HomeMy WebLinkAboutAPPROVED ENERGY CALCS & MANUAL J - 6104 SPANISH LAKES BLVD(1)FORM R405-2020 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: WYNNE THE GRAND CARLTON IMPACT Builder Name: WYNNE BUILDING COPR. street: Permit Office: ST. LUCIE COUNTY City, State, Zip: FT. PIERCE, FL, Permit Number: Owner: WYNNE BUILDING CROP Jurisdiction: ST. LUCIE COUNTY Design Location: FL, Fort Pierce County: St. Lucie (Florida Climate Zone 2 ) 1. New construction or existing New (From Plans) 10. Wall Type> 1442.0 sqft.) Insulation Area 2. Single family or multiple family Detached a• Concrete Block - Int Insul, Exterior R=4.1 1250.00 ft2 b. Frame - Wood, Adjacent R=11.0 192.00 ft2 3. Number of units, if multiple family 1 c. NIA R= ft2 4. Number of Bedrooms 2 d. NIA R= ft2 5. Is this a worst case? Yes 11. Ceiling Types (1476.0 sqft.) Insulation Area a. Under Attic (Vented) R=30.0 1446.00 ft2 6. Conditioned floor area above grade (ft2) 1446 b. Knee Wall (Vented) R=19.0 30.00 ft2 Conditioned floor area below grade (ft2) 0 c. NIA R= ftz 7. Windows(141.3 sqft.) Description Area 12. Ducts sup: Attic, Fief: Attic, R ft2 a. U-Factor: SgI, U=1.04 101.25 ft2 AFi: Attie 6 175 SHGC: SHGC=().29 b. U-Factor: Sgl, U=1.11 40.00 ft2 13. Cooling systems kBtulhr Efficiency SHGC: SHGC=0.27 a. Central Unit 34.8 SEER:15.00 c. U-Factor: N/A ft2 SHGC: Area Weighted Average Overhang Depth: 3.832 ft. 14. Heating systems kBtulhr Efficiency Area Weighted Average SHGC: 0284 a. Electric Heat Pump 34.8 HSPF:8.50 8. Skylights Area c. U-Factor:(AVG) NIA ftz 15. Hot water systems SHGC(AVG): NIA a. Electric Cap: 50 gallons 9. Floor Types (1445.5 sqft.) Insulation Area EF: 0.970 a. Slab -On -Grade Edge Insulation R=0.0 1445.50 ft2 b. Conservation features b. NIA R= ft2 None c. NIA R= ft2 16. Credits None Glass/Floor Area: 0.098 Total Proposed Modified Loads: 44.57 PASS Total Baseline Loads: 45.19 I hereby certify that the plans and specifications covered by Review of the plans and otJaE this calculation are in compliance with the Florida Energy specifications covered by this = p Code. calculation indicates compliance � ,_ z r. with the Florida Energy Code.rf PREPAR D Y Before construction is completed m DATE:-1 -02 this building will be inspected for compliance with Section 553.908 „ I hereby certify that this building, as designed, is in compliance Florida Statutes. with the Florida Energy Code.WE -� OWNER BUILDING OFFICIAL: DATE., DATE: --- - Compliance requires certification by the air handler unit manufacturer that the air handier enclosure qualifies as certified factory -sealed in accordance with R403.3.2.1. - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 7.00 ACH50 (R402.4.1.2). 1/12/2021 12:02 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5 FORM R405-2020 INPUT SUMMARY CHFCKI MT RFanOT PROJECT Title: WYNNE THE GRAND CARL Bedrooms: 2 Address Type: Street Address Building Type: User Conditioned Area: 1446 Lot # Owner Name: WYNNE BUILDING CROP Total Stories: 1 Block/Subdivision: # of Units: 1 Worst Case: Yes PlatBook: Builder Name: WYNNE BUILDING COPR. Rotate Angle: 180 Street Permit Office: ST. LUCIE COUNTY Cross Ventilation: No County: St. Lucie Jurisdiction: ST. LUCIE COUNTY Whole House Fan: No City, State, Zip: FT. PIERCE, Family Type: Detached FL New/Existing: New (From Plans) Comment: CLIMATE Design Temp Int Design Temp Heating Design Daily Temp V Design Location TMY Site 97.5 % 2.5 % Winter Summer Degree Days Moisture Range FL, Fort Pierce FL_VERO_BEACH_MUNI 39 90 70 75 299 62 Low BLOCKS Number Name Area Volume 1 Entire House 1446 11568 SPACES Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated 1 BEDROOM 301 2408 No 0 1 1 Yes Yes Yes 2 WIC 63 504 No 0 1 No Yes Yes 3 M. BATH 56 448 No 0 1 Yes Yes Yes 4 KITCHEN 192 1536 Yes 0 1 No Yes Yes 5 BATH 45 360 No 0 1 Yes Yes Yes 6 BEDROOM 2 204 1632 No 0 1 1 Yes Yes Yes 7 ENTRY 55 440 No 0 1 Yes Yes Yes 8 LAUNDRY 42 336 No 0 1 Yes Yes Yes 9 GREAT/DINING 488 3904 No 0 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet _ 1 Slab -On -Grade Edge Insulatio BEDROOM 52 ft 0 301 ft' 0 1 0 2 Slab -On -Grade Edge Insulatio WIC 1 ft 0 63 ft- 0 1 ___ 0 3 Slab -On -Grade Edge Insulatio M. BATH 8 ft 0 56 ft' ____ 0 1 0 4 Slab -On -Grade Edge Insulatio KITCHEN 1 ft 0 192 ft- ____ 0 1 0 5 Slab -On -Grade Edge Insulatio BATH 5 ft 0 45 W ___ 0 1 0 _ 6 Slab -On -Grade Edge Insulatio BEDROOM 2 32.2 ft 0 203.5 ft' ___ 0 1 0 7 Slab -On -Grade Edge Insulatio ENTRY 7 ft 0 55 ft' ___ 0 1 0 1/12/2021 12:02 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 5 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet _ 8 Slab -On -Grade Edge Insulatio LAUNDRY 6 ft 0 42 ft2 0 1 _ 0 9SIab-On-Grade Edge Insulatio GREAT/DINING 46ft 0 488 ft2 0 1 0 ROOF / V Roof Gable Roof Red Solar SA Emitt Emitt Deck Pitch # Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg) 1 Gable or Shed Metal 1524 ft2 240 ft2 Light N 0.6 No 0.9 No 0 18.4 ATTIC V # Type Ventilation Vent Ratio (1 in) Area RBS IRCC 1 Full attic Vented 150 1446 ft' N N CEILING # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 Under Attic (Vented) BEDROOM 30 Blown 301 ft2 0.1 Wood 2 Under Attic (Vented) WIC 30 Blown 63ft2 0.1 Wood 3 Under Attic (Vented) M. BATH 30 Blown 56 ft2 0.1 Wood 4 Under Attic (Vented) KITCHEN 30 Blown 192 ft2 0.1 Wood 5 Under Attic (Vented) BATH 30 Blown 45 ft2 0.1 Wood 6 Under Attic (Vented) BEDROOM 30 Blown 204 ft2 0.1 Wood 7 Under Attic (Vented) ENTRY 30 Blown 55 ft2 0.1 Wood 8 Under Attic (Vented) LAUNDRY 30 Blown 42 ft2 0.1 Wood 9 Under Attic (Vented) GREAT/DINING 30 Blown 488 ft2 0.1 Wood 10 Knee Wall (Vented) GREAT/DINING 19 Blown 30 ft2 0.11 Wood WALLS Adjacent Space Cavity Width Height Sheathing Framing Solar Below _ a 1 NE=>SW Exterior Concrete Block - Int InsuBEDROOM 4.1 10 0 8 0 80.0 ft2 0 0 0.4 0 _ 2 SW=>NE Exterior Concrete Block- Int InsuBEDROOM 4.1 28 0 8 0 224.0 ft2 0 0 0.4 0 3 NW=>SE Exterior Concrete Block - Int InsuBEDROOM 4.1 14 0 8 0 112.0 ft2 0 0 0.4 0 4 SW=>NE Exterior Concrete Block- Int Insul M. BATH 4.1 8 0 8 0 64.0 ft2 0 0 0.4 0 5 NE=>SW Exterior Concrete Block- Int Insul BATH 4.1 5 0 8 0 40.0 ft2 0 0 0.4 0 6 NE=>SW Exterior Concrete Block - Int Ins@EDROOM 2 4.1 16 0 8 0 128.0 ft2 0 0 0.4 0 _ 7 SE=>NW Exterior Concrete Block - Int InsBIEDROOM 2 4.1 10 0 8 0 80.0 ft2 0 0 0.4 0 _ 8 S=>N Exterior Concrete Block - Int InsBEDROOM 2 4.1 4 3 8 0 34.0 ft2 0 0 0.4 0 9 SW=>NE Exterior Concrete Block - Int InsREDROOM 2 4.1 2 0 8 0 16.0 ft. 0 0 0.4 0 10 SE=>NW Exterior Concrete Block - Int Insul ENTRY 4.1 6 0 8 0 48.0 ft2 0 0 0.4 0 11 SW=>NE Exterior Concrete Block - Int Insul ENTRY 4.1 1 0 8 0 8.0 ft2 0 0 0.4 0 12 SW=>NE Exterior Concrete Block- Int InsuLAUNDRY 4.1 6 0 8 0 48.0 ft2 0 0 0.4 0 13 NE=>SW Exterior Concrete Block- Int InstOREAT/DINI 4.1 26 0 8 0 208.0 ft2 0 0 0.4 0 14 NW=>SE Exterior Concrete Block - Int InsIGbREAT/DINI 4.1 20 0 8 0 160.0 ft2 0 0 0.4 0 1/12/2021 12:02 PM EnergyGauge@ USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 5 FORM R405-2020 INPUT SUMMARV CNPCIII IST PPPnPT WALLS Adjacent Cavity Width Height Space - Sheathing Framing Solar Below o _ 15 N=>S Garage Frame - Wood KITCHEN 11 24 8 192.0 ft' 0.23 0.4 0 DOORS # Omt Door Type Space Storms U-Value Ft Width Height In Ft In Area 1 SE=>NW Insulated ENTRY None .39 3 1 6 8 20.6ft- WINDOWS Orientation shown is the entered orientation => changed to Worst Case. / Wall V # Omt ID Frame Overhang Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening _ 1 NW=>SE 3 Metal 2 SW=>NE 4 Metal 3 SE=>NW 7 Metal 4 NE=>SW 13 Metal 5 NW=>SE14 Metal Low-E Single Yes 1.04 0.29 Y 32.9 ft' 1 ft 0 in Low-E Single Yes 1.04 0.29 Y 6.9 ft' 1 ft 0 in Low-E Single Yes 1.04 0.29 Y 24.0 ft' 6 ft 0 in Low-E Single Yes 1.04 0.29 Y 37.5 ft' 1 ft 0 in Low-E Single Yes 1.11 0.27 Y 40.0 ft' 8 ft 0 in 1 ft 5 in Drapes/blinds 1 ft 5 in None 1 ft 5 in None 1 ft 5 in None 1 ft 5 in Drapes/blinds Exterior 5 None None None Exteriors GARAGE # Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation 1 315 ft2 315 ft' 24It 8ft 11 INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000356 1349.6 74.04 139.01 .1263 7 HEATING SYSTEM # System Type Subtype Speed Efficiency Capacity Block Ducts 1 Electric Heat Pump/ Split Singl HSPF:8.5 34.8 kBtu/hr 1 sys#1 COOLING SYSTEM # System Type Subtype Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit/ Split Sing] SEER: 15 34.8 kBtu/hr cfm 0.8 1 sys#1 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation _ 1 Electric None Garage 0.97 50 gal 60.9 gal 120 deg None 1/12/2021 12:02 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT SOLAR HOT WATER SYSTEM FSEC Collector Storage Can # Company Name System Model # Collector Model # Area Volume FEF None None ft' DUCTS / -- Supply --- V --- Return— Air CFM 25 CFM25 HVAC # # Location R-Value Area Location Area Leakage Type Handler TOT OUT ON RLF Heat Cool 1 Attic 6 175 fY Attic 65 ft- Default Leakage Attic (Default) (Default) 1 1 TEMPERATURES Programable Thermostat: N Ceiling Fans: Cooling �r[x],J Jan Feb Heating Jan Feb [�rxJjMar Mar r Apr APr r[` Ma May (� Jun (XI Jul r ,Jun [ ]Jul (� Au r , Au[ (XI Se ] SeP ((( Oct r ,Nov Oct (X( Nov r' Dec [)C) Dec Venting I I Jan Feb l l I�7 Mar lxJ Apr t [ May [ 1 Jun [ 1 Jul [ 1 Aug [ 1 Se Oct [XJ Nov [ I Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling (WD) AM PM 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 Cooling (WEH) AM PM 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 Heating (WD) AM PM 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 Heating (WEH) AM PM 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 MASS Mass Type Area Thickness Furniture Fraction Space Default(8 Ibs/sq.ft. 0 ft' 0 ft 0.3 BEDROOM Default(8 lbs/sq.ft. ft' ft 0.3 WIC Default(8 Ibs/sq.ft. ft' ft 0.3 M. BATH Default(81bs/sq.ft. ft' ft 0.3 KITCHEN Default(8 lbs/sq.ft. ft' ft 0.3 BATH Default(8 lbs/sq.ft. ft' ft 0.3 BEDROOM 2 Default(81bs/sq.ft. ft' ft 0.3 ENTRY Default(8 lbs/sq.ft. ft' ft 0.3 LAUNDRY Default(8 lbs/s.ft. ft' ft 0.3 GREAT/DINING 1/12/2021 12:02 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA a Project Name: WYNNE THE GRAND CARLTON IMPACT Builder Name: WYNNE BUILDING COPR. Street: Permit Office: ST. LUCIE COUNTY City, State, Zip: FT. PIERCE, FL, Permit Number: Y Owner: WYNNE BUILDING CROP Jurisdiction: ST. LUCIE COUNTY w Design Location: FL, Fort Pierce V COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. The insulation in any dropped ceiling/soffit Access openings, drop down stairs or knee wall doors to shall be aligned with the air barrier. unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. Knee walls shall be sealed, with a material having a thermal resistance of R-3 per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including above -garage insulation. maintain permanent contact with the underside of and cantilevered subfloor decking, or floor framing cavity insulation floors) shall be permitted to be in contact with the top side of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace wall . Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spa s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind ninino and winno Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids a. In addition, inspection of log walls shall be m accordance with the provisions of CC-400. 1/12/2021 12:02 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 99 The lower the EnergyPerformance Index, the more efficient the home. 1. New construction or existing 2. Single family or multiple family 3. Number of units, if multiple family 4. Number of Bedrooms 5. Is this a worst case? 6. Conditioned floor area (ft2) 7. Windows** Description a. U-Factor: Sal, U=1.04 SHGC: SHGC=0.29 b. U-Factor: Sgl, U=1.11 SHGC: SHGC=0.27 c. U-Factor: N/A SHGC: d. U-Factor: N/A SHGC: Area Weighted Average Overhang Depth: Area Weighted Average SHGC: 8. Skylights Description a. U-Factor(AVG): N/A SHGC(AVG): N/A , FT. PIERCE, FL, New (From Plans) 10. Wall Type and Insulation Insulation Area Detached a. Concrete Block - Int Insul, Exterior R=4.1 1250.00 ft2 b. Frame - Wood, Adjacent R=11.0 192.00 ft2 1 c. N/A R= ft2 2 d. N/A R= ft2 Yes 11. Ceiling Type and insulation level Insulation Area a. Under Attic (Vented) R=30.0 1446.00 ft2 1446 b. Knee Wall (Vented) R=19.0 30.00 ft2 Area c. N/A R= ft2 101.25 ft2 12. Ducts, location & insulation level R ft2 a. Sup: Attic, Ret: Attic, AH: Attic 6 175 40.00 112 13. Cooling systems kBtu/hr Efficiency ft2 a. Central Unit 34.8 SEER:15.00 ft2 3.832 ft. 0.284 Area ft2 9. Floor Types Insulation Area a. Slab -On -Grade Edge Insulation R=0.0 1445.50 ft2 b. N/A R= ft2 c. N/A R= ft2 14. Heating systems a. Electric Heat Pump 15. Hot water systems a. Electric b. Conservation features None Credits (Performance method) I certify that this home has complied with the Florida Energy Efficiency Code for Building Construction through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL Display Card will be completed t based on installed Code compliant features. --- e `-- _ Builder Signature: '' Date: Address of New Home: �,V-\ �� Cj� Q �5� FL Zip: kStu/hr Efficiency 34.8 HSPF:8.50 Cap: 50 gallons EF: 0.97 None *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 1/12/2021 12:02 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 wrightsW Project Summary Job: Entire House Bye' QUICK CALCS, INC. 317 ST.. LUCIE LN., Fr. PIERCE, FL 34946 Phone: 772466-6799 Fax 772-0660796 Emil: QUICKCALCS@A0L.O0M For: WYNNE DEVELOPMENT CARLTON III, FT. PIERCE, FL Notes: Design Information Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 Inside db 70 OF OF Outside db Inside db 90 OF OF Design TD 28 OF Design TD 75 15 OF Daily range L Relative humidity 50 % Moisture difference 61 grAb Heating Summary Sensible Cooling Equipment Load Sizing Structure 19691 Btuh Structure 16785 Btuh Duds 590 Central vent (0 Dim) 0 Btuh Cenral vent (0 cfm) 8919 0 Btuh Btuh none Humidification 0 Btuh (none) Blower 0 Btuh Piping 0 Btuh Equipment load 25591 Btuh Use manufacturer's data n Infiltration Rate/ "'in g1 multipplier Equipmentsensibleload 0.95 24418 Btuh Method Simplified Construction quality Average Latent CoolingEquipment Load Sizing g Fireplaces 0 Structure 2065 Btuh Duds 2429 Btuh Central vent (0 Dim) 0 Btuh Heatingg Area Coolingg (none) (tf) 1602 Volume (ft') 14827 1602 14827 Equipment latent load 4493 Btuh Airchanges/hour 0.38 Equiv. AVF (chn) 94 0.20 49 Equipment Total Load (Sen+Lat) 28912 Btuh Req. total capacity at 0.70 SHR 2.9 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Trade CARRIERAIR CONDITIONING Model 25HBC536XO30 AHRI ref 7914585 Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat Capacity balance point = 34 OF 8.5 HSPF 34600 Btuh @ 47-F 27 OF 1160 dim 0.045 dm/Btuh 0 in H2O Backup: Input=7kW, Output= 23009 Btuh, 100 AFUE Make Cater Trade CARRIERAIRCONDITIONING Cond 25HBC5369030 Coil FX4DN(B,F)037 AHRI ref 7914585 Efficiency 12.0 EER,15 SEER Sensible cooling 24360 Btuh Latentcooling 10440 Btuh Total cooling 34800 Btuh Actual air flow 1160 Dim Airflowfactor 0.045 crm/Btuh Static pressure 0 in H2O Load sensible heat ratio 0.85 Calculations approved byACCAto meetall requirements of Manual J 8th Ed wr10h*6oft- 2021-Jarv1212A496 ^+ RgftSLiLD Ur mml201919.021 RSU06101 Page 1 ...'ts Wrigl6oft FNAGWYNNE-THE GRAND CARLTON.rtp Calc=MI8 FroRWorface&N wrightsott° RighttiJ® Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Prone: 772-466-6799 Fax 772L66-6796 Email: QUICKCALCS@AOL.COM 1 Rcomname Enfire House BEDROOM 2 EVosedwall 1762 ft 41.0 ft 3 Room height 9.3 It d 8.0 ft heaUmol 4 Room dimensans 14.0 x 18.0 ft 5 Room area 1601b ft' 252.0 ft' Ty Corrsaucton U-value Or HTM Area (� Load Area Load number (Bbh/ftk.°F] (BbhAB) or perimeter (H) (Btuh) or perimeter (ft) Buh) Heat Cool Gross N/P/S Heat Cool Gloss NIPS Heat Cool 6 W I-G 13A-0as 0.143 re 4.00 2.55 557 573 2055 7306 72 72 288 183 1Actom 13ACos 1270 0.143 m � 3556 4.00 70.43 2.55 38 128 87 0 1344 348 2662 221 0 0 0 0 1Ac1om 1270 se 35.56 70.95 20 0 711 1419 0 0 0 0 0 0 0 0 11 11D0 0390 se 10.92 11.31 21 21 229 238 0 0 0 0 w 13A4. 0.143 s 4.00 2.55 34 34 136 86 0 0 0 0 y/ 13A-4os 0.143 sw 4.00 2.55 416 390 1562 993 144 144 577 367 1Aclom 1270 sw 35.56 70.95 6 0 213 426 0 0 0 0 1Aclom 1270 w 35.56 70.95 20 0 711 1419 0 0 0 0 13A4os 0.143 nw 4.00 2.55 352 288 1151 732 112 88 354 225 1Ac1om 1270 nw 35M 4524 12 0 415 528 12 0 415 528 tAclom 1270 nw 35.56 4524 12 0 427 543 12 0 427 543 45-2omd 0.770 nw 2156 36.90 41 0 880 1505 0 0 0 0 P 12C-O w 0.091 - 255 128 12C 120 306 154 0 0 0 0 C 16A30md 0.032 - 0.90 232 1602 1602 1435 3715 252 252 226 585 F 22A-tpl 0.989 - 27.69 0.00 1602 176 4878 0 252 41 1135 0 6 c)AED ex arson 23 197 Envelope losslgain 16802 15970 3421 2627 12 a) Infiltration 2890 815 w 180 b) Roomventlabon 0 0 0 0 13 Intemalgaim Oocupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines6 b 13) 19691 16785 4061 2807 Lewexh:malload 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 19691 16785 4061 2807 15 Duct loads 30% S3% 5900 8979 30°/, 53% 1217 1491 Total room load 25591 52 798 428 Air required (m) 0 194 Calculations approved byACCA to meet all requirements of Manual J 8th Ed ,C -*' wriglMtsolC• 2021Jarv1212:04:36 A RlgttSute®Uri..l 201919.021 RSU08101 Page 1 ..15\Wngheoft WAMWYNNE-THE GRAND CARLTON.ny CaIc=M18 FrortDoorfaces: N wrightsoft° RighW@ Worksheet Joe. Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN, Fr. PIERCE, FL 34W Ptone:772-466.6799 Fax 772466-6796 Emai: OUICKCALCS@AOL.COM 1 Room name WIC MASTER BATH 2 Eyosad wall 0 ft 17.0 It 3 Room height 4 Room dimensions 8.0 It heallmol 8.0 ft heaftol 5 Room area 7.0 x 9.0 ft 63.0 7.0 x 17.0 ft fF 119.0 ft' Ty Construction U--value Or HTM Area Load �perimeter Load number I (BWhflF-°F) (BILK or Wrnetar (ft) (Btuh) or(ft) (BWh) Heat Cool Gros N/P/S Heat Cool Gros NIPS Heat Cool 6 Vjl 13A-0as 0.143 ne 4.00 2.55 0 0 0 0 1A�lom 127o ne 35M 70.43 0 0 0 0 0 0 0 0 0 0 V1 13A4= 0.143 se 4.00 2.55 0 0 0 0 0 0 �G 1Ac1wn 1270 se 35M 7095 0 0 0 0 0 0 0 0 11 I-D 11D0 0.143 s 14.00 11.31 0 0 0 0 0 0 0 0 W 13A4ors 0.143 s 4.00 2.55 0 0 0 0 0 0 Vl 1AAlors sv 4.56 0 0 0 0 736 130 0 0 527 0 331 II--(G' tA-ciom 127C 1270 sv 35.56 0.95 70.95 0 0 0 0 6 0 213 420 1Actom 7270 av 3556 70.95 0 0 0 0 0 0 0 0 13A-0os 0.143 nw 4.00 2.55 0 0 0 0 0 0 1Aclom 1270 nw 3556 4524 0 0 0 0 0 0 0 1A-clom 1270 nw 35.56 4524 0 0 0 0 0 0 4A5-2omd 0.770 nw 21.56 36.90 0 0 0 0 0 0 0 0 P 12C.O w 0.091 255 128 0 0 0 0 0 g C F 16A30md 0A32 - 0.90 2.32 63 63 56 146 119 0 119 0 107 0 276 22A-ml 0.989 - 27.69 0.00 63 0 0 0 119 17 471 0 6 o)AED etturson -13 55 Envelope IosWgain 56 133 1 1311 1087 12 a) Infiltration 0 0 265 75 b) Roomventileton 0 0 1 0 0 13 Intemal gains: O=pants@ 230 0 0 0 0 Applianceslotter 0 0 Subtotal (lines6 m 13) 56 133 1 1577 1162 Lessextamalload 0 0 0 0 Lestransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 56 133 1577 1162 15 Duciloads 30% 53% 17 71 30% 530/6 472 618 Total mom load 73 21 2049 1780 Air required(dm) 3 9 93 80 Calculations approved bvACCAto meet all requirements of Manual J 8th Ed c. 44*- ��'K" 2021-Jan1212:04:36 cw Rlgrt-SUL@Uri eml20l9l9.021 RSU08101 Page ...nbAWdgh WAQW NE-THEGR NDCARLTONxW Calc=MI6 FroRWorface&N wrightsofr Right-J® Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317ST. LUCIE LN.,Fr..PIERCE, FL34946 Pfnre:772-466-6799 Fax772-466-6796 ErraiI:QUICKCALCS@40LCOM 1 Room name Kri CHEN BATH 2 E1posed wall 0 It 5.0 It 3 Room height 8.0 It heaVwol 9.4 It hea%oaol 4 Room dimensions 1.0 x 192.0 ft 9D x 5.0 ft 5 Room area 1920 # 45.0 ff Ty Construcbon U-value Or HTM Area fl Load number (BWh/R;°r7 (B"'ff) or perm (ft) (Bh1h) or perimeter (ft) (Bhnh) Heat Coof Gross NIPS Hea[ Cool Gross N/P/S Heat Cool 6 y/ �C 134� 0.143 m 4.00 2.55 0 0 0 0 47 47 188 120 1Aaiom 1270 ne 35.56 70.43 0 0 0 0 0 0 0 0 13A4o¢ 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 tAclom 1270 se 3556 70.95 0 0 0 0 0 0 0 0 11 11DO 0.390 se 10.92 11.31 0 0 0 0 0 0 0 0 W 13AAocs 0.143 s 4.00 2.55 0 0 0 0 0 0 0 0 13A4as 0.143 six 4.00 2.55 0 0 0 0 0 0 0 0 1Ac1am 1270 w 35.56 70.95 0 0 0 0 0 0 0 0 1Ac1om 1270 sw 3556 70.95 0 0 0 0 0 0 0 0 13A4ocs 0.143 nw 4.00 2.65 0 0 0 0 0 0 0 0 1A-clom 1270 nw 35.56 4524 0 0 0 0 0 0 0 0 1Ac1wn 1270 nw 3556 4524 0 0 0 0 0 0 0 0 4 5-20md 0.770 nw 21.66 36M 0 0 0 0 0 0 0 0 P 12C-Ow 0,091 - 255 128 0 0 0 0 0 0 0 0 C 16A30md 0.032 - 0.90 2.32 192 192 172 445 45 45 40 104 F 22A-tol 0.989 - 27.69 0.00 192 0 0 0 45 5 138 0 6 c)AEDexnlrsion -39 22 Ernelope lossigain 172 406 1 367 202 12 a) Infiltration 0 0 92 26 b) Roca enblafion 0 0 0 0 13 Internal gains: O=pan5@ 230 0 1 0 0 0 Appliwoes/other 0 0 SubtrffiI (lines610 13) 172 406 1 459 228 Lessea4rnalload 0 0 0 0 Lestransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 172 406 428 15 Durfloads 30% 53% 52 216 30% 53% 137 37 121 -r room load 224 622 r,% 349 Airrequired(dm) 10 28 27 16 Calculations approved bvACCAto meet all requirements of Manual J 8th Ed -!Id- ..Aaft esosc' 2021-,Iarv12120436 AA I ARigttSute®Universal201919.021 RSU08101 Page ...nisi\Wngte;oft WAC\WVNNE-THE GRAND CARLMN.rup Calc=W8 Fror¢Doorfaws: N wrightsow Right-M Worksheet Job: Entire House Dare' QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34W PF re: 712466-6799 Fax 772466.6796 Email: DUICKCALCS@.40L.COM 1 Room name BEDROOM2 ENTRY 2 Expocetl wall 302 ft 6.0 ft 3 Room height 8.0 ft heav=l 8.0 ft heaVrool 4 Room dimensions 1.0 x 190.5 ft 6.0 x 10D ft 5 Room area 1905 IF 60.0 IF Ty Construction U-value Or HTM Area (tP) Load Area Load number (BWhr2F) (Btuh" or Penmekr (tp (Bluh) or Penme�s (ft) (Btuh) Heat Cool Gross NIPS Heat Cool Gross NIPS Heat Cool 6 13A4= 0.143 ne 4.00 2.55 120 120 480 305 0 0 0 tAclom 1270 re 35.56 70.43 0 0 0 0 0 0 0 0 0 13A4ocs 0.143 se 4.00 2.55 80 60 240 153 48 27 108 69 1Aclom 1270 ce 3556 70.95 20 0 711 1419 0 0 0 0 11 11D0 0.390 se 10.92 11.31 0 0 0 0 21 21 229 238 W 1344ocs 0.143 s 4.00 2.65 34 34 136 86 0 0 0 0 Y)1 13A4os 0.143 sN 4.00 2.55 8 8 32 20 0 0 0 0 II 1Ac1am 1270 sv 3556 7095 0 0 0 0 0 0 0 0 --CC 1Aclom 1270 sv 35.56 70.95 0 0 0 0 0 0 0 0 13A4ccs 0.143 nw 4.00 2S5 0 0 0 0 0 0 0 0 1Aclwn 1270 nw 3556 4524 0 0 0 0 0 0 1Ac1= 1270 nw 3556 4524 0 0 0 0 0 0 0 0 4A5-2omd 0.770 nw 21.56 35.90 0 0 0 0 0 0 0 0 P 12C-09N 0.091 - 255 128 0 0 0 0 0 0 0 0 C 16A30md 0.032 - 0.90 2.32 191 191 171 442 60 60 54 139 F 22A-01 0.989 - 27.69 0.00 191 30 835 0 60 6 166 0 6 c)AEDexurson 20y 1 1 41 Envelope lossigain 2606 2635 557 404 12 a) Infiltration 472 133 94 26 b) Rwrrventilaton 0 0 0 0 13 Internal gains Occupants@ 230 0 0 0 0 Appliancesrotiler 0 0 Subtotal(lines6b 13) 3078 2768 651 430 Less external load 0 0 0 0 Lestransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 3078 2768 651 430 15 Duct loads 30% 53% 922 1471 30% 53% 195 229 Tonal room load 4000 4239 846 659 Air require1(Um) 181 191 38 30 Calculations approved bvACCAto meet all requirements of Manual J 8th Ed Af•f' w!i9ti>�rt"' Gal201979.021 RS 2021Jan1212A496 A ...rblWrgPmftFNAC1WYNNE-THEANDCARLTONrp CaIc=M6 FnortDoorfacesN Page wrightsoft Right-J@ Worksheet Job: Entire House Daft: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phore: 772-466.6799 Fax 772466-6796 Email: QUICKCALCS AOL.COM 1 Room name LAUNDRY GREATIDINING 2 Elyosed wall 6.0 ft 46D ft 3 Room height 8.0 ft heaV000l 12.0 It heaVmol 4 Room dimensions 7.0 x 6.0 ft 1.0 x 488.0 It 5 Room area 420 IF 488.0 IF Ty Construction U-value Or HTM Area (W) Load Area Load number (Bluhfil °q (Btuhd2) or perimeter (ft) (Btuh) or perimeter (ft) (Bluh) Heat Cool Gross NIPS Heat Cool Gross NIPS Heat Cool 6 L-G 13A-0as 0.143 ne 4.00 2.55 0 0 0 0 312 274 1098 698 tActom 13A-0ws 1270 0.143 m se 3556 4.00 70.43 Z55 0 0 0 0 0 0 38 0 1344 - 2662 1Ac1om 1270 se 3556 70.95 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 D 11130 0390 se 10.92 11.31 0 0 0 0 0 0 0 0 W 13A4ots 0.143 s 4A0 2.55 0 0 0 0 0 0 0 0 y! 13A-4ors 0.143 av 4.00 2.55 48 48 192 122 0 0 0 0 1Aclom 1270 sv 3556 70.95 0 0 0 0 0 0 0 0 1Ac1om 1270 sw 3556 70.95 0 0 0 0 0 0 0 0 13A-0acs 0.143 nw 4.00 255 0 0 0 0 240 199 798 507 1Ac1om 1270 nw 35.56 4524 0 0 0 0 0 1A-dom 1270 nw 3556 4524 0 0 0 0 0 0 0 0 4A52cmd 0.770 rw 2156 36M 0 0 0 0 41 0 880 1505 P 12C-09v 0.091 - 2.55 128 0 0 0 0 0 0 0 0 C 16Aaomd 0.032 - 0.90 2.32 42 42 38 97 488 488 437 1132 F 22A-ml 0.989 27.69 0.00 42 6 166 0 488 46 1274 0 6 c)AED e=rson p -1 1 -597 Envelope lossgain 3% 1 198 5830 5908 12 a) IMltration 94 26 1077 304 b) Roomventilafion 0 0 0 0 13 Int9mal gains: Omlpants@ 23D 0 0 0 0 Applianoasiother 0 0 Subtotal (lirxs6to 13) 490 224 6907 6212 Lesemmalload 0 0 0 0 Lestlansfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 490 224 6907 6212 15 Dud loads 30% 539/. 147 119 30% 539f. 2070 3301 Total room load 636 344 8977 9512 Air requxed(dm) 29 16 407 429 Calculations approved bvACCAto meet all requirements of Manual J 8th Ed -rp- 2021-lan1212U436 A Right -Suter Urrversal 201919.0.21 RSU08101 Page s _.ri,xWrigHsoft HVAQWYNNE-THE GRAND CARLION.np Calc=WB Froflt DoOrfaceSN wrightsoR- Right @ Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., Fr. PIERCE, FL 34946 Phone: 772466-6799 Fax 772-466-6796 Email: QUICKC4LCS A01-COM 1 Room name SEDROOM3 2 Bposedwall 25.0 R 3 Room height 8A R heaV=l 4 Room dimensions 15.0 x 10.0 1t 5 Room area 1500 R Ty Construcilm U-value or HTM Area (fF) Load Area Load number (BWhM'--°F) (BWhflf� or perimeter (ft) (BWh) or perimeter Heat Cool Gross N[PS Heat Cool Gross NIPS Hea[ Cool 6 VII 134-0ar 0.143 ne 4.00 2.55 0 0 0 0 I--G 1Aciom 1270 ne 3556 70.43 0 0 0 0 13A-0¢ o 0.143 se 4.00 255 0 0 0 0 IAc7om 1270 se 3556 70.95 0 0 0 0 11 11D0 0.390 se 10.92 11.31 0 0 0 0 IN 13A-4ocs 0.143 s 4A0 2.55 0 0 0 0 13A-0ow 0.143 sw 4.00 2.55 80 60 240 153 1Ac7om 1270 sx 35.56 70.95 0 0 0 0 1Acton 1270 sv 3556 70.95 20 0 711 1419 13A-4o s 0.143 nw 4.p0 255 0 0 0 0 tAc7om 1270 nw 3556 4524 0. 0 0 0 1Ac1on 1270 nw 3556 4524 0 0 0 0 4A5.2omd 0.770 nw 21.56 36.90 0 0 0 0 P 12C-0sa 0.091 - 2.55 128 120 120 300 154 C 16A30md 0.032 - 0.90 2.32 750 150 134 348 F 22A-ml 0.989 - 27.69 0.00 750 25 692 0 6 c)AED e=rsion 296 Envelopelossigain 2084 2369 12 a) Infiltration 156 44 b) Roomventilation 0 0 13 Internal gains: Om[pants@ 230 0 0 Applianos/other 0 Subtotal(lines6trt13) 2240 2413 Lesse>hamattoad 0 0 Less tansfer 0 0 Redistribution p p 14 Subtotal 2240 2413 15 Durtloads 30% 53% 671 1282 Total room load 2911 3695 Air required (Cm) 132 167 Calculations approved bvACCAto meet all reauirements of Manual J 8th Ed Aft'*- Mts:!R slsoR^ ...tc Url .021 RS 2021-1an-12129436 k n5Wngt�oRHJACWYNNE-THE GRAND CARLTONnp Calc=NUB FrortDaorfaces N Page