HomeMy WebLinkAboutENERGY CALCS & MANUAL J - 33 MEDITERRANEAN NORTH FORM R405-2020
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: WYNNE THE WINDSOR IMPACT Builder Name: WYNNE DEVELOPMENT
Street: THE WINDSOR Permit Office: ST.LUCIE COUNTY
City,State,Zip: FT.PIERCE,FL, Permit Number:
Owner: Jurisdiction:
Design Location: FL, Fort Pierce County: St Lucie(Florida Climate Zone 2)
1. New construction or existing New(From Plans) 10. Wall Type;1432.0 sgft.) Insulation Area
2. Single family or multiple family Detached a.Concrete Block-Int Insul,Exterior R=4.1 1224.00 ft2
b. Frame-Wood,Adjacent R=11.0 208.00 ft2
3. Number of units,if multiple family 1 c.NIA R= ft2
4. Number of Bedrooms 3 d.NIA R= ft2
5. is this a worst case? Yes 11.Ceiling Types (1783.0 sgft.) Insulation Area a.Under Attic(Vented) R=30.0 1753.00 ft2
6. Conditioned floor area above grade(ft2) 1753 b.Knee Wall(Vented) R=19.0 30.00 ft2
Conditioned floor area below grade(ft2) 0 a N(A R= ft2
7. Windows(151.4 sgft.) Description Area 12.Ducts R ft2
a.Sup:Attic,Ret:Attic,AFI:Attic 6 195
a. U-Factor: Sgl,U=1.02 111.36 ft2
SHGC: SHGC=0.29
b. U-Factor: S91,U=1.11 40.00 ft2 13.Cooling systems kBtulhr Efficiency
SHGC: SHGC=0.27 a.Central Unit 34.8 SEER:15.00
c. U-Factor. NIA ft2
SHGC: 14,Heating systems kBtu/hr Efficiency
Area Weighted Average Overhang Depth: 2.850 ft.
Area Weighted Average SHGC: 0.235 a.Electric Heat Pump 34.8 HSPF:8.50
8. Skylights Area
c. U-Factor:(AVG) NIA ft2 15,Hot water systems
SHGC(AVG): NIA a.Electric Cap:40 gallons
9. Floor Types (1753.0 sgft.) Insulation Area EF:0.970
a.Slab-On-Grade Edge Insulation R=0.0 1753.00 ft2 b. Conservation features
b. NIA R= ft2 None
c.NIA R= ft2 16.Credits None
Glass/Floor Area: 0.086 f�i
Total Proposed Modified Loads: 49.38 PASS
S S
Total Baseline Loads: 50.69
I hereby certify that the plans and specifications covered by Review of the plans and .q
this calculation are in compliance with the Florida Energy specifications covered by this a 0,�
Code. calculation indicates compliance
with the Florida Energy Code. rfrrr "�h .' Ci
PREPARED BY: Before construction is completed 15:
DATE: 1-12-2021 this building will be inspected for
compliance with Section 553.908
f hereby certify that this building,as designed, is in compliance Florida Statutes. I .
with the Florida Energy Code.. G'p�W,S,
OWNERIAUENT BUILDING OFFICIAL:
DATE: N, I� DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.3.2.1.
-Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 5.00 ACH50(R402.4.1.2).
1/12/2021 1:15 PM EnergyGauge@ USA 7.0.00-FlaRes2020 FBC 7th Edition(2020) Compliant Software Page 1 of 6
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
PROJECT
Title: WYNNE THE WINDSOR IMP Bedrooms: 3 Address Type: Street Address
Building Type: User Conditioned Area: 1753 Lot#
Owner Name: Total Stories: 1 BloWSubdivision:
#of Units: 1 Worst Case: Yes PlatBook:
Builder Name: WYNNE DEVELOPMENT Rotate Angle: 180 Street: THE WINDSOR
Permit Office: ST.LUCIE COUNTY Cross Ventilation: No County: St.Lucie
Jurisdiction: Whole House Fan: No City,State,Zip: FT.PIERCE,
Family Type: Detached FL,
New/Existing: New(From Plans)
Comment:
CLIMATE
Design Temp Int Design Temp Heating Design Daily Temp
Design Location TMY Site 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,Fort Pierce FL_VERO_BEACH_MUNI 39 90 70 75 299 62 Low
BLOCKS
Number Name Area Volume
1 Entire House 1753 14024
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms Infil lD Finished Cooled Heated
1 MASTER BEDROO 224 1792 No 0 1 1 Yes Yes Yes
2 WIC 63 504 No 0 1 No Yes Yes
3 MASTER BATH 56 448 No 0 1 Yes Yes Yes
4 M.BATH 61 488 No 0 1 Yes Yes Yes
5 LAUDRY 36 288 No 0 1 No Yes Yes
6 BEDROOM 2 180 1440 No 0 1 1 Yes Yes Yes
7 DINING/GREAT R 588 4704 No 2 1 Yes Yes Yes
8 KITCHEN 209 1672 Yes 0 1 Yes Yes Yes
9 BATH 50 400 No 0 1 Yes Yes Yes
10 HALL 25 200 No 0 1 No Yes Yes
11 FOYER 92 736 No 0 1 Yes Yes Yes
12 BEDROOM 3 169 1352 No 0 1 1 Yes Yes Yes
FLOORS
# Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
1 Slab-On-Grade Edge Insulatio MASTER BEDRO 37 ft 0 224 W --_ 0 1 0
2 Slab-On-Grade Edge Insulatio WIC 1 ft 0 63 ft' ____ 0 1 0
3 Slab-On-Grade Edge Insulatio MASTER BATH 8 ft 0 56 fN --- 0 1 0
4 Slab-On-Grade Edge Insulatio M.BATH 7 ft 0 61 W --_ 0 1 0
5 Slab-On-Grade Edge Insulatio LAUDRY 1 ft 0 36 fF ___ 0 1 0
1/12/2021 1:15 PM EnergyGauge®USA 7.0.00-FlaRes2020 FBC 7th Edition(2020) Compliant Software Page 2 of 6
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
FLOORS
# Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
6 Slab-On-Grade Edge Insulatio BEDROOM 2 12 ft 0 180 ft. — 0 1 0
7Slab-On-Grade Edge Insulatio DINING/GREAT 50 ft 0 588 ft' -- 0 1 0
8Slab-On-Grade Edge Insulatio KITCHEN lift 0 209 fF _ 0 1 0
9 Slab-On-Grade Edge Insulatio BATH 5 It 0 50 ft' — 0 1 0
10SIab-On-Grade Edge Insulatio HALL 1 it 0 25 ft' -- 0 1 0
11SIab-On-Grade Edge Insulatio FOYER 9 ft 0 92 ft' 0 1 0
12SIab-On-Grade Edge Insulatio BEDROOM 3 14 ft 0 169 ft' -- 0 1 0
ROOF
/ Roof Gable Roof Red Solar SA Emitt Emift Deck Pitch
� # Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg)
1 Hip Metal 1847 ft- 0 ft' Light N 0.6 No 0.9 No 0 18.4
/ ATTIC
V # Type Ventilation Vent Ratio(1 in) Area FIBS IRCC
1 Full attic Vented 150 1753 W N N
CEILING
# Calling Type Space R-Value Ins Type . Area - Framing Free Truss Type
_ 1 Under Attic(Vented) MASTER BEDRO 30 Blown 2241t2 0.1 Wood
2 Under Attic(Vented) WIC 30 Blown 63 ft' 0.1 Wood
3 Under Attic(Vented) MASTER BATH 30 Blown 56 fF 0.1 Wood
4 Under Attic(Vented) M.BATH 30 Blown 61 fF 0.1 Wood
5 Under AWm(Vented) LAUDRY 30 Blown 36 ft' 0.1 Wood
_ 6 Under Attic(Vented) BEDROOM 2 30 Blown 180 ft' 0.1 Wood
7 Under Attic(Vented) DINING/GREAT 30 Blown 588ft' 0.1 Wood
8 Under Attic(Vented) KITCHEN 30 Blown 209 ft- 0.1 Wood
_ 9 Under Attic(Vented) BATH 30 Blown 50 it= 0.1 Wood
10 Under Attic(Vented) HALL 30 Blown 25ft 0.1 Wood
_ 11 Under Attic(Vented) FOYER 30 Blown 92 ft2 0.1 Wood
12 Under Attic(Vented) BEDROOM 3 30 Blown 169 ft' 0.1 Wood
13 Knee Wall(Vented) DINING/GREAT 19 Blown 30 fN 0.11 Wood
WALLS
Adjacent Space Cavity Width Height Sheathing Framing Solar Below
0
1 NE=>SW Exterior Concrete Block-Int InsdAASTER BE 4.1 16 0 8 0 128.0 ft- 0 0 0.3 0
2 SW=>NE Exterior Concrete Block-Int InsMASTER BE 4.1 7 0 8 0 56.0 fF 0 0 0.3 0
3 NW=>SE Exterior Concrete Block-Int InsEAASTER BE 4.1 14 0 8 0 112.0 It° 0 0 0.3 0
1/12/2021 1:15 PM EnergyGauge®USA 7.0.00-FlaRes202O FBC 7th Edition(2020) Compliant Software Page 3 of 6
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
WALLS
Adjacent Space Cavity Width Height Sheathing Framing Solar Below
0
-4 NE=>SW Exterior Concrete Block-Int InsWASTER BA 4.1 8 0 8 0 64.0 ft2 0 0 0.3 0
-5 NE=>SW Exterior Concrete Block-Int Insul M.BATH 4.1 7 0 8 0 56.0 ft2 0 0 0.3 0
- 6 NE=>SW Exterior Concrete Block-Int lnstEDROOM 2 4A 12 0 8 0 96.0 ft2 0 0 0.3 0
7 SW=>NE Exterior Concrete Block-Int InsMINING(GRE 4.1 30 0 8 0 240.0 ft2 0 0 0.3 0
_ 8 NW=>SE Exterior Concrete Block-Int lns(DINING/GRE 4.1 20 0 8 0 160.0 ft2 0 0 0.3 0
9 SW=>NE Exterior Concrete Block-Int InsulKITCHEN 4.1 11 0 8 0 88.0 ft2 0 0 0.3 0
10 NE=>SW Exterior Concrete Block-Int Insul BATH 4.1 5 0 8 0 40.0 ft2 0 0.3 0
_11 SE=>NW Exterior Concrete Block-Intlnsul FOYER 4.1 8 0 8 0 64.0ft2 0 0 0.3 0
12 SW=>NE Exterior Concrete Block-Int Insul FOYER 4.1 1 0 8 0 8.0 ft2 0 0 0.3 0
_13 NE=>SW Exterior Concrete Block-Int InsIEDROOM 3 4.1 13 0 8 0 104.0 ft2 0 0 0.3 0
_14 SW=>NE Exterior Concrete Block-Int InsBEDROOM 3 4.1 1 0 8 0 8.0 ft2 0 0 0.3 0
15 N=>S Garage Frame-Wood BEDROOM 3 11 26 8 208.0 ft2 0.23 0.3 0
DOORS
# Omt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 SE=>NW Insulated FOYER None .39 3 3 6 8 21.7 ft2
WINDOWS
Orientation shown is the entered orientation => changed to Worst Case.
/ Wall Overhang
V # Omt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening
1 NW=>SE 3 Metal Low-E Single Yes 1.02 0.29 Y 32.4 ft2 1 ft 0 in 1 ft 4 in Drapes/blinds Exterior 5
2 NE=>SW 5 Metal Low-E Single Yes 1.02 0.29 Y 6.9 ft2 1 ft 0 in 1 ft 4 in None None
3 NE=>SW 6 Metal Low-E Single Yes 1.02 0.29 Y 16.2 ft2 1 ft 0 in 1 ft 4 in None None
4 SW=>NE 7 Metal Low-E Single Yes 1.02 0.29 Y 39.8 ft2 1 ft 0 in 1 ft 4 in None None
5 NW=>SE 8 Metal Low-E Single Yes 1.11 0.27 Y 40.0 ft2 8 ft 0 in 1 ft 4 in None None
6 NE=>SW 13 Metal Low-E Single Yes 1.02 0.29 Y 16.2 ft2 1 ft 0 in 1 ft 4 in Drapes/blinds Exterior 5
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation
1 806 ft- 806 ft2 6 ft 8 ft 11
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000254 1168.7 64.12 120.37 .0902 5
1/12/2021 1:15 PM EnergyGauge®USA 7.0.00-FlaRes202O FBC 7th Edition(2020) Compliant Software Page 4 of 6
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
HEATING SYSTEM
# System Type Subtype Speed Efficiency Capacity Block Ducts
1 Electric Heat Pump/ Split Singl HSPF:8.5 34.8 kBtu/hr 1 sys#1
COOLING SYSTEM
# System Type Subtype Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit/ Split Sing) SEER:15 34.8 kBtu/hr cfm 0.85 1 sys#1
HOT WATER SYSTEM
# System Type SubType Location EF Cap Use SetPnt Conservation
1 Electric None Garage 0.97 40 gat 60.9 gal 120 deg None
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Can # Company Name System Model# Collector Model# Area Volume FEF
None None ft2
DUCTS
/ —Supply-- --Return--- Air CFM 25 CFM25 HVAC#
V # Location R-Value Area Location Area Leakage Type Handler TOT OUT ON RLF Heat Cool
1 Attic 6 195 ft' Attic 55 ft2 Default Leakage Attic (Default) (Default) 1 1
TEMPERATURES
Programabl(e 7Thermosta[[t:��N [[ � [ ] Ceiling Fans:MM:yfXI l)C) lJ0 NovIrJC,INov [
Dec
Heating [Jq Jan [X]Feb [X]Mar l 1 AApppr € May Jun [ 1 Jul [ ]Aug [ ]Sep Oct [X]Nov [ Dec
Venting I( 11 Jan LL 11 Feb [[�X]]Mar lxl Jun [ 1 Jul ( 1 Aug [ 1 Sep
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 68 68 68 68 68 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 68 68
Heating(WEH) AM 68 68 68 68 68 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 68 68
MASS
Mass Type Area Thickness Furniture Fraction Space
Default(8 Ibslsq.fL 0 ft2 0 ft 0.3 MASTER BEDROO
Default(8 lbs/sq.ft. ft2 ft 0.3 WIC
Default(8 Ibs/sq.ft. ft2 ft 0.3 MASTER BATH
Default(8 lbslsq.ft. ft2 ft 0.3 M.BATH
Default(8 lbs/sq.ft. ft2 ft 0.3 LAUDRY
Default(8 lbs/sq.ft. ft2 ft 0.3 BEDROOM 2
Default(8 lbslsq.ft. ft' ft 0.3 DININGIGREAT R
Default(8 lbs/sq.ft. ft2 ft 0.3 KITCHEN
1/12/2021 1:15 PM EnergyGaugeO USA 7.0.00-FlaRes2020 FBC 7th Edition(2020) Compliant Software Page 5 of 6
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
MASS
Mass Type Area Thickness Furniture Fraction Space
Default(81bs/sq.ft. ft' ft 0.3 BATH
Default(8 lbs/sq.ft. ft' ft 0.3 HALL
Default(8 lbs/sgfL ft' It 0.3 FOYER
Default(8 lbs/s .ft. ft' It 0.3 BEDROOM 3
1/12/2021 1:15 PM EnergyGauge®USA 7.0.00-FlaRes2020 FBC 7th Edition(2020) Compliant Software Page 6 of 6
2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA a
Project Name: WYNNE THE WINDSOR IMPACT Builder Name: WYNNE DEVELOPMENT
Street: THE WINDSOR Permit Office: ST.LUCIE COUNTY
City,State,Zip: FT.PIERCE,FL, Permit Number: Y
Owner: Jurisdiction: w
x
Design Location: FL,Fort Pierce O
COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA
General A continuous air barrier shall be installed in the building envelope. Air-permeable insulation shall
The exterior thermal envelope contains a continuous air barrier. not be used as a sealingmaterial.
requirements Breaks or joints in the air barrier shall be sealed.
Ceiling/attic y pp ceiling/soffit
The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in an dropped /soffit
g
the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier.
Access openings,drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls The junction of the foundation and sill plate shall be sealed. Cavities within comers and headers of frame walls
The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity
sealed. with a material having a thermal resistance of R-3
Knee walls shall be sealed. per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows,skylights The space between window/doorjambs and framing,and
and doors skylights and framing shall be sealed.
Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated.
Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to
(including insulation. maintain permanent contact with the underside of
above-garage subfloor decking,or floor framing cavity,insulation
and cantilevered shall be permitted to be in contact with the top side
floors) of sheathing,or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation,insulation
a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace wall .
Shafts,penetrations Duct shafts,utility penetrations,and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit,or narrow
Narrow cavities cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spa s.
Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building
shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls,or insulation that on
installation readily conforms to available space shall
Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall
on exterior wall tubs shall separate them from the showers and tubs. be insulated.
Electrical/phone box or The air barrier shall be installed behind electrical or communication
exterior walls boxes or air-sealed boxes shall be installed.
HVAC register boots HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub-floor,wall covering or
Concealed When required to be sealed,concealed fire sprinklers shall only be
sprinklers sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
I between fire a. In addition,inspection of log walls shall be in accordance vrith the provisions of ICC-400.
1/12/2021 1:15 PM EnergyGauge®USA 7.0.00-FlaRes202O FBC 7th Edition(2020) Compliant Software Page 1 of 1
FORM R405-2020
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 97
The lower the EnergyPerformance Index,the more efficient the home.
THE WINDSOR, FT. PIERCE, FL,
1. New construction or existing New(From Plans) 10. Wall Type and Insulation Insulation Area
2. Single family or multiple(amity Detached a.Concrete Block-IM Insul,Exterior R=4.1 1224.00 ft'
b.Frame-Wood,Adjacent R=11.0 208.00 ft'
3. Number of units,if multiple family 1 c.WA R= fP
4. Number of Bedrooms 3 d.NIA R= ftz
5. Is this a worst case? Yes 11.Ceiling Type and insulation level Insulation Area a.Under Attic(Vented) R=30.0 1753.00112
6. Conditioned floor area(W) 1753 b.Knee Wall(Vented) R=19.0 30.00 ft'
c.NIADucts,
R=
7. Windows" Description Area r. S I,U=1.02 111.36 ft' 12.Ducts,location&insulation level R ft'
a. U-Facto
9 a.Sup:Attic,Ret:Attic,AH:Attic 6 195
SHGC: SHGC=029
b. U-Factor. Sgl,U=1.11 40.00 ft
SHGC: SHGC=0.27 13.Cooling systems kBtuthr Efficiency
c. U-Factor. N/A ft a.Central Unit 34.8 SEER:15.00
SHGC:
d. U-Factor. N/A ft2
14.Heating systems kBtulhr Efficiency
SHGC: a.Electric Heat Pump 34.8 HSPF:8.50
Area Weighted Average Overhang Depth: 2.850 ft.
Area Weighted Average SHGC: 0.285
8. Skylights Description Area 15.Hot water systems Cap:40 gallons
a. U-Factor(AVG): N/A ft2 a.Electric EF:0.97
SHGC(AVG): NIA b. Conservation features
9. Floor Types Insulation Area None
a.Slab-On-Grade Edge Insulation R=0.0 1753.00 ft` Credits(Performance method) None
b.NIA R= ff2
c.N/A R= ft'
1 certify that this home has complied with the Florida Energy Efficiency Code for Building 0,11BE STIP
Construction through the above energy saving features which will be installed(or exceeded) 'IV
= a O
in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code complant featu
e
Builder Signature: Date:
Address of New Home: 7� `- ` iZcYa O 1, CIC'\ fry/FL Zip:
*Note: This is not a Building Energy Rating. If your Index is below 70,your home may qualify for energy efficient
mortgage(EEM)incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code,
Energy Conservation, contact the Florida Building Commission's support staff.
*`Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation,if not DEFAULT.
1/12/2021 1:15 PM EnergyGaugc@ USA 7.0.00-FlaRes2020 FBC 7th Edition(2020) Compliant Software Page 1 of 1
Project Summary Job:
:
- wrightsoftm Entire House By.
QUICK CALCS, INC.
317 ST.LUCIE LN,Fi.PIERCE,FL 34946 PM.:772-466-6799 Fax 772466-6796 Email:OUICKCALCS@AOL.COM
For: WYNNE DEVELOPMENT
THE W INDSOR,FT.PIERCE,FL
Notes:
Design Information
Weather. FortPierce,FL,US
Winter Design Conditions Summer Design Conditions
Outside db 42 OF Outside db 90 OF
Inside db 70 OF Inside db 75 OF
Design TD 28 OF Design TD 15 OF
Da ly range L
Relative humidity 50 %
Moisture difference 61 grAb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 21542 Btuh Structure 16420 Btuh
Duds 6191 Btuh Duds 9337 Bluh
Central vent(0 cirri) 0 Btuh Central vent(0 cfm) 0 Btuh
(none) (none)
Humidification 0 Btuh Blower 0 SUh
Equpmentload 27734 Btuh Use manufacturers data n
Rate/swingg multipplier 0.95
Infiltration Equipmentsensbleload 24470 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 2495 Btuh
Duds 2546 Stuh
Central vent(0 cfm) 0 Btuh
HeafinBg Coolin (none)
Area(fP) 1753 17 Equipment latent load 5041 Btuh
Volume(fl 16478 16478
Airchangesrhour 0.38 0.20 Equipment Total Load(Sen+Lat) 29511 Btuh
Equiv AVF(cim) 104 55 Req.total capacity at 0.70 SHR 2.9 ton
Heating Equipment Summary Cooling Equipment Summary
Make Carrier Make Carrier
Trade CARRIERAIR CONDITIONING Trade CARRIERAIRCONDITIONING
Model 25HBC536A 030 Cond 25HBC536A*030
AHRI ref 7914585 Coil FX4DN(B,F)037
AHRI ref 7914585
Efficiency 8.5 HSPF Efficiency 12.0 EER,15 SEER
Heating Input Sensible cooling 24360 Btuh
Heating output 34600 Btuh @47-F Latent cooling 10440 BWh
Temperature rise 27 OF Total cooling 34800 Btuh
Actual airflow 1160 crm Actual airflow 1160 cfrrl
Air flow factor 0.042 cfm/Btuh Airflowfador 0.045 dm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.84
Capacity balance point=36 OF
Backup:
Input=7kW, Output=23009 Btuh,100 AFUE
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
WrightSoft- 2021-Jan1213:18:18
---. RigttSuteZ Uriversal 201919A21 RSU08101 Paget
...Don *XWngktoft NAC1W1'NNE-THEWINDSORRP Caic=NUB Ror¢CnorfaceeN
wrighftw RighW@ Worksheet Daw.
Entire House Date:
By
QUICK CALCS, INC.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 P1ore:T2-466 799 Fe, T12-0 "796 Emil:QUICKCALCSm�jiOL.COM
TRoom name Errllre House BEDROOM
2 Eposd.11 207.6 ft 41.0 ft
3
1Roan hei9ft 9.4 R d 9A ft heavcool
4 Room dimensons 14.0 x 20D ft
5 Roomarea 1753.0 ft' 280.0 ft-
Ty I ConsVucfion U-value Or rea HTM A (ftF) Load Area (iF) Load
number (BWh4F-°F) or perimeter (ft) (BWh) or pedmetar (ft) (BWh)
Heat Cool Gross WP/S Heat Cool Gross NVPS Heat Cool
6 %J13A-4acs 0.143 n 4.00 2.55 649 596 2386 1517 66 66 263 167
F—G 1Ac1om 1270 n 3556 34.77 15 0 533 522 0 0 0 0
L--G 4A5.2om 0.770 n 21.56 19.31 38 0 815 730 0 0 0 0
w 13A-4= 0.143 ne 4.00 2,55 27 27 106 68 0 0 0 0
11 y/ 13A-4= 0.143 a 4A0 2S5 141 10D 400 255 0 0 0 0
I1--DC 1Ac1om 1270 a 35M 67A6 20 1 711 1741 0 0 0 0
11QD 0.390 a 1022 11,31 21 21 229 238 0 0 0 0
w 13A-4= 0.143 se 4A0 2.55 27 27 106 68 0 0 0 0
W 13AAo 0.1 s 4.00 255 536 5w 2121 1349 188 188 753 479
I—C 1Ac1om 1270 s 3556 34.77 6 6 213 209 0 0 0- 0
l7/ 13A-4os 0.143 w 4A0 2.55 320 255 1022 649 132 108 432 275
{---C' 1Ac1om 1270 w 3556 54.53 12 1 415 636 12 1 415 636
FL-----GG 1Ac1om 1270 w 35.56 54.53 12 1 427 654 12 1 427 654
4i5-2om 0.770 w 2156 45.63 41 2 880 1862 0 0 0 0
P 12C-C w OD91 - 2.55 128 254 254 647 326 0 0 0 0.
C 16A30md 0.032 - 0.90 2.32 1753 1753 1571 4067 280 280 251 650
F 22A-fil 0.989 - 27.69 0.00 1753 208 5748 0 280 41 1135 0
6 c)AED exaLrd n 397 488
Ernelope los/gan 18331 15285 1 36761 3349
12 a) InfiltrAon 3211 905 729 205
b) Roomwnfilafion 0 0 0 0
13 Inkmaigains: O=pants@ 230 1 230 0 0
Apphwoasrother 0 0
Subtotal lire ft 13) 21542 16420 4405 3554
Les emal load 0 0 0 0
LeIrarsfer 0 0 0 D
Redistribution 0 0 0 0
14 SubMI 21542 16420 4405 3554
15 Ductlwds 29% 57% 6191 9337 29% 57°/, 1266 2021
Total room load 27734 25757 5671 5575
Airrequired(Qm) 1160 1160 237 251
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
Wrh .SvM' 2021-JaM213:18:18
ARigltSUbeSUmerm120l9l9.021 RSU08101 Page 1
._Doa rts\WdgtdDft HUAQWYNNE-TFEWINDSORfrp Calc=MZ F=DoorPaoes:N
> wrightsow Right-A)Worksheet Date:
Entire House Date:
By.
QUICK CALCS, INC.
317 ST.LUCIE LN.,Fr.PIERCE,FL 34946 PI-ore:772-466-6799 Fax T72-466-6796 EmaiC OUiCKCALCS@AOL.COM
1 Room name WIC MASTER BATH
2 Elyosdxell 0 It 9.0 ft
3 Room height 9.4 it hewb3d 9A it he9koot
4 Room dimervsons 7,0 x 9.0 It 7.0 x 9.0 ft
5 Room area 63.0 ft' 63.0 if
Ty Construrbon U-value Or HTM Area (ft Load Area (iM Load
number (BWIV F) (BWhfln or penmeter (ft) (EWh) or perimeter (ft) (Bfuh)
Heat Cool Gros N/P/S Heat Cool Gros NAPS Heat Cool
6 y/ 13A-4= 0.143 n 4A0 255 0 0 0 0 0 0 0 0
I-G 1Aclom 35.1270 n 56 34.77 0 0 0 0 0 0 0 0
I-G 4A5-2om 0.770 n 21.56 19.31 0 0 0 0 0 0 0 0
W 13A-4= 0.143 m 4.00 2.55 0 0 0 0 0 0 0 0
11 1�/ 13A4= 0.143 a 4A0 255 0 0 0 0 0 0 0 0
LI-----DG 1A-d= 1270 a 3556 $7.06 0 0 0 0 0 0 0 0
7100 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0
W 13A4= 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0
y/ 13A-4ocs 0.143 s 4.00 255 0 0 0 0 85 85 339 215
I-G tAchom 1270 s 35,56 34.77 0 0 0 0 0 0 0 0
U�1 13AA= 0.143 w 4.00 2.55 0 0 0 0 0 0 0 0
F--G 1P-clom 1270 w 35.56 54.53 0 0 0 0 0 0 0 0
1Ac1om 1270 w 35.56 54.53 0 0 0 0 0 0 0 0
475-2om 0.770 w 21.56 45.63 0 0 0 0 0 0 0 0
p 120-0s 0.091 2.55 128 0 0 0 0 0 0 0 0
C 16A.30md 0.032 - 090 232 63 63 56 146 63 63 56 146
F 22AAPI 0.989 27.69 0.00 63 0 0 0 63 9 249 0
6 c)AEDe=rson -10 -28
Ernelopelos/gain 56 136 644 334
12 a) Infiltration 0 0 160 45
b) Roomeentilation 0 0 0 0
13 Intematgaim Ooa,pants@ 230 0 0 0 0
Applaioasbolher 0 0
Subt3fal(Iiries6to13) 56 136 804 379
Lesexlamalload 0 0 0 0
Less transfer 0 0 0 0
Redzhbuflon 56 136 804 379
14 Sut)bbi 29% 57% 16 77 29-A 57% 231 216
15 Ductloads
Total room load 73 214 1 59257
Air required(Um) 3 10
Calculations approved b ACCAto meet all requirements of Manual J 8th Ed.
- wrlghtsoTi` 2021-Jarrv1213:18:18
A�CA - NgitSdte&Uriwmi201919.021RSU08101 Page
..Do rtrtWngFtsot HVAC\WYNNE-1HEWINOSOR2 Calc=MlB FrorQDoorfacesN
wrightsoR° Right-JO Worksheet �:
Entire House 8y.
QUICK CALLS, INC.
317 ST.LUCIE LN.,Ff.PIERCE,FL 34946 P1nre:772-466-6799 Fax 772.466-6796 Email:QUICKCALCS@40L.COM
1 Room name MBATH K-FCHEN
2 EVosed M1I 8.0 ft 8.0 ft
3 Room height 94 ft hea b3ot 9A ft heaYbOd
4 Room dimensom 7.0 x 8.0 ft 1.0 x 172.0 ft
5 Room area 56.0 fF 172.0 fN
Ty Construction U-value Or HTM Area (W) Load Area (T) Load
number (BWhMF--9 (BWhfiF) or perimeter (ft) (BWh) or perimeter (ft) (B1uh)
Heat Cool Gross N/P/S Heat Cool Gross N/P!S Heat Cool
6 V)1 13A4ocs 0.143 n 4.00 2.55 0 0 0 0 0 0 0 0
IL- 1Aclorn 1270 n 3556 34.77 0 0 0 0 0 0 0 0
4A5-20m 0.770 n 21.56 19.31 0 0 0 0 0 0 0 0
W 13AAom 0.143 ne 4.00 2.55 0 0 0 0 00 0 0
11 V�1 13A-4= 0.143 a 4.00 2.55 0 0 0 0 0 0 0 0
F--G tActan 1270 a 3556 87.06 0 0 0 0 0 0 0 0
L-D 11DO 0.390 a 1092 11.31 0 0 0 0 0 0 0 0
W 13A4os 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0
V�1 laA-4= 0.143 s 4.00 2.55 75 69 277 176 0 0 0 0
L---G 1Ac1om 1270 s 3556 34.77 6 6 213 209 0 0 - 0 0
13A-4ocs 0.143 w 4.00 2.55 0 0 0 0 0 0 0 0
1Aclom 1270 w 35.56 54.53 0 0 0 0 0 0 0 0
1Aclom 1270 w 3556 5453 0 0 0 0 0 0 0 0
05.2om 0.770 w 2156 45.63 0 0 0 0 0 0 0 0
P 12C-Oav 0.091 - 2.55 128 0 0 0 0 75 75 192 96
C 16A30md 0.032 - 0.90 2.32 56 56 50 130 172 172 154 399
F 22A-tpl 0.989 - 27.69 0.00 56 8 222 0 172 8 222 0
6 c)AEDexmrsion 38
Envelope losigain 762 477 567 462
12 a) IMtltralon 142 40 0 0
b) Roomvenfilation 0 0 0 0
13 hams]gam: Ooarpants@ 230 0 0 0 O
Appliances/other 0
Subtotal(lines 6 to 13) 904 517 567 462
LesseAsmalload 0 0 0 0
LesstranSer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 904 517 567 462
15 Dud loads 29% 57% 260 294 29% 57% 163 263
Total room load 1164 811 730 725
Air required(dim) 49 37 31 33
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
wry hrsot'! 2021-.k 1213:18:18
c .WW�9-�-^`^ Rigk-Site®lNixersa1201919.021 ftSW8101 Page
AMA ..poamerblW69ftsDfLHVACIWYNNE-THE WINDSORnp Calc=MIB Front Doortaces:N
wrightsoft^ Right-JO Worksheet Jdr.
Entire House Date:
QUICK CALCS, INC. By.
317 ST..LUCIE LN,Fr.PIERCE,FL 34946 Ptnre:772-46"799 Fax 772-466E796 Eneil:QUICKCALCS@A.OL.COM
1 Room name WH BEDRODM2
2 Elposd Hall 5.0 it 426 It
3 Room height 9.4 it heaUbDOI - 9.4 ft heffitmd
4 Room 6trnertcons 90 x 50 ft 1.0 x 2D6.0 it
5 Room area 450 T 204.0 if
Ty CCon14uc5on U-%due Or HTM Area (fly Load Area (fly Load
wmw (BWMF-'o (BWhin or perimehx (ft) Auh) or perimeter (1h (BWh)
Heat Cool Gross WPIS Heat Cool Gross NIPS Heat Cod
6 Vy 13A4as 0.143 n 4A0 255 47 47 188 120 132 132 527 335
1AtIom 1270 n 35,56 3477 0 0 0 0 0 0 -0 0
4A5-2am 0.770 n 21-% 19.31 0 0 D 0 0 0 0 - 0
w 13A-4= 0.143 m 4.00 255 0 0 0 0 27 27 106 68
11 Vy 13A4ocs 0.143 a 4A0 255 0 0 0 0 85 65 259 164
FL—D(• 1Ac1om 1270 a 35.56 87A6 0 0 0 0 2D 1 711 1741
11DO 0390 a 1092 - 1131 0 0 0 0 0 0 - 0 0
w 13A4= 0.143 re 4DO 255 0 0 0 0 27 27 106 68
1Rl 13A-4= 0.143 5 4A0 2M 0 0 - 0 0 - 132 132 527 335
I—G 1Ac1om 12M s 3556 34T/ 0 0 0 0 0 0 0 0
13A4ocs 0.143 w 4DO 255 0 0 0 0 0 0 0 0
1Ac1om 1270 w 3556 5453 0 0 0 0 0 0 0 0
1Ac1on 1270 w 3556 54.53 0 0 0 0 0 0 0 0
4A5-2om 0.770 w 2156 45M 0 0 0 0 0 0 0 0
P 12C-09N OD91 255 128 0 0 0 0 0 0 0 0
C 16A30md OD32 - 09D 2.32 45 45 40 104 204 204 183 473
F 22AApl 0989 - 2759 0D0 45 5 138 0 204 43 1179 0
6 c)AED excursion -17 -99
Emalope bslgain 1367 207 35991 3085
12 a) Infiltration 89 25 75B 214
b) Roomlartilation 0 0 0 0
13 Internal gains Ccolpants@ 230 0 0 0 0
Appliancesbgler 0 0
SubWlal(Iines6W 13) 456 232 4357 3299
Leseldemalload 0 0 0 0
Lestransfer 0 0 0 0
RedLshibulim 0 0 0 0
14 Subtotal 456 232 4357 3299
15 Dudloads 29% 57% 131 132 29% 57% 1252 1876
Total mom load 597 364 56D9 5175
Air required(o5n) 25 16 235 233
Calculations approved bVACCAtO meet all requirements of Manual J 8Ih Ed.
wr✓fgtit�soit- 2021Ja 1213:18:18
MgttSutE@Uiwrsa1201919.021 RSU08101 Page4
...Dop r6lWAgtsoft HUAQWYNNE-THEWINDSORnp Calc=MIB Front Doorface&N
i wrightsoft° Right-J@ Worksheet Date:
Entire House
By.
QUICK CALCS, INC.
317 ST.Ll1GE LN.,Fr.PIERCE,FL 34946 Pare:772-466-6799 Fax T72466-6795 Email:gUICKCALCS@ADL.COM
1 Room name ENTRY LAUNDRY
2 bpoyy wall 18.0 It 13.0 It
3 Room height 9.4 it heaflmol 9.4 ft hed=l
4 Room dimenaane 1.0 x 92.0 ft 7.0 x 6.0 ft
5 Room area 92.0 IF 42.01E
Ty I Construction U-value Or HTM Area M� Load Area (HO Load
number (BWhAPL-F) (BWh4d') or perimeter (ft) (BWh) or perimeter M (BWh)
Heat Cool Gras NLFS Heat Cool Gros NIPS Heat Cool
6 rllf 13AA= 0.143 n 4A0 2.55 0 0 0 0 0 0 0 0
Il--CC 1Aoiom 1270 n 3556 34.77 0 0 0 0 0 0 0 0
4A5-2om 0.770 n 2156 1931 0 0 0 0 0 0 0 0
W 13NAM 0.143 ne 4.00 2-55 0 0 D 0 0 0 0 0
11 l?/ 13A4a 0.143 a 4.00 2.55 56 35 142 90 0 0 0 0
L�---DG 1Aclon 1270 a 3556 87.06 0 0 0 0 0 0 0 0
11DO D290 a 10.92 11.31 21 21 229 238 0 0 0 0
W 13A4003 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0
t13A4as 0.143 s 4.00 2.55 0 0 0 0 66 56 226 144
-C 1Ac1am 1270 s 35.56 34.77 0 0 0 0 0 0 0 0
13A-4= 0.143 w 4.00 2.55 0 0 0 0 0 0 0 0
F--G 1AtIom 1270 w 35.56 54.53 0 0 0 0 0 0 0 0
LI--.--GG 1A-c1om 1270 w 3556 54.53 0 0 0 0 0 0 0 0
4A5-2om 0.770 w 21.56 46.63 0 0 0 0 0 0 0 0
P 12C-0ew O091 - 2,55 128 113 113 287 145 66 66 158 84
C 16A30md 0.032 - 0.90 2.32 92 92 82 213 42 42 38 97
F 22A-tpl D.989 - 27.fi9 0.00 92 18 498 0 42 13 360 0
6 c)AED exaxsion -24
EroelopeloWgain 1239 637 7911 301
12 a) Infiltration 107 30 107 30
b) Roomvenfilabon 0 0 1 0 0
13 IMemal gaire: O=pants@ 230 0 0 0 0
Applianoslother 0 0
Subtotal(lines6to13) 1346 667 898 331
Lessextemal load 0 0 0 0
Lesstransfer 0 0 0 0
Redistribution 0 0 0 0
13
14 Subtotal 379 258 898 331
15 Ductloads 29% 57% 387 79 57% 188
Total room load 1733 104711
047 29% 1156 520
Air required(cfn) n 47 48 23
_ Calculations approved bvACCAto meet all requirements of Manual J Sib Ed.
- wr�9hLsvTC` 2021.1aM213:18:18
Ar ,. RigK-Sates Ueiver�1201919.021 RSU08101 Pages
Comrts\W6g�ftHVAaWY - p M Frond Doorfaces:N
wrightsof- Right°J®Worksheet Jcb:
Entire House Date:
By.QUICK CALCS, INC.
317 ST.LUCIE LN.,Fr..PIERCE,FL 34946 Phone:772-466-6799 Fax 7724666796 Email:QUICKCALCS@AOL.COM
1 Room name GREAVDINING Room7
2 Eaposedwali 50.0 ft 13.0 ft
3 Room height 9.4 ft heatbDol 9.4 R heaV=l
4 Room dimensions 1,0 x 567.0 ft 13.0 x 13.0 ft
5 Room area 567.0 ft- 169.0 fFi
Ty Construction U-value Or HTM Area (� Load
Load Arm
number (BWh%P--°F) (Bh1h/R') or perimeter (ft) (BWh) or perimeW (R) (6Wh)
Heat Cool Gros N/P/S Heat Cool Gross N/P/S Heat Cool
6 \Q/ 13A4= 0.143 n 4.00 2.55 282 244 978 622 122 107 429 273
II--GC 1A lom 1270 In 3556 34.77 0 0 0 0 15 0 533 522
4A5-2om 0.770 n 21.56 1931 38 0 815 730 0 0 0 0
W 13A4ocs 0.143 ne 4.00 2S5 0 0 0 0 0 0 0 0
11 V�= 13A4ors 0.143 a 4.00 2.55 0 0 0 0 0 0 0 0
1A-clom 1270 a 3556 87.06 0 0 0 0 0 0 0 0
11DO 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0
W 13A4ors 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0
VN 1344= 0.143 s 4.00 2.55 0 0 0 0 0 0 0 - 0
I-G 1Ac1om 1270 s 3556 34.77 0 0 0 0 0 0 0- 0
Vy 13A4ocs 0.143 w 4.00 2.55 188 147 589 375 0 0 0 0
1A-tlom 1270 w 3556 54M 0 0 0 0 0 0 0 0
1Acicm 1270 w 35.56 54.53 0 0 0 0 0 0 0 0
4A5-2om 0.770 w 21.56 45.63 41 2 880 1862 0 0 0 0
P 12C-0sv 0.091 2.55 128 0 0 0 0 - 0 0 0 0
C 16A-30md 0.032 - 0.90 2.32 567 567 508 1315 169 169 151 392
F 22A-tpl 0.989 - 27.69 0.00 567 50 1385 0 169 13 360 0
6 c)AED emgsion 307 -100
Envelope lossgain 5154 5210 1474 1086
12 a) Infiltration 889 251 231 65
b) Roomventilation 0 0 0 0
13 Internal gains Omlpants@ 230 0 0 1 230
ApplianosloRer 0 0
Subtoml(Ilnes6to 13) 6043 5461 1705 1381
Les eternal load 0 0 0 0
Lestaruder 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 6043 5461 1705 1381
15 Dudloads 29% 57% 1737 3105 29% 579/6 490 785
Total room load 7780 8556 2195 2167
Air required(dm) 325 386 1 92 98
Calculations approved bVACCAto meet all requirements of Manual J 8th Ed.
-*-wrl9hLsoTC- 2021Ja01213:18:18
.9C h RightSdte@Uriwrsa1201919.021RSU08101 Page
6
...Doa rd;\W6gYboft HVAQWYNNE-THEWINDSORnp CaIc=M18 FrortOoorlanes:N
Duct System Summary Job:wrightsoft y ry Date:
Entire House By.
QUICK CALCS, INC.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 PInre:772-466-6799 Fa 772466-6796 Emil:OUICKCALCS@AOL.COM
Project •
For. WYNNE DEVELOPMENT
THE W INDSOR,FT.PIERCE,FL
Heating Cooling
Extemal static pressure 0 in H2O 0 in H2O
Pressure losses 0 in H2O 0 in H2O
Available static pressure 0 in H2O 0 in H2O
Supply/retumavailable pressure 0.000/0.000 in H2O 0.000/0.000 in H2O
Lowest fdctionrate 0 in/100ft 0 in/100ft
Actual air low 1160 cfm 1160 cIm
Total effective length(TEL) 0 ft
SupplyDetail
Design Htg Clg Design Diam H x W Duct Actual Ftg.FAv
Name (Btuh) (cfm) (dm) FIR (in) (in) Mat Ln(ft) Ln(ft) Trunk
BATM h 364 25 16 0 0 Ox 0 ShMt 0 0
BEDROOM c 2788 119 126 0 0 Ox0 ShMt 0 0
BEDROOM2 h 2587 117 117 0 0 Ox0 ShMt 0 0
BEDROOM2-A h 2587 117 117 0 0 Ox0 ShMt 0 0
BEDROOM-A c 2788 119 126 0 0 Ox0 ShMt 0 0
ENTRY h 1047 72 47 0 0 Ox 0 ShMt 0 0
GREAT/DINING c 2855 108 129 0 0 OxO ShMt 0 0
GREAT/DINING-A c 2855 108 129 0 0 OXO ShMt 0 0
GREATIDINING-B c 2855 108 129 0 0 Ox0 ShMt 0 0
KITCHEN c 725 31 33 0 0 Ox0 ShMt 0 0
LAUNDRY h 520 48 23 0 0 Ox0 ShMt 0 0
M.BATH h 811 49 37 0 0 Ox 0 ShMt 0 0
MASTER BATH h 595 43 27 0 0 Ox0 ShMt 0 0
Ro=7 C 2167 92 98 0 0 OXO ShMt 0 0
WIC C 214 3 10 0 0 Ox0 ShMt 0 0
Return Branch Detail Table Htg CIg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size(in) (Cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening(in) Mat Trunk
rb1 Ox0 1 1160 1160 0 1 0 0 0 Ox 0 1 ShMt
wrightsoit' 2021-Jan1213:18:19
Rigk-Sufe&Uriversal201919.021 RSU08161 ACM Pagel
...Downerts\Wdgfts ftWAMWYNNE-THEWINDSOR.np CaIc=M18 FrontDoorfaces:N