Impact Window”, sheets 1 through 10 of 10, dated 05/30/09, with revision F dated 07/31/20, prepared by manufacturer, signed and sealed by Thomas J. Sotos, P.E. B. TESTS 1. None C. CALCULATIONS 1. None. D. QUALITY ASSURANCE 1. Miami-Dade Department of Regulatory and Economic Resources (RER) E. MATERIAL CERTIFICATIONS 1. Notice of Acceptance No. 19-0305.02 issued to Kuraray America, Inc. for their “Trosifol® Ultraclear, Clear and Color PVB Glass Interlayers” dated 05/09/19, expiring on 07/08/24. 2. Notice of Acceptance No. 20-0622.01 issued to Eastman Chemical Company (MA) for their “Saflex PVB Clear and Color Glass Interlayers” dated 08/06/20, expiring on 05/21/21. F. STATEMENTS 1. Statement letter of conformance, complying with FBC 7th Edition (2020), dated August 03, 2020, issued by the manufacturer, signed and sealed by Thomas J. Sotos, P.E. G. OTHERS 1. Notice of Acceptance No. 19-0708.09, issued to Lawson Industries, Inc. for their Series “HS-8700 (Flange Frame)” Aluminum Horizontal Sliding Window – L.M.I., approved on 08/01/19 and expiring on 04/11/22. PRODUCT REVISED as complying with the Florida Building Code NOA–No. 20-0813.06 Expiration Date: 04/11/2022 By:________________________ Miami–Dade Product Control PRODUCT REVISED as complying with the Florida Building Code NOA–No. 20-0813.06 Expiration Date: 04/11/2022 By:________________________ Miami–Dade Product Control PRODUCT REVISED as complying with the Florida Building Code NOA–No. 20-0813.06 Expiration Date: 04/11/2022 By:________________________ Miami–Dade Product Control PRODUCT REVISED as complying with the Florida Building Code NOA–No. 20-0813.06 Expiration Date: 04/11/2022 By:________________________ Miami–Dade Product Control PRODUCT REVISED as complying with the Florida Building Code NOA–No. 20-0813.06 Expiration Date: 04/11/2022 By:________________________ Miami–Dade Product Control PRODUCT REVISED as complying with the Florida Building Code NOA–No. 20-0813.06 Expiration Date: 04/11/2022 By:________________________ Miami–Dade Product Control PRODUCT REVISED as complying with the Florida Building Code NOA–No. 20-0813.06 Expiration Date: 04/11/2022 By:________________________ Miami–Dade Product Control PRODUCT REVISED as complying with the Florida Building Code NOA–No. 20-0813.06 Expiration Date: 04/11/2022 By:________________________ Miami–Dade Product Control PRODUCT REVISED as complying with the Florida Building Code NOA–No. 20-0813.06 Expiration Date: 04/11/2022 By:________________________ Miami–Dade Product Control PRODUCT REVISED as complying with the Florida Building Code NOA–No. 20-0813.06 Expiration Date: 04/11/2022 By:________________________ Miami–Dade Product Control