October 26, 2021 Job Order No.: 21-5982
Permit No: SLC 2108-0571
Total Home Roofing
9030 Bellhurst Way, Suite 130
West Palm Beach, Florida 33411
RE: TRUSS REPAIR INSPECTIONS
Lorraine Ingram Residence
3309 Avenue S
Fort Pierce, FL 34947
Dear Sir or Madam:
Per your request, Florida Engineering & Testing Inc. (Inspector: Naresh Persaud, EI#1100008977), has
conducted a visual inspection supplemented by client provided photographs on October 25, 2021, to
evaluate truss/rafter repairs at all eaves of the residence that exhibited damage.
Background Information
The client is re-roofing the above referenced building. Based on the client's visual observation from below,
all the wood roof trusses/rafters would require the 16-inch eave overhang around the roof perimeter only to
be repaired. It is our understanding that all areas with damaged wood roof trusses/rafters were repaired in-
place.
Engineered Truss/Rafter Repair Observations
• 2"x4″ of the same size/species/grade lumber was ″sistered-in" (scabbed) to the truss/rafter member.
• The "sistered-in" (scabbed) piece extended a minimum of two (2) feet past the damaged area of
each damaged member at the eaves.
• All "sistered-in" (scabbed) lumber was attached with 2 rows of 8d ring shank nails spaced
approximately 4" o.c. (nails in each row spaced 4" o.c.)
Based on our inspection of the repaired wood roof trusses/rafters and our engineer’s analysis, a ll
repaired wood roof trusses/rafters at the 16-inch eave overhang around the roof perimeter only were
observed to meet the minimum standards of the 2020 Florida Building Code, latest edition, and are
now acceptable.
Florida Engineering & Testing, Inc. appreciates the opportunity to be of service to you at this phase of your
project. If you should have any questions or comments, please feel free to contact us at your earliest
convenience.
Sincerely,
Troy Bishop, P.E.
Florida Engineering & Testing, Inc.
Florida Reg. No. 76131
Certificate of Authorization No. 6923