HomeMy WebLinkAboutNEW Prop Manual J UpdatedCalculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-11 13:33:35
Right-Suite® Universal 2021 21.0.08 RSU27054 Page 1
...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Load Short Form Jul 15, 2020Date:House Vicki Lynne NisaBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Thomas Residence, Air Conditioning Unlimited, LLCFor:
5313 S 25th St, Fort Pierce, FL 34981
Design Information
InfiltrationClgHtg
SimplifiedMethod9041Outside db (°F)
AverageConstruction quality7570Inside db (°F)
0Fireplaces1529Design TD (°F)
L-Daily range
5030Inside humidity (%)
572Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Lennox
Trade Trade LENNOX
Model Cond ML14XC1S042-230A**
AHRI ref Coil CBA27UHE-042-230*++TDR
AHRI ref 10259441
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW8.1 Sensible cooling Btuh29400
Heating output Btuh27587 Latent cooling Btuh12600
Temperature rise °F18 Total cooling Btuh42000
Actual air flow cfm1400 Actual air flow cfm1400
Air flow factor cfm/Btuh0.049 Air flow factor cfm/Btuh0.049
Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.81
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
Bed 2 161 2830 1781 140 88
Bath 2 54 726 386 36 19
Lin 6 0 0 0 0
Hall 30 0 0 0 0
Bed 3 173 3070 2151 151 106
Family Room 185 4286 5645 211 278
Kitchen/Nook 215 1963 5095 97 251
Living Room 266 1950 4106 96 202
Laundry 77 1064 889 52 44
Dining Room 108 2190 1885 108 93
Foyer 72 1146 607 57 30
Wtr Clst 28 1275 604 63 30
Linen 5 0 0 0 0
WIC 42 764 251 38 12
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-11 13:33:35
Right-Suite® Universal 2021 21.0.08 RSU27054 Page 2
...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
Master Bath 129 1652 828 82 41
Master Bedroom 217 5459 4225 269 208
House d 1766 28375 28454 1400 1400
Other equip loads 1519 807
Equip. @ 0.95 RSM 27914
Latent cooling 7063
TOTALS 1766 29894 34977 1400 1400
2021-Nov-11 13:33:35
Right-Suite® Universal 2021 21.0.08 RSU27054 Page 1
...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Building Analysis Jul 15, 2020Date:House Vicki Lynne NisaBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Thomas Residence, Air Conditioning Unlimited, LLCFor:
5313 S 25th St, Fort Pierce, FL 34981
Design Conditions
Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
Other
Ceilings
Floors
Infiltration
Ducts
Ventilation
% of loadBtuhBtuh/ft²Component
15.445973.1Walls
19.7588717.5Glazing
0.51483.7Doors
5.516540.9Ceilings
19.959493.43.4Floors
11.032852.0Infiltration
22.96856Ducts
00Piping
00Humidification
5.11519Ventilation0Adjustments
100.029894Total
Cooling
Walls
Glazing
OtherCeilingsInfiltration Ducts
Internal Gains
Ventilation
% of loadBtuhBtuh/ft²Component
9.427521.9Walls
26.1764122.8Glazing
0.51503.7Doors
4.613480.8Ceilings
000Floors
3.19180.6Infiltration
26.17624Ducts
2.8807Ventilation
27.48020Internal gains
00Blower
0Adjustments
100.029260Total
Latent Cooling Load = 7063 Btuh
Overall U-value = 0.117 Btuh/ft²-°F
Data entries checked.
2021-Nov-11 13:33:35
Right-Suite® Universal 2021 21.0.08 RSU27054 Page 1
...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Component Constructions Jul 15, 2020Date:House Vicki Lynne NisaBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Thomas Residence, Air Conditioning Unlimited, LLCFor:
5313 S 25th St, Fort Pierce, FL 34981
Design Conditions
Location: CoolingHeatingIndoor:
7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr
BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft²
Walls
Blk Wall, Stucco Ext, R-4.1 Ext Bd Ins, 8" Thk, 1/2" Gyp Bd Int Fnsh 1303.155.10.10941n 832.02
6042.029443.155.10.109300ne
4192.026543.155.10.109208se
7502.0211723.155.10.109372sw
6342.029923.155.10.109315nw
24902.0238923.155.10.1091235all
Partitions
Frm Wall, 1/2" Gyp.Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16"
OC Stud
2621.097052.9411.00.101240
Windows
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 14 ft overhang (6.7 ft window ht, 3 ft sep.); 6.8 ft head ht
45911.972618.800.65039n
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
foreground = green grass (0.23); 1 ft overhang (1.2 ft window ht, 1 ft sep.);
6.8 ft head ht
13127.48116.800.5805ne
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht
34722.326216.800.58016ne
66921.552516.800.58031sw
101721.778716.800.58047all
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
foreground = green grass (0.23); 6.6 ft overhang (1.6 ft window ht, 1 ft
sep.); 6.8 ft head ht
15316.016116.800.58010se
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (6.8 ft window ht, 1 ft sep.); 9 ft head ht
88621.768616.800.58041se
Impact, Clear Low-e, TEMP: Impact, Clear Low-e, TEMP; NFRC rated
(SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen;
foreground = green grass (0.23); 1 ft overhang (3 ft window ht, 1 ft sep.);
6.8 ft head ht
18620.615116.800.5809se
2021-Nov-11 13:33:35
Right-Suite® Universal 2021 21.0.08 RSU27054 Page 2
...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 20 ft overhang (5.2 ft window ht, 3 ft sep.); 6.8 ft head ht
20913.426216.800.58016sw
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (6.7 ft window ht, 3 ft sep.); 6.8 ft head ht
87122.074718.800.65040sw
Impact, TEMP, OBSC: Impact, TEMP, OBSC; NFRC rated (SHGC=0.24);
foreground = green grass (0.23); 1 ft overhang (3 ft window ht, 1 ft sep.);
6.8 ft head ht
15125.110116.800.5806sw
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.2 ft window ht, 3 ft sep.); 6.8 ft head ht
104122.378716.800.58047nw
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 10 ft overhang (5.2 ft window ht, 3 ft sep.); 6.8 ft head ht
34722.326216.800.58016nw
51122.338616.800.58023nw
85822.364916.800.58039all
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 16 ft overhang (6.7 ft window ht, 3 ft sep.); 6.8 ft head ht
86021.774718.800.65040nw
Doors
Door, wd sc type: Fbrgls Door 1503.731483.697.00.12740se
Ceilings
Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.0341766 13480.7616540.9430.0
Floors
On Grade Depth, Tile Flr Fnsh 00594928.700.989207
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-11 13:33:35
Right-Suite® Universal 2021 21.0.08 RSU27054 Page 1
...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Project Summary Jul 15, 2020Date:House Vicki Lynne NisaBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Thomas Residence, Air Conditioning Unlimited, LLCFor:5313 S 25th St, Fort Pierce, FL 34981
Notes:
Design Information
St Lucie Co Intl, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75
Design TD °F29 Design TD °F15Daily range L
Relative humidity %50Moisture difference gr/lb57
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh21520 Structure Btuh20829
Ducts Btuh6856 Ducts Btuh7624Central vent (48 cfm) 1519 Btuh Central vent (48 cfm) Btuh807
Outside air Outside airHumidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh29894 Use manufacturer's data n
Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh27914
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh2896
Ducts Btuh2325Central vent (48 cfm) Btuh1842
CoolingHeating Outside air17661766Area (ft²) Equipment latent load Btuh7063
1627416274Volume (ft³)Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh34977
Equiv. AVF (cfm) 54103 Req. total capacity at 0.70 SHR ton3.3
Heating Equipment Summary Cooling Equipment Summary
Make Make LennoxTrade Trade LENNOX
Model Cond ML14XC1S042-230A**AHRI ref Coil CBA27UHE-042-230*++TDR
AHRI ref 10259441Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW8.1 Sensible cooling Btuh29400Heating output Btuh27587 Latent cooling Btuh12600
Temperature rise °F18 Total cooling Btuh42000Actual air flow cfm1400 Actual air flow cfm1400
Air flow factor cfm/Btuh0.049 Air flow factor cfm/Btuh0.049Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.81
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-11 13:33:35Right-Suite® Universal 2021 21.0.08 RSU27054 Page 1...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Right-J® Worksheet Jul 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name House Bed 2
2 Exposed wall 207.4 ft 29.0 ft
3 Room height 9.2 dft 8.1 heat/coolft
4 Room dimensions ft161.3x1.0
5 Room area 1765.8 ft²161.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 80 41 130 83 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 11.9211.92 39 0 726 459 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 320 300 944 604 113 98 308 197
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 27.3727.37 5 0 81 131 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.2522.25 16 0 262 347 16 0 262 347
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 307 208 654 419 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 15.9615.96 10 10 161 153 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.7221.72 41 4 686 886 0 0 0 0
GG Impact, Clear Low-e, 0.580Impact, Clear Low-e, 0.580 sese 16.8216.82 20.6420.64 9 2 151 186 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 sese 3.693.69 3.733.73 40 40 148 150 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 464 372 1172 750 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.4621.46 31 4 525 669 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.3713.37 16 16 262 209 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 21.9821.98 40 0 747 871 0 0 0 0
GG Impact, TEMP, OBSC 0.580Impact, TEMP, OBSC 0.580 swsw 16.8216.82 25.1125.11 6 1 101 151 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 440 315 992 634 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 47 0 787 1041 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 16 0 262 347 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 23 0 386 511 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 21.7021.70 40 0 747 860 0 0 0 0
PP Frm Wall, 1/2" Gyp.B 0.101Frm Wall, 1/2" Gyp.B 0.101 --2.942.94 1.091.09 240 240 705 262 122 122 357 133
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.940.94 0.760.76 1766 1766 1654 1348 161 161 151 123
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1766 207 5949 0 161 29 832 0
6 c) AED excursion 819 -65
Envelope loss/gain 18235 11891 1910 736
12 a) Infiltration 3285 918 231 65
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 4 920 0 0
Appliances/other 7100 500
Subtotal (lines 6 to 13)21520 20829 2141 1300
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 5 4
14 Subtotal 21520 20829 2146 1304
15 Duct loads 32%37%6856 7624 32%37%684 477
Total room load 28375 28454 2830 1781
Air required (cfm)Air required (cfm)1400 1400 140 88
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-11 13:33:35Right-Suite® Universal 2021 21.0.08 RSU27054 Page 2...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Right-J® Worksheet Jul 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bath 2 Lin
2 Exposed wall 6.0 ft 0 ft
3 Room height 8.1 heat/coolft 8.1 heat/coolft
4 Room dimensions ft6.0x9.0 ft2.5x2.5
5 Room area 54.0 ft²6.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 11.9211.92 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 49 44 138 88 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 27.3727.37 5 0 81 131 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 15.9615.96 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.7221.72 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e, 0.580Impact, Clear Low-e, 0.580 sese 16.8216.82 20.6420.64 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 sese 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.4621.46 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.3713.37 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 21.9821.98 0 0 0 0 0 0 0 0
GG Impact, TEMP, OBSC 0.580Impact, TEMP, OBSC 0.580 swsw 16.8216.82 25.1125.11 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 21.7021.70 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp.B 0.101Frm Wall, 1/2" Gyp.B 0.101 --2.942.94 1.091.09 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.940.94 0.760.76 54 54 51 41 6 6 6 5
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 54 6 172 0 6 0 0 0
6 c) AED excursion -14 0
Envelope loss/gain 441 247 6 5
12 a) Infiltration 99 28 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)540 275 6 5
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 10 8 -6 -5
14 Subtotal 550 282 0 0
15 Duct loads 32%37%175 103 32%37%0 0
Total room load 726 386 0 0
Air required (cfm)Air required (cfm)36 19 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-11 13:33:35Right-Suite® Universal 2021 21.0.08 RSU27054 Page 3...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Right-J® Worksheet Jul 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Hall Bed 3
2 Exposed wall 0 ft 27.5 ft
3 Room height 8.1 heat/coolft 8.1 heat/coolft
4 Room dimensions ft8.5x3.5 ft172.5x1.0
5 Room area 29.8 ft²172.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 11.9211.92 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 122 122 383 245
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 27.3727.37 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 15.9615.96 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.7221.72 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e, 0.580Impact, Clear Low-e, 0.580 sese 16.8216.82 20.6420.64 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 sese 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.4621.46 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.3713.37 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 21.9821.98 0 0 0 0 0 0 0 0
GG Impact, TEMP, OBSC 0.580Impact, TEMP, OBSC 0.580 swsw 16.8216.82 25.1125.11 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 101 86 270 173
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 16 0 262 347
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 21.7021.70 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp.B 0.101Frm Wall, 1/2" Gyp.B 0.101 --2.942.94 1.091.09 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.940.94 0.760.76 30 30 28 23 173 173 162 132
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 30 0 0 0 173 28 789 0
6 c) AED excursion -1 45
Envelope loss/gain 28 22 1865 941
12 a) Infiltration 0 0 454 127
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 500
Subtotal (lines 6 to 13)28 22 2320 1568
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -28 -22 8 7
14 Subtotal 0 0 2328 1575
15 Duct loads 32%37%0 0 32%37%742 576
Total room load 0 0 3070 2151
Air required (cfm)Air required (cfm)0 0 151 106
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-11 13:33:35Right-Suite® Universal 2021 21.0.08 RSU27054 Page 4...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Right-J® Worksheet Jul 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Family Room Kitchen/Nook
2 Exposed wall 25.0 ft 10.5 ft
3 Room height 10.1 heat/coolft 10.1 heat/coolft
4 Room dimensions ft185.0x1.0 ft214.5x1.0
5 Room area 185.0 ft²214.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 11.9211.92 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 27.3727.37 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 15.9615.96 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.7221.72 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e, 0.580Impact, Clear Low-e, 0.580 sese 16.8216.82 20.6420.64 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 sese 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 101 61 193 124 61 45 142 91
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.4621.46 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.3713.37 0 0 0 0 16 16 262 209
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 21.9821.98 40 0 747 871 0 0 0 0
GG Impact, TEMP, OBSC 0.580Impact, TEMP, OBSC 0.580 swsw 16.8216.82 25.1125.11 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 152 120 379 242 45 30 94 60
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 31 0 525 694 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 16 0 262 347
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 21.7021.70 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp.B 0.101Frm Wall, 1/2" Gyp.B 0.101 --2.942.94 1.091.09 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.940.94 0.760.76 185 185 173 141 215 215 201 164
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 185 25 717 0 215 11 301 0
6 c) AED excursion 185 132
Envelope loss/gain 2735 2258 1263 1002
12 a) Infiltration 515 144 216 60
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 1 230 2 460
Appliances/other 1500 2200
Subtotal (lines 6 to 13)3249 4132 1479 3723
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 1 1 10 8
14 Subtotal 3251 4133 1489 3730
15 Duct loads 32%37%1036 1513 32%37%474 1365
Total room load 4286 5645 1963 5095
Air required (cfm)Air required (cfm)211 278 97 251
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-11 13:33:35Right-Suite® Universal 2021 21.0.08 RSU27054 Page 5...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Right-J® Worksheet Jul 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Living Room Laundry
2 Exposed wall 7.5 ft 14.0 ft
3 Room height 10.1 heat/coolft 8.1 heat/coolft
4 Room dimensions ft265.5x1.0 ft11.0x7.0
5 Room area 265.5 ft²77.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 11.9211.92 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 27.3727.37 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 15.9615.96 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.7221.72 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e, 0.580Impact, Clear Low-e, 0.580 sese 16.8216.82 20.6420.64 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 sese 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.4621.46 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.3713.37 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 21.9821.98 0 0 0 0 0 0 0 0
GG Impact, TEMP, OBSC 0.580Impact, TEMP, OBSC 0.580 swsw 16.8216.82 25.1125.11 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 76 36 114 73 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 21.7021.70 40 0 747 860 0 0 0 0
PP Frm Wall, 1/2" Gyp.B 0.101Frm Wall, 1/2" Gyp.B 0.101 --2.942.94 1.091.09 0 0 0 0 113 113 333 124
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.940.94 0.760.76 266 266 249 203 77 77 72 59
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 266 8 215 0 77 14 402 0
6 c) AED excursion 197 -32
Envelope loss/gain 1325 1333 807 150
12 a) Infiltration 154 43 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 1 230 0 0
Appliances/other 1400 500
Subtotal (lines 6 to 13)1479 3006 807 650
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 1479 3006 807 650
15 Duct loads 32%37%471 1100 32%37%257 238
Total room load 1950 4106 1064 889
Air required (cfm)Air required (cfm)96 202 52 44
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-11 13:33:35Right-Suite® Universal 2021 21.0.08 RSU27054 Page 6...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Right-J® Worksheet Jul 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Dining Room Foyer
2 Exposed wall 12.5 ft 8.0 ft
3 Room height 10.1 heat/coolft 10.1 heat/coolft
4 Room dimensions ft9.0x12.0 ft9.0x8.0
5 Room area 108.0 ft²72.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 11.9211.92 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 27.3727.37 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 121 80 253 162 81 31 98 62
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 15.9615.96 0 0 0 0 10 10 161 153
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.7221.72 41 4 686 886 0 0 0 0
GG Impact, Clear Low-e, 0.580Impact, Clear Low-e, 0.580 sese 16.8216.82 20.6420.64 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 sese 3.693.69 3.733.73 0 0 0 0 40 40 148 150
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.4621.46 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.3713.37 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 21.9821.98 0 0 0 0 0 0 0 0
GG Impact, TEMP, OBSC 0.580Impact, TEMP, OBSC 0.580 swsw 16.8216.82 25.1125.11 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 21.7021.70 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp.B 0.101Frm Wall, 1/2" Gyp.B 0.101 --2.942.94 1.091.09 5 5 15 6 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.940.94 0.760.76 108 108 101 82 72 72 67 55
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 108 13 359 0 72 8 229 0
6 c) AED excursion 175 -22
Envelope loss/gain 1414 1311 704 398
12 a) Infiltration 247 69 165 46
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)1661 1380 869 444
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 1661 1380 869 444
15 Duct loads 32%37%529 505 32%37%277 163
Total room load 2190 1885 1146 607
Air required (cfm)Air required (cfm)108 93 57 30
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-11 13:33:35Right-Suite® Universal 2021 21.0.08 RSU27054 Page 7...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Right-J® Worksheet Jul 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Wtr Clst Linen
2 Exposed wall 11.5 ft 1.5 ft
3 Room height 8.1 heat/coolft 8.1 heat/coolft
4 Room dimensions ft8.0x3.5 ft1.5x3.5
5 Room area 28.0 ft²5.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 11.9211.92 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 27.3727.37 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 28 28 89 57 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 15.9615.96 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.7221.72 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e, 0.580Impact, Clear Low-e, 0.580 sese 16.8216.82 20.6420.64 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 sese 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 65 59 185 119 12 12 38 24
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.4621.46 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.3713.37 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 21.9821.98 0 0 0 0 0 0 0 0
GG Impact, TEMP, OBSC 0.580Impact, TEMP, OBSC 0.580 swsw 16.8216.82 25.1125.11 6 1 101 151 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 21.7021.70 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp.B 0.101Frm Wall, 1/2" Gyp.B 0.101 --2.942.94 1.091.09 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.940.94 0.760.76 28 28 26 21 5 5 5 4
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 28 12 330 0 5 2 43 0
6 c) AED excursion 27 -2
Envelope loss/gain 732 375 86 27
12 a) Infiltration 190 53 25 7
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)921 428 111 34
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 46 14 -111 -34
14 Subtotal 967 442 0 0
15 Duct loads 32%37%308 162 32%37%0 0
Total room load 1275 604 0 0
Air required (cfm)Air required (cfm)63 30 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-11 13:33:35Right-Suite® Universal 2021 21.0.08 RSU27054 Page 8...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Right-J® Worksheet Jul 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name WIC Master Bath
2 Exposed wall 7.0 ft 14.0 ft
3 Room height 8.1 heat/coolft 8.1 heat/coolft
4 Room dimensions ft41.5x1.0 ft128.8x1.0
5 Room area 41.5 ft²128.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nn 18.8518.85 11.9211.92 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 36 36 115 73
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 27.3727.37 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 77 68 214 137
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 15.9615.96 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.7221.72 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e, 0.580Impact, Clear Low-e, 0.580 sese 16.8216.82 20.6420.64 0 0 0 0 9 2 151 186
DD Door, wd sc typeDoor, wd sc type 0.1270.127 sese 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 57 57 179 114 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.4621.46 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.3713.37 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 21.9821.98 0 0 0 0 0 0 0 0
GG Impact, TEMP, OBSC 0.580Impact, TEMP, OBSC 0.580 swsw 16.8216.82 25.1125.11 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.2522.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 21.7021.70 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp.B 0.101Frm Wall, 1/2" Gyp.B 0.101 --2.942.94 1.091.09 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.940.94 0.760.76 42 42 39 32 129 129 121 98
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 42 7 201 0 129 14 402 0
6 c) AED excursion -8 41
Envelope loss/gain 418 138 1002 536
12 a) Infiltration 116 32 231 65
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)534 170 1234 600
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 46 14 20 6
14 Subtotal 580 184 1253 606
15 Duct loads 32%37%185 67 32%37%399 222
Total room load 764 251 1652 828
Air required (cfm)Air required (cfm)38 12 82 41
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-11 13:33:35Right-Suite® Universal 2021 21.0.08 RSU27054 Page 9...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Right-J® Worksheet Jul 15, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Master Bedroom
2 Exposed wall 33.4 ft
3 Room height 9.4 heat/coolft
4 Room dimensions ft216.5x1.0
5 Room area 216.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area Load
number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 W Blk Wall, Stucco Ext 0.109 n 3.15 2.02 80 41 130 83
.G Impact, Clear Low-e 0.650 n 18.85 11.92 39 0 726 459
.W Blk Wall, Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0
.G Impact, Clear Low-e 0.580 ne 16.82 27.37 0 0 0 0
11 G Impact, Clear Low-e 0.580 ne 16.82 22.25 0 0 0 0
W Blk Wall, Stucco Ext 0.109 se 3.15 2.02 0 0 0 0
G Impact, Clear Low-e 0.580 se 16.82 15.96 0 0 0 0
G Impact, Clear Low-e 0.580 se 16.82 21.72 0 0 0 0
G Impact, Clear Low-e, 0.580 se 16.82 20.64 0 0 0 0
D Door, wd sc type 0.127 se 3.69 3.73 0 0 0 0
W Blk Wall, Stucco Ext 0.109 sw 3.15 2.02 169 138 435 278
G Impact, Clear Low-e 0.580 sw 16.82 21.46 31 4 525 669
G Impact, Clear Low-e 0.580 sw 16.82 13.37 0 0 0 0
G Impact, Clear Low-e 0.650 sw 18.85 21.98 0 0 0 0
G Impact, TEMP, OBSC 0.580 sw 16.82 25.11 0 0 0 0
W Blk Wall, Stucco Ext 0.109 nw 3.15 2.02 66 43 135 86
G Impact, Clear Low-e 0.580 nw 16.82 22.25 0 0 0 0
G Impact, Clear Low-e 0.580 nw 16.82 22.25 0 0 0 0
G Impact, Clear Low-e 0.580 nw 16.82 22.25 23 0 386 511
G Impact, Clear Low-e 0.650 nw 18.85 21.70 0 0 0 0
P Frm Wall, 1/2" Gyp.B 0.101 -2.94 1.09 0 0 0 0
C Attic, Shngl Roof, R 0.034 -0.94 0.76 217 217 203 165
F On Grade Depth, Tile 0.989 -28.68 0.00 217 33 958 0
6 c) AED excursion 161
Envelope loss/gain 3498 2413
12 a) Infiltration 642 179
b) Room ventilation 0 0
13 Internal gains: Occupants @ 230 0 0
Appliances/other 500
Subtotal (lines 6 to 13)4140 3093
Less external load 0 0
Less transfer 0 0
Redistribution 0 0
14 Subtotal 4140 3093
15 Duct loads 32%37%1319 1132
Total room load 5459 4225
Air required (cfm)269 208
2021-Nov-11 13:33:36
Right-Suite® Universal 2021 21.0.08 RSU27054 Page 1
...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Duct System Summary Jul 15, 2020Date:House Vicki Lynne NisaBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Thomas Residence, Air Conditioning Unlimited, LLCFor:
5313 S 25th St, Fort Pierce, FL 34981
CoolingHeating
External static pressure in H2O0.70in H2O0.70
Pressure losses in H2O0in H2O0
Available static pressure in H2O0.70in H2O0.70
Supply / return available pressure 0.509 / 0.191 in H2O in H2O0.509 / 0.191
Lowest friction rate in/100ft0.149in/100ft0.149
Actual air flow cfm1400cfm1400
Total effective length (TEL) ft469
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st1200.019.3VlFx0x04.00.2322343726hBath 2
st1200.024.3VlFx0x07.00.2271051682830hBed 2
st4300.041.2VlFx0x08.00.1491271823070hBed 3
st3200.09.4VlFx0x07.00.2431111302190hDining Room
st4300.029.4VlFx0x08.00.1551671272823cFamily Room
st4300.033.8VlFx0x08.00.1531671272823cFamily Room-A
st2200.038.9VlFx0x05.00.21336681146hFoyer
st1200.014.4VlFx0x06.00.237100391698cKitchen/Nook
st4300.032.3VlFx0x06.00.153100391698cKitchen/Nook-A
st4300.040.1VlFx0x06.00.150100391698cKitchen/Nook-B
st3200.08.9VlFx0x05.00.24452631064hLaundry
st2200.039.6VlFx0x07.00.212121582053cLiving Room
00VlFx0x000121582053cLiving Room-A
st2200.039.8VlFx0x06.00.21249981652hMaster Bath
st2200.048.6VlFx0x07.00.2051251622729hMaster Bedroom
st2200.039.0VlFx0x07.00.2131251622729hMaster Bedroom-A
st2200.036.8VlFx0x04.00.2151545764hWIC
st2200.042.5VlFx0x05.00.21036761275hWtr Clst
Bold/italic values have been manually overridden
2021-Nov-11 13:33:36
Right-Suite® Universal 2021 21.0.08 RSU27054 Page 2
...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st4 Peak AVF 513 661 0.149 618 14.0 0x0 VinlFlx st1
st1 Peak AVF 762 889 0.149 832 14.0 0x0 VinlFlx
st2 Peak AVF 667 506 0.205 850 12.0 0x0 VinlFlx
st3 Peak AVF 193 164 0.243 552 8.0 0x0 VinlFlx
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb4 0x 3680 264 127.9 0.149 469 12.0 x0 0 VlFx rt1
rb3 0x 1820 127 85.4 0.224 521 8.0 x0 0 VlFx rt1
rb2 0x 1680 105 76.9 0.248 480 8.0 x0 0 VlFx rt1
rb1 0x 9050 1062 83.2 0.229 601 18.0 x0 0 VlFx rt1
Return Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
rt1 Peak AVF 1622 1559 0.149 744 20.0 0x0 VinlFlx
2021-Nov-11 13:33:36
Right-Suite® Universal 2021 21.0.08 RSU27054 Page 1
...oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N
1282Job:Manual S Compliance Report Jul 15, 2020Date:House Vicki Lynne NisaBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Thomas Residence, Air Conditioning Unlimited, LLCFor:
5313 S 25th St, Fort Pierce, FL 34981
Cooling Equipment
Design Conditions
°F76.5Entering coil DB:Btuh29260Sensible gain:°F90.4Outdoor design DB:
°F63.7Entering coil WB:Btuh7063Latent gain:°F77.4Outdoor design WB:
Btuh36323Total gain:°F75.0Indoor design DB:
cfm1400Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
ML14XC1S042-230A**+CBA27UHE-042-230*++TDRModel:LennoxManufacturer:
cfm1400Actual airflow:
% of load100Btuh29400Sensible capacity:
% of load178Btuh12600Latent capacity:
%70SHR:% of load116Btuh42000Total capacity:
Heating Equipment
Design Conditions
°F68.6Entering coil DB:Btuh29894Heat loss:°F41.0Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Elec stripEquipment type:
Model:Manufacturer:
cfm1400Actual airflow:
°F50Temp. rise:% of load92kW8.1Output capacity:
Meets all requirements of ACCA Manual S.
Job #: 1282
Performed by Vicki Lynne Nisa for:
Thomas Residence
5313 S 25th St
Fort Pierce, FL 34981
Air Calcs, LLC
7550 Hidden Hammock Ln
Vero Beach, FL 32966
Phone: 772.800.8413
vickilynne@aircalcs.com
Scale: 1 : 243
Page 1
Right-Suite® Universal 2021
21.0.08 RSU27054
2021-Nov-11 13:33:52
... 25th St Thomas Res PSL Prop.rup
N
Level 1
Garage
Bed 2
Bath 2
LinHall
Bed 3
Family Room
Kitchen/Nook
Living Room
Laundry
Dining RoomFoyer
Wtr Clst
Linen
WIC
Master Bath
Master Bedroom
10 x 10
167 cfm
10 x 10
167 cfm
8 x 8
100 cfm
8 x 8
100 cfm
10 x 10
162 cfm
10 x 10
162 cfm
12 x 8
182 cfm
12 x 8
168 cfm
10 x 6
100 cfm
8 x 4
45 cfm
10 x 6
76 cfm
8 x 8
98 cfm
12 x 8
130 cfm
10 x 6
68 cfm
10 x 6
63 cfm
12 x 8
121 cfm 36 x 18
1062 cfm
12 x 12
168 cfm
12 x 12
182 cfm
16 x 16
368 cfm
8 x 4
43 cfm
20 "
8 "
8 "
12 "
5 "
7 "
5 "
7 "
7 "
7 "
4 "
5 "
6 "
12 "
8 "
6 "
14 "
7 "
4 "
14 "
6 "
6 "8 "
8 "8 "