HomeMy WebLinkAboutWolflube - Bldg 1 Loading Dock Ramp - S. Side 251541-1 DTUES Project No:
Workorder No:
Report Date:
3310.2100259.0000
251541-1
11/12/2021
607 Northwest Commodity Cove, Port St. Lucie, FL 34986 - P: 772-924-3575 - F: 772-924-3580
In-Place Density Test Report
Client:Panelli Fort Pierce, LLC UES Technician:Juan Hernandez
16460 SW 137th Avenue
Miami, FL 33177
Date Tested:11/11/2021
Project:CMT Wolflube Warehouse-Manufacturing Building Phase I
Post Office Road, Fort Pierce, St. Lucie County, FL 34981
Type of Test:
Area Tested:Building 1 Loading Dock Ramp - South
Side
Field:ASTM D-6938 Nuclear Gauge Method
Material:Backfill Laboratory:AASHTO T180 Modified Proctor
Reference Datum:0 = Top of Final Grade
The tests below meet the 98% minimum compaction requirement.
Test
No.Location of Test Range
Maximum
Density
(pcf)
Optimum
Moisture
(%)
Field Dry
Density
(pcf)
Field
Moisture
(%)
Soil
Compaction
(%)
Pass
or
Fail
1 South East corner of loading ramp 0-1 ft 114.2 13.8 113.5 13.6 99 Pass
2 South West corner of loading ramp 0-1 ft 114.2 13.8 114.8 12.8 101 Pass
3 Center of loading ramp 0-1 ft 114.2 13.8 113.9 13.2 100 Pass
Remarks:Permit: 2012-0558
Reviewed By
GFA International, Inc
FBPE Registry No.4930
Allan G. Abubakar, P.E.
STATE OF FLORIDA
Professional Engineer No. 69952
This item has been digitally signed and sealed by Allan G. Abubakar,
P.E. on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
To establish a mutual protection to Universal's clients, the Public and ourselves, all reports are submitted as confidential property of our clients and
authorization for publication of statements, conclusions or extracts from or regarding Universal's reports is reserved pending our written approval.
Page 1