HomeMy WebLinkAboutAPPROVED Holloway Residence_page_9 Sealed(1)REVSHEET NAMESHEET SIZESHEET NUMBERHOLLOWAY RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEE-02CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC5290 OAKLAND LAKE CIRCLE,
FORT PIERCE, FL 34951WIRING CALCULATIONSAC CONDUCTOR AMPACITY CALCULATIONS:FROM ROOF TOP SOLADECK TO COMBINER BOXAC CONDUCTOR AMPACITY CALCULATIONS:FROM AC COMBINER BOX TO MSPELECTRICAL NOTES1.ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FORITS APPLICATION.2.ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 DEGREE CWET ENVIRONMENT. THE TERMINALS ARE RATED FOR 75 DEGREE C.3.THE WIRES ARE SIZED ACCORDING TO NEC 110.14.4.WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BEROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO THENEAREST RIDGE, HIP, OR VALLEY.5.WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICALEQUIPMENT SHALL COMPLY WITH NEC 110.26.6.DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS.CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS,FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES ANDSTANDARDS.7.WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOTSPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY.8.ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED ANDREADILY VISIBLE.9.MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAMEAND MODULE SUPPORT RAIL, PER THE GROUNDING CLIPMANUFACTURER'S INSTRUCTION.10.MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER G.E.C.VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG.11.THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE .12.UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALLPHOTOVOLTAIC SYSTEM COMPONENTS LOCATED AT THE SERVICEENTRANCE.13.MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.14.RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.15.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHTRESISTANT PER NEC ARTICLE 300.6 (C) (1) AND ARTICLE 310.10 (D).16.CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USEIN WET LOCATIONS PER NEC ARTICLE 310.10 (C).17.THIS SYSTEM IS EQUIPPED WITH RAPID SHUTDOWN OF PVCONDUCTORS IN COMPLIANCE WITH NEC 690.12.18.LABELING IN COMPLIANCE WITH NEC 690.12 AND 690.56(C) IS SHOWN ONSHEET E-03.19.ALL CONDUITS TO BE INSTALLED A MIN OF 7/8" ABOVE THE ROOFSURFACE.ENPHASE IQ7PLUS-72-2-US MICROINVERTERInput Data (DC)Output Data (AC)Recommended Input Power (STC)Maximum Input DC VoltagePeak Power Tracking VoltageOperating RangeMin. / Max. Start VoltageMax DC Short Circuit CurrentMaximum Output PowerNominal Output CurrentNominal Voltage / RangeNominal Frequency / RangeExtended Frequency / RangePower Factor at rated powerMaximum unit per 20A Branch Circuit235-400W +60V27V-45V16V-60V22V / 60V15A290W1.21A240V/211-264V60 Hz47-68 Hz1.013 (240 VAC)I ERMOCRATES CASTILLO PE# 52590 AN ENGINEERLICENSED PURSUANT TO CHAPTER 471, CERTIFYTHAT THE PV ELECTRICAL SYSTEM ANDELECTRICAL COMPONENTS ARE DESIGNED ANDAPPROVED USING THE STANDARDS CONTAINED INTHE MOST RECENT VERSION OF THE FLORIDABUILDING CODE. FBC 107, THE NEC 2017, ANDTHOSE SET FORTH BY THE FLORIDA SOLARENERGY CENTER CERTIFICATION